You are on page 1of 10

Building and Environment 71 (2014) 223e232

Contents lists available at ScienceDirect

Building and Environment


journal homepage: www.elsevier.com/locate/buildenv

Thermal comfort in undergraduate laboratories d A field study in


Kharagpur, India
Asit Kumar Mishra*, Maddali Ramgopal
Department of Mechanical Engineering, Indian Institute of Technology Kharagpur, Kharagpur 721302, West Bengal, India

a r t i c l e i n f o a b s t r a c t

Article history: A thermal comfort field survey is carried out inside a naturally ventilated laboratory in the tropical
Received 3 June 2013 climatic region of India. The building chosen is used for courses in an undergraduate engineering cur-
Received in revised form riculum. We aimed at assessing how the occupants perceive their thermal environment in a free running
6 October 2013
building while carrying out their normally scheduled tasks. A total of 121 acclimatized subjects were
Accepted 9 October 2013
interviewed and 338 responses were collected during the months of spring semester. Survey results
show a strong correlation between indoor comfort conditions and outdoor temperature. Occupants show
Keywords:
adaptability across a comfort zone that is well beyond recommendations of rational models. Overall, 78%
Thermal comfort
Field study
of the responses found their thermal environment to be acceptable. Based on indoor temperature ob-
Adaptive thermal comfort servations, we calculate comfort temperatures for the subjects using Griffiths’ method. The comfort
Tropical climate temperature values are then related with prevailing mean outdoor air temperature to give an adaptive
Laboratory class comfort equation. Predictions from our equation show satisfactory to good agreement with the pre-
dictions from similar equations in comfort standards.
Ó 2013 Elsevier Ltd. All rights reserved.

1. Introduction mind as a tempting and quick fix solution. Projections show India


beating both USA and China by 2055 to become the world leader in
Activities involved in teaching-learning process are known to be energy consumption for AC [7]. But India’s current energy scenario
affected by the immediate thermal environment [1e3]. Thermal is hardly reassuring and forebodes a grim future. During the
environment’s effect on mental performance is necessarily associ- recession of 2009, while overall world energy demand decreased
ated with occupants’ subjective evaluation of thermal comfort [1,4]. by 1%, India’s total final energy consumption increased by about
So thermal comfort of occupants in classrooms and other rooms 10% [8]. Also in 2009, India became world’s third largest energy
related to educational facilities is of vital concern. consumer but with a 26% energy deficit [8]. More than a third of
In India, the demographic eligible for attending institutes of India’s electricity consumption is in residential and commercial
higher education, i.e. 18e23 year old, makes up 11e12% of the na- sectors and the electricity demand of these sectors has been
tional population [5]. Actual enrolment is nowhere near 100% of growing at more than 8% [9]. In both of these sectors, a significant
this age group, yet, at the beginning of the 2010e11 academic year, portion of the energy demand is from buildings while more than
India had 14.6 million students enrolled in its 544 universities (or half the buildings India will have in 2030 are yet to be built [10]. All
equivalent institutes) and 31,324 colleges [6]. Add to this the 0.7 these statistics and estimations prove a great urgency for energy
million faculty members and that number beats the combined saving measures in Indian buildings.
population of Finland, Ireland, and Norway! Further, data shows While the National Building Code of India (NBC) [11] is ‘the’
that both the number of institutions and enrolments in them are guideline for building construction in India, until 2007, there were
growing at more than 5% annually [5]. no codes or requirements to be satisfied for energy efficiency in
For providing thermal comfort in all these classrooms spread new buildings. When it comes to AC in classrooms, the NBC pre-
across a country having mostly tropical weather, AC can come to scribes a rather narrow comfort zone of 23e26  C, 50e60% RH. In
2007, the Bureau of Energy Efficiency (a body under Ministry of
Power, Government of India) brought out the Energy Conservation
* Corresponding author. Tel.: þ91 8768073875.
Building Code (ECBC) for achieving energy efficiency in large
E-mail addresses: asit.mishra@mech.iitkgp.ernet.in, writeto.asit@gmail.com commercial buildings. But ECBC still takes NBC as the reference
(A.K. Mishra), ramg@mech.iitkgp.ernet.in (M. Ramgopal). standard for both AC requirements and ventilation requirements in

