You are on page 1of 7

Capacitor Bank Switching

with Vacuum Circuit Breakers


Hans Schellekens
Schneider Electric, Power SBU, Medium Voltage Development, Usine 38V, ZAC Champ Saint-Ange, Varces, France

Abstract : After interruption of a capacitive current For vacuum CB’s, the physical processes during the
sometimes Non Sustained Disruptive Discharges (NSDDs) capacitive switching duty have been studied by [5].
are observed when using vacuum circuit breakers. They found that the pre-ignition at contact closing and
According to network calculations, NSDDs generate the subsequent inrush current heavily eroded the
significant over-voltage on the terminal of the capacitor contacts leading to detached particles. These particles
bank to ground and across the circuit breaker (CB) cause late breakdowns which appear as NSDDs 1 .
terminals. In a full scale experiment at 12kV on an 8Mvar Breakdown frequencies of typically 3/1000 where found
capacitor bank artificial NSDDs are produced using a under the experimental conditions studied. The
Triggered Vacuum Gap. The over-voltage depends on the probability of breakdown depends on the dielectric
momentary voltage difference across the breaker and, conception or contact stroke of the vacuum interrupter.
hence, varies with the phase angle. The over-voltage on the So for the same voltage rating different designs lead to
terminal of the capacitor bank to ground varies from 1.5 to different probabilities of occurrence of NSDD. Fig. 1
4.2 pu, and to maximum 5.2 pu. across the CB terminals. shows the experimentally found relation between
The effectiveness of surge arrestors on the limitation of the dielectric conception, based on contact gap, and the
over-voltages is measured. The over-voltages are limited to probability of a NSDD during an operation. It shows
2.2 pu. on the terminals of the capacitor bank to ground that a minimum contact distance of 16 mm is necessary
and 3.2 pu. across the CB terminals. A single surge to reduce this probability below 1/500.
arrestor on the neutral point of the capacitor bank yields The overvoltage produced by a NSDD differs
the same level of protection and, therefore, is a cost notably from the overvoltage produced by a restrike. A
effective alternative. An application guide for switchgear restrike can generate an overvoltage of 3 pu. between
and arrestors is presented. the terminals of the capacitor bank, whereas a NSDD
causes a sudden voltage shift of the neutral capacitor
I. INTRODUCTION bank voltage, which leaves the voltage across the
capacitor unchanged, but creates an overvoltage
The capacitive current switching duty is characterised between 1.5 and 5 pu. on the terminal of capacitor bank
by frequent, day to day or hour by hour, switching of to ground and between 2.5 and 6 pu. across the CB
low to moderate currents in industrial or public terminals. Due to this high overvoltage a second NSDD
networks, and by a low rate of rise of recovery voltage. in the adjacent phases becomes more likely.
Modern circuit breakers (CB’s) which claim a long
mechanical but also electrical life without maintenance
seem to be best adapted to this switching duty [1,2,3].
Yet the behaviour of vacuum CB’s is rather different
from that of gas CB’s.
Today, the circuit breaker envisioned for capacitor
bank switching is either a vacuum or SF6 circuit breaker
or a vacuum or SF6 contactor. All these devices are
known for their long service life. The circuit breaker
offers a protection against short circuit currents with an
electrical life between 10.000 and 30.000 operations at
nominal current. Contactors offer an electrical life up to
1 million operations depending on load conditions. SF6
CB’s, in the past referred to as “restrike free” breakers,
are according to the new IEC62271-100 class C2 Fig.1 : Experimentally found dependence between probability of a
NSDD and nominal contact stroke of vacuum interrupter.
breakers with proven “very low restrike probability” [4].
Field experience indicates that the restrike probability 1
even for the electrically very stressed 36 kV networks is NSDD or non-sustained disruptive discharge [7] is a disruptive
discharge associated with current interruption that does not result in
lower than 1/50.000. the resumption of power frequency current or, in the case of capacitive
current interruption does not result in current in the main load circuit.
When two NSDDs occur simultaneously, the illustrated by Fig. 2, the voltage across the breaker
phenomenon turns into a restrike. Typically, a vacuum moves as a travelling wave through the line impedance
CB with a contact gap of about 16 mm has a probability towards the capacitor bank. The capacitor bank being a
of about 1/500 for producing a NSDD and belongs to
the class C2 with proven “very low restrike probability”.
Due to the rare occurrence and the random nature of
the phenomenon, the relation between NSDD and
