Professional Documents
Culture Documents
Copyright 2010 by Dawson Technology Pty Limited. All rights reserved. This document may not be reproduced or distributed to
a third party without prior approval.
________________________
Dec-13/rev K
WARNING
Please read this entire manual and all other publications pertaining to the work to be performed
before installing, operating or servicing this equipment.
Practise all plant and safety instructions and precautions. Failure to follow instructions may result in
personal injury and/or damage to property.
WARNING
The engine, turbine or other type of prime mover must be equipped with an overspeed
(overtemperature, or overpressure, where applicable) shutdown device(s) that operates totally
independently of the prime mover control device(s) to protect against runaway or damage to the
prime mover and to protect against possible personal injury or loss of life, should the mechanical
hydraulic governor(s) or electric control(s), the actuator(s), fuel control(s), the driving mechanism(s),
the linkage(s), or the controlled device(s) fail.
In the case of generator sets, an effective monitoring system must be available to prevent damages
by overcurrent, voltage differences or reverse power.
PLEASE NOTE
This manual has attempted to provide instructions on the techniques of electronic governing and the
use of accessories, using examples and data that are believed to be accurate.
However, the examples, data and other information are intended solely as a training aid and should
not be used in any particular application without independent testing and verification by the party
performing the application.
Independent testing and verification are critical in any application, particularly where malfunction of
the equipment may result in personal injury and/or property damage.
For these reasons Dawson Technology provides no warranty of any kind, either expressed or
implied, with respect to the contents of this manual, that the examples and data used are consistent
with industry standard and that they meet the requirements of any particular application.
Dawson Technology disclaims any implied warranties for the manual’s quality, performance,
merchantability or fitness for any particular purpose. Dawson Technology also disclaims all liability
for direct, indirect, incidental or consequential damages that result from any use of the examples,
data or other information in this manual.
IMPORTANT
Correct set points must be entered into the Si-TEC Xtend module for each specific application
prior to starting the turbine.
Particular care should be taken with regard to cable shielding and power supply connections to
ensure the equipment meets all requirements specified by Dawson Technology concerning EMI.
CONTENTS
Subject Heading Page
4 Control Notes 64
4.1 Logic Inputs 65
4.2 Fixed Logic Inputs 65
4.3 Combined Alarms 67
5 PID Controls 68
5.1 P.I.D. Definitions 68
5.2 Speed PID Application 68
5.3 Performance Enhanced PID Settings 69
5.4 Multiple On Load PIDs 70
5.5 Extraction Control 72
5.6 Si-TEC Xtend CGC governor tuning sequence 78
6 Operation and Service Information 79
6.1 Actuator – MPU – Linkage Adjustments 79
6.2 AVR Bias Output set up and configuration 84
6.3 AVR Connections for voltage bias control 85
6.4 Si-TEC Xtend CGC & GSM Vector Disturbance Relay 88
8 Fault Finding 98
NOTE: This manual version (549-024 rev K) is applicable up to the Si-TEC Xtend CGC control
software program version BX_1.32 and BX1.32-NoPCU, that is current for December 2013.
1.1 Introduction
The Si-TEC Xtend CGC control module is a 32-bit pre-programmed microprocessor control
operating with a combination of designated inputs and outputs for steam turbine-generator control.
In addition to the "standard" control inputs and outputs for start/stop sequencing, speed governing,
synchronising, load control, etc., a number of inputs and outputs are provided for user application
selection. The Si-TEC Xtend CGC control module is supplied with default settings for several input
and output functions. These settings may differ for each application requirement and therefore it
may be necessary to verify all preset values prior to the initial starting of the turbine-generator.
1.2 Terminology
Preset Value: default set point value of an internal control function, which is adjustable
via the menu system for final application settings.
Mains CB: the circuit breaker(s) connecting the main bus to the incoming supply,
supply grid or utility.
Vector Disturbance: the rate of change of phase angle for detecting loss of the supply authority
(mains) grid.
HP Valve: The main control valve through which inlet steam is admitted for turbine
speed / power control.
LP Valve: The secondary control valve through which steam is passed out for
extraction pressure / process control.
1
_________________________________________________________________________
i) A three tier menu system is used. The ^ and v keys and the "Select Menu" key will
scroll you through all the menu items.
ii) Push the "Select Menu” key to enter within a "Main Menu" or a "Sub Menu".
iii) At the end of a “Sub Menu” group an "End of Sub Menu" text will appear. The ^ and v
keys will continue to operate within the "Sub Menu"
iv) To exit a "Sub Menu" press the "Select Menu" key, which will return you to the "Sub
Menu" header.
v) Pressing the v key at the last “Sub Menu” header will move to the next “Main Menu”
header.
vi) To edit the preset values it is necessary for the correct user “Access” PIN to be
entered, followed by pressing the "Reset" key. The factory shipped “Access” PIN is “3”.
vii) The factory “Access” PIN of “3” will be restored by entering “7654321” for the PIN. This
provides access in case the user forgets the PIN, and also advises the supervisor of
the change.
viii) A shortcut key is available to provide direct access to a menu item. This is possible by
pressing the "Go To Menu #" key followed by the menu item number. The menu item
number for any display screen is displayed after pressing the “Help” key. Pressing the
“Help” key a second time will exit the “Help” screen.
ix) Should the screen “Text” flash, this would indicate that a menu item value has been
altered without being saved.
x) Pressing the "Reset" key at the displayed "Active Alarm" will stop the “Back Light” from
flashing. The Shortcut "Alarm" key may be used for quick navigation of the menu.
xi) It should be noted that the "Course" adjust keys (i.e. the “large” + or – keys) do not
operate several preset menu items.
xii) Should a set point be beyond the range limit, the "Back Light" will commence flashing.
xiii) The “Fine” adjust keys (i.e. the “small” + or – keys) should be used when selecting text
items within the sub-menus, or during PID control dynamics fine-tuning.
xiv) Pressing the “Store” key will update the value of all menu items to the Si-TEC Xtend
module’s EEPROM. It is essential that the “Store” key be pressed after change in the
menu items.
The next section provides a listing (in order of display) of the Si-TEC Xtend menu items. This listing
also includes the menu tier, the menu item for direct accessing, the minimum value and the
maximum value. A detailed description of the menu items will follow this listing (section 3).
2
________________________________________________________________________
2 Si-TEC Xtend Menu Preset Items for CGC (Extraction Steam Turbines)
3
_________________________________________________________________________
053 MPU 1 and MPU 2 – signals
054 Turbine Speed and Actuator Position
4
________________________________________________________________________
Section 2.3
Menu Description Minimum Maximum Factory
Item # Set
5
_________________________________________________________________________
Section 2.4
Menu Description Minimum Maximum Factory
Item # Set
6
________________________________________________________________________
Section 2.5
Menu Description Minimum Maximum Factory
Item # Set
Speed Governor – Control Function Set Point
Parameters – Main Menu
7
_________________________________________________________________________
8
________________________________________________________________________
Section 2.6
Menu Description Minimum Maximum Factory
Item # Set
9
_________________________________________________________________________
940 dLP/dW K4 -32.767 32.767 0.000
941 dLP/dP K5 -32.767 32.767 1.000
942 LP Offset K6 -32.767 32.767 0.000
10
________________________________________________________________________
Section 2.7
Menu Description Minimum Maximum Factory
Item # Set
11
_________________________________________________________________________
12
________________________________________________________________________
Section 2.8
Menu Description Minimum Maximum Factory
Item # Set
13
_________________________________________________________________________
Section 2.9
Menu Description Minimum Maximum Factory
Item # Set
14
________________________________________________________________________
Section 2.10
Menu Description Minimum Maximum Factory
Item # Set
Logic and Analog I/O – ‘Configure’ ‘Set
Parameters’ – Main Menu
15
_________________________________________________________________________
470 CAN Module Relay RL-2 Select a Function 0 56 Not Used
471 CAN Module Relay RL-3 Select a Function 0 56 Not Used
472 CAN Module Relay RL-4 Select a Function 0 56 Not Used
473 CAN Module Relay RL-5 Select a Function 0 56 Not Used
474 CAN Module Relay RL-6 Select a Function 0 56 Not Used
475 CAN Module Relay RL-7 Select a Function 0 56 Not Used
476 CAN Module Relay RL-8 Select a Function 0 56 Not Used
16
________________________________________________________________________
17
_________________________________________________________________________
18
________________________________________________________________________
Section 2.11
Menu Description Minimum Maximum Factory
Item # Set
19
_________________________________________________________________________
20
________________________________________________________________________
Displays software type, software and hardware version, serial number, actuator type, and user info.
Note: Before powering down the Si-TEC Xtend module, it is advised that the “STORE” key be
pressed to ensure that the current Accumulated Data values are updated in the EEPROM.
21
_________________________________________________________________________
This menu item is expressed as “Gen to Bus” ratio, allowing for generators operating at 415 Vac
Ph/Ph to synchronise with a 11kVac Ph/Ph bus. For this case, the generator sensing inputs are 415
Vac and the Bus sensing inputs are 110 Vac Ph/Ph (100.00 to 1 primary/secondary ratio). The set
ratio would include for both main transformer ratio and the PT ratio. The set ratio in this instance
would be 415 / 110 = 3.77.
22
________________________________________________________________________
23
_________________________________________________________________________
Note: Should logic input 1 "Enable Run" be de-energised the Si-TEC Xtend control will provide an
immediate CB Trip Signal, de-energise the fuel solenoid and drive the actuator to zero fuel.
24
________________________________________________________________________
25
_________________________________________________________________________
Ramp to Warm Up 2 Speed / Fast Ramp to Warm Up 2 Speed - in % per sec of Rated Speed
Menu items: Ramp to Warm Up 2 Speed menu 193
Fast Ramp to Warm Up 2 Speed menu 194
M# 193 is the turbine speed ramp rate from Warmup #1 to Warmup #2 speed when the “Fast Rate”
logic input is switched “Low”. It is typically used for “Cold” start mode and is lower than M#194.
The Fast Ramp is operative if “Fast Rate” logic input is assigned as a logic input and is switched
“High”. The intent of using fast rate (M# 194) is to have steady ramp rates for normal operation and
introduce a faster ramping facility for warm turbine start up, typically higher than M#193 ramp rate.
Ramp to Idle Speed / Fast Ramp to Idle Speed - in % per second of Rated Speed
Menu items: Ramp to Idle Speed menu 199
Fast Ramp to Idle Speed menu 200
This is the turbine speed ramp rate from Warmup #2 to Idle speed. It MUST be lower than M#200.
The Fast Ramp is operative if “Fast Rate” logic input is assigned as a logic input and is switched
“High”. The intent of using fast rate is to have steady ramp rates for normal operation and introduce
a faster ramping facility for warm turbine start up. It MUST be higher than M#199.
Ramp to Rated Speed / Fast Ramp to Rated Speed - in % per second of Rated Speed
Menu items: Ramp to Rated Speed menu 207
Fast Ramp to Rated Speed menu 208
The generator set speed will increase in speed at the selected ramp rate. This applies to the no
load operation of the generator set.
The Fast Ramp is operative if the "Fast Rate" logic input is assigned as a logic input and the input
made "High". The intent of using fast rate is to have steady ramp rates for normal operation and
introduce a faster ramping facility for emergency start up.
(eg. if a steam turbine that was shutdown for less than 1 hour may be started via the “Fast Rate”)
26
________________________________________________________________________
P.I.D. DEFINITIONS
PROPORTIONAL
Proportional is the amount of correction (gain) factor required for a given speed/load error.
Proportional settings “P” range from 1 to 99
Increasing the value will increase the gain.
INTEGRAL
Integral is a correcting factor based on time, the longer the error is present, the greater the
correction. It is sometimes referred to as “Stability”.
Integral settings “I” range from 0 to 99
Increasing the value will decrease the time constant
DERIVATIVE
Derivative is the amount of correction in relation to the RATE OF CHANGE of the speed/load error.
(it is NOT the amount of error)
Derivative settings “D” ranges from 0 to 99
Increasing the value will increase the derivative.
Note: Incorrect derivative values may result in jiggling of the actuator.
The constants used for adjusting the PIDs provide for similar response change across the major
span of adjustments i.e. from 20 to 80. Beyond these values the response change to the PID
constants would require more coarse adjustments. Typically a small change in value of the PID
constants would result in a significant dynamic response change of the governing control. Also refer
to additional Speed PID section in this manual.
The Warmup 1 Proportional is the gain characteristic. Decreasing the Warmup 1 Proportional
setting will lower the sensitivity response to speed change. If the Warmup 1 Proportional is set too
high a fast oscillation of speed would result.
The Warmup 1 Integral is the stability factor of the PID and is tuned relative to the Warmup 1
Proportional (gain). A high setting of the Warmup 1 Integral would result in a slow oscillation of the
turbine at “Warm Up 1” speed. The Warmup 1 Integral is tuned in conjunction with the Warmup 1
Proportional constant to obtain the optimum steady-state speed response. The Warmup 1
Derivative value should be set to 0 for most steam turbine applications.
27
_________________________________________________________________________
The Idle Proportional is the gain characteristic. Decreasing the Idle Proportional setting will lower
the sensitivity response to speed change. If the Idle Proportional is set too high a fast oscillation of
speed would result.
The Idle Integral is the stability factor of the PID and is tuned relative to the Idle Proportional (gain).
A high setting of the Idle Integral would result in a slow oscillation of the turbine at idle speed. The
Idle Integral is tuned in conjunction with the Idle Proportional constant to obtain the optimum
steady-state speed response. The Idle Derivative should be set to 0 for most steam turbine
applications.
Note: The P.I.D. settings at the “Warm Up 2” speed are based on the interpolation between
Warmup 1 P.I.D. and Idle P.I.D. settings.
The Rated Proportional is the gain characteristic. Decreasing the Rated Proportional setting will
lower the sensitivity response to speed change. If the Rated Proportional is set too high a fast
oscillation of speed would result.
The Rated Integral is the stability factor of the PID and is tuned relative to the Rated Proportional
(gain). A high setting of the Rated Integral would result in a slow oscillation of the turbine at rated
speed. The Rated Integral is tuned in conjunction with the Rated Proportional constant to obtain the
optimum steady-state speed response. The Rated Derivative value should be set low for most
steam turbine applications (eg. 0 to 5).
