ID3000 FEATURES ü Degraded mode of operation


for processor failure
2 - 8 loop Intelligent Fire Alarm • Intelligent Features ü Automatic time control
Panel ü Certified to EN54 parts 2 and 4 functions by day of week for
ü Up to 198 devices per loop (99 “Control-by-Event” (CBE)
Section: Intelligent Fire Alarm Panels
sensor and 99 modules)
ü Time of day and day of week
GENERAL ü Expandable from 2 to 8 loop exclusions for “CBE”
capacity
The NOTIFIER ID3000 intelligent fire ü Remote reset output capability
alarm panel offers a technically ü Adjustable sensor sensitivity for peripheral equipment
sophisticated range of facilities and ü Drift compensation ü Configurable rapid response
functions whilst remaining easy to from manual call points (less
ü Network options
install, program and operate. Modern than 3 seconds)
styling and a variety of aesthetic
• ID2net (Peer to Peer)
options are sure to win over facility • Master / Slave ü 255 Zone capacity per panel
owners and architects. It has been 3rd ü 10 separate levels of sensitivity ü Zone sub-division to cells for
party certified to the current EN54 for alarm and pre-alarm per “CBE”
standards part 2 and 4. point ü Coincidence detection
A full range of intelligent sensors, configurable by zone or cell for
ü Configurable day / night
advanced detection products, input “CBE”
sensitivity adjustment
and output devices, repeaters, mimic
drivers, printers and other ü Addressable device LED blink ü Fire and fault verification delays
peripherals complement the ID3000 control configurable by address
to bring you the most complete and ü Automatic or Manual “Loop ü Pre-defined device type
versatile fire alarm system in the Learn” options characteristics
market place. ü Evacuate pushbutton used as
ü Automatic device “high test” at
configured time of day input to “CBE” for user defined
action
ü “Walk Test” function by zone
for efficient commissioning ü Output device test activation by
address
ü On screen “test” tally (tested /
untested count) for devices in ü Selective event log display or
zone walk test print by date and time
ü Configurable “walk test” time ü Automatic daylight saving time
limit change (configurable)
The ID3000 panels can be networked ü Autoprogram option ü Full configuration edit capability
together either as a true peer to from panel or PC
ü 600 event history file
peer network or in a Master / Slave ü Multiple options for RS232 port
network, extending the total capacity ü Duplicate address fault
protocol
of the system to fit the largest monitoring
applications. • PC Support Tool
ü 2 optional user configurable
communication ports
The ID3000 is designed in a modular
fashion to allow for a wide range of ü Dual pulse rate capability for
applications, facilitating installation outputs
and servicing whilst making the ID3000 ü Pulsing loop powered sounders
very easy to tailor to the requirements capability with steady override
of the application. The large LCD ü Non-alarm non-latching
graphic provides easy to read and
addressable device support for
understand messages complying with
lower priority functions
the EN54 standard for primary user
interfaces.
ü Variety of Mounting options

This document is not intended to be used for installation purposes. Every care has been taken in the ISO9001
preparation of this document but no liability can be accepted for the use of the information therein.
Design, Manufacture and Supply
Design features may be changed or amended without prior notice. For more information, contact NOTIFIER.
Charles Avenue, Burgess Hill, West Sussex, RH15 9UF. United Kingdom to Quality Management Systems
Phone: +44 (1444) 230300 Fax: +44 (1444) 230888 Certified to ISO9001:1994 Quality Systems Certificate No. 154
Assessed to ISO9001

