You are on page 1of 6

2020 FORTEI-International Conference on Electrical Engineering (FORTEI-ICEE)

Design of Battery Energy Storage System Control


Scheme for Frequency Regulation for PV Integrated
Power System
Izzuddin Fathin Azhar Lesnanto Multa Putranto Sasongko Pramono Hadi
Department of Electrical and Department of Electrical and Department of Electrical and
Information Engineering Information Engineering Information Engineering
Universitas Gadjah Mada Universitas Gadjah Mada Universitas Gadjah Mada
Yogyakarta, Indonesia Yogyakarta, Indonesia Yogyakarta, Indonesia
izzuddin.fathin.azhar@mail.ugm.ac.id lesnanto@ugm.ac.id sasongko@ugm.ac.id

Abstract— The penetration of intermittent renewable energy United States and Canada [7], South Australia [8], and Europe
sources (IRES) will affect the power balance between generation [9]. During under frequency events, the frequency stability
and load, which can disturb the stability of the frequency in the can be maintained by regulating generator dispatches,
system. Ancillary service that can be used to increase frequency performing load shedding, or activating ancillary services.
stability due to IRES penetration is a battery energy storage
system (BESS). This paper discusses the effect of BESS One of the ancillary services used to improve frequency
implementation on the performance of frequency stability due stability is energy storage technologies such as battery energy
to interference from the generation of IRES. Tests carried out storage systems (BESS) [10]. BESS can be used as energy
on the IEEE 9 bus system modified with IRES generator in the management and frequency regulation. In frequency
form of photovoltaic (PV). The control circuit in BESS that is regulation, BESS uses a control circuit with an algorithm that
used is virtual inertia control as inertial response (IR) unit and will initiate a frequency response when the frequency
droop control as primary frequency response (PFR) unit. The decreases by its threshold value [11], hence it will supply
results show that BESS as a support unit for frequency active power in response to the event. Thus, the frequency
regulation can reduce the frequency nadir of the system from deviation that occurs due to the disturbance of load imbalance
49.49 Hz to 49.80 Hz. The rate of change of frequency (RoCoF) becomes smaller [12].
value is reduced from 0.270 Hz/s to 0.078 Hz/s. The steady-state
frequency value also approaches the reference frequency value An analysis of the feasibility of BESS is carried out as a
of 50 Hz from 49.80 Hz to 49.89 Hz. support unit for frequency regulation in [13]. The researcher
analyses characteristics and types of batteries that are suitable
Keywords—Frequency Stability, Battery, Energy Storage for frequency regulation. Moreover, BESS installation is
System, Frequency Nadir. performed to support fast inertial frequency response in [14].
BESS is used as a unit that provides an inertia response that
I. INTRODUCTION
affects the rate of change of frequency (RoCoF) with simple
The increment of gas emission has a global impact due to loop control added in the converter’s power control.
the influence of various fields, one of which is the electricity Meanwhile, The free governor mode of operation has been
system. For the environmental consideration, renewable added in power system generators for supporting the
energy source (RES) technologies are used, including the frequency stability in [15]. The researchers [16] determined
IRES such as wind and solar generation, as shown through the the size of BESS as a unit for an inertial response (IR) and
energy mix target set by several countries such as Indonesia primary frequency response (PFR). The BESS contribution is
has targeting RES of 23% in 2025 and 31% in 2050 [1]. China obtained by setting the inertia constant and the droop gain
has also targeting RES at 20% by 2030 [2], while Germany magnitude. In [17], it uses virtual inertia and frequency droop
has a RES target of 30% in 2020 and 60% in 2050 [3]. There control in the photovoltaic generation for supporting
are two types of RES, dispatchable and intermittent. frequency stability. Virtual inertia control is used to decrease
Dispatchable RES means the output can be regulated, while the rate of change of frequency when a disturbance occurs,
the intermittent RES cannot be regulated because of the while frequency droop control is used for improving the
uncertainty in energy production. An accidental phenomenon frequency after the disturbance has occurred. In [18], the
like cloud cover in photovoltaic (PV) can affect on decrement virtual inertia control circuit is applied to BESS to support the
of PV power output, as found in [4]. The nature of the PV high penetration of IRES generators on islanded microgrids.
intermittence can affect the stability of the system, especially Something similar is done in [19], which combines droop
in frequency stability. control and virtual inertia control on the microgrid.
One aspect of the stability of an electric power system is This paper focuses on BESS control modeling as a support
frequency stability [5]. Frequency stability is defined as the unit for frequency regulation with IR and PFR control based
ability of an electrical power system to maintain the frequency on conventional generator droop control and swing equation
value of a disturbance that causes an imbalance between of synchronous machine, instead of using photovoltaic for
power generation and load. If the frequency stability of the frequency regulation circuits for compensating the
system is not maintained, it might cause the system to intermittence of PV generation. The modified IEEE 9-bus test
collapse. In this situation, under or over frequency relay would system having a PV generating unit is used as the test system
be active and some generator might be shutdown. If this for demonstrating the merit of the control method. In this test
continues, it can lead to blackouts. For example, there system, BESS is placed on the same bus as PV. The drop of
occurred in some regions such as Hokkaido Japan. [6], the