To enhance dynamics tuning the actuator may be "Bumped" using the Si-TEC Xtend module. The
“Bump Magnitude” (%) is set to decrease the HP actuator position. The “Bump Duration” (seconds)
is the time duration required for the "Bump". Push the “BUMP” button on the keypad to operate the
disturbance. While this function may be used when the generator is unloaded or loaded, care must
be taken when setting the value of the magnitude and duration before the “bump” test is performed.
Do FAST RESPONSE when out of % Band is the percentage of speed error where the fast
response multipliers become active. Nominally set to 1.5%.
28
________________________________________________________________________
Negative Acting PROP. Gain Multiplier is the factor that the Rated Proportional is multiplied by
when the turbine speed is above the upper limit of the “Fast Response Band”.
Positive Acting PROP. Gain Multiplier is the factor that the Rated Proportional is multiplied by
when the turbine speed is below the lower limit of the “Fast Response Band”.
The Proportional Gain Multipliers are both nominally set to 1.5. Increasing the preset value will
increase the proportional gain when speed is outside the “Fast Response Band”. Reduce the
Proportional Gain Multipliers value if excessive actuator output overshoot is observed after a
transient, and if the Rated Proportional is optimally set. The Proportional Gain Multipliers are also
utilised during the synchronising and load control modes.
Negative Acting INTEGRAL Multiplier is the factor that the Rated Integral is multiplied by when
the turbine speed is above the upper limit of the “Fast Response Band”.
Positive Acting INTEGRAL Multiplier is the factor that the Rated Integral is multiplied by when
the turbine speed is below the lower limit of the “Fast Response Band”.
The Integral Multipliers are nominally set to 2.0. Increasing the preset value will increase the
integral response when speed is outside the “Fast Response Band”. Reduce the Integral Multiplier
values if the actuator output is unstable and if the Rated Integral is optimally set. Integral Multipliers
are also utilised during the synchronising and load control modes.
These PID settings only function in “islanded mode” operation if menu item 256 is set to ‘yes’ and
they do NOT operate when the generator is paralleled to the mains supply (grid).
Also refer to the “Speed PID” section of this manual.
29
_________________________________________________________________________
These are the P.I.D. settings controlling at 100% load. The PIDs interpolate from the Mid Point
settings to the 100% Load settings.
The following parameters need to be set for applications involving output to OEM supplied actuator
(eg. 0 – 20 mA, 0 – 5V, +/- 3.0V, +/- 5.0V, +/- 10V, 0 – 200 mA, etc.)
30
________________________________________________________________________
Extraction Proportional is the gain characteristic. Decreasing the Extraction Proportional setting
will lower the sensitivity response to the process extraction change. If the Extraction Proportional is
set too high a fast oscillation of process would result.
Extraction Integral is the stability factor of the PID and is tuned relative to the Extraction
Proportional (gain). A high setting of the Extraction Integral would result in a slow oscillation of the
PV (process variable). The Extraction Integral is tuned in conjunction with Extraction Proportional
constant to obtain the optimum steady-state speed response.
Extraction Derivative is the amount of correction in relation to the rate of change of the process
extraction error. The Extraction Derivative value should be set low for most steam turbine
applications (eg. 0 to 10).
Mode 0: Typically used in most controlled extraction steam turbine applications. Here,
the HP and LP parameters ONLY operate inside the steam map.
Mode 1: The HP and LP parameters are allowed to operate outside some areas of the
steam map.
31
_________________________________________________________________________
Non-Matched Extraction Ramp Rate is the ramp rate (%/sec) for extraction setpoint until the
extraction setpoint is reached.
Matched Extraction Ramp Rate is the ramp rate (%/sec) for extraction setpoint once the
extraction setpoint is reached.
The ramp rate % is determined / calculated based on span between the Max. Extraction Setpoint
(M# 889) and Min. Extraction Setpoint (M# 888) being equivalent to 100% of ramp rate value.
32
________________________________________________________________________
Process Proportional is the gain characteristic. Decreasing the Process Proportional setting will
lower the sensitivity response to process change. If the Process Proportional is set too high a fast
oscillation of process would result.
Process Integral is the stability factor of the PID and is tuned relative to the Process Proportional
(gain). A high setting of the Process Integral would result in a slow oscillation of the PV (process
variable). The Process Integral is tuned in conjunction with the Process Proportional constant to
obtain the optimum steady-state speed response.
33
_________________________________________________________________________
Control Overview of Speed PID and Extraction PID with Ratio Control and Limiter
Control Overview of Process PI (eg. Inlet Pressure) interface with kWatt PID and Speed PID
34
________________________________________________________________________
Note 1: The above parameters need to be programmed to suit the specific extraction turbine it is
intended for. It is important to obtain the “Steam Map / Envelope” from the client or turbine OEM.
Please note attached “Steam Map / Envelope” example, and the corresponding steam map /
envelope programmed via Si-TEC pcConfigure (see next page).
Note 2: The above parameters may ONLY be programmed when the turbine is shutdown. Upon
programming, the STORE button should be pressed followed by either pressing the BUMP button
when at menu 930 (“Steam Map Data – Sub Menu”), or by re-booting (re-powering) CGC module.
Note 1: K1 to K6 coefficients may be adjusted and STORED when turbine is running or shutdown.
Note 2: Si-TEC pcConfigure software may be used to determine optimum values for K1 to K6. **
35
_________________________________________________________________________
36
________________________________________________________________________
The menu items from M# 951 to M#972 allow an accurate approximation of the HP Valve
Linearization to be carried out based on HP Steam Flow (up to 11 co-ordinates as shown below).
Upon programming, the STORE button should be pressed followed by pressing the BUMP button
when at menu 950 (“HP Valve Linearization” – sub menu header). For further details, please refer
to section 6 (Operation and Service).
The menu items from M# 976 to M#997 allow an accurate approximation of the LP Valve
Linearization to be carried out based on LP Steam Flow (up to 11 co-ordinates as shown below).
Upon programming, the STORE button should be pressed followed by pressing the BUMP button
when at menu 975 (“LP Valve Linearization” – sub menu header). For further details, please refer to
section 6 (Operation and Service).
37
_________________________________________________________________________
Rated Frequency / Follow Bus to Min Hz Limit / Follow Bus to Max Hz Limit
Menu items: Rated Frequency (Hz) menu 277
Follow Bus Freq to Min Limit (in % of rated) menu 278
Follow Bus Freq to Max Limit (in % of rated) menu 279
The Rated Frequency is the generator operating frequency set to match the desired system
frequency (eg. 50Hz). The Minimum Limit is set to a level below the operating frequency (eg. 96%).
The Maximum Limit is set to a level above the operating frequency (eg. 104%). Hence, there will be
a corresponding increase (when Bus frequency decreases) and a decrease (when Bus frequency
increases) of the generator kWatt output.
When paralleled to the supply grid the Si-TEC Xtend control will not correct beyond the minimum or
maximum limit frequency settings. This protects the system should there be any incorrect
information (eg. Gen CB relay is faulty, Mains C.B auxiliary input is faulty etc).
NOTE: The Rated Frequency setting must correspond to the turbine Rated Speed setting.
38
________________________________________________________________________
Note: For menu items 300, 301 and 302, please refer to the Appendix section for more details.
These are the P.I. settings for controlling the AVR Bias Output. The proportional is the gain
characteristic. Decreasing the proportional will lower the sensitivity response. If the proportional
were set too high, fast oscillation of voltage would result. The Integral is the stability factor of the
P.I. A high setting of the Integral would create a slow oscillation of the AVR voltage control. The
Integral is tuned to obtain optimum response of the voltage stability. The response of the Si-TEC
Xtend voltage P.I. should be tuned to lag the response of the AVR stability control.
39
_________________________________________________________________________
Follow Bus Volts to Min Limit % / Follow Bus Volts Max Limit %
Menu items: Follow Bus Volts to Min Limit (in % or rated) menu 317
Follow Bus Volts to Max Limit (in % or rated) menu 318
Set Minimum Volts to a level below the operating frequency, say 90%.
Set Maximum Volts to a level above the operating frequency, say 110%.
When paralleled to the supply grid the Si-TEC Xtend control will not correct beyond the minimum or
maximum voltage settings. Should bus voltage rise above the maximum voltage limit, the generator
would not continue to follow that voltage. Subsequently in trying to maintain the voltage there will be
a corresponding decrease in kVAr load from the generator, possibly resulting in leading kVArs. This
may result in Reverse kVArs (Under Excitation) alarm. Similarly, if bus voltage is below the
minimum voltage limit, this will result in an increase in generator kVAr load. This operation is
required to protect the system against incorrect information (eg. Mains C.B closed input is faulty).
Min. AVR Bias Voltage from Si-TEC Xtend module / Max. AVR Bias Voltage from Si-TEC
Xtend module
Menu Items: Min AVR Bias Voltage from Si-TEC Xtend module menu 319
Max AVR Bias Voltage from Si-TEC Xtend module menu 320
This is the minimum and maximum “DC Volt Bias” levels that the Si-TEC Xtend CGC will provide to
the AVR. This range should be set to provide the generator with the required bias span to provide
adequate compensation for the generator voltage droop, AVR drift, and utility voltage swings.
All generators should have similar span adjustment range settings, ensuring similar minimum and
maximum generated voltage outputs (ph/ph). The bias preset values are also set to comply with the
AVR unit’s minimum and maximum voltage bias range. The “Null” bias point is the midpoint
between minimum and maximum settings, and is used on initial generator excitation.
Note: Refer to section 6.3 for details of interface and settings to suit various AVR makes & models.
AVR Bias Disturbance Bump Magnitude (test) / AVR Bias Disturbance Bump Duration (test)
Menu items: AVR Bias Disturbance - Bump Magnitude menu 321
AVR Bias Disturbance - Bump Duration menu 322
To facilitate optimum tuning of the Voltage and kVAr dynamics (PI), the bias signal to the AVR may
be "Bumped" via the Si-TEC Xtend module. The Disturbance Magnitude is set to provide a step
increase or decrease to the AVR Bias Output. The Disturbance Bump Duration is the time required
for this disturbance, after the “BUMP” button on the CGC keypad is pressed (in User Access
mode).
40
________________________________________________________________________
Coming OFF LINE Open Gen CB at % of Rated / Coming OFF LINE Open Gen CB Time-out
Menu Items: Coming OFF LINE Open Gen CB at % of Rated menu 340
Coming OFF LINE Open Gen CB Time-out menu 341
This provides a kWatt level for opening of the generator CB when ramping down the kWatt load to
come “Off Line”. This provides for switching at low current and kWatt levels. Should this kWatt level
not be achieved (eg. last generator on), the open CB signal will be activated after the preset time-
out. This time commences from de-energising the “Start Seq.” input of the CGC. Note that the
generator kVArs must also have ramped to between +/- the value of menu 340 for the CB to open
before the time-out.
Base Load Mode (1) kWatt Set Point / Base Load Mode (2) kWatt Set Point
Menu Items: Base Load Mode (1) kWatt Set Point menu 342
Base Load Mode (2) kWatt Set Point menu 343
These are the kWatt set point values that operate when the “Base Load” logic input functions are
activated.
41
_________________________________________________________________________
Note: Base Load Mode 1 set point may be external adjusted via the Load (Speed) Raise and Lower
logic inputs, and is limited between the “Jump To Minimum kWatt” (minimum reference) and the
“Rated kWatt” (maximum reference). External referencing of Base Load Mode 2 is carried out via
an analog 4-20 mA input reference.
Load (ON) Ramp Rate at % /sec of Rated kW / Load (OFF) Ramp Rate at % /sec of Rated kW
Menu Items: Load (ON) Ramp Rate at % /sec of Rated kW menu 344
Load (OFF) Ramp Rate at % /sec of Rated kW menu 345
These are the kWatt (in % of Rated kW) Ramp Rates for loading and unloading of the generator.
The Load Rates do not affect sudden load changes on "Islanded" operating power stations, and
relate to the on-line and off-line ramping of the generator kWatt setpoint. This provides "Soft"
(bumpless) loading and unloading of the generator.
Fast Load (ON) Ramp % /sec of Rated kW / Fast Load (OFF) Ramp % /sec of Rated kW
Menu Items: Fast Load (ON) Ramp % /sec of Rated kW menu 346
Fast Load (OFF) Ramp % /sec of Rated kW menu 347
These are the kWatt (in % of Rated kW) Ramp Rates for loading and unloading of the generator
when the “Fast Rate” logic input is “High”. The Load Rates do not affect sudden load changes on
"Islanded" operating power stations, and relate to the on-line and off-line ramping of the generator.
This provides faster but controlled loading and unloading of the generator.
42
________________________________________________________________________
Description of Modes:
Mode 0: The generator kWatts and kVArs are ramped to below the “Coming Off Line” settings (i.e.
menu item 340), followed by automatic CB trip command issued by CGC. The generator is then in
“Cool Down” mode, prior to its normal shutdown sequence. The recommended setting is 2.0% to
5.0% of Rated kWatt load.
Mode 1: The generator kWatts and kVArs are ramped to 0 kWatts and 0 kVArs, but no CB trip
command is issued by CGC. In this mode, the CB may only be tripped externally. Upon CB tripping,
the generator is then in “Cool Down” mode, prior to its normal shutdown sequence.
Mode 2: The generator kWatts and kVArs are ramped to 0 kWatts and 0 kVArs, upon which the HP
actuator is then ramped down to 0.0% based on the “Actuator Ramp Off Grid Ramp Rate” (menu
item 358). This is followed by automatic CB trip command issued by CGC, and eventual shutdown
of the turbine. The recommended setting is – 2.0% to – 5.0% of Rated Load.
Mode 3: The generator kWatts and kVArs are ramped to 0 kWatts and 0 kVArs, but no CB trip
command is issued by CGC. In this mode, the CB may only be tripped externally. When the
generator reaches 0 kWatts, the HP actuator is then ramped down to 0.0% based on the “Actuator
Ramp Off Grid Ramp Rate” (menu item 358). This will lead to eventual shutdown of the turbine.
Mode 4: The generator kWatts and kVArs are ramped to 0 kWatts and 1000 kVArs, upon which the
HP actuator is then ramped down to 0.0% based on “Actuator Ramp Off Grid Ramp Rate” (menu
item 358). This is followed by automatic CB trip command issued by CGC, and eventual shutdown
of the turbine. The recommended setting should be equivalent to – 1.0MW as a % of Rated Load.
Mode 5: The generator kWatts and kVArs are ramped to 0 kWatts and 1000 kVArs respectively, but
no CB trip command is issued by CGC. In this mode, the CB may only be tripped externally. When
the generator reaches 0 kWatts, the HP actuator is then ramped down to 0.0% based on “Actuator
Ramp Off Grid Ramp Rate” (menu item 358). This will lead to eventual shutdown of the turbine.