Page 1 of 8 — 990-053
ü Windows™ 95, 98, NT 4.0 security option ü Dynamic grouping of up to 99
operating system compatible ü Back Boxes supplied separately VIEW™ sensors.
ü System Wide project ü Primary electronics supplied in ü Addressable operation pinpoints
configuration for multi-panel chassis format for ease of the fire location
networks installation ü No moving parts to fail or filters
ü Platform for multiple product ü Optional lockable glazed door to change
support for access restriction • OptiPlex Sensor
ü Integrated “error checking” • Optional secondary ü Self optimising Optical, Thermal
ü Zone or Loop tree structure RS232 port (isolated) sensing technology combined in
views at any time one sensor.
ü Graphics System Interface
ü Cut, Copy and Paste editing ü 5 smoke sensitivity levels, two
ü Paging System Interface
functions self-optimising with heat only
ü 80-column Printer Interface output.
ü Multiple options for reporting
and printing data • Optional RS485 port • HARSH™ Sensor
ü Site specific user installation (isolated)
ü Operates as standard optical
information embedded into PC • Analogue Loop Devices sensor in “dirty” environments,
configuration file Support with no loss of smoke detection
ü Comment fields for “CBE” Rules performance
ü Type A1, A1R and B2 Heat
ü On-line help file Sensors ü Dual filters for immunity to
nuisance alarms
• User Interface ü Low-Profile Optical Sensors
ü Resistant to problems
Fire ZONE 2 04:52 Total
1
ü Low-Profile Ionisation Sensors associated with water droplets,
Faults: ZONES: 1; EVENTS: 1
Fault Event: ZONE 2
Device description
Fire Fault Test User
01-May 10:07:39
HEAT
01-May 11:20:07
ü Loop Powered Beam Detectors visible dust and fibres
MUTE
BUZZER
EXTEND
DELAY
END DELAY/
EVACUATE
SILENCE/
RESOUND
RESET 7 8 9 ü Manual Call Points ü Intake fan motor, power
4 5 6
availability and filter state fully
FIRE O/P CHANGE ZONES IN 1 2 3 ü Analogue Input Modules
monitored
DAY MODE
DISABLE TABS ALARM

ü Analogue Output Modules


• HAZARD™ Sensor
DISABLEMENT
FIRE
TEST
FAULT
ü Loop Powered Sounders
POWER

ü BASEEFA approved to EEx ia


PRE-ALARM DAY MODE
SYSTEM FAULT DELAYS ACTIVE
SOUNDER FAULT/DISABLED
FIRE O/P FAULT/DISABLED
NON-FIRE ACTIVE
ID3000
FIRE CONTROL PANEL
Complies With EN54-2/4 1997
ü Very Intelligent Early Warning IICT5.
Sensors (VIEW™)
Period Of Manufacture 2000
FIRE O/P ACTIVE

ü Zone 0 hazardous enviroment


ü Large 240 x 64 pixel graphics ü Self Optimising Optical, Thermal installations.
display Multi-Sensors (OptiPlex)
ü Configurable Zone and ü Hostile-ARea Smoke Head System Modules
Individual Point location text Sensors (HARSH™)
The ID3000 is a flexible modular control
ü Unique “TABulation” method ü Intrinsically safe Intelligent panel, built from various option
of event categorisation, for Optical smoke sensors
simple navigation modules. Choose the combinations
(HAZARD™)
best suited to the particular application.
ü On screen QWERTY keyboard for • VIEW™ Sensor
simple text edit functions Each module is supplied with required
ü Revolutionary Point Laser mounting screws, connection cables,
ü Clear and concise fascia layout detection washers etc. and installation
ü Software adjustment of ü Advanced AWACS™ algorithms instructions.
timekeeper clock speed differentiate between smoke
ü Programmable passcode and and non-smoke signals
security keyswitch for access ü 99 VIEW™ sensors per loop
restriction capability
ü Optional integral thermal ü 9 levels of alarm sensitivity from
printer 0.1% to 3.24% per metre
ü Optional Zonal indication LED’s obscuration, per sensor
ü Intuitive operation ü 9 levels of pre-alarm sensitivity
from 0.07% to 1.63% per metre
ü Short-cut options for
obscuration, per sensor
disablement, enablement, and
end walk test ü Multi-device algorithm, uses
nearby sensors in alarm
• Modern Housing
determination
ü Choice of 5 cabinet sizes with
ü Maintenance alert
expansion capability
ü Air quality reference detection.
ü Stylish moulded covers with high