978-1-7281-9434-9/20/$31.00
Authorized IEEEUniv. Downloaded7on June 21,2021 at 15:28:44 UTC from IEEE Xplore. Restrictions apply.
©2020State
licensed use limited to: San Francisco
25% of PV power output fluctuation is simulated for
triggering the frequency deviation. The drop of 25% of PV
power output is based on [4], which occurs due to cloud cover.
The frequency response shows that the BESS implementation
decreases the frequency nadir and steady-state frequency
deviation.
II. BATTERY ENERGY STORAGE SYSTEM FOR FREQUENCY
REGULATION

A. Energy Storage System


Some of the energy storage system (ESS) technologies
shown in Fig. 1, such as a battery, pumped hydro storage,
supercapacitor, flywheel, compressed air energy storage, and
power-to-gas, have its characteristics that are used for certain
purposes [10]. Applications that can be implemented with
ESS technology are generally divided into three such as in
generation side, network operators or systems, and on the user
side. ESS technology as frequency regulation requires
technology with a response of some seconds to hours and the
power required is around 10 kW to 100 GW. So, battery Fig. 1. Comparison of energy storage technology [10].
technology is chosen that has a response time in the resolution
of seconds to days with a power capacity of about 1 kW to 100 TABLE I. COMPARISON OF BATTERY TECHNOLOGIES
GW. BESS
Lead-acid Li-ion Ni-Cd Na-S
technology
B. Battery Energy Storage System
Power capacity 0-40 0-50
0-100 [13][23] 0-100 [13][23]
Battery energy storage system (BESS) technology can be (MW) [13] [13][23]
used for several purposes, such as a power supply unit (UPS) Energy capacity
0,25-50 [23] 0,25-25 [23]
0-75 0-300
for improving power quality, transmission service operator (MWh) [24] [23]
(TSO), distribution service operator (DSO), energy millisec millisec
milliseconds milliseconds onds onds
management including load shifting, and as large-scale energy Time response
[13][23][24] [13][23][24] [13][23] [13][23]
storage. In the application of BESS, frequency regulation can [24] [24]
be used to control active power output faster than conventional 10-15
Lifetime (year) 5-15 [23][25] 5-15 [23][25] >10 [25]
power plants because BESS has no mechanical inertia and [23]
delay. Therefore, the addition of BESS to the network can 500- 300-500
Energy capital 200-600 1200-4000
1500 [13][24]
make the frequency deviation smaller [12]. cost ($/kWh) [24][26] [26]
[26] [26]
The batteries in UPS applications and power quality
C. Primary Frequency Response Control
improvement require some criteria, such as having a response
at seconds to minutes resolution, high power capacity to meet In conventional plants that use synchronous generators, if
the active power requirements of the network for primary there is a spinning reserve, the plant can provide primary
regulation, long life cycles on partial cycles that refer to regulation according to its droop characteristics. The control
battery age under the pattern certain discharges, low battery of the PFR can be modeled with the attributes of the droop, as
cycle costs, and fast response to meet active power output in a shown in (1) [27].
short time [13]. ∆
= (1)
TABLE I shows several types of battery technology, such ∆
as lead-acid, Ni-Cd, NaS dan Li-Ion. Ni-Cd and NaS are With,
widely applied to improve network stability. Li-ion battery is = droop gain (pu)
a type of battery that can also be used for UPS applications
∆ = frequency deviation (Hz)
because of its high performance. However, this type of battery
requires expensive costs, so it is not suitable to use on certain ∆ = power generation deviation (MW)
occasions. In (1) is shown a proportional relationship between
Lead-acid batteries are widely used in various industries. changes in frequency and power generation. If there is a
Lead-acid batteries in the Alaska electrical system are used for frequency change in the system, the generator will
a 0.5-second frequency response in an emergency, as compensate for these changes by changing the power
mentioned in [20]. Lead-acid batteries are also used for generation to follow its droop regulations. Thus, the PFR at
frequency regulation in the 8.5 MWh system at the BEWAG BESS is modeled with the proportional controller, as in (2).
plant, Berlin, Germany [21], the 4 MWh ESCAR system at the The power contributed by BESS changes following the
Iberdrola Technology Demonstration Center, Madrid, Spain, frequency deviation between the reference frequency 50
the 14 MW h 1.5 h system at PREPA, Puerto Rico, and the 40 Hz and measurement frequency in point of common
MWh system in Chino, California, United State [22]. coupling (PCC). It is also affected by the number of gain
control in PFR controller, which affects the slope
between power and frequency.