Note: For modes 2, 3, 4 and 5 the “Cool Down Speed” (menu 158) MUST be equal to the rated
speed and the “Cool Down Time” (menu 159) MUST be set to 0.0 minutes.
43
_________________________________________________________________________
Base Load Mode (1) PF Set Point / Base Load Mode (2) PF Set Point
Menu Items: Base Load Mode (1) PF Set Point menu 373
Base Load Mode (2) PF Set Point menu 374
These are the Power Factor set point values that operate when the base load function is activated.
44
________________________________________________________________________
The Speed Proportional (Grid) is the gain characteristic. Decreasing the Speed Proportional
(Grid) setting will lower the sensitivity response to load change. If the Speed Proportional (Grid) is
too high, a fast oscillation of load would result.
The Speed Integral (Grid) is the stability factor of the PID and relative to the Speed Proportional
(Grid). A high setting of the Speed Integral (Grid) would create a slow oscillation of the generator
load. The Speed Integral (Grid) is tuned in conjunction with the Speed Proportional (Grid) to obtain
the optimum steady-state load response. The Speed Derivative (Grid) value should be set low for
responsive turbines and actuator (eg. 0 to 5).
Typically the Speed P.I.D. (Grid) settings are required to be set lower than the Rated PIDs.
Comparative "Rated P.I.D." and "Paralleled P.I.D." settings for a steam turbine would be:
Proportional Integral Derivative
Idle 50 60 0
Rated 70 80 0
Paralleled 50 60 0
Also refer to the "Performance Enhanced " and "Multi Point On-Load PID" menus below.
The kWatt Control Proportional is the gain characteristic of the P.I. settings for kWatt load sharing
(under GSM Master control) and kWatt control, when paralleled to the Grid. Decreasing the kWatt
Control Proportional setting will lower the load sharing or kWatt control sensitivity response. If the
proportional is set too high, a fast oscillation of the kWatt load results.
The kWatt Control Integral is the stability factor of the PID and is relative to the kWatt Control
Proportional. A high setting of the kWatt Control Integral would create a slow oscillation of the kWatt
load. The kWatt Control Integral is tuned in conjunction with the kWatt Control Proportional to
obtain the optimum steady-state load response. The kWatt Control Derivative value should be set
low for responsive turbines (eg. 0 to 5).
The kWatt Multiplier Band is the error window (in % of Rated kWatts) between the desired and
actual kWatts. Should the kWatt error exceed this band, the kWatt Integral Multiplier (menu item
393) will take effect. The kWatt Integral Multiplier is a factor that multiplies with the kWatt Control
Integral.
45
_________________________________________________________________________
Note: The above voltage bias functions (menus 400, 401 and 402) may be used for some grid
parallel applications, where “Clamping” of the voltage bias output (to AVR) may be required for
overall stability requirements.
46
________________________________________________________________________
Note: Compared with “Grid Droop Control” mode, the conventional “Speed Droop” mode is less
preferred. In “Speed Droop” mode, the kWatt load (or actuator position) changes the governor
speed reference, making this droop less accurate with frequent load swings due to variations in grid
frequency. In addition, there is only a single droop curve with no frequency deadband, and there
are NO kWatt load limits to safeguard the system from “Overload” or “Reverse Power”.
47
_________________________________________________________________________
The following description is based on the generator being paralleled to a load bus or the supply
grid:
The setting of “1” (actuator droop) may be utilised during commissioning when confirming the
correct current transformer (CT) polarity. With ”actuator droop” the generator will continue to take
kWatt load even if the polarity of the CTs is reversed.
(a) Set the droop mode to “1”.
(b) Set the droop % to about 5%.
(c) Immediately after the generator has synchronised and paralleled, switch the Si-TEC Xtend
control to manual mode (“Auto” input switched to “Low”). This will hold the kWatt load steady
even if the CTs are reversed.
(d) Check the kWatt displayed for each phase in the generator information display.
(e) In the manual mode, energise the “Increase Speed” input. This will raise the speed reference,
resulting in an increase of the kWatt load of the generator.
(f) Verify the kWatt display for an increase in positive kWatt. Positive kWatts should be displayed
for all three phases. Should any phase show a negative value, unload and trip the generator CB
before reversing the C.T. connections of the phases displaying negative kWatt.
(g) Perform steps (e) and (f) again until correct CT polarity is confirmed.
(h) Set the Droop Mode back to “0”
Note: For actuator droop, the Effective (Actual) Droop % = (100 X M#404)/(M#167 – M#166).
48
________________________________________________________________________
3.10 LOGIC and ANALOG I/O – Configure – Set Parameters – Main Menu
49
_________________________________________________________________________
50
________________________________________________________________________
If switched to the manual mode while the circuit breaker is open, the speed and voltage of the
generator remain at the levels prior to switching. If switched when the generator circuit breaker is
closed, then the generator kWatt and kVAr remain at the levels prior to switching. The exception
being that when input 1 (Enable Run) goes “Low”, the relay outputs for the generator CB and fuel
solenoid open immediately, resulting in any immediate shutdown of the turbine-generator unit.
Under manual control the generator speed control will operate under “droop” mode. The droop can
be referenced to kWatt loading or Actuator position. Refer to “Manual Control Sub Menu” - “Select
Droop Mode” (menu item 405 in the “Set Up and Commissioning Manual”).
The automatic adjustment of load as described below under "Sequence Hold", does not function in
the manual mode.
Note: In the manual mode the system mode state does not change, except on start up where the
initial hold state is in the synchronising mode (automatic CB closure is inhibited). In addition, the
turbine-generator will not go through the sequence shutdown if it is in manual mode.
Upon the generator CB closure (i.e. input 3 is “High”), the active power (kWatt) and the reactive
power (kVAr) are automatically controlled to maintain a balance between all sets on line. The kVAr
is controlled via Analog DC Volt or Relay Output AVR bias trimming and kWatt load via the
actuator.
51
_________________________________________________________________________
In addition if there is no master module in the system, then turbine speed and generator voltage are
controlled to each operational unit’s preset frequency and voltage. These need to be set at exactly
the same value for all units, in order for isochronous load sharing to function. If a GSM master is
enabled, it sets the bus frequency and voltage references for island generators via the Si-TEC LAN.
52
________________________________________________________________________
Note: It is critical that the “Extraction Priority” input should NOT be switched over, while the turbine
generator is operating at a limit of the steam map, as this may caused a severe disturbance on the
turbine generator system.
Note: The “Enable Manual HP Valve Control” function may ONLY be applicable under the following
conditions:
(1) “Mains/Grid CB” input and “Generator CB” input should be “High” (On)
(2) “Auto” input should be “High” (On)
(3) “Base Load 1” input should be “Low” (Off)
(4) CGC for Condensing or Backpressure turbine generators ONLY (i.e. this function DOES
NOT apply for Extraction turbine generators).
53
_________________________________________________________________________
Relay outputs may be allocated as both control and alarm functions. Select the required relay then
use the ^ and v keys to scroll through the control and alarm selection. Press the ‘Store’ key to set
that selection. These functions are described in detail in the “Design and Installation Manual”
In addition, up to eight (8) Modbus addresses may be allocated to the above relays, for Modbus
relay functions (eg. remote start signal via Modbus). The Modbus relay address range is from 4100
to 4107.
Note 1: Relay output function marked with * means relay function with “Fail-Safe” operation.
Note 2: AVR Relay Output Bias (Raise Volts & Lower Volts)
Use one relay for raising the voltage and one relay for lowering of the voltage. This is only required
if a motor operated potentiometer is utilised OR if only logic inputs are used by the AVR for biasing.
54
________________________________________________________________________
55
_________________________________________________________________________
Analog Inputs are available to provide references and control inputs. Each of the analog input
functions has three associated menu items.
The “Allocate to a Source” provides for selection of the input “channel” (i.e. AI-1, AI-2, AI-3, Modbus
Communications, etc).
The “Min Reference” is the value represented by the minimum range of the input source (i.e. 4mA
for a 4-20mA input, 0 for a communicated value, etc).
The “Max Reference” is the value represented by the maximum range of the input source (i.e.
20mA for a 4-20mA input, “High Modbus Ref. Value” for a communicated value, etc).
The reference input values may be assigned so that the maximum input value may be either
positive or negative, and similarly for the minimum input value. This allows greater flexibility with the
selection of transducers. The following examples are provide:
The Modbus Analog Inputs AX0 – AX7 correspond to the Modbus Write Addresses 4000 – 4007
respectively, and may be used as a source for the following Analog Input Functions:
kWatt Control [BL#2] – menu 494 Extraction Reference – menu 518
kWatt Limit (Grid) – menu 497 Extraction Pressure – menu 521
kVAr Control (Grid) – menu 500 Exhaust Pressure – menu 524
PF Control (Grid) – menu 503 Process Reference – menu 527
Warm Up Speed – menu 506 Process Measurement – menu 530
Import kWatt Sensor – menu 509 Spare 1 – menu 533
Minimum Import kWatt Setpoint – menu 512 Spare 2 – menu 536
Inlet Pressure – menu 515 kWatt Simulated PV – menu 539
56
________________________________________________________________________
PF Control (Grid) –
This sets the Power Factor (PF) reference for a generator paralleled to the supply grid operating
without a master Si-TEC Xtend (GSM) module, and for external PF reference control where a
variable 4-20 mA reference is required over the preset PF references. The default setting is menu
370 (“Paralleled to Grid PF Setpoint”).
Warm Up Speed –
This is the warm up speed of a turbine prior to synchronising, which may be varied externally.
There is no default value. This replaces normal start sequence from Warm Up 1 to Rated speed.
57
_________________________________________________________________________
Import kWatt Sensor –
This 4-20mA input is for a bi-directional kWatt transducer measuring the load from the supply grid.
The input signal representing Import/Export kWatt provides for a Minimum Import (or Maximum
Export) kWatt level. The default setting is menu 349 (“On Import Sensor Failure Gen. kWatt Ref.”).
Inlet Pressure –
This 4-20mA input is from a pressure transmitter measuring inlet pressure from supply steam to
turbine.
Extraction Reference –
This sets the extraction reference for a generator paralleled to the supply grid or islanded, provided
that the “Enable Extraction” input (M# 442) and the “Extraction Ref. Analog” input (M# 447) are
switched “High”. The default setting is menu 885 (“Default Extraction Setpoint”).
Extraction Pressure –
This 4-20mA input is from a pressure transmitter measuring extraction pressure of the turbine.
Exhaust Pressure –
This 4-20mA input is from a pressure transmitter measuring exhaust pressure of the turbine.
Process Reference –
This sets the process reference for a generator paralleled to the supply grid, provided that the
“Enable Process Control” input (M# 450) and the “Process Ref. Analog” input (M# 451) are
switched “High”. The default setting is menu 915 (“Internal Setpoint Process”).
58
________________________________________________________________________
Process Measurement –
This 4-20mA input is from a pressure transmitter measuring a process PV (eg. exhaust pressure).
Spare 1 –
This 4-20mA input is from a sensor or transducer.
Spare 2 –
This 4-20mA input is from a sensor or transducer.
kWatt Simulated PV –
This 4-20mA input is from a kWatt transducer or a simulated signal representing generator kWatts.
Note: For normal operation, menu 539 MUST be set to “Internal Setpoint”, as this function is used
for simulation purposes only.
59
_________________________________________________________________________
Three 4-20mA outputs are provided on the Si-TEC Xtend module with additional 4-20mA outputs
available on the CAN Bus expansion module (**).
The analog outputs may be selected to represent the following data types:
Turbine Speed Inlet Steam Pressure
HP Actuator Position % Extraction Reference
LP Actuator Position % Extraction Pressure
Generated kWatt Exhaust Pressure
Generated kVAr Process Reference
Generator Power Factor Process Measurement
Sum of kW Import Sensors Spare 1 Output
Final kWatt Set Point Spare 2 Output
Droop kWatt Trim
In configuring the 4-20mA outputs first assign a data type to the output, then set the value to
represent 4mA and then set the value to represent 20mA. These settings would correspond to the
scaling of instrument or device that the 4-20 mA output is driving into.
The Si-TEC Xtend module provides for adjustable and reverse range scaling of power factor meter.
Examples:
Meter Scaling set preset unit values to
4mA - 20mA 4mA @ 20mA @
0.50 lead 0.50 lag 0 10000
0.70 lead 0.70 lag 2000 8000
0.50 lag 0.50 lead 10000 0
0.80 lead 0.40 lag 3000 11000
0.30 lead 0.20 lag - 2000 13000
60
________________________________________________________________________
The following set points provide for the triggering of the alarm/control functions.
The selection “[D/E/T]” (abbreviated [Disable / Enable / Trip the generator CB].
When an alarm is Disabled that alarm will not even be displayed if the set points are exceeded.
When an alarm is Enabled that alarm will be displayed and be active in the alarming system.
If the selection is set to Trip the generator CB, the Si-TEC Xtend module will display the alarm and
will also carry out a Generator CB trip function via the allocated relay output or a “Combined Alarm”
output (refer to Logic Outputs – Allocate a Function to a Relay, page 47-48).
The alarm functions should be interlocked with the control system to provide the desired operational
requirements. For example during the operation of “Reverse Power”, the Si-TEC Xtend module may
trip the generator CB. However, should the alarm:
this would depend on the external control logic and protection. If a “Combined Alarm” output is
used, then the combined latched alarm may be reset either from the Si-TEC Xtend module keypad
or via a logic input assigned to perform the “Remote Fault Reset” function.
61
_________________________________________________________________________
62
________________________________________________________________________
63
_________________________________________________________________________
4 CONTROL NOTES
## THIS IS A CONTROL DEVICE AND IS NOT TO BE USED FOR TURBINE SPEED
PROTECTION. SEPARATE INDEPENDENT SAFETY SHUTDOWN DEVICES MUST BE
USED FOR OVERSPEED PROTECTION.
## The internal Si-TEC Xtend alarm functions may be selected to operate the module's CB trip
output and/or to switch an output relay. Internal tripping of the generator CB should be
interfaced to latching circuit(s) to inhibit generator control under such alarm conditions. This
provides flexibility to suit the required control operation. The alarm relay outputs are only
operative under an “Alarm” condition, and do not latch within the module. All latching for
alarm indication and/or control interfacing should be conducted external to the module.
