Low-voltage high resistance grounding Application Note AP019004EN
system basics Effective October 2018
Resistance grounding
Low resistance grounding
Low resistance grounding is normally used on medium-voltage to
high-voltage systems to limit the ground return current to a high
level, typically 100 A or more [1].
This setup is chosen in systems where there is a high investment in
capital equipment to limit damage to said equipment. The resistance
must be low enough to let high current flow and allow detection by
the protective devices, which in turn trip the circuit offline.
EATON www.eaton.com 3
Application Note AP019004EN Low-voltage high resistance grounding
Effective October 2018 system basics
Factors to consider when choosing a grounding system
From Table 1, it is possible to compare and decide whether or not
to ground a low-voltage system and which grounding method will
fit one’s preferences. This document is intended as a guide toward
grounding in general, and high resistance grounding in particular.
Thus, it is important to consider a few points when choosing high
resistance grounding:
• There is a need for service continuity after the first ground fault
• There is a need to be able to easily locate ground faults
• There is no need to serve line-to-neutral loads
• If there is no available neutral, then it will be necessary to create
an artificial neutral
• It will be necessary to estimate, calculate, or measure the
capacitive charging current of the system
• The magnitude of maximum current acceptable on the system
under ground fault conditions
References
1. IEEE std. 142 – 2007 “IEEE Recommended Practice for
Grounding of Industrial and Commercial Power Systems”
(IEEE Green Book), IEEE, NY, NY.
2. Neutral Grounding Resistors Technical information, Post Glover,
2012, KY, USA.
3. D.D. Shipp, F.J. Angelini “Characteristics of Different Power
Systems neutral Grounding Techniques: Fact and Fiction”
Cutler-Hammer, 1988.
4. IEEE std. 141-1993 “IEEE Recommended Practice For Electric
Power Distribution for Industrial Plants”(IEEE Red Book),
IEEE, NY, NY.
5. Baldwin Bridger, Jr., “High-Resistance Grounding, IEEE
Transactions on Industry Applications, Vol. IA-19, No. 1”,
Jan/Feb 1983.