Authorized licensed use limited to: San Francisco State Univ. Downloaded8on June 21,2021 at 15:28:44 UTC from IEEE Xplore. Restrictions apply.
1 1
= ( − = ∆ (2)

With,
= power contribution from PFR (pu (MW))
= gain of PFR
= frequency (Hz)
= nominal frequency (Hz)
D. Inertial Response Control
In controlling virtual inertia, energy is obtained from dc- Fig. 2. Frequency Controller Model of BESS
links in the form of capacitors [28]. Balancing power between given to maintain the value of ∆ remains zero after the
the energy source and the grid inverter is done by charging initiation of power flow [12]. The power injection output from
and discharging the capacitors. Thus, the dynamic behavior of PFR and IR is limited to a value between pmax and pmin.
the inverter dc-link capacitor can resemble the characteristics
of the rotational inertia that rotates on the synchronous III. SIMULATION SETUP
generator as in (3). Another component to produce virtual
The test system uses IEEE 9 bus, which has 3 synchronous
inertia is in the form of a dc-current source to supply the
generators. However, in this research, 1 synchronous
amount of energy needed. Because the energy stored in the
generator is replaced with PV, as shown in Fig. 3. This system
capacitor alone is not enough to provide an inertia response,
is modeled in PowerFactory. There are 10 ac buses, 1 dc bus,
so it needs another additional energy source such as BESS.
3 loads, 4 transformers, 2 synchronous generators, 1 PV
− (3) system, 1 converter, and 1 battery. The voltage levels are 230,
= 18, 16.5, 13.8, 0.9 and 0.4 kV. BESS is placed on bus 9 which
2
is close to the PV system.
With,
Active power on Load A is 125 MW, Load B is 90 MW,
= grid frequency (Hz) and Load C is 100 MW. G2 is regulated as a voltage-
= time (s) controlled bus with a voltage magnitude of 1.025 V and a
= mechanical power (pu) voltage angle of 00. G1 is regulated as a reference bus with a
= electrical power (pu) voltage magnitude of 1.04 V and a voltage angle of 00. G2 is
= inertia constant (s) dispatched at 80 MW, while the PV system has a dispatch
The contribution of IR to BESS can be defined based on approaching 50% of the total system load, in this case, 150
the swing equation (3). Hence, it becomes in (4) and (5). MW with a power factor of 1.
Power contribution from IR is produced with following
The nominal frequency of the system is 50 Hz. G1 uses the
the change of frequecy deviation in power network and
HYGOV governor model for representing the hydro-
corresponding to gain control of IR .
generator, and G2 uses the GAST governor model for
∆ (4) representing the gas turbine generator [29], each model uses a
=2∙ ∙ 5% droop setting [30]. Other parameter values are typical in
PowerFactory.
∆ (5)
= ∙ PFR will be active when a frequency deviation exceeds ±
20 mHz or ± 0.0004 pu [31]. When a frequency deviation
The model is a derivative controller circuit. Hence, a filter occurs at ± 200 mHz or ± 0.004 pu [31] then BESS must send
is added as in (6) with a value of 1 s as for stability [18]. the maximum power or as the nominal power. So, the amount
s of droop or gain from PFR setting is 0.0036 pu and the
= ∆ (6) dead band is 0.0004 pu. the gain in this study was set at
1 s
500, and the dead band for IR is 0.001 pu [32].
With,
= power contribution from IR (pu (MW))
= inertia constant of IR control (s)
= rate of change of frequency (RoCoF) (Hz/s)
= gain control of IR
= filter time constant of IR
= time (s)
s = Laplace operator
E. Frequency Controller Model
Based on (2) and (6), a model can be formed for the BESS
frequency control circuit shown in Fig. 2. Deadband blocks
are given to make BESS work only if the frequency value is
outside the set dead band limit [16]. The offset block is
Fig. 3. Modified IEEE 9 Bus System with PV and BESS