Page 2 of 8 — 990-053
Basic Equipment kits • 020-470-009 Extension • 020-548 PSU 7A Status
chassis with PRN2000 Indication Kit
Note: Printer Module Kit This optional unit includes
Yuasa battery sizes are referenced complete assembly and
Includes extension interconnection cables.
unless otherwise stated. chassis with integral Mounts on the side of the
• 020-538-xxx ID3000 Basic printer fitted. The RS232 externally mounted
card is not required. Uses
Equipment Kit 1 panel COMMS port.
Power Supply Unit Kit and
Includes main chassis gives status indication of
assembly, with hinged the PSU.
display, Base PCB • 020-471 PRN2000
containing two loop Printer Module Kit • 020-541-009 78Ah Remote
interfaces, icroprocessor Includes thermal printer
PCB containing relevant with power supply unit and
Battery / PSU Enclosure Kit
software and spare fuses. roll of thermal paper. May Floor mounted only back
020-538 Basic Equipment be fitted to extension box with extra depth for
kit - Language Group 0 chassis kit 020-559-001, additional battery space.
020-538-001 B a s i c 020-559-002 or used as a Powder coated in RAL
Equipment Kit - Language spare. The RS232 card is 7021 extra fine texture.
Group 1 not required. Uses 1 panel Includes power in
020-538-002 B a s i c COMMS port. connectors. Will hold
Equipment Kit - Language batteries up to 78Ah.
Group 2 Compatible with PSU7A
020-538-003 Basic Power supplies & (020-579). PSU not
included.
Equipment Kit - Language
Group 3 accessories Dimensions 680mm(w) x
510mm(h) x 240.5mm(d)

Extension chassis • 020-484 PSU 2.5A


Assembly Kit
• 020-559-001 Extension
Includes complete power
supply unit assembly,
Expansion boards
Chassis Kit. Zone 1-64 interconnection cables
and spare fuses.
Includes extension
Mounts behind the basic • 020-588 Dual Loop
chassis with LED display
board for zones 1 to 64 equipment chassis and Module Kit (LIB)
to indicate fire and fault / charges up to 38Ah Includes PCB for
disablement / test. Will batteries. additional 2 loops, and
also accept integral plug in cable connector.
printer. Max. three modules per
panel. Maximum of 512
• 020-579 Universal input devices per panel
• 020-559-002 Extension Power Supply Kit. 4.5A using standard LIBs.
Chassis Kit. Zone 65-128 or 7A user selectable.
Includes extension
chassis with LED display
Includes complete power • 020-549 Dual Enhanced
supply unit assembly,
board for zones 65 to interconnection cables Loop Module Kit (ELIB)
128 to indicate fire and and spare fuses. Mounts Includes PCB for
fault / disablement / test. inside any deep back box additional 2 loops with on
Will also accept integral kit or the remote battery / board standby
PSU enclosure kit and microprocessor, and
• 020-612 Extension charges up to 130Ah plug in cable connector.
battery capacity. PSU Max. three modules per
Chassis Kit. Zone 1-256 DTP / Booster required in panel. Only required
Includes 2 extension main chassis. where total number of
chassis with LED display input devices controlled
boards for zones 1 to
256 to indicate fire, fault • 020-543 PSU DTP/ by panel main
microprocessor exceeds
/ disablement / test. Booster Kit EN54 limitation of 512.
Requires double Includes complete PSU ELIB may be mixed with
extended backbox interface unit assembly, standard LIBs in a panel.
(standard or deep) and interconnection cables
256 Zone extension and spare fuses.
cover kits, 020-621-xxx. Mounts behind the basic • 020-478 Isolated RS232
A printer module equipment chassis. Module Kit
020-471 cannot be added Essential for use with 7A Includes PCB for isolated
with this option. PSU. RS232 port for OEM
interface, 80 column
printer etc. Uses 1 panel
COMMS port.