## Alternatively, the alarms may be allocated to a “Combined” latched alarm function. This
latch may be reset by pressing the “Reset” key on the keypad, or by using the “Remote
Reset” logic input. For this purpose a combined latched alarm may include numerous alarm
functions, with the allocated “latched relay” wired in series with the Si-TEC Xtend logic input
2 (Start Seq.) for a controlled shutdown or wired in series with logic input 1 (Enable Run) for
an immediate shutdown. Operation of the reset function will unlatch this relay.
## Upon the operation of various alarms it is desirable to "advise" the Si-TEC Xtend module of
a change to the required control state, by de-energising the relative logic input(s). For
example if reverse power is sensed, internally or externally trip the CB, de-energise and
latch out the Start Seq. input (input 2), which then places the module into the cool down
operation mode. Without de-energising input 2 the module is still instructed to operate
normally. In this situation the control realises that the Gen CB input (logic input 3) is de-
energised, and with input 2 energised the mode of operation would be to re-synchronise
the generator with the bus. By de-energising input 2, the mode changes to the normal "off
line" sequence of a “cool down” period followed by a controlled shutdown operation.
Likewise should a turbine fault be detected (eg. Low Lube Oil Pressure or High Inlet
Temperature), it would be advisable to de-energise and latch out the Enable Run input
(input 1) for immediate shutdown. The shutdown control modes (whether by input 1 or 2)
operates the CB trip/open signal as part of the shutdown procedure.
## Refer to the following sequence operation of logic inputs 1 and 2 (section 4.2, page 64).
## CB close relay contacts momentary close when generator is synchronised signalling for the
Circuit Breaker to close. The relay is de-energised should the generator move out of
synchronisation and/or if the Generator CB auxiliary input (via input 3) signals that the
circuit breaker has closed (after a 1-second delay to prevent "pumping" of the CB). This
relay operates as a maintained output if a CB trip relay is not selected.
## The Generator CB auxiliary input (input 3) and the Mains CB auxiliary input (input 4) should
instantaneously receive their status signal change (or with minimum time delay), after a
change in the actual respective CB status. This is critical in ensuring that the Si-TEC
Xtend CGC operates in the correct control mode.
## It is strongly recommended that all external interposing relays for the CGC modules be
equipped with a protective circuit (eg. Diode 1N4007) across relay coil (if coil is for DC
currents), to eliminate high voltage spikes due to “Back EMF”.
64
________________________________________________________________________
## The inputs may be powered from an external 24Vdc supply, provided that the grounding is
common. A separate common terminal (terminal 0) is provided.
The logic input voltage may range from 9V to 36Vdc however 24Vdc is recommended.
Various logic inputs may be configured to suit the user application. Refer to the Menu Functions
and settings for further logic input options and selection. The following list is a description of the
fixed logic input control functions. It should be noted that more than one input control function may
be assigned to a single common logic input. Input functions may be set to:“0” or “always ON”, “1” or
”always OFF”, or allocated to a switched logic input.
The turbine "fault shutdown" or “emergency shutdown” devices should be interlocked with this input
and externally latched off.
1 The “Fuel Solenoid” relay output (if configured) is energised to open the turbine Main Steam
Valve. If this function is not used, the Main Steam Valve may be manually opened before
energising the “Start Sequence” input.
2 The governor actuator is positioned at the “Initial Actuator Start Position”. The actuator will
begin to open at the “Increase Actuator Limit Position %/sec” ramp rate until the “Warm Up 1
Max. Act. Position”. If no speed is achieved after a duration based on the “Start Fail Timeout”, a
‘Start Fail Alarm’ is issued. The “Start Sequence” would need to be re-issued (toggled Off-On)
after the alarm is reset.
3 Under normal conditions, the turbine speed should pick up during the “Increase Actuator Limit
Position %/sec” and will revert to speed PID control once the turbine speed reaches “Warm Up
1 RPM”.
4 After the “Warm Up Time 1” is completed, the turbine will ramp up to “Warm Up 2 RPM” speed.
5 After the “Warm Up Time 2” is completed, the turbine will ramp up to the “Idle RPM” speed.
6 It should be noted that two (2) Critical Speed Bands are available, if required. The Critical
Speed Bands may be set in the range between “Warm Up 1 RPM” and “Rated Speed RPM”.
7 After the “Idle Delay Time” is completed, the turbine will then ramp to the “Rated Speed RPM”.
8 The turbine then warms up for a further duration based on the “Warm Up Time at Rated RPM”.
9 The “Hot Start”, “Fast Rate” and “Sequence Hold” logic inputs have an impact in the turbine
start sequence, and their specific functions are described in section 3.10 (Logic Inputs).
10 Upon the generator excitation, the control then synchronises the incoming generator to the
main bus (or grid) after matching frequency, phase angle and voltage. Phase rotation is further
checked before permitting the closure of the "Close CB" output terminals 17 & 18 (fixed
designated relay output).
11 kWatts and kVArs are ramped at a preset rate (e.g. 0.5% per sec) until load is shared with the
other sets on the bus, or if the unit load reaches it’s set point (base load) reference.
Note: The “Temperature Hold Function” may hold the warm-up of the turbine at a selected
point. Menu 212 selects the “Temperature Hold” method and the first warm up state for this
“temperature hold”.
65
_________________________________________________________________________
If not set to “0”, then the Measured RTD temperature will keep the Xtend in the present
warmup state, until the temperature set in menu 211 - "Min. Temperature for Start" is reached.
1 Generator load ramps down at the preset rate (e.g. 1.0% per sec). kWatts and kVArs must
unload below the preset levels prior to the normal switching off line (opening the CB). Should
unloading not occur within a preset maximum time, the switching off line will occur regardless of
the kWatt/kVAr levels.
2 The generator runs at the “Cool Down Speed RPM” for the preset “cool down” time.
3 Following the cool down period the actuator drives to zero (0%) position and the fuel solenoid
output (if used) is de-energised. The turbine-generator is then fully shutdown, and is ready for
another start sequence.
4 Removal of the signal to input 2 resets the controller following any alarm condition (e.g.
Reverse Power).
## Note: Latch out input 2 if the CB is tripped under a fault condition. This will "advise" the Si-TEC
Xtend module of a sequence stop requirement and prevent any re-synchronising mode
occurring. Switch input 1 to “Low” for an immediate shutdown.
66
________________________________________________________________________
To select the combination of alarm functions for the 4 combined alarm outputs the value has to be
set representing the decimal value of the bit representation.
For example to combine the synchronising failure and the start failure then:
Synchronising Failure 1048576
Start Failure 2097152
--------------
Sum 3145728 : hence set the “Code” to 3145728
Any combination may be set for each of the two Combined Alarms, and each of the Latched
Combined Alarms.
The pcConfigure software provides an option for “ticking” of the required alarms from the
“Combined Alarm Calculator”, to allow the value to be calculated.
67
_________________________________________________________________________
5 PID CONTROLS
The Si-TEC Xtend governor control for steam turbines has 13 (thirteen) sets of PIDs to adjust:
6 Speed PID controls
1 Sync PI control
1 kWatt PID (Grid) control
1 kWatt P (Island) control
1 Extraction PID control
1 Process PI control
1 Voltage PI control
1 kVAr/PF PI control
PROPORTIONAL
Proportional is the amount of correction (gain) factor required for a given speed/load error.
Increasing the preset Proportional value increases the sensitivity of response to an
error.
The Proportional is the gain characteristic. Decrease the proportional setting to lower the
sensitivity response to speed/load change. If the Proportional is set too high a fast oscillation
of speed would result as over correction occurs. If the Proportional set too low, a sluggish
response is experienced along with a slow wandering of the speed about its reference.
INTEGRAL
Integral is a correcting factor based on time, the longer the error is present, the greater the
correction. It is sometimes referred to as “Stability”.
Increasing the preset Integral value will decrease the time constant (stability) or reset
time.
Integral is a correcting factor based on time, the longer the error is present, the greater the
correction. It is sometimes referred to as “Stability”. Increasing the Integral preset value
decreases the time factor. If the Integral setting is too high, it may create a slow oscillation of
the turbine speed. The Integral is tuned in conjunction with the Proportional to obtain the
optimum transient response, while maintaining a stable steady-state speed control.
DERIVATIVE
Derivative is the amount of correction in relation to the rate of change of speed/load error.
Increasing the preset Derivative value will increase the amount of actuator correction.
Derivative is the amount of correction in relation to the rate of change of speed/load error.
Increasing the Derivative will increase the rate of change of control action. Derivative values
should be low for responsive turbines and actuators (eg. 0 to 10). High Derivative values may
cause the actuator to jiggle. NOTE: Systems with a high Proportional value require very little
or no Derivative.
When the turbine is started, the Si-TEC Xtend CGC dynamics are controlled initially by the “Warm
Up 1 RPM” PID, followed by the “Idle RPM” PID and eventually the “Rated RPM” PID. The PID
settings at the “Warm Up 2 RPM” speed are based on linear interpolation between the “Warm Up 1
RPM” PID and the “Idle RPM” PID settings. Similarly, linearly interpolated PID settings between
“Idle RPM” and “Rated RPM” would apply. At Rated Speed and above, the “Rated RPM” PID
settings assume speed control of the turbine.
Once the generator CB is closed, the PID control settings are from:
68
________________________________________________________________________
• If the “Multi Point On-Load PIDs" have been “Enabled”, the values are linearly interpolated
from “Rated RPM” (0% kWatt) PID, “Mid-Point kWatt” PID, and “100% kWatt” PID, with the
interpolation being based on the kWatt load on the generator. The mid-point kWatt % is
programmable, which allows flexible control as shown in the examples below. Note that the
interpolation is done separately for each of the proportional, integral and derivative terms.
For most applications it is not necessary for the "Multi Point On-Load" PID to be enabled. When the
"Enable MULTI Point On-Load Speed PIDs” is set to "NO" the unit is controlled by the “Rated RPM”
PID when off-line or connected to an islanded load bus, and from the “Parallelled To Grid” PID
when connected to the supply grid. The Multi Point PIDs are NOT active when the turbine generator
is paralleled to the supply grid.
The Si-TEC Xtend supports Si-TEC pcTune (PC software tool) for tuning and diagnostics of the Si-
TEC Xtend governor and generator control, providing a range of useful and accurate graphical and
visual displays of governing performance, response, etc. This may also be useful for analysis and
troubleshooting of governing system, to identify problems as well as for control optimisation.
The minimum system requirements for use of the Si-TEC pcTune software on personal computer
are Pentium 100Mhz or higher, MS Windows 98 or above, 32MB RAM and 5GB of minimum hard
disk.
When tuning for optimum turbine-generator dynamic response and stability, it is a normal practice
to go to the fuel system and "Bump” the actuator to create a “disturbance” in order to evaluate the
response, stability etc. With the Si-TEC Xtend CGC module, a consistent disturbance or “Bump”
can be introduced upon command, which provides 100% accuracy in repeating the disturbance.
Enable the “Access” key to make modifications to the set point values. Proceed to the PID
Adjustment – Speed Loop Response sub menu (menu items 216 to 227). The last items in the PID
menu are the "Actuator Disturbance BUMP Magnitude" (menu 225) and the " Actuator Disturbance
BUMP Duration" (menu 226). Set the “Magnitude” to say 20% - 30% and the “Duration” to 1.0 – 2.0
seconds. When the “BUMP” key is operated while in the PID menus, the HP actuator will drive
down 20% below the present actuator position for a 1.0 second duration, providing the set error. A
menu item “Disturbance delay after pressing BUMP” (menu 227) will delay the operation of the
actuator BUMP for that set period.
The “Actuator Bump” function may also be operated for Synchronising and kWatt control response.
Fast Response Proportional is the multiplying factor of the Rated Proportional Setting (the “Rated
P” constant) and operates when the speed error is beyond the preset value of the Fast Response
per cent setting (nominally set to 1.5). Increasing this multiplier will increase the proportional factor
during excessive speed errors.
The Fast Response Proportional value (negative and positive multiplier menus 237 and 238) should
be reduced if excessive actuator overshoot is observed and if the Rated Proportional is optimally
set. The Fast Response Proportional is also operative during the synchronising mode.
The Fast Response Integral value (negative and positive multiplier menus 239 and 240) is the
multiplying factor to the Rated Integral Setting and operates when the speed error is beyond the
setting of the Fast Response per cent. This is nominally set to 2.0. Increasing the preset value will
increases the actuator integral response (reduce the time constant).
Reduce the Fast Response Integral value if the actuator show instability and if the Rated Integral is
optimally set. The Fast Response Integral is also operative during the synchronising mode. The
Fast Response Integral Multiplier is typically set to around 4.0 for less responsive turbines.
69
_________________________________________________________________________
5.4 Multi Point On-Load Speed PIDs (mid point and 100% load - kWatt)
This PID will function when the "Enable Multi Point On-Load PIDs" is set to "YES". The PID only
functions during the “Islanded Mode” operation and does not operate when the turbine-generator is
paralleled to the supply grid.
For easily tunable turbine-generator control dynamics, the "Enable Multi Point On-Load PIDs"
function may be set to "NO". The Si-TEC Xtend will ignore the preset PID settings of this sub menu.
Examples
Example 1: Turbine system that is non-linear and sensitive at higher load (eg. above 60%).
Prop
Prop (Gain)
(Gain)
Here, the Proportional (gain) is higher at the mid point (60% load), but the setting at 100% load is
the same as that of the Mid-Point. This may be applicable in a non-linear system, where the
dynamics between 0% load and Mid-Point (60%) load is significant, but where there is little or no
difference between the dynamics at Mid-Point load and 100% load (i.e. the dynamics are sensitive
with load beyond 60%.
The mid point for the “Mid Point PIDs” may be set from 0% (kWatt load) to 99% (kWatt load) If set
at 0% load then the Mid Point PIDs are operative as soon as the generator CB is closed after the
generator has synchronised.
70
________________________________________________________________________
Prop
Prop (Gain)
(Gain)
Mid Point
set to 20%
This example requires a low Proportional (gain) during synchronising and at lower loads. The
Proportional is increased as the load increases. This application is suitable when the control
compensates for some non-linear systems, which may be sensitive at no load and lower loads.
The Rated speed PID is in control during synchronising. With the Mid Point % set at 0%, the Mid
Point % PID is active when the generator CB closes and then interpolates to the 100% kW PID (full
load).