overvoltage is not evident. Therefore in this paper this
question is addressed in section II using a numerical
network simulation. By this the worst case overvoltage
for different voltage levels is determined. Then in
section III an experiment designed to verify the
simulation results is shown. Here the NSDD is created
artificially, which permits to measure the influence of
phase angle and network parameters. A good
understanding of the origin of the overvoltage enables Fig. 3 : The voltage on all 3 capacitor bank terminals during current
interruption (at 0.1s) followed by a NSDD (at 0.13s) in R phase in a
the definition of protective measures adapted to the 12kV network.
switchgear and capacitor bank. In section IV protection
schemes based on surge arrestors are tested and
high frequency short circuit allows the wave to pass on
compared on their effectiveness. Finally in section V the
to the neutral point of the bank. At the neutral point the
results are discussed and an application guideline is
wave splits itself and continues its propagation in the
presented for the choice of switchgear and arrestor.
neighbouring phases towards the healthy CB poles.
II. ORIGIN OF OVERVOLTAGES These healthy poles are in fact open terminals for the
incoming wave causing it to reflect by doubling the
A. Numerical simulation voltage. After reflection the wave travels back to the
The simplified electrical circuit, Fig. 2, will be used failing CB pole. Here it creates a current zero passage
here to simulate the phenomena associated with a on which the breaker can interrupt. The frequency of
NSDD; the NSDD is simulated as a temporary loss of this current is typically of the order of 100 kHz for cable
dielectric strength in the vacuum interrupter of a connected capacitor banks. Fig. 3 shows the voltage
vacuum CB. swing on the bank terminals with respect to ground.
Note that
- For each of the three bank terminals the voltage
jumps to a new value, which means that the neutral
point of the bank attains also a different value.
- The voltage difference between terminals remains
unchanged. The capacitors themselves are not
stressed by the breakdown.
- The maximum terminal voltage to earth attains a
high value (see table I). This is a dc voltage, so all
parts of the installation are stressed during a long
period.
Fig. 2 : Electric circuit used to calculate overvoltage on capacitor
- The CB is stressed by the composed voltage of
bank during a NSDD. TVG see section III.
network voltage and capacitor bank terminal
The source side of the network is represented by: voltage.
- a generator with a driving voltage of U - The capacity of the bank itself is of no significance
- a short circuit impedance of value Ls for the phenomenon.
- a TRV network as defined by IEC for short circuit Table 1: Compilation of voltages associated with capacitor bank
conditions switching for nominal network voltages
- a capacitor Cp to account for parallel feeders Um US U C-bank UVCB BIL Power
The load side of the network is represented by: frequency
kVrms kVrms kV kV kV kVrms
- a 8Mvar capacitor bank with floating neutral
- single phase cables between CB and the bank. 12 10 47 55 75 28
The load and the source side of the network are 24 20 93 110 125 50
connected to each other by the CB. The CB is treated as 36 30 140 164 170 70
an ideal breaker with a NSDD some time after current
interruption. The moment of NSDD has been chosen in
B. Identification of zones at risk
order to create the worst possible case. The CB is
In table I the maximum possible overvoltage
allowed to recover immediately at the first occurring
produced by a NSDD is shown for three commonly
current zero. At a NSDD, on the R phase for the case
used classes of network voltages. For each voltage class creates a dc voltage on the capacitor bank terminal of
column 2 gives Us the nominal network voltage. 1.5 pu. Then 30 milliseconds after current interruption a
Column 3 gives the maximum overvoltage on the NSDD is generated in phase R at a maximum voltage
capacitor bank terminal to ground and column 4 the difference across the CB. At this moment the voltages
maximum overvoltage across the CB terminals. For on all C-bank terminals change suddenly and settle to a
reference the BIL and power frequency withstand new constant value. The highest overvoltage is found in
voltages of the equipment are given. For all three phase T. The instant of occurrence of the NSDD was
voltage classes both overvoltages exceed the peak value varied by firing the TVG at a predetermined moment to
of the power frequency withstand voltage. For the CB see the influence of the phase angle on the nature and
the overvoltage comes very close to the rated BIL the value of the over-voltage. The waveform of the
voltage for 36 kV class networks. overvoltage is a dc voltage and is the same for all tested
phase angles.
III. EXPERIMENTAL VERIFICATION