Page 3 of 8 — 990-053
• 020-479 Isolated RS485 • 020-574 Mimic Driver &
Module Kit Termination Board PCA • 020-474-009
Includes PCB for isolated Kit Extended Deep Back
RS485 port for
peripherals such This comprises a Control
board and a Termination
Box Kit
as repeaters. Uses 1
board co-located on one Single “extended height”
panel COMMS port.
metal chassis. The back box with extra depth
Control board contains for additional battery
• 020-647 ID2net Network the processor and space, powder coated in
Gateway Module (NGM) memory, and the RAL 7021 extra fine
Termination board allows texture. Includes power in
The NGM PCB plugs
connection of power, connectors. Will hold
directly into the
RS485 and other batteries up to 38Ah.
processor PCB in the
external signals. The Suitable for use with
ID3000. One NGM is
Control board single extension.
required per ID3000. Up
communicates with up to Compatible with internal
to 32 ID3000 can be
eight Mimic Driver and external PSU’s.
networked together. The
NGM can also be used as boards. Dimensions 500mm(w)
an distance booster x 620mm(h) x 220mm(d)
(requires external
power). Product literature and
tools • 020-475-009 Double
• 020-643 PCA Dual port Extended Back Box Kit
fibre optic interface Double “extended height”
The fibre optic interface back box powder coated
PCB plugs directly into • 020-558 Windows™ PC in RAL 7021 extra fine
the NGM via a ribbon- Support Tool Kit texture. Includes power in
cable. Two ports are connectors. Will hold
Includes “Off-line batteries up to 17Ah.
available for fibre optic Configuration” software
communication (left & Suitable for use with dual
and electronic manuals extension. Compatible with
right channel). on CDROM, internal PSU2.5A or
interconnection cable external PSU7A.
assembly and installation
Dimensions 500mm(w) x
instructions.
Repeaters & Mimic 840mm(h) x 122mm(d)
• 020-476-009 Double
panels Back box & enclosure Extended Deep Back
options Box Kit
• 002-452 IDR-6A Active Double “extended height”
back box with extra
Repeater depth for additional
• 020-472-009 Standard battery space, powder
Includes enclosure with
electronics carried on the Back Box Kit coated in RAL 7021 extra
enclosure door. Requires Basic back box powder fine texture. Includes
external 18-32V dc. coated in RAL 7021 extra power in connectors. Will
power supply and panel to fine texture. Includes hold batteries up to 38Ah
be fitted with RS485 card power in connectors. Will with chassis fitted.
020-479. Finished in RAL hold batteries up to 12Ah. Suitable for use with dual
7021 extra fine texture. Suitable only for 16 zone extension. Compatible
Optional Isolated RS232 version. Compatible with with internal and external
Module kit, 020-478 that internal PSU2.5A or PSU’s.
supports a printer. external PSU7A. Dimensions 500mm(w) x
Optional Bezel kit, Dimensions 500mm(w) x 840mm(h) x 220mm(d)
020-600-009. 400mm(h) x 122mm(d)
Dimensions 253.5mm(w)
x 165mm(h) x 50mm(d) • 020-508-009 Standard
• 020-473-009 Extended Extension Back Box Kit
• 020-573 IDR-MD Mimic Back Box Kit Basic back box powder
Control PCA Kit. Single “extended height” coated in RAL 7021 extra
This comprises a Mimic back box powder coated fine texture. Will hold
Driver board and two in RAL 7021 extra fine batteries up to 17Ah.
Mimic termination boards, texture. Includes power Dimensions 500mm(w) x
each mounted on a in connectors. Will hold 220mm(h) x 122mm(d)
discrete metal chassis. batteries up to 17Ah.
Up to eight Mimic Driver Suitable for use with
boards can be driven by single extension.
one Control board. Compatible with internal
PSU2.5A or external
PSU7A.
Dimensions 500mm(w) x
620mm(h) x 122mm(d)