Authorized licensed use limited to: San Francisco State Univ. Downloaded9on June 21,2021 at 15:28:44 UTC from IEEE Xplore. Restrictions apply.
The flowchart in this study is shown in Fig. 4. The TABLE II. PARAMETER VALUE OF BESS
simulation is done in 900 seconds. Disturbance simulation
Parameter Value
conducted in the form of loss of power on the PV system by
Capacity of each cell 200 Ah
25% of the power generated is 150 MW to 112.5 MW at 5 Min. voltage of empty cell 12 V
seconds. There are four test scenarios observed, such as Max. voltage of full cell 13.5 V
without using BESS, with IR control of BESS, with PFR Number of series connected cells 60
control of BESS, and with IR and PFR controls of BESS. Number of parallel connected cells 78
When under normal conditions, BESS is set not to provide Internal resistance of cell 0.001 ohm
Nominal of BESS voltage 810 V
power to the system. BESS only works when frequency
deviations exceed the dead band values of each PFR and IR ∙
control. It will also be observed how each control influences ℎ = (9)
to verify the performance of each control set if it works 3600 ∙ ∙
individually. From (9), the energy capacity of BESS is 12.5 MWh. It is
The parameter of BESS is shown in TABLE II. The power equal to 197.85 Ah per cell with 810 V of BESS nominal
capacity of BESS can be calculated as (7) [16]. voltage. Using a battery with a capacity of 200 Ah per cell, a
battery energy capacity of 12.64 is obtained.
Δ
=− (7) The analysis carried out is to look at the system frequency
Δ response after a disturbance, and compare the value of the
Where, frequency nadir, overshoot, and steady-state error for each
scenario on buses 9. G1 and G2 power generation was also
= power/frequency characteristic (MW/Hz) observed to see the effect of BESS.
Δ = change of active power (MW)
IV. RESULT AND ANALYSIS
Δ = change of frequency from nominal frequency (Hz)
A. Impact on System Frequency Response
Because of power loss in PV system by 37.5 MW and the The recapitulation of the simulation result is shown in
steady-state frequency target by 49.8 Hz, so the power TABLE III. The minimum frequency limit is 49.5 Hz based
capacity of BESS ( ) is shown in (8) [10][16]. on manual load shedding operation in the Java-Madura-Bali
= ∙ ∙ (8) system [30], while the steady-state frequency limit is 49.8 Hz
[30]. The RoCoF is measured every 500 ms after a disturbance
From (8), the power capacity of BESS is 33.75 MW. Instead occurs based on ENTSO-E standard [36]. The RoCoF limit is
of using 33.75 MW, in this research will be used 36 MW 0,5 Hz/s [37].
power capacity of BESS based on the lead-acid As shown in TABLE III and Fig. 5, the frequency nadir