A. Test procedure
The objective was to create in a reproducible way
NSDD type breakdowns in a capacitive current
interruption test. This allowed to minimize the number
of tests to obtain the desired NSDD. NSDDs do not
occur frequently and are therefore difficult to reproduce.
A triggered vacuum gap (TVG) parallel to the R-phase
of the VCB is used to create an artificial NSDD in a
controllable way. A separate experiment confirmed that
the TVG was able to interrupt high frequency currents
of, for instance, 300A at 100kHz and 10 A at 900 kHz
at the first current zero. Hence, the duration of the
“artificial” NSDD is determined by the circuit topology
and only one half cycle of high frequency current will
pass through the TVG. Numerical modelling showed
that this will lead to the highest possible overvoltage.
Using the TVG provided a measurement window with
high frequency sampling centred at the time of
breakdown allowing precise measurements to be made.
Full scale tests are performed in a direct test circuit fed
by a generator 2000 MVA at 12 kV with short circuit Fig. 5a : Normal interruption of Fig. 5b : As Fig. 5a Surge arrestor
current limited at 14 kA. The capacitive load was a 8 capacitive current followed by in phase T limits the overvoltage.
Mvar capacitor bank; nominal current of 430 A. The NSDD in R phase after 30 ms.
detailed characteristics of the test circuit are given in For each phase (R, S, T). Red : Source side voltage on CB.
Green : Load side voltage on CB and capacitor bank terminal.
Fig. 4 and table II. Blue : Current through CB. Time scale: 1ms/div.

