You are on page 1of 4

Cracking...

Defect or Normal?
Part 1: When is concrete cracking a construction defect?

by Jeffrey W. Coleman

P
articipants in the design and construction process, The end use of the concrete application will determine
particularly contractors, are frequently faced with the the extent to which cracking is acceptable or unacceptable.
question of whether cracking of concrete is considered For instance, cracking in a concrete aquarium wall is
a defect or whether it falls within the realm of normal generally unacceptable if it causes leaks; however, cracks in
behavior of concrete. This is a difficult question to answer. a concrete beam, elevated slab, or slab-on-ground are to be
First, there are many different concrete applications that are expected and should be acceptable if they don’t interfere
subject to cracking. Second, the end use will determine with the application (if they don’t result in a loss of capacity
whether the severity of cracking is significant. Third, the or durability). Similar tests may be applied to walls, columns,
terms of the contract and any warranties or guaranties, footings, mass foundations, bridge superstructures and
whether expressed or implied, may affect how cracking of decks, dams, and other retention facilities.
concrete is ultimately resolved. Finally, the expectations of The terms of the contract between the parties could also
the Owner or User (whether fair or unfair, realistic or define the level of cracking that will be acceptable. This will
unrealistic) will determine if a dispute arises. In those be more typical in architectural concrete; however, general
instances, documentation, in the form of contract disclaimers, terms regarding warranties and guaranties against defective
will help to avoid disputes between parties. work may also be used to argue that the level of cracking
It’s important to note that there is no magic answer to experienced is a breach of contract. In many cases, state law
this question—no “silver bullet” to conclude the issue once will require compliance with building codes. A supplier of
and for all. If there were, then authorities would have concrete may also find him- or herself subject to the
published it long ago. What follows is a discussion of the Uniform Commercial Code (UCC) Warranties of Fitness
parameters that define the issue and some suggestions to for the Particular Purpose and Merchantability. These UCC
avoid disputes arising out of cracking of concrete. warranties may also be used to argue that cracking in the
applicable concrete placement is unacceptable.
Why Concrete Cracks Complicating the matter further, architects, engineers,
Concrete cracks can occur because of shrinkage, external owners, contractors, subcontractors, material suppliers, and
effects, or internal expansion. Shrinkage cracking can be homeowners will all have different expectations and
either a result of plastic or drying shrinkage. External effects different understandings of what level of cracking in
can be in the form of thermal stresses, differential settlement, concrete will constitute a “defect.”
differential movement, or freezing and thawing. Internal
expansion can result from corrosion of reinforcement or Concrete Cracks Occur…“Period”
chemical reactions between the components of the concrete, ACI Past President and long-time concrete industry
such as alkali-silica reaction (ASR) or delayed ettringite leader Bryant Mather often stated that “Concrete is simply
formation (DEF). On top of all these factors, errors in synthetic sedimentary rock.” Just as rocks crack in nature,
design and detailing, poor construction practices (including concrete (synthetic rock) will crack as well.
construction overloads, excessive water additions during In the introduction of his 1983 Concrete International
mixing or finishing, and inadequate curing), or overloading article,1 Ed Abdun-Nur stated: “What concrete 10 or more
during use also cause cracks in concrete. Thus, the first years old is free of cracks or micro-cracks? I have not seen
challenge to anyone trying to sort out the cause(s) of concrete any in 65 years of concrete work in all kinds of structures.
cracking is to attempt to determine the source of the cracks. Cracking seems to be a universal characteristic of concrete.