implementation in Texas [33]. after implementation of BESS is reduced. The frequency nadir
In this research, it is assumed that BESS has a depth of for without the BESS scenario is 49.49 Hz, which exceeds the
discharge (DOD) of 80% [34], efficiency ( ) of 90% minimum frequency limit. After BESS implementation, with
[22], and BESS is used to provide primary frequency reserve IR control only, the frequency nadir reduces to 49.62 Hz,
for 900 seconds ( ) [35]. The energy capacity of BESS while the frequency nadir with PFR only on BESS reduces to
( ℎ ) can be calculated as (9). 49,84 Hz. The best configuration is combining IR and PFR
control, which can reduce the frequency nadir to 49,86 Hz.
The steady-state frequency of without BESS scenario and IR
control only of the BESS scenario is 49.8 Hz, which coincides
with the steady-state frequency limit. With IR control only,
BESS will reduce the RoCoF value, which is correspondence
to the system inertia response, so the deviation of steady-state
frequency is not decreased. When the control of BESS
includes PFR control, the deviation of steady-state frequency
will be decreased because of the addition of power injected by
PFR control in BESS. The steady-state frequency of with PFR
control only of the BESS scenario and with IR and PFR
controls of the BESS scenario is 49.89 Hz.
The RoCoF simulation result, as shown in TABLE III and
Fig. 6, is calculated by using the backward difference
approximation from the frequency response, as shown in Fig.
5 with a time sampling of 500 ms, as mentioned before. It
TABLE III. SIMULATION RESULT OF FREQUENCY RESPONSE

Freq. Steady
RoCoF
Scenario nadir state freq.
(Hz/s)
(Hz) (Hz)
without BESS 49.49 49.80 0.270
with IR BESS 49.62 49.80 0.111
with PFR BESS 49.84 49.89 0.098
Fig. 4. Workflow of research with IR and PFR BESS 49.86 49.89 0.078

10on June 21,2021 at 15:28:44 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: San Francisco State Univ. Downloaded
50.1 40

Active Power (MW)


50 30
Frequency (Hz)

49.9
49.8 20
49.7 10
49.6 0
49.5
-10
49.4 0 5 10 15 20 25
0 20 40 60 80 100 120 140 160 180
Time (second)
Time (second)
with IR BESS with PFR BESS
without BESS with IR BESS
with IR and PFR BESS
with PFR BESS with IR and PFR BESS
Fig. 7. Power contribution from BESS in each scenario
Min. freq. limit
Fig. 5. Frequency response simulation result 100

Active Power (MW)


0.1 95
0 90
without BESS
-0.1 85
RoCoF (Hz/s)

with IR BESS 80
-0.2
75
-0.3 with PFR BESS 0 5 10 15 20 25
-0.4 Time (second)
with IR and
-0.5 PFR BESS without BESS with IR BESS

-0.6 RoCoF limit with PFR BESS with IR and PFR BESS
0 5 10 15 20 25 Fig. 8. Power contribution from G1 in each scenario
Time (second)
130
Active Power (MW)