PID PID
If the Mid Point % is set to 0%, then synchronising is done through the Rated speed PID. When the
breaker closes, the control uses Mid Point % PID at no load (or -ve load!) and interpolates to the
100% PID at full load or higher kW loads. This PID option is useful for “difficult to control” turbines,
allowing flexible proportional, integral and high derivative action for fast and accurate synchronising,
without degrading on-load performance.
71
_________________________________________________________________________
Introduction
The CGC governor provides controlled extraction, by simultaneously controlling both HP and LP
actuators. The PCU (Process Control Unit) module provides the interface with the LP actuator, as
Illustrated below.
The CGC communicates with the PCU via the CAN BUS port, providing high-speed read and write
commands to control the position of the LP actuator. Apart from facilitating the interface with the LP
actuator, the PCU is also equipped with additional I/Os, “Doubling” the digital and analog I/Os of the
overall CGC governor system.
Should either the CAN Bus communication between the CGC and PCU fail or if the 4-20mA signal
from the extraction pressure transmitter fail, then extraction control is automatically disabled until
these interfaces are restored.
It should be noted that the PCU module is NOT a close loop control module. It simply functions as a
remote I/O module of the CGC governor interfaced via CAN Bus communications. Using the PCU
nd
would not only facilitate using the 2 actuator (for LP valve) via CAN Bus, but will also expand that
overall I/Os for the CGC governor.
The PCU option should be considered if 2nd actuator to LP valve is NOT 4-20mA, or if additional
I/Os are required for the specific application. Expansion of I/Os via PCU would be additional 16
logic inputs, 9 x relay outputs, 4 x analog inputs, 3 x analog outputs and 1 x actuator output.
72
________________________________________________________________________
Alternatively, the CGC governor for controlled extraction may be utilised as a single control module
(i.e. no PCU required). In this case, the actuator output to the LP valve MUST be 4-20mA ONLY,
and may be configured using either analog output 1, 2 or 3. This is illustrated below.
One important point to note when using the above application (without PCU module) is that the I/Os
available would be within the list of the CGC governor itself (i.e. 16 x logic inputs, 9 x relay outputs,
4 x analog inputs, 2 x analog outputs and 2 x actuator outputs).
As a further option, should the CGC governor for extraction turbine be used without PCU option (LP
actuator output used from an available 4-20mA analog output), and if expansion of I/Os is required
only for logic inputs and relay outputs, a Mini RIO unit may be used. The Mini RIO is a compact
size, DIN Rail mounted unit, which provides I/O expansion to additional 16 x logic inputs and 8 x
relay outputs.
Note: It is essential that all 4-20mA actuator outputs MUST use a signal isolator, to ensure full
isolation between CGC governor and the respective Current to Hydraulic Pressure I/H converter
(eg. Voith, CPC, Moog, etc.).
Control Overview
For controlled extraction steam turbine to function, extraction pressure must be controlled in
tandem with the turbine kWatt load. This is achieved by the CGC directly controlling both HP
actuator and LP actuator via independent Speed PID and Extraction PID loops respectively. The
Control Overview, Live Steam Map and Extraction Control Sequence are illustrated hereafter.
73
_________________________________________________________________________
Control Overview of Speed PID and Extraction PID with Ratio Control and Limiter
Live Steam Map illustration HP Valve (Power) Demand and LP Valve (Extraction) Demand
74
________________________________________________________________________
75
_________________________________________________________________________
The Ratio Control and Limiter receives the Speed PID and Extraction PID outputs. The Ratio
Control function utilises these inputs and based on the turbine performance parameters, produces
two output signals to control the HP actuator and LP actuator respectively. The Ratio Limiter
function keeps the actuator outputs within the boundaries of the turbine steam map.
The Ratio Control regulates the interaction of both HP and LP valves to maintain the desired turbine
speed / load and extraction pressure levels. By regulating the interaction, the Ratio Control function
minimises the effects of one controlled process on the other controlled process.
When system conditions cause a turbine to reach an operating limit, the Ratio Limiter function limits
the HP or LP valves to maintain kWatt load or extraction, depending on the priority selected.
Typically, the turbines HP and LP valve movements are coupled together to control both processes
without the two processes interacting with each other. Turbine load and extraction pressure are
controlled by positioning both the HP and LP valves simultaneously. For a change in either process,
both valves are repositioned to create a net effect of no change on the other process.
Changing the position of either the HP valve or the LP valve affects both turbine speed / load and
extraction pressure. If either the turbine load or the extraction demand changes, both the HP valve
position and LP valve position MUST be changed to maintain speed / load and extraction / process.
The movement of both valves (i.e. actuators) is calculated by the CGC’s Ratio Control and Limiter
function based on the turbine performance parameters (as detailed in the “Steam Map Data” sub
menu), to minimise any adverse interaction between the two control processes.
Refer to page 76 for illustrative representation of the “Si-TEC Flow Control for Extraction Turbine”.
Since a controlled extraction steam turbine has two control valves, it can control two parameters
simultaneously. If the turbine reaches an operating limit (i.e. HP valve and LP valve reach their
maximum limits), only one valve may be controlled by the CGC. It is at these limits that the CGC
may be configured to select which single parameter should remain in control, or have priority over
the other parameter.
If “Speed / kWatt Priority” is selected, the CGC will only control turbine speed / load when the
turbine reaches an operating limit. Therefore, speed / load will be maintained and extraction control
will be sacrificed. Under this condition, the Extraction PID control is temporarily suspended until the
system conditions change to allow the turbine to move away from the operating limit.
If “Extraction Priority” is selected, the CGC will only control the Extraction PID’s process when the
turbine reaches an operating limit. Under this condition, Speed / kWatt PID is control is temporarily
suspended until the system conditions change to allow the turbine to move away from the operating
limit.
76
________________________________________________________________________
77
_________________________________________________________________________
5.6 Si-TEC Xtend CGC governor (with extraction control) tuning sequence
The recommended “Step-By-Step” sequence of CGC governor “Close Loop Control” system tuning
is outlined below. For any queries, please consult Dawson Technology for technical assistance.
4 Voltage Control PI
(to AVR Bias input)
5 Sync. Control PI
78
________________________________________________________________________
{Note: The following procedures are intended for Si-TEC Xtend controls that interface with
StG all–electric actuators}
The actuator drive and feedback test function may be checked only when the turbine is completely
shutdown with HP Valve and MS (Main Stop) Valve fully closed. The actuator feedback adjustment
is preset within the Si-TEC Xtend control module (CGC for HP actuator and PCU for LP actuator).
To perform “Actuator Stroke Test”, proceed to the “System Diagnostics and Functional Tests” main
menu, scroll via the “Select Menu” key to the “Actuator Test” sub menu, and then to “Set Actuator
Position” 1 or 2 within this sub menu (CGC for HP actuator and PCU for LP actuator).
Alternatively the user may proceed directly to menu 081 (Actuator Position 1) or 082 (Actuator
Position 2). Both desired output position and actual actuator position (feedback) are displayed (%).
Pressing the “Bump” key will enable the actuator test. Adjusting the “Set Actuator Position” from 0
to 100% (by operating the + / - buttons on the keypad) will cause the actuator to drive from 0% to
100%. The feedback is on the display to the left side of the LCD screen.
Confirm that using the + button will increase the actuator position and feedback. It is necessary to
conduct a physical check of the actuator at forced minimum position (0%), maximum position
(100%), and 2 intermediate positions. This will verify the correct driving of the actuator including
direction, and will confirm correct feedback voltage signal. The feedback should match the output
position within a small percentage.
Allow for the actuator to drive hard against the minimum and maximum fuel positions, where with
correct stroking the actuator would not be able to physically achieve 0 or 100% due to the
mechanical stops. The minimum and maximum positions of 5–10% and 90–95% respectively
should be achieved with the linkage correctly set.
The “Actuator” information button on the face of the Si-TEC Xtend module provides details of the
output to the actuator, actuator feedback, actuator current, and actuator dc supply voltage. The
“Auto Toggle Actuator Test” may also be conducted from this sub menu.
The length of the actuator lever should be such as to allow approximately 90% to 95% actuator
travel to move the fuel rack from the minimum position to its maximum fuel position. The maximum
fuel position should be at the 95% to 98% position. With the fuel rack at minimum position the
actuator should be at the 3% to 5% position. The linkage geometry should be adjusted to achieve
this actuator travel.
HP and LP Valve Linearization (applicable to StG all-electric actuators and other actuators)
Where applicable, it is also important to set up the “HP & LP Valve Linearization” curves (Steam
Flow vs Actuator Position) after “Actuator Stroke” tests. This will provide an accurate approximation
when mapping the desired actuator position with the valve position, based on HP steam flow. The
data required for setting up the “Valve Linearization” is based on the respective “Valve Position vs.
Steam Flow” curves. If no details are available, then the default (Straight Line) settings will apply.
For programming of the “HP & LP Valve Linearization” curve co-ordinates, it is recommended that
this be done via the Si-TEC pcConfigure software tool, as it will greatly aid the user in quick and
accurate set up of the curve. While programming the co-ordinates may also be possible via the Si-
TEC Xtend CGC module keypad, this will be more tedious. In any case, it is always recommended
to view the final “HP & LP Valve Linearization” curve via Si-TEC pcConfigure, to ensure that there
are no errors during programming of the co-ordinates.
79
_________________________________________________________________________
i) Programming of co-ordinates (Desired Actuator Position & Steam Flow) via pcConfigure
ii) Mapping of HP Valve Linearization Co-ordinates (Desired Actuator Position vs. Steam Flow)
80
________________________________________________________________________
i) Programming of co-ordinates (Desired Actuator Position & Steam Flow) via pcConfigure
ii) Mapping of LP Valve Linearization Co-ordinates (Desired Actuator Position vs. Steam Flow)
81
_________________________________________________________________________
i) Default programmed co-ordinates (Desired Actuator Position & Steam Flow) via pcConfigure
ii) Default HP Valve Linearization Map (Straight Line) assuming no specific mapping required
82
________________________________________________________________________
The distance between the magnetic pick up and top of the teeth of the ring gear should be 0.5mm
to 0.8mm. (With the prime mover stationary, it is possible to screw the magnetic pick up on to the
top of the teeth and unscrew it for about 1/3 to 1/2 turn)
It is NOT recommended that gears mounted on an auxiliary shaft (eg. camshaft gears) coupled to
the turbine rotor be used to sense turbine speed. Auxiliary shafts tend to turn more slowly than the
turbine rotor and have coupling gear backlash, which results in poor speed control. It is also not
recommended that the MPU senses speed from a gear coupled to a generator or mechanical drive
side of a turbine’s rotor coupling.
To confirm successful speed sensing via MPU, the correct turbine RPM (speed) will be displayed
on the CGC module’s “Home” (default) display while the turbine is starting.
Proceed to the “System Diagnostics and Functional Tests” main menu, and scroll to the “Display
I/O States” sub menu. Scrolling through this sub menu will eventually display “MPU1 and MPU2 –
signals”, which displays the actual speed sensor signal value. Alternatively, the user may proceed
directly to Menu 050 to access this menu item.
The resistance of the MPU may vary depending on manufacturer specification, to suit different
applications. The MPU resistance range varies from 52Ω (low impedance) to 1100Ω (high
impedance). The MPU coil is isolated from the MPU body (> 100kΩ).
Disconnect the MPU and Feedback screen (shield) connections to terminals 58, 82 & 87. The
screens should now be isolated (above 100kΩ) from ground, and the DC supply negative. All
screen connections should be wired to "ground" at one point ONLY to avoid ground loops. This
single connection is done at terminals 58, 82 & 87 for the respective cables. Verify the sheathing of
the screen cables to ensure that chaffing has not occurred, as this may cause momentary
secondary grounding of the shielding.
It is a MUST that a dedicated MPU be used as a speed sensor for the governing system. Should
any other device be connected to this MPU, it is essential that the other device connections do not
cause the MPU input signal to be referenced to a positive DC voltage supply. If any of the devices
that are interfaced with the MPU inputs are linked to ground or positive DC voltage supply, it should
be ensured that that this does not conflict with the grounding of connections to terminals 80 and 85
within the Si-TEC Xtend module.
Proximity Switches
Speed sensing may also be possible through the use of proximity switches with either a NPN or
PNP open collector output. The default setting of the speed sensors is for MPU speed sensing.
However, it is possible for the speed sensing to be configured for proximity switch sensing through
internal jumper selection. Consult Dawson Technology if an application involving proximity switches
is required.
83
_________________________________________________________________________
AVR Bias Output may be provided either via an isolated analog DC voltage, or by Raise/Lower
relay outputs driving a MOP (motorised operated potentiometer) or logic inputs of a digital AVR.
To select the desired AVR bias output, proceed to the “AVR Control Method” menu item (menu
313). Set a value of “1” to select “Analog (DC Volt) Bias” control or “0” for “Relay Output (Digital)
Bias” control. This menu item is within the “Voltage / AVR Control” sub menu.
Relay Output (MOP) Bias: Raise Volts – User select relay output
Lower Volts – User select relay output
The isolated “Analog Bias Output” DC voltage range may be adjusted from – 8.4V to + 8.4V by the
set point adjustments (menu items 319 and 320). Terminal 71 goes more positive with respect to
terminal 72, for an increased excitation in generator voltage output.
The tuning procedure should be as follows, with the Voltage and kVAr Proportional and Integral
initially set at low values (i.e. the lower end of the typical value range):
(a) Ensure that the AVR has been set up for optimum voltage control, without the Si-TEC Xtend
AVR Bias Output.
(b) The Si-TEC Xtend “Voltage Proportional” and “Voltage Integral” should be tuned for stable
voltage control when generator is off-line, and during voltage trimming for synchronisation. If
the Proportional and Integral values are too high, the AVR Bias Output correction will be too
fast when interacting with the AVR control. This is particularly noticeable when the generator
starts with a voltage overshoot.
(c) The Si-TEC Xtend kVAr/PF Proportional and Integral should be tuned for stable kVAr/PF
sharing with other generators, or kVAr/PF control when paralleled to the supply grid.
The kVAr limits are enforced when a generator is paralleled with the supply grid. The limits are
located in the kVAr/PF Control sub menu. Lagging kVArs are limited to Rated kVAr calculated from
Rated kWatt (menu 333) and Rated P.F. (menu 369). Leading kVArs are limited to the value set in
the Leading kVAr Rating (menu 372).