Page 4 of 8 — 990-053
• 020-509-009 Deep • 020-513-009 Main • 020-485-009 Extension
Extension Back Box Kit Cover High Security Kit Cover Blanking Plate Kit
Deep back box with extra Includes moulding, Blanking plate kit for
depth for additional hinges for user interface extension cover
battery space, powder door, high security moulding where no
coated in RAL 7021 extra fasteners and Notifier extension chassis is
fine texture. Will hold label. Finished in RAL required. May be used
batteries up to 38Ah. 7021 extra fine for customisation such
Dimensions 500mm(w) x texture. Moulding adds as mounting of plant
220mm(h) x 220mm(d) 31mm to switches. Finished in
overall depth of back box. extra fine texture.

• 002-439 Multi-Mount
Enclosure • 020-481-009 Extension • 020-482 Main User
Will accept any 2 standard
Cover Kit Interface Door Kit
modules / isolators, a Includes moulding, Lockable user interface
single CMX-10R, a Serial hinges for user interface door kit for additional
Nion or a MRM-1 mains door, push clip primary display level 2
relay. Finished in RAL fasteners and printer slot access restriction and
7021 extra fine texture. covering label. Finished in tamper resistance.
RAL 7021 extra fine
texture. Moulding adds
31mm to overall depth of
• 020-483 Extension User
Covers & bezels back box.
Interface Door Kit
options Lockable user interface
• 020-514-009 Extension door kit for tamper
resistance to extension
Cover High Security Kit interface.
• 020-038-009 Bezel Includes moulding,
Standard hinges for user interface
door, high security
Semi-flush mount bezel
fasteners and printer slot
for standard height back
covering label. Finished in
box. Finished in RAL
RAL 7021 extra fine
7021 extra fine texture.
texture. Moulding adds
• 020-039-009 Bezel 31mm to overall depth of
back box.
Extended
Semi-flush mount bezel • 020-621-009 256
for extended height back Zone Extension Cover
box. Finished in RAL Kit
7021 extra fine texture.
Includes sheet metal
cover, push clip
• 020-040-009 Bezel fasteners and hex fixing
Double Extended tool. Finished in RAL 7021
extra fine texture. For use
Semi-flush mount bezel for with the 256 Zone Display
double extended height Module Kit, 020-612.
back box. Finished in
RAL 7021 extra fine
texture.
• 020-515 High Security
Tool
• 020-480-009 Main Cover For use with the high
security fasteners on the
Kit high security moulded
Includes moulding, covers 020-513-009 and
hinges for user 020-514-009.
interface door, push
clip fasteners, Notifier
label and hex fixing tool. • 020-486 Dual
Finished in RAL 7021 Microswitch Kit
extra fine Includes 2
texture. Moulding adds microswitches,
31mm to overall depth interconnection cabling
of back box. and fitting instructions.
Used to allow panel to
monitor the removal of
one or two extension
covers. Main cover is
monitored by a
microswitch on the
display PCB, fitted as
standard.
Page 5 of 8 — 990-053
Controls and ü 2 to 8 Loops per panel
Indicators ü 255 Software Zones per Panel

• Led Status Indicators ü 64, 128 or 255 Zone LED


indication options on Extended
ü FIRE Panel cabinets

ü FAULT ü 99 Intelligent Sensors per loop


ü PRE-ALARM ü 99 Addressable Monitor/Control
SYSTEM FAULT Modules per loop
ü
ü SOUNDER FAULT/DISABLED
ü FIRE O/P FAULT/DISABLED ID2net capacity
ü FIRE O/P ACTIVE
ü 100 nodes
ü DISABLEMENT
ü 32 ID3000 intelligent fire alarm
ü TEST panels
ü POWER ü 8160 Zones
ü DAY MODE
ü 25344 intelligent Sensors
ü DELAYS ACTIVE
ü 25344 addressable Monitor/
ü NON-FIRE ACTIVE Control modules

