Monitoring Manual
Product Documentation
English, code: 10014119 rev. 2021.10.22
INDEX
1. SCOPE 4
2. MONITORING PROTOCOLS 4
3. CONNECTIONS 5
ETHERNET CONNECTION ON ICOM3 LARGE 5
4. MODBUS TCP/IP 6
INPUT STATUS 6
HOLDING REGISTERS 13
INPUT REGISTERS 15
5. BACNET 19
BACNET IMPLEMENTATION 19
BINARY VALUES 20
ANALOG VALUES 25
MULTI STATE VALUES 28
6. SNMP 30
OID TABLE 30
7. FAQS 40
GENERAL FAQS 40
MODBUS RELATED FAQS 40
SNMP RELATED FAQS 40
BACNET RELATED FAQS 40
2. Monitoring Protocols
All the monitoring protocols provided are over IP through a dedicated Ethernet port, that is physically disconnected from the rest of
the other controller interfaces and communicating via serial RS485 protocol with the micro processor.
The web site is available at that address. At the first access the user is guided by a “First Boot Access” wizard that forces the creation
of the web user accounts.
The following standard monitoring protocols are made available together in parallel:
➢ Modbus TCP/IP
- Port 502
- default address: 1
➢ BACnet IP v1.14
- UDP Port 47808
- default address: 1
- default device name: NHES1
➢ SNMP v2c
- UDP Port 161
- R/W community: “private”
- RO community: “public”.
The last column on every datapoints table reports the SW version from which the specific datapoint is made available.
Monitoring Port
HOLDING REGISTERS
The following Analog and Integer datapoints are available on:
- Holding Registers Command 03
Segmentation Capability:
Able to transmit segmented messages Window Size: 16
Able to receive segmented messages Window Size: 16
Network Security Options: Non-secure Device - is capable of operating without BACnet Network Security
R 0=Local On
2=Local Off
3=Remote Off
6=Manual
7=Alarm Off
Unit Status 8=Power Failure
9=Alarm On
10=Warning On
11=System Off
.1.3.6.1.4.1.476.1.42.4.3.30.1.1.0 12=Standby 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.2.0 Current Temperature Setpoint R -10.0 / + 30.0 °C; 1/10 °C 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.3.0 Unit Inlet Temperature R -40.0 / +110.0 °C; 1/10 °C 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.4.0 Evaporator Inlet Temperature R -40.0 / +110.0 °C; 1/10 °C 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.5.0 Unit Outlet Temperature R -40.0 / +110.0 °C; 1/10 °C 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.6.0 Ambient Temperature R -40.0 / +110.0 °C; 1/10 °C 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.7.0 Status of Freecooling R 0=Not Active, 1=Active 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.8.0 Evaporator Pump 1 Status R 0=N.A.,1=ON,2=Maintenance,3= 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.9.0 Evaporator Pump 2 Status R OFF,4=Alarm,5=Starting,6=Stop 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.10.0 FC Pump Status R ping 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.11.0 Freecooling Valve Position Request R 0 - 100 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.12.0 Circuit 1 Fans Speed Request R 0 - 100 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.13.0 Circuit 2 Fans Speed Request R 0 - 100 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.14.0 Reserved --- --- ---
.1.3.6.1.4.1.476.1.42.4.3.30.1.15.0 Compressor 1 Circuit 1 Status R 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.16.0 Compressor 2 Circuit 1 Status R 0=N.A.,1=ON, 2=MTN, 3=OFF, 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.17.0 Reserved --- 4=ALARM, 10=STARTING, ---
.1.3.6.1.4.1.476.1.42.4.3.30.1.18.0 Compressor 1 Circuit 2 Status R 11=LOADING,12=LOADED 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.19.0 Compressor 2 Circuit 2 Status R 13=UNLOADING,14=UNLOADED 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.20.0 Reserved --- ---
.1.3.6.1.4.1.476.1.42.4.3.30.1.21.0 Consender Pressure Circuit 1 R -100 / +500; 1/10 bar 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.22.0 Evaporating Pressure Circuit 1 R -100 / +500; 1/10 bar 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.23.0 Consender Pressure Circuit 2 R -100 / +500; 1/10 bar 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.24.0 Evaporating Pressure Circuit 2 R -100 / +500; 1/10 bar 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.25.0 Working Hours Evaporator Pump 1 R 0-32000 h 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.26.0 Working Hours Evaporator Pump 2 R 0-32000 h 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.27.0 Working Hours Evaporator FC Pump R 0-32000 h 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.28.0 Working Hours Fans Circuit 1 R 0-32000 h 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.29.0 Working Hours Fans Circuit 2 R 0-32000 h 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.30.0 Reserved --- --- ---
.1.3.6.1.4.1.476.1.42.4.3.30.1.31.0 Working Hours Comp. 1 Circuit 1 R 0-32000 h 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.32.0 Working Hours Comp. 2 Circuit 1 R 0-32000 h 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.33.0 Reserved --- --- ---
.1.3.6.1.4.1.476.1.42.4.3.30.1.34.0 Working Hours Comp. 1 Circuit 2 R 0-32000 h 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.35.0 Working Hours Comp. 2 Circuit 2 R 0-32000 h 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.36.0 Reserved --- --- ---
.1.3.6.1.4.1.476.1.42.4.3.30.1.37.0 Starts Compressor 1 Circuit 1 R 0-32000 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.38.0 Starts Compressor 2 Circuit 1 R 0-32000 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.39.0 Reserved --- --- ---
.1.3.6.1.4.1.476.1.42.4.3.30.1.40.0 Starts Compressor 1 Circuit 2 R 0-32000 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.41.0 Starts Compressor 2 Circuit 2 R 0-32000 1.0.0
.1.3.6.1.4.1.476.1.42.4.3.30.1.42.0 Reserved --- --- ---
.1.3.6.1.4.1.476.1.42.4.3.30.1.43.0 Remote On/Off Status R 0=OFF, 1=ON 1.0.0
GENERAL FAQS
Question / Issue Solution
1) Are the three monitoring protocols available - Yes they are
simultaneously?