Professional Documents
Culture Documents
AC880Technical Data
Powered by
Cummins KTA38-G2B
800KVA at 50Hz, 400V
General feature:
♦ Assembled by Cummins diesel engine and Kaijieli alternator.
♦ Three filters as standard, fuel and water separator as optional.
♦ Radiator and fan with safety guard.
♦ Single bearing alternator IP 23, Insulation Class H.
♦ Heavy duty steel as base frame and 8hrs operation base fuel tank.
♦ Automatic control panel and 3 poles circuit breaker, internal cable.
♦ 12V or 24V battery, battery wires.
♦ Battery charger and float battery charger as standard supply scope.
♦ Optional soundproof canopy, ATS, synchronization panel, movable trailers.
(1) PRP: Prime Power is available for an unlimited number of annual operating hours in variable load applications, in
accordance with ISO8528-1. A 10% overload capability is available for a period of 1 hour within 12-hour period of
operation. In accordance with ISO 3046-1.
(2) ESP: The Standby Power Rating is applicable for supplying emergency power in variable load applications for
AOSIF Cummins Series
AC880Technical Data
(2) ESP: The Standby Power Rating is applicable for supplying emergency power in variable load applications for
up to 200 hours per year in accordance with ISO8528-1. Overload is not allowed.
Fuel Consumption:
Exhaust system:
Lubrication system:
Oil pressure
-----------Idle speed 20 psi(138 kPa)
-----------Governed speed 296-483 kPa
Max. allowable oil temperature 121 ℃
Oil Capacity with OP 6012 Oil Pan : High - Low 23 _ 30 L
Total system capacity 135 L
Angularity of oil pan- Front down /Front up /Side to side 30°/30°/30°
Fuel system:
Cooling system:
Coolant capacity
---------------------Engine only 31.2 US gal (118 L)
.---------------------with Heat Exchanger 13 US gal (49.2 L)
Max coolant friction head external to engine 7psi(48kpa)
Maximum Static Head of Coolant Above Engine Crank
18.3 m
Centerline.
Standard thermostat(modulating) range 82-94 ℃
Min. allowable pressure cap 69 Kpa
Max. allowable top tank temperature for standby/prime power 104 _ 100 ℃
Engine water flow 21.8 L/s
Electric system:
AOSIF Cummins Series
AC880Technical Data
Min. recommended battery capacity (24v)
Cold Soak @ 50 °F (10 °C) and Above 0°F CCA1200
Cold Soak @ 32 °F to 50 °F (0 °C to 10 °C). 0°F CCA1280
Cold Soak @ 0 °F to 32 °F (-18 °C to 0 °C). 0°F CCA1800
Max allowable resistance of starting circuit with 24V starter 0.002 Ω
Standard cranking motor(heave duty, positive engagement) 24 V
Battery charging system,negative ground 35amper
ALTERNATOR Specifications:
Manufacturer Suzhou Defeng Motor Co.,Ltd
Model TWGⅡ404C
Frequency 50HZ
Rated voltage 400V
Rated power at Class H (40℃) temperature rise 640KW
Drip-leak-proof structure IP22 protection class
Insulation class H
Phase Thress phase four wires
AVR include
Adjusting rate of stable voltage ≤+/-1%
Transient state voltage ≤-15% ~ +20%
Wave aberration rate of voltage(THD) ≤3%
Telephone hamony wave factor of telephone(THF) ≤2%
Telephone effective factor of telephone (TIF) ≤50
Altltude ≤1000m
Cooling air temperature -15℃ ~40℃
Relative air humidity ≤90%
Standard International IEC, GB755 and relevant standard
AOSIF Cummins Series
AC880Technical Data
Deepsea 6020
⑤ Auto start and stop control panel
④ ③ ②①
Deepsea 6020 is an auto mains ♦Volt adjuster and frequency
failure controller for single adjuster.
generator, it can monitor and ♦Emergency stop
protect the generator working all ♦Fail to start
① Power switch
the time. it has a LCD display
which clearly shows the status of ② Lamp switch
the engine. this controller include
Features: ③ Power indicator
seven inputs and six outputs. This♦Protection: Automatic start/stop, ④ Operation buttons
controller can also be load transfer and alarming of ⑤ LCD display
programmed using the frong generator;
panel or by using DSE ♦ CAN and magnetic pick-up
configuration Suite PC software. versions.
♦PC and front panel configurable
Parameters: ♦4 digital inputs and 3 analogue
This controller can provide inputs.
Generator frequency, Under/over ♦6 outputs(4 configurable on
speed, Generator volts, Generator magnetic pick-up, 6 configurable on
current, Engine oil pressure, Canbus version).
Engine coolant temperature, ♦3 phase generator and mains
Flexible fuel level, Hours run voltage monitoring. Open type
counter, Battery volts, Fail to ♦remote start on or off load.
start/stop, Emergency Stop. ♦advanced metering capability.
Failed to reach loading ♦test button.
voltage/frequency, Charge fail, ♦protected solid state outputs.
Loss of magnetic pick-up signal, ♦transfer between mains and
Low DC voltage, CAN diagnostics generator power.
and CAN fail/error, Mains volts 3 ♦user-friendly set-up and button
phase, Mains frequency, AMF layout.
indications ♦multiple engine parameters are
monitored simultaneously.
Protection: ♦module can be configured to suit
♦Low Oil Pressure individual applications. Silent type
♦High water Temperature ♦IP 65 rating offers advanced
♦High voltage and low voltage resistance to water ingress when
♦Overspeed gasket is fitted.
AOSIF Cummins Series
AC880Technical Data
AOSIF Soundproof Enclosure Specification:
AOSIF silent generator is designed by professional acoustic
engineers based on 11 years experience, Now we can
make the noise of the generator less than 80-85dB(A) at
1m, or 70~75dB(A) at 7m, 60~65dB(A) at 15m.
Supply scope
AOSIF Cummins Series
AC880Technical Data
1.Standard supply scope:
③
⑤
②
⑦ Exhaust silencer
①
⑧ Starting battery
⑥ ⑤ ④
⑧ Elec.coolant Heater
⑩ Trailer &
⑥ Synchronization ⑨ Oil drain Pump
⑦ Lub oil heater Silent Canopy
System
AOSIF Cummins Series
AC880Technical Data
Our Sales Promises
★AOSIF Engineering provides a full line of brand new and high quality products. Each and every unit is strictly
factory tested before shipment.
★Quality Warranty is according to our standard conditions: 12 months from BL date or 1,000 running hours,
whichever comes first.
★Service and parts are available from XIAMEN AOSIF Engineering Ltd. or distributors in your location.
★All the products from Xiamen AOSIF Engineering Ltd. is CE marked.