PRODUCT DATA
FEATURES
• Reduced total installed cost: Existing standard
Ethernet/LAN infrastructure is used for
communication between CIPer Model 50
controllers, 3rd-party BACnet® controllers, and
BACnet® front-ends. Costs are further reduced by
the flexible and optional use of Panel Bus I/Os
(which allow manual override independent of the
controller, thus eliminating the need for external
switches) and of onboard I/Os.
Panel Bus I/Os allow for wiring lengths of up to
2625 ft (800 m), thus eliminating the need to
install wire from field devices all the way back to the
controller.
• Reduced life cycle cost: CIPer Model 50 supports
GENERAL the highly reliable Honeywell Panel Bus I/O
CIPer Model 50 is a BACnet-compliant heating, modules, which allow for plugging and replacing
ventilation, and air conditioning (HVAC) building without any need for re-wiring or engineering, thus
controller. It runs the WEBs-N4 framework, integrating minimizing system down-time. The Panel Bus is
all trades in a building. polarity-insensitive, thus reducing potential wiring
Thus, CIPer Model 50 is the ideal solution for HVAC errors. Furthermore, Panel Bus I/O modules allow
controls requiring combination with lighting, shading, the predefinition of output safety positions,
access control, and security applications. It provides ensuring safe operation even if communication
unparalleled energy efficiency through a vast HVAC with CIPer Model 50 is disrupted.
Application Library. • Universal operation: Via Internet browser, CIPer
CIPer Model 50 enables uniform graphical operation, Model 50 can be operated from any place, from any
control, data logging, alarming, scheduling, and PC and/or mobile device connected to the (CIPer
network management functions for HVAC and non- Model 50) network. Optionally, via the onboard or
HVAC applications. Through its integrated web server, detached HMI, the controller can be operated
it allows real-time access to all information through independently of any network connection.
web-based graphical views. • Vendor independence: Multiple international
CIPer Model 50 supports full remote engineering, communication standards are supported, e.g.:
including changes to the control program and the BACnet/IP (ISO 16484-5); BACnet MS/TP (ISO
graphical user interface. This greatly supports 16484-5); LONWORKS (ISO 14908); Modbus RTU
reduction of life cycle and maintenance cost. and Modbus TCP; M-Bus (EN 1434-3); oBIX;
SNMP; etc.
OPERATION IN IP NETWORKS • Trending: Datapoints can be trended and historical
When operating CIPer Model 50 in IP networks, values stored and viewed.
either private (e.g. VPN) networks must be used or • Reliable control performance: Embedded QNX
protection against the open Internet (e.g., by ensures reliable, independent, and secure
means of external firewalls) must be ensured. See operation, especially for systems with Internet
Network Security on pg. 5. access.
• Embedded email alarming: Configurable email
alarming options allow alarms to be sent (via
network or Internet-DSL connection) to email
accounts and thus also to mobile device using
SMTP protocol.
• Optional SMS alarming: SMS alarming via GSM
modem using the optional SMS driver.
® U.S. Registered Trademark
Copyright © 2020 Honeywell Inc. • All Rights Reserved 31-00197-02
CIPerTM MODEL 50 CONTROLLER — PRODUCT DATA
31-00197-02 2
CIPerTM MODEL 50 CONTROLLER — PRODUCT DATA
BIAS
END
MID
GND1
GND2
485-1+
485-1-
485-2+
485-2-
UI10
GND
n.a.
n.a.
n.a.
BI1
UI1
UI9
BI2
BI3
UI2
UI3
UI7
UI8
BI4
UI4
UI5
UI6
RS485-1
AO1
24V-0
DO2
DO3
DO7
DO8
AO2
AO3
DO4
DO5
DO6
AO4
24V~
IN7
IN8
IN4
IN5
IN6
IN
Secure web browser communication is supported for Figure 4: Top view (with HMI and full complement of
web access via standard web browsers. onboard I/Os)
SMTP 1 2
3 4
3 31-00197-02
CIPerTM MODEL 50 CONTROLLER — PRODUCT DATA
LEGEND Cables
1. RS232 / RJ45 socket (for connection of M-Bus See section "M-Bus Connection" in CIPer Model 50
and other RS232-based protocols; factory Installation & Commissioning Instructions - 31-00233.
debugging) Use shielded, twisted pair cable Honeywell cable 3322
or 3251.