Concrete international september 2013 35


Books and hundreds of papers have been written on the Special considerations need to be taken with respect to
subject of cracking of concrete. mass concrete. Mass concrete is defined by ACI 116R4 as
“Large sums of money have been expended in an effort “any volume of concrete with dimensions large enough to
to find a cure, but concrete seems to go on its own way and require that measures be taken to cope with generation of
crack anyway. I am sure that researchers will not stop heat from hydration of the cement and attendant volume
looking for a cure, and I wish them all the luck—they need change, to minimize cracking.” Mass concrete thus requires
it and the concrete industry needs it also.” special precautions because of the large thermal buildup
due to heat of hydration and attendant volume changes.
Industry Guidance ACI 207.2R-075 states in Section 1.3:
Great effort has been undertaken within the industry to “The measures used to control cracking depend, to a large
understand and limit the amount of cracking in concrete. extent, on the economics of the situation and the seriousness
A simple literature search for the word “cracking” in current of cracking if not controlled. Cracks are objectionable where
ACI documents lists 135 documents with applicable their size and spacing compromise the strength, stability,
references to that word. Some guidance can be found serviceability, function, or appearance of the structure.
among those documents. ACI 224.1R-072 states in its preface: “While cracks should be controlled to the minimum
“Cracks in concrete have many causes. They may affect practicable width in all structures, the economics of
appearance only, or they may indicate significant structural achieving this goal should be considered.”
distress or lack of durability. Cracks may represent the total ACI 360R-106 also discusses cracking and crack mitigation
extent of the damage, or they may point to problems of in the abstract:
greater magnitude. Their significance depends on the type “Advantages and disadvantages of these slab design
of structure, as well as the nature of the cracking. For methods are provided, including the ability of some slab
example, cracks that are acceptable for buildings may not designs to minimize cracking and curling more than others.
be acceptable in water-retaining structures.” Even with the best slab designs and proper construction, it
Under Chapter 2—Evaluation of Cracking, the committee is unrealistic to expect crack-free and curl-free floors. Every
goes on to report: owner should be advised by the designer and contractor
“Cracks need to be repaired if they reduce the strength, that it is normal to expect some cracking and curling on
stiffness, or durability of the structure to an unacceptable every project. This does not necessarily reflect adversely on
level, or if the function of the structure is seriously impaired.” the adequacy of the floor’s design or quality of construction.
ACI 302.1R-043 states under Chapter 11—Causes of Design examples are given.”
Floor and Slab Surface Imperfections:
“Some curling and cracking can be expected on every When is Cracking Expected?
project.” To understand when concrete cracking is expected, one
And further in Section 11.2: must understand the basics of structural concrete design.
“Contractors are not necessarily responsible for all In general terms, concrete is about 10 times stronger in
cracks. Many floor or slab design features and concrete compression than it is in tension. In a simple span beam
mixture proportions are responsible for, or contribute to, subjected to a gravity load, the top and bottom surfaces
cracking of concrete construction.” will be in compression and tension, respectively. Because
the bottom surface would crack under a fraction of the
compression required to crush the top surface, design
engineers place reinforcing steel in the concrete to carry
the tensile load. Before the reinforcing steel becomes
effective (that is, carries the load), the concrete must crack.
Errata for ACI Publications Thus, cracking in concrete beams, columns, or walls that

Available Online
are subject to bending forces is to be expected and is
quite normal.
While cracking is normal, it’s difficult to precisely
define acceptable crack widths. The title to Table 4.1 in
ACI 224R-01,7 for example, indicates that the table provides
Under the pull-down menu for “Bookstore &
“reasonable” crack widths in reinforced concrete under
Publications” at www.concrete.org, errata can be
service loads. But a footnote to the table states:
searched by document number or keywords. “It should be expected that a portion of the cracks in the
structure will exceed these values. With time, a significant
Call ACI Member Services at (248) 848-3700 for portion can exceed these values. These are general guide-
more information. lines for design to be used in conjunction with sound
engineering judgment.”