B. Test results
Fig. 5a shows an oscillogram of a normal
interruption with NSDD. The first phase to interrupt, R,

TABLE II : Main characteristics of test system of Fig. 4


Capacitive circuit directly fed by generator
Rated voltage 12.1 kV
Rated current 430 A
Short circuit current 14.7 kA
TRV circuit
rise time t3 61 µs
peak voltage 23 kV
Capacitor bank 184 µF/phase
Cable connection 30 Metres
C cable 10 nF
Short circuit inductance
Lw 1,51 mH
Fig. 4 : 3-phase test circuit with generator and 8 Mvar capacitor bank. R < 30 mOhm
Test object : VCB : 12 kV 25 kA 1250 A
Triggered Vacuum Gap on phase R
and a voltage jump due to the NSDD. The amplitude of
the voltage jump depends on two factors :
• the voltage across the breaker at the instant of
breakdown, which varies with time or phase angle,
and which is maximum 2.5 pu. (see Fig. 5a).
• an amplitude multiplication K-factor (section IIIC)
The voltage difference at breakdown is transmitted
integrally to the neighbouring phases as predicted by the
numerical simulation. Except for a reduced amplitude
factor the behaviour found is identical to the simulation.
Moreover, the most severe overvoltage is produced by a
NSDD in the first phase to interrupt at the moment of
Fig. 6a : Variation of over-voltage in phase T expressed in pu due to the largest voltage difference across the CB.
instant of occurrence (phase angle) of the NSDD in 1st phase R to
interrupt. C. Influence of TRV circuit
The influence of the TRV circuit on the high
Fig. 6a shows the measured voltage on the capacitor frequency behaviour of the breakdown has been studied
bank terminal in phase T to ground after the NSDD in with the following circuits:
phase R. Before the NSDD the voltage is about 0.89 pu. TRV-1 : The standard TRV circuit composed of 2
The voltage jump is between 0.6 and 3.2 pu. leading to branches see Fig. 2.
an over-voltage of maximum 4.1 pu. The height of the TRV-2 : No TRV circuit; only stray capacitance
overvoltage varies harmonically with the phase angle. between Generator and CB.
In order to investigate whether the above condition
is the most severe one, the experiment was repeated by TABLE III : Influence TRV circuit on peak value of overvoltage
TRV-1 TRV-2
keeping the first phase to clear in phase R and Voltage jump
generating the NSDD in phase T. The highest K-theoretical 2 2
overvoltage is now found in phase R. The instant of K-Immediate 1.6 1.7
occurrence of the NSDD was varied by firing the TVG K-Late 1.3 1.6
Damping time 16.5µs 13.5µs
at a predetermined moment to see the influence of the Frequency NSDD current 150 kHz 28 kHz
phase angle on the nature and the value of the over- Current 28 A 6A
voltage. The waveform of the overvoltage is a dc
voltage and is the same for all tested phase angles. Fig. Results are shown in table III. The voltage jump after
6b shows the measured voltage on the capacitor bank breakdown can be characterised by :
terminal in phase R to ground after the NSDD in phase • A peak voltage immediately after the NSDD: with
T. Before the NSDD the voltage is about 1.5 pu. The K factor : K-immediate.
voltage jump is between 0 and 2.5 pu. resulting into an • A dc voltage after a transition period: K-late. The
over-voltage of maximum 4.0 pu. The height of the transition is characterised by a time constant here
overvoltage varies harmonically with the phase angle. called “damping time”.
• The frequency of the NSDD current.
Fig. 7 shows an oscillogram of the voltage on both sides
of the CB during the NSDD for TRV-2 circuit. During
the NSDD, between 12 and 30 µsec, both voltages are
identical as an arc in the CB allows for current to pass
from the source side to the load side. Due to the small
TRV capacitance, the source side voltage collapses at
12 µsec and joins the load side voltage. During the
current flow the voltage makes an oscillation around the