0360-1323/$ e see front matter Ó 2013 Elsevier Ltd. All rights reserved.
http://dx.doi.org/10.1016/j.buildenv.2013.10.006
224 A.K. Mishra, M. Ramgopal / Building and Environment 71 (2014) 223e232

Nomenclature TSI tropical summer index


TSV thermal sensation vote (individual’s)
TSVS thermal sensation votes in mid three points of scale
Abbreviations WBT wet bulb temperature
AC air-conditioning
ACE adaptive comfort equation Symbols
APD actual percentage dissatisfied pa absolute pressure of water vapour in air
DBT dry bulb temperature ta air temperature
MRT mean radiant temperature tc comfort temperature
MTCV mean thermal comfort vote tg globe temperature
MTSV mean thermal sensation vote tm daily mean temperature
NV naturally ventilated tmm monthly mean temperature
PMOAT prevailing mean outdoor air temperature tmrt mean radiant temperature
PMV predicted mean vote to outdoor temperature index
PPD predicted percentage dissatisfied top operative temperature
PS percentage of acceptable votes/percentage satisfied trmt running mean temperature
RH relative humidity va air velocity
RMT running mean temperature Dtc absolute difference between comfort temperature
TCV thermal comfort vote (individual’s) predictions from different models
TCVS thermal comfort votes in mid three points of scale

NV spaces [12]. For NV buildings, the ECBC User Guide does the study by Pellegrino et al., no other studies have been reported
mention the adaptive model given in ASHRAE Standard 55 as an from Indian classrooms. Considering the importance of comfort
option for determining comfort [12]. requirements in classrooms and the fast growing number of in-
Adaptive thermal comfort standards have shown great promise stitutes for higher education in India, classroom thermal comfort
in reducing energy consumption of buildings, without sacrificing needs serious attention. Our study was aimed at finding the level of
occupant comfort. Several studies done for NV classroom occupants thermal comfort and acceptance amongst students of an under-
in tropical regions (Köppen climate classification type A) have graduate course during their regular semester classes. We also
borne out significant levels of adaptation amongst occupants [13e aimed to ascertain if the adaptive comfort model can be applicable
16]. These studies have come up with comfort zones between 22 at sustained metabolic rates that are slightly over ASHRAE Standard
and 31  C and neutral temperatures in the range of 26.5e29  C. 55-2010 current specification of 1e1.3 met [24]. So we decided to
These findings are an obvious testament to the fact that comfort is survey the conditions during a laboratory class.
not exclusively found within the confines of a conditioned building. Our main objectives for this study were:
Field studies in India also attest to remarkable levels of occupant
adaptation both to the local climate and to NV buildings. In a very e Assessing occupants’ perception of thermal comfort in a free
early comfort study done in Calcutta, Rao reported a comfort running building during their regular classes.
temperature of 25.8  C DBT [17]. Sharma and Ali [18] did a very e Determining the range of temperature found most suitable by
comprehensive study on comfort, developing the sole empirical these occupants.
index of thermal comfort based on Indian subjects and Indian e Determining if adaptive comfort principle can be applied at
conditions d TSI. They found that a TSI value of 27.5  C elicited slightly higher than sedentary metabolic rates.
maximum percentage of comfortable votes. Over the past decade, e Establishing a path and framework for future studies.
there has been a significant rise in the number of thermal comfort
studies being done across India. A summary of some such studies in
presented in Table 1.
2. Study methodology
Pellegrino et al. have also reported a short duration comfort
study done in NV classrooms of two universities in Kolkata [23].
2.1. Location, building, and subjects
This study was over a couple of days and during the summer month
of May. As would be expected from the adaptive hypothesis of
2.1.1. Study location and duration
comfort, the neutral temperature obtained in this survey came out
Kharagpur e located in the eastern Indian state of West Bengal
to be rather high (30.9  C). To the best of our knowledge, apart from
e has a climate classification of Tropical savannah type (Aw) under
the Köppen system. Summers are hot and humid, monsoon months
Table 1 are slightly cooler than summer but more humid, and the winter
Summary of recent Indian studies. months are cool. Maximum outdoor temperature during summer
Location Building type Conditioning Regression neutral
days often crosses 40  C. Temperatures during winter nights have
temperature also been known to fall below 10  C. Historical monthly mean
temperatures over past ten years (collected from the in-campus
Hyderabad [19] Residences NV 29.23  C
Chennai [20] Railway waiting lounge NV 31.93  C weather station manned and operated by the Department of
Hyderabad [21] Offices NV 26.4  C Physics and Meteorology of Indian Institute of Technology (IIT)
AC 26.3  C Kharagpur) show that January is the coolest month while May is
Chennai [21] Offices NV 26.1  C the hottest.
AC 27.5  C
Jaipur [22] Student dormitories NV 30.15  C
The comfort survey was done in a laboratory classroom of IIT
Kharagpur which is a premier institutes of technical education in
A.K. Mishra, M. Ramgopal / Building and Environment 71 (2014) 223e232 225

