You are on page 1of 8

YQ211890

Orders to record

Orders to record...................................................................................................................

1. Product overview.............................................................................................................

1.1 Overview of the Outdoor Integrated Cabinet................................................

1.2 Structure Overview.................................................................................................

1.3 Cabinet Features.....................................................................................................

1.4 Main technical indicators..................................................................................

1.4.1 Cabinet Parameters.......................................................................................

1.4.2 Environment Requirements..........................................................................

1.4.3 Rated voltage.................................................................................................

2.Installing and Securing the Cabinet........................................................................

3. Use and maintain the cabinet.......................................................................................

3.1 Use of the Cabinet.................................................................................................

3.1.1 Use of cabinet threshold devices..........................................................

3.1.2 Use of cabinet Door locks........................................................................

3.1.3 Use and Maintenance of the heat dissipation Device......................

3.2 Grounding the Cabinet...........................................................................................

3.3 Cabinet Maintenance...............................................................................................

4. Packaging, storage and transportation..................................................................

5. List of spare parts and special tools required for cabinet maintenance

...................................................................................................................................................

-2-
YQ211890
1. Product overview

1.1 Overview of the Outdoor Integrated Cabinet

The cabinet is made of metal or non-metal materials and is directly under the influence of climate
environment. The operator is not allowed to enter the cabinet.Communication equipment, transmission
equipment, power supply equipment, monitoring equipment, batteries and other supporting equipment
can be installed inside the device, which can provide reliable mechanical and environmental protection
for the normal operation of internal devices.

1.2 Structure Overview

1.2.1 Double cabin cabinet


The outer and inner panels of the outdoor integrated cabinet are galvanized steel plates, and the
interlayer is 45mm heat insulation material.The equipment bay can support a maximum of 40U
installation space.
Dimensions of the cabinet: 2100mm x 1800mm x 900 mm.Inner size: 1800mm×1700mm× 800mm
Figure 1-1 shows the front of the two cabinets

Figure 1-2 shows the internal structure of the two cabinets

-3-
YQ211890

The

Cabi

air
Elect

The

Figure 1-2

1.3 Cabinet Features

 Built-in structure design, effectively ensure the cabinet door is pry.


 Column mounts support 19 - and 21-inch interchanges.
 Protection grade IP55, effectively prevent rainwater leakage.
 The cabinet adopts the assembled structure design, which can effectively meet the
requirements of bulk delivery and package delivery.
 The door lock adopts outdoor cabinet special mechanical lock, three-point locking
structure, to provide reliable security protection for the cabinet.
 The cabinet is installed on the ground.

1.4 Main technical indicators

1.4.1 Cabinet Parameters

 The maximum dimensions inside the cabinet are 1800mm x 1700mm x 800mm

-4-
YQ211890
 Equipment bay: The equipment bay can support a maximum of 40U equipment installation
space.

1.4.2 Environment Requirements

 Ambient temperature: -40 ° C to +55 ° C


 Storage temperature: -40℃ ~ +70℃
 Relative humidity: 5%-95% RH
 Atmospheric pressure: 54kPa ~ 101kPa (approximately 0m ~ 5000m above sea level)
 Total solar radiation intensity: ≤1120× (1±10%) W/m2

1.4.3 Rated voltage

 Ac 220-240V to 50/60Hz

2.Installing and Securing the Cabinet

2.1 Cabinet Installation

Figure 2-1 shows the mounting holes for a cabinet base.

Figure 2-1

-5-
YQ211890
3. Use and maintain the cabinet

3.1 Use of the Cabinet

3.1.1 Use of cabinet threshold devices

When opening the cabinet door, the limiting device automatically realizes the limiting
function. When closing the door, please gently lift the limiting device to cancel the
limiting function.

When the door is


opened to the
maximum, it will
fall into the card

3.1.2 Use of cabinet Door locks

3.1.2.1 Anti-theft design of door locks


A、The anti-destructive use of anti-theft lock meets the B-level requirements in GA/T
73-1994 Mechanical Anti-theft Lock, as shown in the figure.

B. Three-point anti-theft lock and door frame

-6-
YQ211890

3.1.3 Use and Maintenance of the heat dissipation Device

The outdoor integrated cabinet uses a 1500W AC compressor for heat dissipation. For
details, see the manual delivered with the air conditioner.

3.2 Grounding the Cabinet

(1)A cabinet is equipped with a ground bar. The ground bar is an anticorrosive coated
copper bar with a cross-sectional area of 50mm2. Ten appropriate screw holes and screws
are reserved.See Figure 3-2

Figure 3-2

3.3 Cabinet Maintenance

 Light maintenance: Open the door and check whether the light is on normally.Check
whether the wiring is damaged and the lamp plug is off.See Figure 3-3

-7-
YQ211890

LED

Figure 3-3

4. Packaging, storage and transportation

After packaging, the product can be transported by car, train, ship, plane, etc.Avoid
collisions, falls, direct exposure to rain and snow, and sun exposure during
transportation.
Products should be stored in well-ventilated, dry warehouse, there should be no
corrosive gases around, storage temperature of -40℃ ~ +70℃.

5. List of spare parts and special tools required for cabinet maintenance

The serial
Spare part/tool name The number of
number

Electric hand drill (12V)


1 1
With battery, cross head

2 Grand cross screwdriver 2

3 Small flat-head screwdriver 2

4 Vice pliers 1

5 Wire stripper 1

6 Needle nose pliers 1

-8-
YQ211890

7 Multipurpose meter 1

-9-