driving voltage (the source voltage before the NSDD).
When this reaches a new maximum at 30 µsec the
current passes through zero and interruption takes place.
After interruption, the source voltage is subject to the
Fig. 6b : Variation of over-voltage in phase R expressed in pu due to TRV generated by the driving voltage of the generator
instant of occurrence (phase angle) of the NSDD in 2nd phase T to and the TRV circuit. The load side voltage settles to a
interrupt.
new dc voltage level. Numerical simulation suggests
Note that the over-voltage is the addition of the voltage doubling with a K-factor equal to 2. Therefore
original capacitor bank voltage after current interruption the reduced value of K-immediate is attributed to
damping of the high frequency current at NSDD.
1. The series impedance of two branches R and T of
the capacitor bank and the series inductance of
phase R and the resistance to ground of the
generator.
2. The voltage difference across the capacitor prior to
breakdown minus the voltage of the arrestor.
Notice, that during the limitation of an overvoltage due
to a NSDD only one surge arrestor is conductive and
dissipates the energy. Due to the random nature of
current interruption the maximum overvoltage can be in
any of the three phases. Therefore, surge arrestors have
Fig. 7 Zoom at voltage behaviour at NSDD in R phase with TRV-2. to be installed on all three phases.
Green (1) : Load side voltage on CB and capacitor bank terminal.
Red (2) : Source side voltage on CB. Time scale 10µs/div. B. Surge arrestor on neutral to ground
Test conditions are similar as under section IIIA but
IV. PROTECTION BY SURGE ARRESTORS with a single surge arrestor on the neutral point of the
capacitor bank. If a NSDD was initiated in phase R, the
Arrestors are commonly proposed as means to protect highest overvoltage of 2.1 pu. was in phase T due to
the capacitor bank against excessive overvoltages due to immediate limitation of the overvoltage by the surge
restrikes [6]. In such a case the overvoltage rise-time is arrestor. A significant current flows through the surge
of the order of milliseconds. Yet in case of an NSDD arrestor: 575 A during 2.5 ms; representing an energy
the overvoltage rise-time is only several microseconds. of about 13 kJoule. This current is determined by
In order to verify the effectiveness of the surge arrestor 1. The series impedance of one branch of the
the following two cases are investigated. capacitor bank, the inductance of one phase of the
circuit and the resistance to ground of the
A. Surge arrestors on all three phases to ground generator.
Test conditions are similar as under section IIIA but 2. The voltage difference across the capacitor prior to
with surge arrestors on the load side of the CB to breakdown minus the voltage of the arrestor.
ground. On initiation of a NSDD in phase R, the highest The energy dissipated in the arrestor is higher than
overvoltage of 2.2 pu. was in phase T due to immediate under IV-A due to the lower COV of the arrestor. Yet
limitation of the overvoltage by the surge arrestor in here the arrestor will function regardless the phase in
phase T; the associated oscillogram is shown in Fig. 5b. which the maximum overvoltage will occur. This limits
A significant current flows through the surge arrestor: the number of surge arrestors to install to one.
890 A during 1 ms; representing an energy of about 8
kJoule. This current is determined by :
Table IV : Choice of continuous operating voltage of the arrestor and the resulting overvoltage protection level
depends on network operation conditions and arrestor location.
Overvoltage
Arrestor location Continuous Operating Voltage protection level
[pu] or Un√(2/3)
CB terminals
networks with high-ohmic insulated Un/√3 2.2
neutral system and automatic earth
fault clearing Neutral point 0.5*Un/√3 2.1