2. Three-position slide switch (for setting bias
and termination resistance of RS485-1) Shielding
3. Two Ethernet / RJ45 sockets (for BACnet IP Shielding is especially recommended when the M-Bus
communication); 10/100 Mbit/s; 1 "link" LED + cable is installed in areas with expected or actual
1 "activity" LED electromagnetic noise. Avoiding such areas is to be
preferred.
4. USB 2.0 Host Interface (for connection of IF-
LON2); max. 200 mA, high speed Use shielded, twisted pair cable Honeywell cable 3322
or 3251 and connect the shield to a noise-free earth
5. RS485-1* (isolated; for BACnet MS/TP, Panel
ground – only once per M-Bus connection.
Bus, Modbus RTU communication, etc.)
M-Bus Repeaters
6. RS485-2* (non-isolated; for BACnet MS/TP,
Panel Bus, Modbus RTU communication, etc.) The M-Bus can be extended to 3,000 feet, depending
on the communication rate, and provided that the
7. LEDs
electrical limitations are observed. For details refer to
8. USB 2.0 Device Interface (for connection to the CIPer Model 50 Installation & Commissioning
WEBs-N4 web browsers, and 3 rd-party touch Instructions - 31-00233.
panels)
For bus length extension, M-Bus repeaters can be
HMI (or RJ45 socket for connection of portable HMI) used, but have not been tested by Honeywell. Hence, it
*Modbus RTU Master/Slave communication is is the responsibility of the installing / commissioning
possible on the two RS485 interfaces. personnel to ensure proper functioning.
M-BUS MASTER SPECIFICATIONS
WARNING
For a detailed description of the M-Bus functionality,
Risk of electric shock or equipment damage please refer to the M-Bus Online Help.
It is prohibited to connect any of the RJ45 sockets Physical Layer
of the CIPer Model 50 controller to a so-called PoE- RS232 to PW3/PW20/PW60
enabled device ("Power over Ethernet"). Physical connector: RS232 / RJ45 socket (see
Figure 5 on pg.3)
M-BUS CONNECTION
Cable order number: XW586
The CIPer Model 50 controller supports M-Bus Master
functionality via its onboard RS232 / RJ45 socket. It Communication 300, 2,400, and 9,600
uses standard PW3/PW20/PW60 converters to rates: bps are supported,
connect to the M-Bus devices. individually per M-Bus
Wiring Topology slave.
Max. bus length is 1050 feet. M-Bus devices are Max. no. of devices: 60 (excluding the CIPer
connected to the bus cable in parallel. Model 50 controller)
SLAVE 1 SLAVE 2 SLAVE 3 Cable and wiring specifications: See CIPer Model 50
Installation & Commissioning Instructions - 31-00233.
PW
CIPer Model 50 CONVERTER
Address Range
Figure 6: Allowed M-Bus wiring topology M-Bus slaves can have a primary address between 1
and 250.
Measurement Cycle
Individually per M-Bus slave, the measurement cycle
can be configured from 1 to 604,800 sec (i.e. 1
second to 7 days).
31-00197-02 4
CIPerTM MODEL 50 CONTROLLER — PRODUCT DATA
Shielding
MODBUS CONNECTION
Shielding is especially recommended when the
The CIPer Model 50 controller can function as a Modbus cable is installed in areas with expected
Modbus Master/Slave. or actual electromagnetic noise. Avoiding such
For Modbus RTU, the RS485 wiring rules must be areas is to be preferred.
followed. Use shielded, twisted pair cable Honeywell cable
WIRING TOPOLOGY 3322 or 3251 and connect the shield to a noise-
free earth ground, only once per Modbus
Only daisy-chain wiring topology is allowed. connection.