A typical scenario where these limits may be utilised is when the supply grid voltage drifts beyond
the minimum/maximum limit voltage range set within the Si-TEC Xtend module. If the grid voltage
increases above the maximum limit, generator kVArs will be decreased due to the lower excitation
relative to the grid. If the kVArs decrease to the Leading kVAr limit, the Si-TEC Xtend control will
automatically adjust the generator excitation to hold the kVArs at the Leading kVAr limit until the
grid voltage reduces. Similarly, if the grid voltage decreases below minimum Volts, kVAr will be
increased but only as far as the Rated kVAr limit. This limit will be maintained until the grid voltage
increases.
On generator start up, the AVR Bias voltage level is set at the mid-point between the “minimum”
and “maximum” AVR Bias voltage settings. This holds the bias at a constant level until the “Voltage
Delay Before Action” (menu 316) delay time has elapsed, or if the generator voltage is greater than
“Gen. Rated Voltage” (menu 314). Until this biasing is actuated, the alternator AVR is the only
controlling device of the generator voltage.
84
________________________________________________________________________
It should be noted that when excitation commences after starting of the turbine-generator, the initial
voltage overshoot is controlled by the AVR only. The Si-TEC Xtend “Voltage Control” PID assumes
control thereafter.
Testing the AVR Bias effect on the alternator may be conducted when the generator CB (circuit
breaker) is open. For example, the generator is started and it is ensured that the Si-TEC Xtend is in
“Manual Mode” (i.e. “Auto” logic input is switched “low”). Using the “Force AVR Bias Output Test”
(menu 068), the required bias voltage level is set, and is followed by operating the “BUMP” key.
The generator Ph/N voltage may be observed in the lower left-hand corner of the Si-TEC Xtend
display screen. The test may also be carried out by using the “Si-TEC pcTune” software.
Basler
85
_________________________________________________________________________
Kato
KCR-760
Connect AVR terminal R1 to Si-TEC Xtend terminal 71
Connect AVR terminal R2 to Si-TEC Xtend terminal 72
–4.0 V bias = –10%; 0.0 V bias = set voltage; 4.0 V bias = +10%
External voltage trim pot is not utilised. Droop CT bridge link is hidden.
GenAust
AVR380 terminal connections
Set the onboard Voltage Trim Pot (under terminals A1 and A2) to fully clockwise
Connect terminal A2 to Si-TEC Xtend terminal 71
Connect terminal A1 to Si-TEC Xtend terminal 72
–5.0 V bias = –10%; 0.0 V bias = set voltage; 5.0 Volt bias = +10%
Leroy-Somer
R200 AVR terminal connections
Use terminal strip CN2 of the AVR (same terminal strip as the droop CT / Pot)
Connect terminal 6 of AVR to Si-TEC Xtend terminal 71 with series 4.7 kOhm resistor.
Connect terminal 5 of AVR to Si-TEC Xtend terminal 72
Marathon
DVR 2000E
Voltage trimming via logic input (Raise / Lower).
Use Si-TEC Xtend relay outputs (via 2 x external interposing relays) for volt trim interface.
Mecc Alte
Mecc Alte UVR6
Adjust the “Volt” potentiometer to minimum (fully CCW) position, and remove external pot.
Connect second from end volt trim terminal of AVR to Si-TEC Xtend terminal 71
Connect end volt trim terminal of AVR to Si-TEC Xtend terminal 72
Set Minimum Bias (90%), Null Bias (100%) and Maximum Bias (110%) accordingly.
86
________________________________________________________________________
Newage–Stamford
MX 341 – MX 321 - SX 440 terminal connections
Loop terminal 1 to terminal 2 at the top of the AVR terminal strip (strip including x and xx )
Connect terminal A2 of vertical strip to Si-TEC Xtend terminal 71
Connect terminal A1 of vertical strip to Si-TEC Xtend terminal 72
Set Minimum Bias (90%), Null Bias (100%) and Maximum Bias (110%) accordingly.
AVK
AVK terminal connections
Remote voltage trimming pot can be deleted from circuit.
Connect terminal T of AVR to Si-TEC Xtend terminal 71 (check polarity)
Connect terminal S of AVR to Si-TEC Xtend terminal 72 (check polarity)
Install a 1.0 KOhm 0.5 watt resistor in series.
Sanelec
SES12S-D AVR terminal connections
Set Rated Voltage via motorised pot. DO NOT make any further adjustment via this pot.
Set the “Accessory Gain” pot to around MID-RANGE position.
Connect terminal A2 of AVR to Si-TEC Xtend terminal 71
Connect terminal A1 of AVR to Si-TEC Xtend terminal 72
–4.5.0 V bias = –10%; 0 Volt bias = rated voltage; 4.5 V bias = +10%
BHEL
Modified Compact Analog AVR
Use Si-TEC Xtend relay outputs (via 2 x external interposing relays) for volt trim interface
with AVR motorised potentiometer.
Naren
Digital Static AVR with DRU
Use Si-TEC Xtend relay outputs (via 2 x external interposing relays) for volt trim interface
with DRU.
NOTES:
(1) When terminal 71 is more positive than terminal 72 the voltage is biased for increased
excitation in the generator voltage output.
(2) It MUST be ensured that all AVRs are equipped with “Droop CT Kit” (Reactive Droop
Compensation) for paralleling requirements between generators, and/or between generator and
Mains / Grid Supply.
87
_________________________________________________________________________
The vector disturbance relay allows rapid detection of the loss of mains supply by a paralleled Si-
TEC Xtend CGC (or GSM) unit. This is possible through the detection of a small change in the
generator voltage vector angle relative to the rotor mechanical position. For the vector angle
change to occur as a result of the loss of mains, the load on the generator must change by a
specific amount depending on the sensitivity setting. It is important to note that the operation of the
vector disturbance relay does not depend on frequency deviation or voltage amplitude variations.
The relay detects the vector disturbance within 2 cycles (40ms) of the mains (grid) separation,
allowing the generator connection to the mains to be tripped well before mains power system
automatic re-closure occurs (typically 200 ms to 5 secs after trip).
The one condition that the relay cannot detect is a mains separation when the load on the
generator side of the separation point is such that the generator set sees little or no load change.
In most power systems, this situation is unlikely. Should this occur, the vector disturbance relay
activates if and when the load attached to the generator changes sufficiently to cause the requisite
vector angle change .
The relay sensitivity setting is the vector angle change required to activate the relay, and is
adjustable via the Si-TEC Xtend keyboard from 1 degree to 15 degrees in 1 degree increments.
Approximate load changes required to cause vector disturbance magnitudes are listed below.
1 5%
2 15%
5 35%
10 70%
The sensitivity adjustment is normally set to 5, which give the best compromise between a nuisance
tripping and detection coverage. The setting may be reduced to 1 degree in areas without ripple
voltage control systems, which at high amplitudes can cause apparent vector disturbances of up to
1 degree.
This relay provides protection from transmission system faults, where the mains voltage may be
absent or reduced for a significant period of time before the fault is cleared. Operation of the relay
and subsequent disconnection of the generator from the mains prevents possible loss of
synchronism ("pole slipping" or "out of step" operation) after the fault is cleared. When the fault
occurs the system impedance as seen at the generator terminals changes, with both real and
reactive components normally decreasing. The impedance change causes a rapid generator
loading change and voltage vector change, triggering the relay. In the unlikely circumstance of the
impedance change being gentle enough that the relay is not triggered when the fault occurs, then
should pole slipping occur when the fault is cleared, the violent load changes associated with pole
slipping are guaranteed to trigger the relay.
The vector disturbance relay is further energised upon the loss of a single or two phases. This is
achieved by utilising differential phase sensing of kWatts.
88
________________________________________________________________________
Section 7
2 Check the actuator linkage travel for HP and LP valves. The actuator should be
approximately 5% with the valve fully closed and approximately 95% position with the fuel
valve fully open. For LP valve, it is important to verify whether actuator-stroke is based on
forward or reverse acting, corresponding to minimum and maximum extraction valve position.
OK / .................
3 Check that the actuator linkage and valve assembly operates freely through the full travel
range without binding, and that there is no "slop" from loose or worn joints.
OK / .................
4 Apply 24 Volt DC supply to the Si-TEC Xtend module. The display should indicate power-up
tests, and then revert to the default “Genset is Shutdown” display.
OK / .................
5 Scroll up twice to the "Actuator Info" display (menu 87). Manually move the actuator from
minimum to maximum. Check that the indicated feedback % agrees with the graduated scale
on the actuator side plate. If not, refer to the Fault Finding section.
OK / .................
6 The actuator test function will only operate with the turbine in the “shutdown condition”. Scroll
to menu 081 “Set Actuator Position 1” in the “Actuator Test” sub menu (via CGC module for
HP valve stroke and PCU module for LP valve stroke). After entering the menu press the
“Bump” key to enable the actuator test. Changing the controlled value from 0 to 100% causes
the actuator to drive from 0% to 100%. The feedback is on the display to the left and
expressed in %. At 0% actuator output the feedback should read about 5%. At 100% actuator
the feedback should read about 95%. The 5% and 95% feedback should be where the
actuator is driving hard against the zero fuel and full fuel mechanical stops respectively. Set
the controlled value to 50% and check that the actuator positions correctly at about 50% with
a feedback reading of around 50%. Use the 0% and 100% actuator feedback calibration if
the minimum and maximum readings are undesirable. Where applicable, set up the “HP & LP
Valve Linearization” for accurate approximation of “Valve Position – Steam Flow” mapping.
OK / .................
89
_________________________________________________________________________
7 Note that the 5% to 95% actuator minimum-maximum range for valve minimum- maximum
range is used typically to achieve maximum actuator stroke distance and therefore work
output. Determining this minimum-maximum actuator range for valve minimum-maximum
range should be verified with turbine OEM prior to the actuator-valve linkage set up. In this
case, it is desirable to utilise as much actuator travel as possible.
OK / ………….
9 Ensure that the “Steam Map Data” is set up (via pcConfigure software) to correspond with
the turbine OEM “Steam Map” provided by the turbine OEM. Upon programming all the
parameters for the “Steam Map”, the “BUMP” key should be pressed to automatically enable
these settings.
OK / …………
10 Ensure that the PCU menu items 205 (Actuator Position on Comms Failure) and 206
(Actuator Ramp Rate on Comms Failure) are programmed, with settings determined after
consulting with client / turbine OEM.
OK / …………
11 Check all the preset values and set them to the correct values for the application. Some
values (eg. PID settings) will not be known and should be left at the preset values until tuning
is done. Record all the set values in the space provided in the Menu Summary section. This
will provide a permanent written record of the control system settings.
OK / .................
The Si-TEC Xtend support software "Si-TEC pcConfigure" facilitates the cross loading of the
preset values to a PC (personal computer). Set values are easily stored, loaded, modified
and printed out. An on-line help system is included with the “Si-TEC pcConfigure” software.
12 Check steam availability and confirm that all valves are in operating conditions. Conduct all
preliminary pre-start procedures in accordance with the prime mover manufacturer’s
recommendations.
Static and functional tests of all safety shutdown systems should be checked prior to starting
the turbine.
An independent shutdown system for over speed should be checked for correct operation
prior to proceeding with the commissioning.
OK / .................
13 Disconnect the main alternator excitation circuit to prevent voltage excitation of the generator
and subsequent voltage generation.
OK / .................
14 Set the Rated Speed input to “Low” (holds the set at Idle Speed). If the Rated Speed is not
selected as a logic input, the function should be set to “always OFF”. Ensure that the “Enable
Run” input (input 1) is active. Disconnect the actuator feedback terminal plug (terms 58 – 61).
This should cause a "Low Actuator Feedback Alarm” on the display and will hold the actuator
at minimum fuel. Replace the feedback terminal plug and reset the alarm. Check the
actuator “Start Fuel Limit %” setting.
OK / .................
90
________________________________________________________________________
15 After ensuring that the Main Steam Valve is fully open, activate the “Start Seq.” input (input 2)
to initiate the turbine start sequence. Verify the position of the actuator as it opens to permit
steam flow through the turbine throttle valve. After receiving the first MPU signals, the turbine
speed should increase until it matches the Warmup 1 speed. Verify that smooth speed
control is achieved and tune the Warmup 1 PID settings if required. After the Warm Up 1
delay is completed, the turbine speed should increase to the Warmup 2 speed level. Adjust
the Warmup 1 PID settings and/or the Idle PID settings to achieve smooth control at Warmup
2 speed level.
OK / .................
16 The turbine speed should now ramp to the preset Idle speed. Adjust the Idle speed PID
settings for stable operation. Check that the LCD displays the idle mode operation. (Refer to
PID set up procedure)
OK / .................
17 Check the operation of all safety shutdown devices during the initial starting eg. lube oil
pressure, inlet steam temperature, turbine axial displacement, turbine vibration, over speed,
emergency stop etc. (refer to the turbine manufacturer’s manual)
OK / .................
18 Switch the Rated Speed input to “High” or set the input to "always ON". The turbine should
ramp to rated speed at the preset ramp rate. Adjust the Rated Speed PID settings to obtain
maximum response, along with stable operation. (refer to the PID set up procedure for full
tuning details) When the tuning is complete, set the “Approx Actuator Position at No Load”
(menu 166) value in the “Actuator Settings” sub-menu. The value to set can be read from the
left side of the display while the turbine is operating at rated speed with no load.
OK / .................
19 Shutdown and re-start the turbine as necessary to optimise turbine operation for the
requirements and site conditions with respect to:
Warm Up 1 Time
Warm Up 2 Time
Idle Delay Time
Actuator Max Limits
Normal and Fast Speed Ramp Rates
Record all changed preset values in the Menu Summary section
OK / .................
21 Ensure that the load bus is “dead” or the fuse is isolated. Check the phasing of the bus to the
bus voltage inputs.
Red Phase: Input Aφ (terminal 100)
White Phase: Input Bφ (terminal 101)
Blue Phase: Input Cφ (terminal 102)
Star Point: Input N (terminal 103)
(Terminal 103 is not essential for 110Vac 3-phase, 3-wire PT inputs)
OK / .................
22 Connect the excitation circuit of the main alternator to enable voltage generation. Check the
main power cabling for phase and earth isolation.
OK / .................
91
_________________________________________________________________________
23 For MOP voltage Trimming: (to enable this function, set menu item 328 to “0”)
Set the voltage adjusting motorised operated pot (MOP) to its mid-point. For Dawson
Technology’s MOP, do not manually turn the clutch cylinder or cams. The MOP may be
controlled even while the turbine is shutdown, by switching to manual mode control (“Auto”
input “Low”) and using the manual raise and lower Volts inputs. If the inputs are not wired to
terminals, the functions can be configured ON and OFF to control the motor pot.