36 september 2013 Concrete international


ASCC Position Statements With respect to slabs-on-ground, a disclosure might state:
The American Society of Concrete Contractors (ASCC) “Minor cracking is expected on any concrete slab-on-
has published position statements on the subject of ground. The (contractor/supplier/designer/subcontractor)
cracking. Position Statement No. 29, “Cracks in Slabs is not responsible for minor cracking that occurs in
on Ground,” quotes part of the forward of ACI 302.1R,3 concrete slabs or that are due to subgrade preparation
text that is quite similar to that previously quoted from and/or settlement.”
ACI 360R-10.6 In the event that the contractor was responsible for
“Even with the best floor designs and proper construction, subgrade preparation, a disclaimer might state:
it is unrealistic to expect crack-free and curl-free floors. “Minor concrete cracking will occur in any slab-on-
Consequently, every owner should be advised by both the ground. The (contractor/subcontractor) is not responsible
designer and contractor that it is normal to expect some for minor concrete cracking. In the event of crack widths in
amount of cracking and curling on every project, and that excess of ___inches or crack faulting in excess of ___inches,
such occurrence does not necessarily reflect adversely on the contractor may elect to repair or replace the concrete
either the adequacy of the floor’s design or the quality of work or a section thereof.”
its construction.” In any event, the contractor should always exclude the
ASCC Position Statement No. 29 goes on to recommend UCC warranties of fitness for the particular purpose and
a crack repair allowance and also makes the point that merchantability. The contractor should also consult with
repairing cracks may not hide them, but may in fact legal counsel to determine the proper language required to
accentuate them and that removing and replacing cracked disclaim these warranties in the state in which the project is
floor panels often constitutes economic waste and is located, as state laws may differ.
counter to sustainability ideals. The following is an example of a disclaimer in a concrete
ASCC Position Statement No. 5, “Specifications for supplier’s warranty:
Crack Repair,” also gives guidance regarding crack repairs “limitations. THE WARRANTY STATED ABOVE
and highlights the practical difficulty contractors face in IS THE SOLE AND EXCLUSIVE WARRANTY APPLICABLE
attempting to estimate crack repair costs. An allowance for TO THIS PURCHASE. ALL OTHER WARRANTIES,
unit prices for crack repair is a more equitable solution. EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED
This of course is based on an assumption that the cracks are TO, THE WARRANTIES OF MERCHANTABILITY
within the “normal and expected” range based upon the AND FITNESS FOR A PARTICULAR PURPOSE, ARE
given design, concrete mixture, and restraints (if any) on EXPRESSLY DISCLAIMED. THE PURCHASER MAY
placement, finishing, and curing. NOT TRANSFER OR ASSIGN THIS WARRANTY.
ASCC Position Statement No. 33, “Cracks in Structural “This warranty does not cover:
Concrete,” provides guidance for ensuring awareness of •• Cracking of any kind caused by, but not limited to,
the potential for cracking: improper joint installation, improper placement,
“ASCC concrete contractors will make themselves improper finishing, improper curing, structural over-
available to meet with the design team, construction manager, loading, and improper subgrade and/or base preparation;
and general contractor to discuss crack expectations for the •• Surface or other distress caused by improper placement,
project. Concrete contractors want to ensure awareness by finishing and/or curing;
all parties that cracking will occur when the structure is •• Any defects caused by the addition of water exceeding
built in accordance with the Contract Documents.” the water-cement ratio specified above and/or water
added to the surface of the concrete during placing and/
Managing Owner Expectations or finishing;
Because concrete is known to crack and, in fact, certain •• Concrete placed between October 1 and May 1;
cracking is not only expected but also required, cracking of •• Any concrete specified by others that does not meet the
concrete is a good example of an area where educating mixture proportions listed above;
the ultimate Owner and User through the design and •• Damage caused by others including, but not limited to,
construction process is important. One way to accomplish damage resulting from the use of snow plows or other
this would be to provide a disclaimer in the contracts used equipment.”
for concrete construction, such as:
“Some amount of minor cracking is to be expected in Principles and Precedents
any concrete work. In fact, structural concrete is required to In Part 2 of this article, I’ll present relevant legal principles
crack in order for the reinforcing steel to become effectively and case law regarding concrete cracking. Principles of
engaged. The (contractor/supplier/designer/subcontractor) particular interest to concrete contractors will be
is not responsible for minor cracking in the concrete work discussed, including:
that does not affect the strength or serviceability of the •• Substantial performance;
structure of which the concrete is a part.” •• Measure of damages;

Concrete international september 2013 37


•• Impossibility of performance; and Note: Additional information on the ASCC position statements
•• Assignment of responsibility. discussed in this article can be found at www.ascconline.org.