MODBUS
MASTER
MODBUS
SLAVE
MODBUS
SLAVE
Modbus Specifications
For Modbus RTU and TCP specifications, refer to
docModbus found in the docs directory of the
WEBStation-N4.x.x installation.
MODBUS MODBUS
SLAVE SLAVE
WARNING
Figure 7: Allowed Modbus wiring topology
Other wiring topologies (e.g., star wiring, or mixed
NETWORK SECURITY
star wiring and daisy chain wiring) are prohibited; Honeywell hereby expressly states that the CIPer
this is to avoid communication problems of the Model 50 is not inherently protected against cyber-
physical layer. attacks from the Internet and that it is therefore
intended solely for use in private, protected networks.
MODBUS MODBUS MODBUS
Unprotected Internet connections can expose the
XX
MASTER SLAVE SLAVE
controller to cyber-attacks from third parties who can
then damage it and connected facility components
or cause them to malfunction, or who can misuse it
for illegal purposes for which the operator may then
MODBUS MODBUS MODBUS be held liable.
SLAVE SLAVE SLAVE
When directly connected to the Internet, the CIPer
Model 50 automatically becomes a potential target
MODBUS for cyber-attacks. Corresponding protective
SLAVE
measures are therefore essential if safe and reliable
Figure 8: Prohibited Modbus wiring topology operation is to be ensured.
(example) If it is not necessary for the CIPer Model 50 to be
accessible from the Internet, the CIPer Model 50
Cables should be isolated from the Internet via a suitable
See section "EIA 485 Cable Specifications" in firewall.
CIPer Model 50 Installation & Commissioning If it is necessary for the CIPer Model 50 to be
Instructions - 31-00233. accessible from the Internet (e.g., in order to perform
Use shielded, twisted pair cable Honeywell cable remote maintenance), the use of a coded VPN
3322 or 3251. connection is indispensable. Suitable VPN routers
You must use three wires:
are available from numerous third-party
manufacturers in a wide variety of designs, for
• One wire for D1 = Modbus + operation at 230 V or 24 V.
• One wire for D0 = Modbus –
• One wire for the signal common
When using one pair for D1 and D0 and one wire of
another pair for the signal common, CAT5 cable may
also be used.
For connection details, see also CIPer Model 50
Installation & Commissioning Instructions - 31-
00233.
5 31-00197-02
CIPerTM MODEL 50 CONTROLLER — PRODUCT DATA
EARTH GROUND
32..104°F (0...40°C), wall- SHORT-CIRCUITING!
Ambient mounting
temperature 32..122°F (0...50°C), PC 1 PC 2
cabinet/door mounting
Storage
-4 … +158 °F (-20...70°C) CPU 1 CPU 2
temperature USB 2.0
Device Interface
Humidity 5 … 95% r.h. non-condensing 24V~0 24V~ 24V~0 24V~
ELECTRICAL DATA
Table 2. Electrical data
31-00197-02 6
CIPerTM MODEL 50 CONTROLLER — PRODUCT DATA
ADDITIONAL PARTS
Table 3. Additional Parts
7 31-00197-02
CIPerTM MODEL 50 CONTROLLER — PRODUCT DATA
MODELS
Table 4. Overview of Models (hardware)
Order No.