Set the main voltage adjust on the AVR for MINIMUM Volts.
OK / .................
For MOP voltage trimming: (to enable this function, set menu item 328 to “0”)
At no load set the main voltage adjustment for rated voltage. Raise the MOP to maximum
using the “Raise Volts” input (in manual mode). Check that the voltage is increasing. If
necessary, reverse the input connections to the MOP to ensure the correct output.
For Analog AVR biasing: (to enable this function, set menu item 328 to “1”)
The minimum and maximum DC voltage bias range should be set to suit the specific AVR
model (through menu items 334 and 335). If necessary, adjust the AVR Bias set points in the
“Voltage / AVR Control” sub menu for the correct voltage bias output range. The DC voltage
bias is displayed during this test. With the generator running and in the Si-TEC Xtend in
manual mode, (“Auto” input is “Low”) proceed to the “AVR Bias Output – Forced to” menu
item (menu 068) and use the “BUMP” key to force the bias test output. Check that the
maximum voltage reached is adequate (+15%) but not excessive. Lower the voltage and
check the low voltage range. Re-adjust the main AVR voltage control to optimise the
available voltage trimming range for the system conditions and kVAr loads. Please note that
kVAr generation on load will cause voltage droop and kVAr absorption will cause voltage
boost. The voltage P.I. must be tuned to stabilise the voltage control loop.
OK / .................
25 Check the phase rotation of the generator and change the main power connections if not
correct.
Should main power connections be altered, re-do tests 16 and 17 to confirm that the sensing
voltages have not been affected. Remember to change the generator current transformer
(CT) connections as well if the rotation has to be changed. Verify that the phases are correct
after the CT connection change.
OK / .................
26 Stop the generator. Reconnect the Generator Circuit Breaker (CB) for closure. Set the Si-
TEC Xtend module to manual mode (“Auto” input function switched “Low” or “always OFF”).
OK / .................
27 Set the MOP AVR trim pot for the operating (rated) voltage, or “AVR Bias Voltage starting in
manual” setting (menu 409) corresponds to the bias setting for operating (rated) voltage.
OK / .................
29 Start the generator and then externally close the CB on to a "No Load" dead bus.
NOTE THE NO LOAD BUS VOLTAGE
OK / .................
30 Apply an INDUCTIVE load by closing the Feeder circuit breakers to obtain a load of say 50 %
of the generator’s rated capacity.
The inductive load should be sufficient to obtain a power factor of between 0.70 and 0.90 and
best if this represents the actual connected load power factor.
OK / .................
92
________________________________________________________________________
31 The voltage droop should be set to provide a droop representing around 4% of the rated
voltage at full load, and at what will be the maximum lagging power factor. The voltage droop
is affected by the actual power factor and the load. Verify the alternator manual or
specifications for setting of the voltage droop.
IMPORTANT NOTE:
The voltage droop should be set so that at FULL LOAD and at the LOWEST POWER
FACTOR achieved at full load operation, the droop DOES NOT EXCEED the 6% voltage trim
as outlined in item 20 above.
eg. At 50% load and a power factor of say 0.80 the droop should be set for:
5% of 240 Vac Ph/N = 12 Vac at full load at 50 % load = 12 x 50/100 = 6 Vac droop Ph/N.
For paralleled generators the voltage droop(s) should be set to provide similar droop levels
on all generators.
OK / .................
32 After the voltage droop has been set, the Si-TEC Xtend “Auto” input function should be set to
automatic mode. The generated voltage should now be trimmed to maintain the preset rated
voltage.
Vary the loads on the generator to check for correct adjustment of the generator output
voltage such that the preset operation voltage is obtained.
OK / .................
33 Check the correct direction of Current Transformer connections by monitoring the “Info /
Alternator” sub menu – the kWatts should display positive values for all three phases.
OK / .................
34 Note the response of the generator under changing loads and tune the rated PID preset
values to provide for the optimum governor control response, namely fast response to
transient load changes and stable steady-state response. The “Si-TEC PC Tune” software
package is available to assist with governor dynamics tuning.
OK / .................
39 SHUTDOWN the generator and conduct all of the above procedures for all the other Si-TEC
Xtend control modules to be used in the application.
OK / .................
40 Check the menu preset values for both synchronising and parallelling of generators on ALL
the units.
Determine whether the “Si-TEC LAN” connections and terminators have been installed.
Verify the correct “Si-TEC LAN” communications by utilising the “Module to Module
Communications” sub menu. Scroll through the connected module numbers confirming that
the communication time (top right of the LCD screen) for each and every module displays ‘0’,
93
_________________________________________________________________________
occasionally changing to ‘1’. This confirms the proper communications between all Si-TEC
Xtend modules in the system.
OK / .................
41 Select a "Lead" generator and close this lead set to the DEAD BUS.
OK / .................
42 ENSURE YOU ISOLATE the Circuit Breaker relating to the generator which is to be
synchronised to the Main Bus.
OK / .................
43 Start the generator as if it is to synchronise and parallel with the bus. WITH THE GEN CB
ISOLATED closure should not occur.
OK / .................
44 Check the synchronising control and the CB "CLOSE" signal. The CB close signal should
only operate when all three phases are within the preset phase window angle. Check this by
measuring the voltage across the generator circuit breaker. Steps 16 and 17 should have
already confirmed correct phase sensing at the Si-TEC Xtend module.
The CB close signal will not operate if the generator voltage is beyond the preset minimum /
maximum voltage levels.
The Si-TEC Xtend preset synchronising voltage window should be set to a value greater than
the Si-TEC Xtend preset voltage dead band.
OK / .................
45 Voltage on the same phase ACROSS THE CIRCUIT BREAKER (at the circuit breaker)
should be less than 5% of the line to line Volts when a “Close CB” relay output is energised
(terminals 17 & 18). along with the corresponding LED indication.
Check and note voltage difference on RED (A) PHASE
Check and note voltage difference on WHITE (B) PHASE
Check and note voltage difference on BLUE (C) PHASE
OK / .................
49 Ensure that the “Extraction Control Enable” logic input function is switched “Low” prior to
synchronising and paralleling the generator.
OK / ……………
50 Re-excite the generator will now permit CB closure upon the generator synchronising with
the main bus. Check that the Gen CB (input 3) is energised when the generator CB closes.
OK / .................
51 Monitor the synchronising, kWatt ramping, kWatt sharing, and kVAr sharing of the sets.
Trimming of the load is not necessary if the preset kWatt rating and CT ratios have been set
correctly. Adjustments may be made to the kWatt ramp rate and Volts adjust rate to suit the
application.
OK / .................
94
________________________________________________________________________
52 Conduct tuning of the kWatt PID and the kVAr PI to provide responsive and stable kWatt and
kVAr sharing dynamics.
Set preset dead band of kWatt and kVAr to obtain fine and stable control.
OK / .................
53 Switch the “Extraction Enable” input function to “High” (On) and verify that the Extraction PI
control positions the LP valve based on the setpoint (i.e. Extraction Pressure Reference).
Conduct required tuning for optimum response (via pcTune software) based on both process
load transients, as well as turbine generator load transients.
OK / …………..
54 After ensuring that the other sets on the load bus have the capacity to carry the load, de-
energise input 2 (Start Seq.) to permit the unloading, opening of the Gen CB, and turbine
cool down cycle to commence. The generator should shutdown after the preset cool down
time has expired.
OK / .................
56 If “Grid Droop Control” is required for this application, ensure that all relevant parameter
settings have been programmed / fine-tuned to satisfy paralleling with National / State Grid.
OK / .................
57 Enable Extraction Control and verify smooth and optimum Extraction PID control. It is also
important to ensure smooth and optimum operation of “Ratio Control and Limiting”, for proper
and simultaneously operation of HP valve and LP valve under all transient and steady state
conditions.
OK / .................
95
_________________________________________________________________________
58 Set all menu preset values. Configure the module for the desired control functions. Refer to
the GSM menu items.
OK / .................
65 ENSURE THE ISOLATION of the Circuit Breaker relating to the switched output of the GSM
module.
OK / .................
66 Start the generator as if to synchronise and parallel to the bus. WITH THE CB ISOLATED
closure should not occur.
OK / .................
67 Check the synchronising control and the CB "CLOSE" signal. The CB close signal should
only operate when all three phases are within the preset phase window angle. Check this by
measuring the voltage across the switched circuit breaker. Steps 52 and 53 above should
have already confirmed correct phase sensing at the Si-TEC Xtend module.
The CB close signal will not operate if the grid voltage is beyond the preset minimum /
maximum voltage levels.
OK / .................
68 Voltage on the same phase ACROSS THE CIRCUIT BREAKER (at the circuit breaker)
should be less than say 1% of the line to line Volts when a circuit breaker close signal is
output on terminals 17 & 18.
Check and note voltage difference on RED (A) PHASE
Check and note voltage difference on WHITE (B) PHASE
Check and note voltage difference on BLUE (C) PHASE
OK / .................
96
________________________________________________________________________
69 DO NOT CONTINUE SHOULD STEP 60 PROVE THAT THE PHASES ARE NOT IN
SYNCHRONISM WHEN THE CB CLOSE SIGNAL ACTIVATED.
OK / .................
70 Adjust the Synchronising Proportional (gain) in the menu presets to achieve the optimum
synchronising control response.
OK / .................
71 Remove the “Sync Inhibit” of the CB closure enabling closure of the circuit breaker.
OK / .................
72 The generator bus will now be permitted to synchronise to the incoming grid supply and
provide CB closure.
OK / .................
73 Check the correct direction of Current Transformer connections by monitoring the “Info /
Alternator” sub menu for kWatt and kVAr readings, ensuring that values for all three phases
are positive for export and negative for import.
OK / .................
74 Monitor the synchronising, kWatt and kVAr ramping, as well as kWatt and kVAr control
across the mains incomer feeder. Adjustment of the Import / Export kWatts and kVAr can
now be conducted by adjusting the relative reference set point.
OK / .................
97
_________________________________________________________________________
8 FAULT FINDING
(a) Check for correct logic input signals for the required mode of operation.
(b) Check for loose terminations, wiring faults, and faulty contacts.
(d) Check the actuator linkages for any binding or excessive slop (lost motion).
(e) Check the Circuit Breaker (CB) auxiliary contact input for correct operation.
(f) Check if Voltage Droop CTs are connected, and if reversed or on the incorrect phase.
(h) Check the AVR settings, for proper control stability and operation.
Note: After the generator has been commissioned the PID settings should not require any
adjustment. Unless changes to steam supply, linkages, turbines, etc. have been made no error
would be expected due to the PID settings. If the cause for any of the following fault conditions are
stated as “Incorrect PID Settings”, this would mean that the commissioned PID settings may have
been adjusted and should be re-tuned back to the original commissioned values.
3) Actuator torque output relaxes momentary after a time period (15 sec +)
a) Actuator is operating in current limit.
b) Linkages and/or actuator are not moving freely due to binding.
c) Torque requirement too great (larger actuator required).
98
________________________________________________________________________
99
_________________________________________________________________________
1 : Reverse kW Alarm
2 : High kW Alarm
3 : Reverse kVAr Alarm
4 : High kVAr Alarm
5 : Phase Unbalanced Alarm
6 : Under Frequency Alarm
7 : Over Frequency Alarm
8 : Under Voltage Alarm
9 : Over Voltage Alarm
10 : Normal Off from PARA
11 : CB on in wrong State
12 : Microprocessor Reset
13 : External Trip
14 : Run Input Removed
15 : Loss of MPU signal
16 : Actuator Feedback Low
17 : Actuator Feedback High
18 : Normal Off Single
19 : Normal Off from ISOL
20 : PARA Off timeout
21 : Start Failure
22 : Speed Deviation
23 : Vector 3 phase loss
24 : Vector ph. unbalanced
25 : ONLINE Off in MAN.
26 : Loss of Gen. kW Input
27 : Turb. Speed Mismatch (for split shaft turbine application)
The corresponding “Modbus” addresses for the trip causes are as follows:
100
________________________________________________________________________
RTU 4 8 N 1
RTU 5 8 E 1
RTU 6 8 O 1
RTU 7 8 N 2
Baud rates of 19200, 9600, 4800 and 2400 are supported on the User RS485 port.
The optional “User RS485” port supports both “MODBUS” ASCII and RTU protocols, and supports
both read and write functions for extensive addressing of the Si-TEC Xtend module. The
addressing supported includes for that detailed below, menu preset values, and selected diagnostic
data points.
The Si-TEC Xtend modules are a slave device on the Modbus network and do not function as a
communications Modbus master.
The Si-TEC pcTune program may only access the Si-TEC Xtend set points via the RS232 port. It is
strongly recommended that the Si-TEC Xtend RS232 port be utilised for generator diagnostics only.
The “User RS485” communications port should be used for interfacing to Programmable Logic
Controllers, SCADA Systems and the like.
The Si-TEC Xtend modules’ communication facility includes for numerous Modbus error message
codes, exception codes 01, 02, 03, 04, 05, 06 and 08. When writing to a slave Modbus device the
“reply” from the slave device should be checked for error codes. Most Modbus propriety drivers
include for adequate error checking and data handling. Should it be necessary to write a Modbus
driver it is essential that the driver includes as a minimum; return function code “bit 7” is not set,
checksum (ASCII) or CRC (RTU) error checking, string length and end character checks, time out
control, error checking and detection of Modbus exceptions, disposal of “bad data packets”, and
buffer clearing.
It should be noted that the master module data address points differ with the generator modules.
Use Modbus function 3 for reading of data – typical start address of 2000 for operational data.
Use Modbus function 16 for writing data – refer to the following list for write addresses.
Use Modbus function 6 for single writes.
The Si-TEC pcTune and pcTransient programs only function on the Xtend module RS232 port. The
Si-TEC pcTune also operates via a modem connection (for off site Tuning and Diagnostics).
The Si-TEC pcConfigure typically operates from the Xtend RS232 port, although it can also operate
from the User RS485 port (applies to pcConfigure ver. 1.34 onward).
The User RS485 must be configured as follows for the pcConfigure communications.
a) Set pcConfigure communications for the correct slave (node) - menu 137
b) RS485 mode - set to ASCII - menu 138
c) User RS485 W.Endian - set to 0 = big - menu 140
d) User RS485 Bit Mode - set to 4 (8N1) - menu 141
The Generator module “User RS485 Address” (menu 137) is the node to address for the
respective generator not the generator module # (menu 132).