• Membrane Switch Controls ü 170km of network cabling

ü MUTE BUZZER
ü EXTEND DELAY Panel Specifications
ü END DELAY/EVACUATE
• Primary Input Power
ü SILENCE/RESOUND
ü 230V, 50Hz (Fused at 5A
ü RESET Recommended, 5A mains spur)
ü DAY MODE • Sounder Outputs
ü FIRE O/P DISABLE
ü 2 Sounder outputs @ 1A each
ü CHANGE TABS • Sounder / Volt-free Outputs
ü ZONES IN ALARM
ü 2 Sounder / Volt-free output
• Membrane Programming contacts rated 30V 1A.
and Selection Keys
• Relay Outputs
ü 10-Key Numeric Keypad
ü Fire Relay Output @ 30V 1A.
ü , , and Navigation
ü Fault Relay Output @ 30V 1A.
Arrows
• Auxiliary Power Output
ü and Pushbuttons
ü 2 Auxiliary Outputs rated @ 26-
28V 1A Each
ü Pushbutton
• Total Auxiliary Output
• LCD Display
ü Total Sounder and auxiliary
ü Graphic 240 x 64 pixel back-lit power dependent on power
display (6 x 40 characters) supply option selected (please
• Keyswitch refer to Notifier’s see PSU
Specifications)
ü Level 2 Access Code Keyswitch
• Battery Space
Panel capacity ü 12Ah with standard back box
ü 17Ah with extended / double-
extended back box
ü 38Ah with extended deep / double-
extended deep back box
ü 78Ah with Remote Battery / PSU
Enclosure

Page 6 of 8 — 990-053
ID3000 SERIES FIRE CONTROL SYSTEM
Master / Slave Network
ID 3000 S e ries ID 3000 S e ries
ID 3000 S e ries P anel E xten de d P ane l
D oub le E xtend ed Pa nel

ID R -6A
MUTE
BUZZER
EXTEND
DE LAY
END DELAY/
EVACUAT E
SIL ENCE/
RE SOUND
RE SET
R epe a te r P a ne l MUTE
BUZZER
EXTEND
DE LAY
END DELAY/
EVACUAT E
SIL ENCE/
RE SOUND
RE SET

DAY MODE FIR E O/P CHANGE ZONES IN


DI S ABLE TAB S AL ARM

DAY MODE FIR E O/P CHANGE ZONES IN


DI S ABLE TAB S AL ARM

DI S ABLEMENT
TES T
DI S ABLEMENT PO WER
TES T
PO WER PRE-A LARM DAY MODE

SYS TE M FA ULT DE LAYS ACTIVE


PRE- ALARM DAY MODE
SOUNDER FAULT /DI SABL ED NO N- FI RE ACTIV E
SYS TE M F AULT DE LAYS ACTIVE
MUTE EXTEND END DELAY/ SILENCE/ FIR E O/P FAUL T/DISA BLE D
DELAY EVACUATE RE SOUND RE SE T
SOUNDER FAULT/DI SABL ED NO N- FI RE ACTI VE BUZZE R FIR E O/P ACTIVE
FIR E O/P FAUL T/DIS AB LE D
FIR E O/P ACTIVE

DAY M OD E FIRE O/P CHANGE ZONES IN


DISABLE TABS ALARM

M U TE E ND D EL A Y / SI LEN C E / C HAN G E ZO NE S IN R E SE T
B U Z Z ER E VA C U A TE R E SOU N D TA B S ALARM

DISABLEMENT

TEST
POWER

PRE-ALARM DAY M OD E

SYSTEM FAULT DELAYS ACT IVE IDR -6 A

SOUNDER FAULT/DISABLED NON-FIRE ACT IVE


FIRE O/P FAULT /D ISABLED
ZONE

FIRE O/P ACTIVE ZONE

ZONE

ZONE

ZONE

ZONE

ZONE

ZONE

C all P oin t O p tiP lexI


S ensor V IE W S ensor V IE W S ensor
.EHA
N O T IN U SE
H O RS S ERV ICE
B UIT EN GE B RU IK
FU O RI S ERV IZI O
A US SE R B E TR IE B
FU E RA DE SE R VI CIO