Without HMI With HMI
Max. cable
Feature Description WEB- WEB-
length
EHSERIESNX26 EHSERIESNX26D
ND
NTC10kΩ (Type II) / NTC20kΩ (Type II) 1200 ft
8 8
/ 0…10V / slow BI, 0.4 Hz (366 m)
UI*
NTC10kΩ (Type II) / NTC20kΩ (Type II) 1200 ft
2 2
/ 0…10V fix pull-up / slow BI, 0.4 Hz (366 m)
open = 24 V / closed 2.0 mA / totalizer 1200 ft
BI 4 4
15 Hz (366 m)
1200 ft
AO 0..11 V (max. 1 mA) 4 4
(366 m)
Relay N.O. contact: 3 A, 250 VAC, 1200 ft
4 4
30 VDC (366 m)
Relay N.O. contact (high in-rush): 10 A, 1200 ft
BO 1 1
250 VAC, 30 VDC (366 m)
Relay N.O. contact with one common: 1200 ft
3 3
3 A, 250 VAC, 30 VDC (366 m)
Total I/Os -- 26 26
RS485-1, isolated, BACnet MS/TP,
Bus 3600 ft
1)
Panel Bus, or Modbus RTU Master or 1 1
interfaces (1097 m)
Slave communication
RS485-2, non-isolated, BACnet MS/TP,
Panel Bus, or Modbus RTU Master or
Slave communication (NOTE: It is
3600 ft
1)
imperative that the RS485-2 be 1 1
(1097 m)
powered by a power supply having the
proper polarity. Failure to do so will
make data transmission impossible.)
Ethernet Interfaces (email
communication, browser access, 300 ft
2 2
BACnet IP communication, Niagara (91.44 m)
Network, Modbus TCP)
USB 2.0 Device Interface (as Network 9 ft
1 1
Interface) (2.74 m)
9 ft
USB 2.0 Host Interface (max. 200 mA) 1 1
(2.74 m)
RS232 M-Bus communication via 45-
3600 ft
1)
feet-long PW3 / PW20 / PW60 1 1
converters (1097 m)
31-00197-02 8
CIPerTM MODEL 50 CONTROLLER — PRODUCT DATA
Order No.
Without HMI With HMI
Max. cable
Feature Description WEB- WEB-
length
EHSERIESNX26 EHSERIESNX26D
ND
LED L2 (yellow; lit = platform has
started / is reachable; flashing = station -- 1 1
has started / is reachable)
bus status LEDs (for isolated RS485-1
-- 2 2
interface)
1)
Depending upon bit rate. However, in the case of configuration of RS485-2 for Panel Bus, the communication rate is
set to 115.2 kbps, and the max. cable length is hence 2400 ft (731.52 m).
* Other supported sensor types are: NI1000 TK6180 DIN, NI1000 TK5000 DIN, PT1000-1, PT1000-2, BALCO500. Refer
to CIPer Model 50 Controller – Installation and Commissioning Instructions 31-00233, for more details.
NOTE: For more details on the licenses, please refer to the Release Bulletin.
9 31-00197-02
CIPerTM MODEL 50 CONTROLLER — PRODUCT DATA
DIMENSIONS
8.4”(215.5) 2.4”(57.5)
1.94”(49.5)
2 1 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47
RS232
BIAS
END
MID
GND1
485-1-
485-2-
GND2
485-1+
485-2+
GND
UI10
n.a.
n.a.
n.a.
BI1
UI1
UI9
BI2
BI3
BI4
UI2
UI3
UI4
UI5
UI6
UI7
UI8
RS485-1
GND
24V-0
DO1
AO1
DO2
DO3
DO4
DO5
DO6
DO7
DO8
AO2
AO3
AO4
24V~
IN4
IN5
IN6
IN7
IN8
IN
1 2 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Figure 10: CIPer Model 50 controller (w/o HMI but with RJ45 socket for connection of portable HMI, and
with full complement of onboard I/Os), dimensions inches (mm)
8.4” 2.4”
(215.5) (57.5)
J1 J8
2.05”
(52)
Figure 11: CIPer Model 50 controller with covers, dimensions inches (mm)
NOTE: Use of the covers (MVC-80-AC1) will obstruct access to the Ethernet, USB 2.0, and RS232 interfaces.
The material in this document is for information purposes only. The content and the product described are subject to change w ithout notice. Honeywell makes
no representations or warranties with respect to this document. In no event shall Honeywell be liable for technical or editorial omissions or mistakes in this
document, nor shall it be liable for any damages, direct or incidental, arising out of or related to the use of this document . No part of this document may be
reproduced in any form or by any means without prior written permission from Honeywell.