Fig. 6. RoCoF simulation result


120
shows that when the frequency drops to its nadir value, the 110
RoCoF value is negative. Then, it starts to increase when the 100
frequency response has reached the nadir value and begins to
90
rise to the steady-state condition.
80
All scenarios have RoCoF values below the RoCoF limit. 0 5 10 15 20 25
The weakest RoCoF is shown in without the BESS scenario, Time (second)
while the best configuration, which has the lowest RoCoF
value, is shown in with IR and PFR control of the BESS without BESS with IR BESS
scenario. When the BESS is not implemented in the system, with PFR BESS with IR and PFR BESS
the RoCoF value is 0,270 Hz/s, while the BESS is
implemented with IR and PFR controls the RoCoF value is Fig. 9. Power Contribution from G2 in each scenario
reduced to 0,078 Hz/s.
the period of the inertia response. BESS will affect the power
B. Impact on Power Generation generated by other generators such as G1 and G2, as shown in
The power drop of the PV system in the fifth second makes Fig. 8 and Fig. 9. The power generation in the inertia response
the BESS’s frequency control strategy and free governor period is decreased after BESS has been implemented in the
response of the generators active, as shown in Fig. 7, Fig. 8, system. The addition of PFR BESS control reduces the power
and Fig. 9. The power injected by BESS, G1, and G2 increases generated by G1 and G2.
simultaneously to compensate for the power generation
disturbance in the power system network. The loss in power V. CONCLUSION
generation makes the frequency of the power system network This paper discussed the impact of BESS implementation
starting to drop. As shown in (3), when there is a difference in as frequency regulation support due to the intermittencies of
active power in the system, it makes the power system’s IRES, especially power loss in the PV system. There are four
frequency changed, as shown in Fig. 5 and Fig. 6. scenarios tested to evaluate the effect of the control circuit on
BESS, such as inertial response control and primary frequency
The comparison of power generation by BESS in each
response control. Based on the result, the IR control of BESS
control scenario is shown in Fig. 7. When BESS only operates
will support only in a short period. The RoCoF value is
with IR control, BESS will only give active power to the
reduced from 0.270 Hz/s to 0.078 Hz/s. The PFR control will
system in a short period, which is the inertia response period.
support for a longer period, in this case, for 900 seconds. The
In this case, it is about 20 seconds. With PFR control, BESS
deviation of steady-state frequency is reduced from 49.8 Hz to
can supply active power in the primary frequency response
49.89 Hz, and the frequency nadir is reduced from 49.49 Hz
period. So, more BESS energy is produced. The combination
to 49.86 Hz. So, the addition of IR and PFR controls to BESS
of IR and PFR controls will increase the power generation in
shows the effectiveness of frequency support by BESS. For