101
_________________________________________________________________________
c) The above accumulated data values can be edited using the Si-TEC pcConfigure
program This enables modifying data should turbines or modules be relocated,
replaced, etc.
Please refer to the 2000 address listing for reading of the data items, with the exception of
the No. of Starts which is read at address 5653.
PLD Type
Read address 5951
Data of 254 is OLD PLD (pre Dead Bus) : Data 29 is NEW PLD including Dead Bus
102
________________________________________________________________________
9.1 Generator Module Address Data Reference (2000 range – read only)
103
_________________________________________________________________________
Notes: K = kWatt Multiplier is used V = Voltage multiplier is used (F) = Filtered value
Communication Notes:
1) kWatt and kVAr (items 2 & 3) are transmitted as 2's complement of 65536 or 16 bit.
2) Frequency (item 32) is in two decimal places (i.e. 50Hz transmitted as 5000).
3) Power Factor (item 33) is in two decimal places and is transmitted as 2's complement of 256 or 8
bit (this is to provide possible negative values).
4) The Modbus protocol provides for all data to be transmitted as word (16 bit) values.
104
________________________________________________________________________
9.2 Generator Module Address Offset Data Reference (6000 to 8300 range – read
only). Data available at every Si-TEC Xtend Module
Module 0 has a base address 6000, module 1 has a base address of 6100.
Increase this base address by 100 for each increment in the module number
105
_________________________________________________________________________
0 Alarm Shutdown
1 Genset Shutting Down
2 Genset is Shut Down
3 Start Fail
4 Pre Start
5 Pre Lube
6 Not Used
7 Not Used
8 Not Used
9 Warm Up 1 Speed
10 Ramp to Warm Up 2 Speed
11 Warm Up 2 Speed
12 Ramp to Idle Speed
13 Idle Speed
14 In Critical Speed Band 1
15 In Critical Speed Band 2
16 Ramp to Rated Speed .
17 Warm Up at Rated
18 Synchronising
19 Ramp Up Island Mode
20 Isolated (Island) Mode
21 Ramp Down Island Mode
22 Ramp Up Parallel to Grid Mode
23 Parallel to Grid Mode
24 Ramp Down Parallel to Grid Mode
25 Not Used
26 Overspeed Test Mode
27 Ramp to Cool Down Mode
28 Cool Down Mode
29 Not Used
30 Not Used
31 Not Used
bits 0 - 4 is a 5 bit unsigned integer, which indicates the state (pub_state) see index below.
bit 5 is set if “Sequence Hold” input is high
bit 6 is set if “Auto” input is high
bit 7 is set if any of the following is true: base loaded, process active, actuator limited, kW
limited, under “grid droop” control, ramping On/Off load share.
bits 8 - 15 are not used, all = 0
Note: A Generator can only be in one of the 0-31 states at any one time. Addition of the value of
the upper 3 bits provides the additional information.
It should be noted that the master module (GSM) address points differ in part from the address
points of the CGC modules. The above addresses may be read from either the CGC or GSM
modules for generator data addresses. Please refer to the Si-TEC Xtend GSM manual for details of
the master data address points.
106
________________________________________________________________________
0 Alarm Shutdown
1 Genset Shutting Down
2 Genset is Shut Down
3 Start Fail
4 Not Used
5 Warm Up 1
6 Ramp to Warm Up 2
7 Warm Up 2
8 Ramp to Idle
9 Idle
10 Not Used
11 In Critical Range 1
12 Not Used
13 In Critical Range 2
14 Ramp to Rated
15 Warm up at Rated Speed
16 Synchronising .
17 Reserved
18 Generator On-Line (isolated) with load ramping up
19 Generator On-Line and load sharing
20 Generator On-Line (isolated) with load ramping down
21 Generator On-Line (parallelled to grid) with load ramping up
22 Generator Parallelled to Grid
23 Generator On-Line (parallelled to grid) with load ramping down
24 Ramp to Cool Down & Cool Down Mode
25 Not Used
26 Not Used
27 Not Used
28 Not Used
29 Not Used
30 Not Used
31 Not Used
Note: A Generator can only be in one of the 0-31 states at any one time. Addition of the value of
the upper 3 bits provides the additional state.
It should be noted that the master module (GSM) address points differ in part from the address
points of the CGC modules. The above addresses may be read from the CGC or GSM modules for
generator data addresses. Please refer to the Si-TEC Xtend GSM manual for details of the master
data address points.
107
_________________________________________________________________________
It should be noted that the master module (GSM) data address points differ from the address points
of the CGC modules.
108
________________________________________________________________________
9.6 Generator Multiplier for kWatt, kVAr & Volt Table (address offset 0)
Bits Function
0 Group 1
1 Group 2
2 Request to Dead Bus
3 Confirm Will Not Dead Bus
4 Dead Bus Close Time Out
5 kVAr Lag Limited (reserved)
6 kVAr Lead Limited (reserved)
7 Spare for Gen
8 Not available = 0
9 Is Gen Module = 0
10 Not used = 0
11 Not used = 0
12 Not used = 0
13 kWatt Multiplier – bit 1
14 kWatt Multiplier – bit 2
15 Voltage Multiplier
Address Address
109
_________________________________________________________________________
This menu Item display also shows on the bottom line: TXE = 0 (or 1) FL = 0 (or 1)
If the value is one in TXE this indicates that the transmission is active. This should mostly
display 0 and flash to 1 on a comms request. If fixed at a value of 1 the Xtend is locked in
transmit mode.
NOTE: The communication counters are reset by powering down & re-booting of the
module, or by pressing the RESET key when in the menu after having Technical
Access.
Menu Item 087 provides for selecting a Modbus address number (3rd line at right side).
The value of the Modbus address is displayed to the left of the 3rd line.
The left of the 4th line displays the next Modbus address number.
110
________________________________________________________________________
Appendix
Technical Details
111
_________________________________________________________________________
This function is incorporated in Si-TEC Xtend firmware version BA1.08 onwards, and fitted with a
version 2.9 PLD
For version BA1.08 firmware or later, the PLD version is displayed at Modbus address 5951. A
value of 254 reflects earlier version PLD, where a value of 29 represents PLD vers2.9.
The Dead Bus function conducts checks and performs a rotating “picking” order for closing the
generator(s) to a dead bus.
The “CB Close” relay output of the Si-TEC Xtend control is operated for the generator CB dead bus
closure.
The “Dead Bus Enable” (M441) logic input can be set to always OFF, always ON, or alternatively
allocated to switch a logic input terminal of the Si-TEC Xtend control.
The bus voltage (all three phases) must be measured below the “Dead Bus Threshold volt % of
Rated” (M300) for that or any other generator in the group to close to a dead bus.
Each Si-TEC Xtend control conducts checks for “OK to Dead Bus” and sets a “flag” to advise all
other generators in the same group, that it is the “Dead Bus” set. When a generator is the
automatically selected set for dead bus closure, this generator remains selected for the “Dead Bus
– Attempt Time” (M301) providing a “Close CB” signal output. Should a dead bus still exist after this
time, a fixed delay of 2.0 sec occurs prior to moving the dead bus close function to the next
generator. The system starts at the highest numbered module and if necessary proceeds to the
lower numbered modules.
The “Dead Bus Fail Reset Time” (M302) when set to 0.0sec does not permit a retry of dead bus
closure should the initial attempt have failed (typically due to external causes). Settings other than
0.0 seconds will provide a “reset”, allowing for continuous rotation of “the picking order” of the
generators. If not set to 0.0 seconds, the “Dead Bus Fail Reset Time” should be set greater than
the maximum number of generators in the same group multiplied by the “Dead Bus Attempt Time”
(i.e. [Number of generators X menu M301 value] + 2 seconds).
The “Dead Bus” function may also be configured as an alarm (using a Combined Alarm) by setting
the “Dead Bus attempts before alarm” (M694) to any value above 0 (1 to 100). The “Dead Bus
Timeout” alarm activates after the initial Si-TEC Xtend unit fails to issue a successful dead bus
closure after the programmed number of attempts.
NOTE: It is recommended that external interlocking be incorporated for the Dead Bus control
function. Such interlocking could be in series with the CB close signal, and/or synchronising inhibit
input, and/or the dead bus enable input.
112
________________________________________________________________________
Diagnostics
The Si-TEC Xtend control module default display will show the “Dead Bus Mode” during dead bus
operation. Additional diagnostic codes will also be displayed on the right side of the lower line of the
Si-TEC Xtend LCD screen. The codes are as follows:
Application Notes
(1) Should the installation have smaller generators that are not desired to do the dead bus closure,
the “Dead Bus Enable” input function may be set to always OFF for these Si-TEC Xtend
modules.
(2) There will be a fixed time of 2 seconds prior to automatically changing “Dead Bus” closure
selection to the next generator.
(3) Where “Grouping Control” is utilised, dead bus closure is conducted separately for each group
of generators.
(4) Where the “Dead Bus Fail Reset Time” (M302) is set to 0.0 seconds, the respective generator
will not conduct a further dead bus closure attempt unless the dead bus failure is reset. This is
possible when the generator:
a) Switches on line
b) Senses bus voltage above the “Minimum Voltage for Synchronising” (M298)
c) Is in Shutdown State
(5) If the voltage sensing of an open bus produces “residual voltages” above the “Dead Bus
Threshold Volt % of Rated” (M300), this could prevent the dead bus closure operation. A load
burden on the bus may be required to eliminate the occurrence of such voltages.
113
_________________________________________________________________________
The Permissive Synchronising Function provides a controlled “CB closure” when the Si-TEC Xtend
Manual control mode was selected (i.e. “Auto” input is low). This function is enabled by switching
the “Permissive Sync. Mode Select” (M440) logic input function to high.
The Permissive Synchronising function allows closure of the generator circuit breaker via the “Close
CB” relay output in Si-TEC Xtend Manual control mode when the synchronising parameters are
met. These include:
a) Slip Speed within tolerance
b) Generator and Bus phases within the Phase Angle Window
c) Generator and Bus voltages within the Voltage Matching Window
d) Generator within the minimum and maximum frequency and voltage range
In the Si-TEC Xtend Manual mode, the “Permissive Sync. Mode Select” input is required to be high
in order for the generator CB to close (external sync check and closure of the generator CB is also
permitted).
During the “Permissive Synchronising” state, manual raise and lower of speed and voltage should
be conducted via the respective logic inputs. When the above synchronising conditions are met, the
Si-TEC Xtend “Close CB” relay output will energise to close the generator CB.
After the generator CB closes, the operator has control of the kWatt and kVAr as the control is still
in the manual mode. Switching the control to Automatic mode will permit the bumpless transfer of
kWatt and kVAr/PF load till they match the respective control references.
If the Si-TEC Xtend control is in Automatic mode (“Auto” input is high) and the “Permissive Sync.
Mode” input is high, NO speed adjustment or voltage matching is conducted for synchronising,
however the generator CB will close if the above speed, phase and voltage matching conditions are
met.
Please refer to the “Truth Table” below, for an illustration of the Permissive Synchronising function.
High Low
C A, C
Si-TEC Auto mode
Legend:
A = Si-TEC Xtend automatically biases speed and voltage to match the bus
C = Si-TEC Xtend issues “Close CB” output for generator CB on sync. matching
S = Manual speed adjustment (Raise/Lower) is operative
V = Manual voltage adjustment (Raise/Lower) is operative
NOTE: For “normal” Si-TEC Xtend control operation, the “Auto” input is High, and the “Permissive
Sync. Mode” input is Low.
114
________________________________________________________________________
Appendix
Si-TEC Xtend
Control
Illustrations
115
Si-TEC Xtend CGC control faceplate
Si-TEC Xtend PCU module faceplate
Si-TEC Xtend Menu Preset Items for PCU (Process Control Unit) module
To enhance dynamics tuning the actuator may be "Bumped" using the Si-TEC Xtend module.
The “Bump Magnitude” (%) is set to decrease the LP actuator position. The “Bump Duration”
(seconds) is the time duration required for the "Bump". Push the “BUMP” button on the
keypad to operate the disturbance. While this function may be used when the generator is
unloaded or loaded, care must be taken when setting the value of the magnitude and duration
before the “bump” test is performed.
Minimum Act. Trim in % (to force press BUMP key) menu 282
This is the minimum position at which the Si-TEC Xtend control will drive the LP actuator.
Maximum Act. Trim in % (to force press BUMP key) menu 283
This is the maximum position at which the Si-TEC Xtend control will drive the LP actuator.
Note: Only parameters under the “Actuator Settings – Sub Menu” of the PCU module have
been described in detail, as other menu items are mainly applicable for display and
diagnostics.
Si-TEC Xtend CGC-ET Extraction-Condensing Turbine
Application
RS232 Diagnostics Port 32 x D/I, 18 x D/O, 8 x A/I & 6 x A/O (via CGC & PCU combined)
HP Act.
AVR
Computer
INLET PRESSURE 25.0 MW T/G
TURBINE SPEED (2 X MPU)
EXTRACTION PRESSURE
HP Act. AVR
Computer
INLET PRESSURE 10.0 MW T/G
TURBINE SPEED (2 X MPU)
EXTRACTION PRESSURE
TURBINE MONITORING
LP Act.
MSV
AVR
HP Act.
Computer
INLET PRESSURE
30.0 MW T/G
TURBINE SPEED (2 X MPU)
EXTRACTION PRESSURE
DCS
Grid CB Aux
Main CB
Modbus RS485
132 kV / 11 kV
Transformer
Grid PTs
Si-TEC LAN
Mains CB Aux
Tie CB GSM
Mains CB Aux
Mains CB Aux
Bus PTs
Gen PTs
Plant Gen PTs Gen PTs
Plant
Gen CTs Load 1 Load 2
Gen CTs Gen CTs
T/G 3 T/G 2 10.0 MW T/G 1 5.0 MW
10.0 MW
Si-TEC LAN
Si-TEC Xtend Control System Overview
(Island & Grid parallel application with multiple incomers & grouping control)
DCS
Grid CB Aux
Grid CB Aux
Main CB Main CB
Modbus RS485
132 kV / 11 kV 132 kV / 11 kV
Transformer Transformer
Grid PTs Grid PTs
Si-TEC LAN
GSM 2
Mains CB Aux
Tie CB GSM 1 Tie CB
11 kV, 50 Hz Bus
Mains CB Aux
Mains CB Aux
Si-TEC LAN