India. The Institutes of Technology Act, 1961, declares IIT Kharagpur


to be an institute of national importance. The institute campus is
spread over 2100 green acres and houses nearly 10,000 students
along with around 2000 faculty and supporting staff. The campus
greenery has an ameliorating effect on the harsh summer heat.
In IIT Kharagpur, spring semester starts from the first week of
January and ends in April. Surveys took place on 12 separate days
from January through mid April 2013. Conducting the survey in the
spring semester implies that we can check occupant perception
through both the coldest and the hottest months during which
regular classes take place.

2.1.2. Building
Fig. 1 shows a broad view of the campus as well as a close up of
the building in which the survey took place (as collected from
Google MapsÓ). The figure gives an idea regarding the surrounding
tree line as well as the near by buildings, both of which protect our
building of concern from most of direct solar radiation. The building
has an East-West orientation with windows placed only along the
North and South walls.
The building’s construction is pillared with brick and mortar
filling. Windows are single glazed, have mild-steel frames, and
cover about 23% of total wall area. The windows also have contin-
uous overhangs, roughly 1 m wide, ensuring protection from rain
and direct sunlight. Average thickness of the walls is 40 cm while
ceiling height is slightly over 7 m. Area of occupancy during class
hours is served by 7 ceiling fans with speed controllers. The fans are
suspended using long rods from the ceiling to ensure that they do
not just churn hot air near the ceiling into the comfort zone (Fig. 2).
Overall, the said building has a strong basis in its design to function
under free running conditions.
Fig. 2. An example of a fan suspended much below ceiling level.
2.1.3. Subjects
The survey was designed to follow the schedule of a sixth se- Students had been divided into three groups and each group had
mester laboratory course that is part of an eight semester curricu- to complete their experiments in this particular laboratory over a
lum. A total of 121 students who were registered for the said course period of four weeks. Each group was further divided into four
were surveyed. There were only five female students in this entire subgroups so that in every class, there were roughly 10 students
group. The students were all aged between 19 and 21 years. To performing a particular experiment. After the four weeks of a
maintain this homogeneous age group, it was decided not to survey particular group were complete, the next group would come in to
the instructors. All subjects were Indians, though they came from start their term in the lab. Thus, the course’s schedule in a way
different provinces, and had been staying in Kharagpur for at least helped us to avoid any kind of survey fatigue setting in or the risk of
five semesters. They were thus well acclimatized to the local subjects getting too familiar with the process. As a further measure,
weather. During the survey, all subjects were assumed to be in good we decided to survey only three of the four subgroups present on
health since any ailment gets a student automatically excused from any day. We cyclically altered between subgroups 1-2-3, followed
attending the class. by subgroups 2-3-4 and so on.