References Selected for reader interest by the editors.


1. Abdun-Nur, E.A., “Cracking of Concrete—Who Cares?”
Concrete International, V. 5, No. 7, July 1983, pp. 27-30.
2. ACI Committee 224, “Causes, Evaluation, and Repair of
Jeffrey W. Coleman, FACI, is an
Cracks in Concrete Structures (ACI 224.1R-07),” American
Attorney at Law and Principal of the
Concrete Institute, Farmington Hills, MI, 2007, 22 pp.
Coleman Law Firm, LLC, Minneapolis,
3. ACI Committee 302, “Guide for Concrete Floor and Slab
MN. An ACI member for more than
Construction (ACI 302.1R-04),” American Concrete Institute,
30 years, he currently serves on the
Farmington Hills, MI, 2004, 76 pp.
ACI Board of Direction and chairs
4. ACI Committee 116 (discharged), “Cement and Concrete Ter-
ACI Committee 132, Responsibility
minology (ACI 116R-00) (Reapproved 2005),” American Concrete
in Concrete Construction. He is a
Institute, Farmington Hills, MI, 2000, 73 pp. member of the Construction Award
5. ACI Committee 207, “Report on Thermal and Volume Committee, Construction Liaison Committee, Convention
Change Effects on Cracking of Mass Concrete (ACI 207.2R-07),” Committee, Financial Advisory Committee, TAC Construction
American Concrete Institute, Farmington Hills, MI, 2007, 28 pp. Standards Committee, and ACI Committee 563, Specifi-
6. ACI Committee 360, “Guide to Design of Slabs-on-Ground cations for Repair of Structural Concrete in Buildings.
(ACI 360R-10),” American Concrete Institute, Farmington Hills, Coleman is the author of Legal Issues in Concrete
MI, 2010, 72 pp. Construction, which was published by ACI in 2004. A
7. ACI Committee 224, “Control of Cracking of Concrete licensed professional engineer, he received his BS in civil
Structures (ACI 224R-01) (Reapproved 2008),” American Concrete engineering and MS in structural engineering.
Institute, Farmington Hills, MI, 2001, 46 pp.

eLearning
Now Available:
Controlled Low-Strength Material (CLSM) Fundamentals
0.2 CEU (2 PDH), $80 nonmembers, $64 members
CLSM (also known as flowable fill) is a self-consolidating, cementitious material used primarily as backfill in
place of compacted fill. This course covers the basics of CLSM technology, including materials used to produce
CLSM; plastic and in-service properties; proportioning, mixing, transporting, and placing; quality control; and
common applications.

Concrete Sustainability: Basics


0.15 CEU (1.5 PDH), $75 nonmembers, $60 members
This course provides an introduction to the subject of sustainability, with a special emphasis on the concrete
industry. Participants will study common definitions of sustainability, identify “greenwashing” in the market-
place, understand the three pillars of sustainability, and identify strategies for the integration of concrete in
sustainable development.

Concrete Sustainability: Incorporating Environmental, Social, and


Economic Aspects
0.15 CEU (1.5 PDH), $75 nonmembers, $60 members
This course provides an in-depth study of topics related to the environmental, social, and economic impacts
of using concrete in sustainable development. Topics include the use of industrial by-products, thermal mass,
storm-water management, longevity, and heat-island effect, among several others.

Also available:
• Concrete Basics • Concrete Field Testing Grade I Certification Training
• Concrete Fundamentals • Concrete Strength Testing Technician Training

Visit our website: ACIeLearning.org

38 september 2013 Concrete international

You might also like