11on June 21,2021 at 15:28:44 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: San Francisco State Univ. Downloaded
future work, the gain control of IR can be optimized for better response and primary frequency reserve,” IEEE Trans. Power Syst.,
frequency regulation in the system. vol. 31, no. 5, pp. 3447–3456, 2016, doi:
10.1109/TPWRS.2015.2503565.
ACKNOWLEDGMENT [17] Z. Jietan, Q. Linan, R. Pestana, L. Fengkui, and Y. Libin, “Dynamic
Frequency Support by Photovoltaic Generation with ‘Synthetic’ Inertia
This work was funded by the Rekognisi Tugas Akhir and Frequency Droop Control,” 2017 Energy Internet Energy Syst.
(RTA) Program of the Research Directorate of Universitas Integr., pp. 1–6, 2017.
Gadjah Mada based on letter no. 2607/UN1/DITLIT/DIT- [18] T. Kerdphol, F. S. Rahman, Y. Mitani, M. Watanabe, and S. Kufeoglu,
LIT/PT/2020 about Pemberitahuan Pemenang Program “Robust Virtual Inertia Control of an Islanded Microgrid Considering
High Penetration of Renewable Energy,” IEEE Access, vol. 6, no.
Rekognisi Tugas Akhir Tahun 2020. Any opinions, February, pp. 625–636, 2018, doi: 10.1109/ACCESS.2017.2773486.
conclusions, or recommendations expressed in this paper are
[19] I. Serban and C. Marinescu, “Battery energy storage system for
those of the authors and do not necessarily reflect those of the frequency support in microgrids and with enhanced control features for
Research Directorate of Universitas Gadjah Mada. uninterruptible supply of local loads,” Int. J. Electr. Power Energy
Syst., vol. 54, pp. 432–441, 2014, doi: 10.1016/j.ijepes.2013.07.004.
REFERENCES [20] National Grid, Enhanced Frequency Control Capability (EFCC).
[1] Pemerintah Republik Indonesia, Peraturan Pemerintah Republik National Grid, 2015.
Indonesia No. 79 tahun 2014 Tentang Kebijakan Energi Nasional. [21] R. Wagner, “Large lead/acid batteries for frequency regulation, load
2014. levelling and solar power applications,” J. Power Sources, vol. 67, no.
[2] J. K. He, “China’s INDC and non-fossil energy development,” Adv. 1–2, pp. 163–172, 1997, doi: 10.1016/S0378-7753(97)02509-3.
Clim. Chang. Res., vol. 6, no. 3–4, pp. 210–215, 2015, doi: [22] H. Chen, Y. Xu, C. Liu, F. He, and S. Hu, Storing Energy in China-An
10.1016/j.accre.2015.11.007. Overview. Elsevier Inc., 2016.
[3] International Energy Agency, Germany 2020. OECD, 2020. [23] M. Faisal, M. A. Hannan, P. J. Ker, A. Hussain, M. Bin Mansor, and F.
[4] A. Bonkaney, S. Madougou, and R. Adamou, “Impacts of Cloud Cover Blaabjerg, “Review of energy storage system technologies in microgrid
and Dust on the Performance of Photovoltaic Module in Niamey,” J. applications: Issues and challenges,” IEEE Access, vol. 6, no. 1, pp.
Renew. Energy, vol. 2017, no. 2013, pp. 1–8, 2017, doi: 35143–35164, 2018, doi: 10.1109/ACCESS.2018.2841407.
10.1155/2017/9107502. [24] X. Fan et al., “Battery Technologies for Grid-Level Large-Scale
[5] P. Kundur et al., “Definition and Classification of Power System Electrical Energy Storage,” Trans. Tianjin Univ., vol. 26, no. 2, pp. 92–
Stability IEEE/CIGRE Joint Task Force on Stability Terms and 103, 2020, doi: 10.1007/s12209-019-00231-w.
Definitions,” IEEE Trans. Power Syst., vol. 19, no. 3, pp. 1387–1401, [25] M. Morris, “Comparison of Rechargeable Battery Technologies,”
Aug. 2004, doi: 10.1109/TPWRS.2004.825981. ASME Early Career Tech. J., no. November 2012, pp. 1-5,7, 2012,
[6] OCCTO, “The Investigation Committee on the Major Blackout by the [Online]. Available:
2018 Hokkaido Eastern Iburi Earthquake Final Report,” 2018. https://www.researchgate.net/publication/281931837_COMPARISO
[Online]. Available: N_OF_RECHARGEABLE_BATTERY_TECHNOLOGIES.
https://www.occto.or.jp/iinkai/hokkaido_kensho/files/Final_report_ho [26] D. Akinyele, J. Belikov, and Y. Levron, “Battery storage technologies