C ontrol R elay O utp ut D oor H older


(E xterna lly Po w ered)
H eat Se nsor

C A U T IO N
D E - E N E R G IZ E U N IT PR IO R T O S E R V IC IN G

D uct S en so r
O p tica l S en so r

H A R S H Se nsor
B eam D ete ctor
(Loop P ow e re d)

S ound er C o ntrol U n it

MODULE

S hort C ircu it ACTIVE

Iso lation M od ule

.EHA
N O T IN U SE
H O RS S ERV ICE
B UIT EN GE B RU IK
C all P oin t Loo p P ow e red
FU O RI S ERV IZI O
A US SE R B E TR IE B
FU E RA DE SE R VI CIO S ound er

In trinsic S afe ty
Isola tion U nit

Translator M o du le
H A ZA R D S e nsor
C A U T IO N
D E - E N E R G IZ E U N IT PR IO R T O S E R V IC IN G

Io nisation S e nsor C onve ntiona l D etector


In te rface

C A U T IO N

Loo p P ow e red D E - E N E R G IZ E U N IT PR IO R T O S E R V IC IN G

Loo p P ow e red
S ound er B ase S ound er B ase
and S ensor and S ensor

B eam D ete ctor C onve ntiona l D etectors


(E xterna lly Po w ered)

Page 7 of 8 — 990-053
ID3000 SERIES FIRE CONTROL SYSTEM
Peer to Peer Network

COMPATIBLE SLC DEVICES


MMX-10 10 Way Monitor Module
Model Description ZMX-1E Conventional Zone Monitor Module
CPX-551E Standard Ionisation Sensor CMX-2E Control Module (Monitored or Relay)
CPX-751E Low Profile Ionisation Sensor PS2-CMX Control Module With PSU and 2 Bell Circuits
SDX-551E Standard Optical Sensor CMX-10R 10 Way Relay Module
SDX-751E Low Profile Optical Sensor ISO-X Standard Isolator Module
HPX-751E HARSH Optical Sensor MRM-1(/DIN) Mains Relay Module
FDX-551E Type A1 Thermal Sensor B501 Standard Sensor Base
FDX-551HTE Type BS Thermal Sensor B524IE Sensor Base With Standard Isolator
FDX-551RE Type A1R Thermal Sensor B524IEFT Sensor Base With FET Isolator
LPX-751 VIEW high sensitivity intelligent sensor B254RE Sensor Base With Relay Output
SDX-751TEM OPTIPLEX Multi-criteria smoke & heat sensor B524FTXE HARSH Sensor Base
IDX-751 HAZARD intrinsically safe optical sensor ANS4 Addressable Loop Powered Sounder
LPB-500 Loop Powered Beam Detector (TX/RX pair) ANSE4 Addressable Externally Powered Sounder
LBP-620 Loop Powered Beam Detector ABS4 Addressable Loop Powered Sounder Base
M500KAC/GB Manual Call Point ABSE4 Addressable Externally Powered Sounder base
M500KACW Weatherproof Manual Call Point IBS3 Addressable Loop Powered Base Sounder
with Built-in Sensor Base
MMX-1E Monitor Module
AWS3/R Addressable Loop Powered Wall Sounder Red
MMX-101E Mini Monitor Module
AWS3/W Addressable Loop Powered Wall Sounder
MMX-102E Micro Monitor Module White
Some devices may be under development.
Contact NOTIFIER for device availability.