Fig. 1. Views of the building (marked by ‘X’) (a) Area of campus around the building (b) Close up view of the laboratory along with surrounding buildings and tree line.
226 A.K. Mishra, M. Ramgopal / Building and Environment 71 (2014) 223e232

Every time a new group of students came in, they were briefly weighted mean of the air temperature and MRT with weighting
introduced to the purpose, duration, and process of the survey. factors of convective (hc) and radiative (hr) heat transfer coefficient
They were assured that this was not some kind of pop quiz and they respectively. We took a constant value of 4.7 W/m2  C for hr while hc
should feel free to give honest responses. Since people might often was calculated from the correlation for standing persons in ASHRAE
link survey questionnaires on thermal comfort with chance of Handbook [25].
change in conditioning type, we also made it clear to the students Values for RH and absolute pressure of water vapour in air (pa)
that this was not some kind of referendum on the requirement of were obtained from the DBT and WBT values using a humidity
AC in laboratories. calculator from Vaisala [26]. All statistical analysis were carried out
using the R statistical computing package (version 2.15.2) [27].
2.2. Data collection
2.2.2. Subjective questionnaire
During the field survey, physical measurements of environ- As mentioned in Section 2.1.3, the subjects had been briefed
mental parameters were taken while the paper based subjective regarding the nature of the survey and the questionnaires. Any
questionnaires were being filled by the occupants. Since we aimed queries individual students had during the survey were also
at recording reactions to typical conditions, every effort was made resolved. The students were from different regions of India and it
not to interfere with the class schedule and thermal environment. would have been difficult to decide on any one particular regional
Survey activities around the three subgroups took a total of 35e language that all students would have been comfortable with. But
40 min. the medium of instruction in all their classes is English. Due to their
common comfort level with English, English was determined to be
2.2.1. Objective data a suitable compromise. The questionnaire options are given in
Measurements were taken for dry bulb and wet bulb tempera- Table 2.
tures, globe temperature, and air velocity. A black globe ther- Numbers in brackets besides the options are numerical equiv-
mometer was constructed by placing an alcohol thermometer at alents used for statistical analysis. The questionnaire included the
the centre of a black painted plastic ball of 70 mm diameter. Dry standard seven point ASHRAE thermal sensation scale, comfort
and wet bulb temperatures were measured with help of a sling vote on Bedford scale, thermal preference on the McIntyre scale, a
psychrometer. The globe thermometer had a range 10e110  C and direct acceptability question, a three point air velocity sensation
resolution 1  C. The two thermometers in the psychrometer had a question, and a five point humidity sensation question. Occupant
range 0e120  F, resolution 1  F. All three thermometers were satisfaction percentage was ascertained on basis of acceptability
calibrated against a reference thermometer from ZealÓ votes. This involves the inherent assumption that a person voting
(range 10e50  C, resolution 0.5  C) over the range of 10e40  C. Air acceptable on the survey questionnaire is satisfied with his/her
velocity was measured with a digital, vane-type anemometer thermal conditions. Percentage of people voting unacceptable was
(Lutron AM-4201, range 0.1e30.0 m/s). taken to be the APD.
Students worked in closely clustered groups. So DBT, WBT, and As the survey was being conducted in between regular opera-
air velocity were measured at five points around the group and an tions of a class, it was of paramount concern to keep the survey
average value of these five readings was taken to represent the questionnaire short and compact. Students took 1e5 min to fill up
thermal condition for a group. Globe temperature readings took and return the questionnaire sheet. The humidity and air velocity
10 min to stabilise and hence we took a single reading of globe sensation questions had fewer options to save time and to not have
temperature per group. As all subjects were in standing position the subjects making subtle distinctions in what is a second lan-
during the survey duration, measurements were taken at shoulder guage to them. The options for the Bedford rating scale were the
level of the occupants. Measurements were taken within 1 m dis- same as those used by Humphreys [28]. These options had been
tance from the occupants while taking care to keep out of the way used by Humphreys in a study done in Pakistan. Due to the com-
of the students and instructors. Just before starting the survey, mon heritage of English shared by India and Pakistan, the word ‘OK’
outdoors DBT and WBT in immediate vicinity of the building were is also very well understood and carries a clear sense in India.
also determined as an arithmetic average of measurements made at
five locations near the building. 2.2.3. Assessing clothing levels and metabolic rates
Mean radiant temperature (tmrt) was calculated from globe Adding an extra section of clothing and activity check-list would
temperature (tg), air temperature (ta), and air velocity (va) using have been time consuming and distracting to the regular class ac-
Equation (1) [25]. tivity. Clothing level was assessed using an approach similar to that
used by Morgan and de Dear for a study done “unobtrusively” on
 