kkaido_blackout.pdf. for electrical applications: Impact in stand-alone photovoltaic
[7] U.S.-Canada Power System Outage Task Force, “Final Report on the systems,” Energies, vol. 10, no. 11, 2017, doi: 10.3390/en10111760.
August 14, 2003 Blackout in the United States and Canada: Causes and [27] D. Barus, “Implementation of Free Governor Action in Power Plant to
Recommendations,” U.S.-Canada Power System Outage Task Force Increase System Resilience of Jawa Bali Power System Network,”
March, 2004. [Online]. Available: Chart, no. September, pp. 1–5, 2010.
https://reports.energy.gov/BlackoutFinal-Web.pdf. [28] X. Huang, K. Wang, G. Li, and H. Zhang, “Virtual inertia-based control
[8] Australian Energy Market Operator, Black system South Australia 28 strategy of two-stage photovoltaic inverters for frequency support in
September 2016: final report. Australian Energy Market Operator, islanded micro-grid,” Electron., vol. 7, no. 11, 2018, doi:
2017. 10.3390/electronics7110340.
[9] Union for the Coordination of the Transmission of Electricity, Final [29] H. Seifi and H. Delkhosh, Model Validation for Power System
Report System Disturbance on 4 November 2006 union for the co- Frequency Analysis. 2019.
ordination of transmission of electricity. Union for the Coordination of [30] Menteri Energi dan Sumber Daya Mineral Republik Indonesia,
the Transmission of Electricity, 2007. Peraturan Menteri ESDM No. 3 Tahun 2007 tentang Aturan Jaringan
[10] Asian Development association, Handbook on Battery Energy Storage Sistem Tenaga Listrik Jawa-Madura-Bali. 2007.
System, no. December. 2018. [31] ENTSO-E, “P1: Load-Frequency Control and Performance,” 2009.
[11] E. Hsieh and R. Johnson, “Frequency Response from Autonomous [Online]. Available:
Battery Energy Storage,” 2012 Grid Futur. Symp., pp. 1–7, 2012. https://www.entsoe.eu/fileadmin/user_upload/_library/publications/en
[12] DIgSILENT GmbH, “DIgSILENT PowerFactory Application tsoe/Operation_Handbook/Policy_1_final.pdf.
Example Battery Energy Storing Systems,” Batter. Energy Storing [32] P. Peltoniemi, O. Pyrhönen, J. Savolainen, R. Weiss, and R. Pasonen,
Syst., pp. 1–28, 2010, [Online]. Available: “Frequency regulation possibilities of power-to-gas plants in grids
https://www.digsilent.de/en/faq-reader-powerfactory/do-you-have-an- including high shares of renewable energy production,” 10th Int.
application-example-for-a-battery-energy-storage-system-bess.html. Renew. Energy Storage, IRES 2016, 2016.
[13] Y. K. Wu and K. T. Tang, “Frequency support by BESS – Review and [33] T. Fenimore, “Energy Storage at Duke Energy.” Duke Energy, 2014.
analysis,” Energy Procedia, vol. 156, no. September 2018, pp. 187– [34] J. Garcia, Analysis and Design of Hybrid Energy Storage Systems.
198, 2019, doi: 10.1016/j.egypro.2018.11.126. MDPI, 2020.
[14] S. M. Alhejaj and F. M. G. Longatt, “Investigation on Grid-Scale BESS [35] Y. Rebours and D. S. Kirschen, “A Survey of Definitions and
Providing Inertial Response Support,” 2016 IEEE Int. Conf. Power Specifications of Reserve Services,” 2005. [Online]. Available:
Syst. Technol., pp. 1–6, 2016, doi: http://www.ee.washington.edu/research/real/Library/Reports/Survey_
10.1109/POWERCON.2016.7754049. of_Reserve_Services.pdf.
[15] DIgSILENT Pacific, Bangladesh Power System Reliability and [36] ENTSO-E, “Rate of Change of Frequency (ROCOF) withstand
Efficiency Improvement Project Final Report Power Grid Company of capability,” 2018.
Bangladesh. Melbourne: DIgSILENT Pacific, 2017.
[37] ENTSO-e, “Supporting Document for the Network Code on
[16] V. Knap, S. K. Chaudhary, D. I. Stroe, M. Swierczynski, B. I. Craciun, Operational Security,” 2013.
and R. Teodorescu, “Sizing of an energy storage system for grid inertial

12on June 21,2021 at 15:28:44 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: San Francisco State Univ. Downloaded

You might also like