networks with earth fault CB terminals 1.5*Un/√3 3.3


compensation or with a high-ohmic
insulated neutral system Neutral point 1*Un/√3 3.2

conditions as well. In table IV two common situations


C . Choice of the surge arrestor are compared.
The surge arrestor limits effectively the overvoltage by • For networks with high-ohmic insulated neutral
suppressing the high frequency (150 kHz) peak system and automatic earth fault clearing the nominal
overvoltage. The absolute value of the remaining voltage of each phase is fixed at Un/√3 and the neutral
overvoltage depends though on the choice of the surge point of the capacitor bank has 0 (zero) voltage. The
arrestor. The voltage limitation is effective at a level of continuous operating voltage of the surge arrestor can
3.1 times the rated continuous operating voltage of the be chosen accordingly. The surge arrestor with
surge arrestor. The choice of the rated voltage of the associated continuous operating voltage (COV) gives a
surge arrestor must take into account abnormal circuit protection of 2.2 pu. During a normal breaking
operation the neutral point attains a peak voltage of
0.5*Un√(2/3), which lasts until discharging of the and above [8] proposes to use two vacuum interrupters
capacitor bank; this corresponds to a COV of in series. Although these measures are effective from a
0.5*Un/√3; the resulting level of protection is 2.1 pu. normative point of view, they do not contribute to an
• For networks with earth fault compensation or economically conclusive and reliable solution as shown
with a high-ohmic insulated neutral system a possible by the following numerical example. For instance,
persistent single phase earth failure increases the contactors which allow for frequent operations have a
nominal voltage of the healthy phases a factor √3, and small contact opening stroke. Even with a NSDD
the voltage on the neutral point of the capacitor bank frequency of only 1/500 they will produce over 2000
increases to 1 pu. These more severe conditions NSDDs in their entire lifespan. Therefore, only the
determine the continuous operating voltage of the surge application of surge arrestors is an effective solution to
arrestor. For arrestors on the circuit-breaker terminals suppress overvoltages and eliminate any risk for
the nominal voltage can reach 1.5*Un/√3; the resulting
equipment: capacitor bank, circuit breaker and switch
level of protection is 3.3 pu. For a single arrestor on the
board. The application guide in table VI summarises
neutral of the bank the continuous voltage can reach
this recommendation relating the choice of switchgear
Un/√3; the resulting level of protection is 3.2 pu. During
interruption of the capacitive current the voltage of the to the application duty. If the CB is used only
neutral can increase slightly more. Yet, the surge occasionally for energizing and de-energizing the
arrestor is capable of dealing with this temporary capacitor bank a vacuum CB with class C1 or C2 can be
overvoltage under this rare abnormal network condition. used. Yet for daily operation of the capacitor bank a
protection by surge arrestor is recommended, and in this
V. DISCUSSION case a class C1 rating is sufficient, as the suppression of
overvoltage during a NSDD reduces significantly the
The main results of this study are summarized in probability of a second simultaneous NSDD, and hence
table V. An important difference is found between the the risk of a restrike. For more than daily operation a
numerically and experimentally obtained overvoltage vacuum contactor with surge arrestor is an economical
values. The measured overvoltage on the bank terminal viable solution in series with a vacuum CB for
to ground is significantly lower than calculated. This is protection.
due to natural damping of the high frequency
phenomena by dissipative elements in the circuit and by Table VI : Application guide
the very small capacitance on the source side due to the Capacitive switching duty
Protection and Daily Frequent
absence of parallel feeders. The peak over-voltage has a
Occasional operation operation operation
limited duration of about 10µs. Surge arrestors Class C1 +
effectively limit these overvoltages to values as low as Vacuum-
Class C1 or C2 Surge ▬
CB
2.2 pu between terminal and ground. The capacitors arrestors
themselves are stressed neither by the NSDD nor by the Vacuum-

