Incomer (Substation) s# Signals sis Dis ‘Analog Measuements 1 [Active Power 2 [Reactive Power 3 [Phase current ‘4 [3 Phase voltage (Phase/Neutral) 5 [Power Factor 6 [Frequency Digital Inputs 7__ [eB oF lsolator Status (Open/Close). 2 8 ___[Proection Relay Failure 1 ‘9 |eFistatus (From Relay) 1 10 [Breaker in Service Position 1 11 [Breaker in Test Position 1 12 [Breaker inoperative 1 13 [IED Watchdog 1 14 |RTU Watchdog 1 15 |RTU's access status a 16 [DC Failure i 17__|Fire Alarm 1 18 [Communication Error 1 19 [CB on Local Mode 1 20 [CB on Remote Mode 1 21 |CBon SCADA Mode 1 22 [CB Opened - Maintenance a 23 [CB Opened - Loadshedding 1 24 [CB Opened - Faulted 1 Tele-control 25 [cB (Open/Close). 2 Outgoing (Substation) st Signals sis Dis ‘Analog Measuements T__[3 Phase current 3 Phase voltage (Phase/Neutral) Digital Inputs 1 [CB or Isolator Status (Open/Close). [Over Current Earth Fault (O/C E/F) 13 [CBonSCADA Mode 14 [CB Opened - Maintenance 15 [CB Opened - Loadshedding 16 |CB Opened - Faulted 3 a 5 [Broken Conductor 1 6 __ [Proection Relay Failure 1 7__ [Breaker in Service Position 1 8 __[Breakerin Test Position 1 9 [Breaker Inoperative 1 10 IED Watchdog. 1 11 |CBon Local Mode 1 12 [CBon Remote Mode 1 1 1 1 1 Tele-control 17___|cB (Open/Close). 1 RMU. s# Signals sis Dis ‘Analog Measuements T__[3 Phase current 3 Phase voltage (Phase/Neutral) Digital Inputs 3 [CBor Isolator Status (Open/Close). 1 ‘4 [Proection Relay Failure 1 5 [EFIStatus (From Relay) 1 6 __|leD Watchdog 1 7__[RTU Watchdog 1 8 __|RTU's access status a 9 [Communication Error 1 10 |€B on Local Mode 1 11 |€Bon Remote Mode 1 12 [CB Opened - Maintenance 1 13 [CB Opened -Loadshedding 1 14 |CB Opened - Faulted 1