Surge Surge
action of the surge arrestors during limitation, as the Contactors arrestors arrestors
discharge current is a single phase current flowing
towards ground. When applying surge arrestors, special attention must be
given to the energy dissipation in the arrestor. It is
TABLE V : Over-voltages in capacitor bank switching proposed to dimension the arrestor to be capable to
Situation Capacitor Across carry out 3 consecutive protective actions without
bank CB cooling down. Furthermore the dimensioning is related
terminal to the reactive power of the capacitor bank, Sk.
1 Normal Interruption 1.5 pu 2.5 pu
2 NSDD : Predicted 6.0 pu 7.0 pu Guidelines are given by [6, 9] in the case of restriking
3a NSDD (K-Late = 1.3) 4.2 pu 5.2 pu CBs, in which case the arrestor has to be dimensioned
3b NSDD (K-Immediate = 1.7) 5.2 pu 6.2 pu for an energy of 6*Sk/ω, where ω : angular frequency
4 Surge arrestors on all terminals 2.2 pu 3.2 pu of the network. Transposing this approach to a
5 Surge arrestor on C-bank neutral 2.2 pu 3.2 pu
protection against NSDD the guidelines as presented in
table VII dimension the energy dissipation capability of
In the introduction it was outlined that NSDDs are a
the arrestor. Hence, for the protection against NSDDs
common phenomenon in vacuum interrupters and that
the arrestor can be designed 3 to 6 times smaller.
the simultaneous occurrence of NSDDs in 2 phases give
rise to a restrike. The frequency of occurrence of a
Table VII : the requested energy dissipation capability of the arrestor
NSDD is related to design parameters like the contact
Protection against
opening stroke. Hence it is possible to design a vacuum NSDD
CB according to the requirements of either “low restrike
probability” class C1 or “very low restrike probability” Arrestor on CB terminals to ground 1 * Sk/ω
class C2 of [7]. For 24 kV Class C2 vacuum CBs with
Arrestor on C-bank neutral to
“very low restriking probability” this leads to a nominal ground
2 * Sk/ω
contact gap of 16 mm, see Fig. 1. For voltages of 36 kV
Chromium Contacts ”, IEEE Power Engeneering 1993 winter
meeting Columbus OHIO
VI. CONCLUSION
[6] L. Gebhardt, B. Richter, ”Surge arrestor application of MV-
capacitor banks to mitigate problems of switching restrikes”,
This study focussed on the interaction of the vacuum paper 0639, 19th CIRED, 2007, Vienna.
circuit breaker with a capacitor bank during switching [7] International Standard IEC 62271-1, 2008, “High Voltage
Switchgear and Controlgear – Part 1: Common specifications ”
operation. The occurrence of a NSDD leads to a shift of
[8] E. Dullni, W. Shang, D. Gentsch,I. Kleberg and K. Niayesh,
the voltage of the neutral point of the bank. Although “ Switching of Capacitive Currents and the Correlation of
the phenomenon in itself is rare, the over-voltages Restrike and Pre-ignition Behavior” , IEEE trans. on dielectrics
produced are deterministic and depend on the recovery and electrical insulation, vol. 13, no1, pp. 65-71, 2006
[9] R. Rudolph and B. Richter, “Dimensioning, testing and
voltage of the phase in which the NSDD occurs and on application of metal oxide surge arrestors in medium voltage
the moment of breakdown. The experimental study networks”, open document ABB, Wettingen, 1999
shows that the overvoltage after NSDD is limited to
about 4.2 pu. on the capacitor bank terminals. Surge About the author
arrestors are shown to be an effective means to limit this
Hans Schellekens (54) received the
overvoltage. As cost efficient solution it is proposed to Ph.D. degree in technical engineering
use a single surge arrestor on the neutral point of the from the Technical University of
capacitor bank. Guidelines are presented to dimension Eindhoven, The Netherlands, in 1983,
with a specialization in plasma physics.
these arrestors. He worked at the HOLEC Research
Laboratory from 1978 to 1982 and at
REFERENCES KEMA testing laboratories from 1983
[1] T. Yokoyama, Y. Matsui, K. Ikemoto and M. Inoyama to 1985. From 1986 to 1993, he was
“ Technique on Overvoltage Phenomenon Analysis for Vacuum responsible for the development of
Switching Equipment ” by, Meiden Review Series No. 78,1986 vacuum interrupters and vacuum
[2] Y. Sunada,N.Ito, S. Yanabu, H. Awaji, H. Okumura and Y. Kanai, circuit breakers at HOLEC. Since
“ Research and Development on 13.8kV 100kA Vacuum CB with 1994, he is involved in the
Huge capacity and Frequent Operation ”, CIGRE, Paris, 1982 development of vacuum interrupters for Schneider Electric Medium
[3] P. Huhse and E. Zielke, “ 3AF Vacuum CBs for Switching in Voltage SBU (formerly Merlin-Gerin) at Grenoble in France. He has
Capacitor Banks ”, Siemens Power ENGENEERING III (1981) been active in the Dutch Brazing Soc. as well as in the CIGRE
No 8-9 Working Group 13.01 from 1985 to 1993. Dr. Schellekens is a
[4] D. Koch, “Control equipment for MV capacitor banks”, ECT142, member of the Current Zero Club.
Schneider-Electric, Grenoble, 1992
[5] T. Kamakawaji, T. Shioiri, T. Funahashi, Y. Satoh, E. Kaneko and E-mail of author: hans.schellekens@schneider-electric.com
I. Oshima, “ An Investigation into Major Factors in Shunt
Capacitor switching Performances By Vacuum CBs With Copper

You might also like