 4 1:1  108 v0:6
a
  1=4 shoppers at a Sydney mall [29]. Students mostly attired in western
tmrt ¼ tg þ 273 þ  tg  ta  273 (1) style outfits: combinations of shirts/t-shirts, trousers/jeans. Jeans is
3 D0:4
a common and frequent apparel amongst students across all sea-
Here 3 is the emissivity of the globe surface (taken as 0.95) and D is sons and was assumed to have clothing insulation of thick trousers.
the globe diameter. Operative temperature (top) was calculated as a Five common ensembles were identified (shown in Table 3) and

Table 2
Survey questionnaire options.

Thermal sensation Thermal comfort Air velocity sensation Humidity sensation Thermal preference Acceptability

Cold(3) Much too cool(3) Still(1) Too dry(2) Cooler(1) Acceptable(0)


Cool(2) Too cool(2) Just right(0) Slightly dry(1) No change(0) Not acceptable(1)
Slightly cool(1) OK(cool) (1) Breezy(1) Just right(0) Warmer(1)
Neutral(0) OK (Just right) (0) Slightly humid(1)
Slightly warm(1) OK (warm) (1) Too humid(2)
Warm(2) Too warm(2)
Hot(3) Much too warm(3)
A.K. Mishra, M. Ramgopal / Building and Environment 71 (2014) 223e232 227

Table 3 use of ceiling fans started, air velocity directly under the fans could
Clothing ensembles. rise above 2 m/s and average air velocities were close to 0.5 m/s. But
Ensemble Clo value at some distance from the fans, air velocity rapidly dropped to ‘0’.
1.T-shirt, thick trousers 0.39
Even with multiple windows open, there was very little of wind
2.Half-shirt, thin trousers 0.50 flow or cross-ventilation. So even during summer, quite some
3.Half-shirt, thick trousers 0.59 portion of the lab had ‘dead zones’ for air velocity. Experimental
4.Full-shirt, thin trousers 0.56 set-ups, and hence the students, were always located near fan
5.Full-shirt, thick trouser 0.65
positions.
Analysis showed that local thermal conditions of different
groups did not vary much from each other. For example, the
maximum variation operative temperature had between any two
their clo values were assigned to subjects depending on what fit
groups for any given day was only 1  C. Hence we decided to
best. The clo values given in Table 3 take into account insulation of
analyse the response data as an average of votes from all the stu-
undergarments and foot wear. Additional winter garments’ clo
dents on a particular day and averaged values of the environmental
values were chosen from those given by Nicol et al. [30] for their
measurements were used. Further calculations and analysis are
study in Pakistan: sweat-shirt, 0.34 clo; cardigan, 0.22 clo; sweater,
done using these day-average values. Regressions done with the
0.30 clo; waistcoat/vest, 0.18 clo; jacket, 0.30 clo.
average values use a weighting factor equivalent to the number of
When girls were not using western outfits, they preferred the
responses on each day.
traditional ensemble of salwarekameez. These were treated similar
Air temperature measurements taken at ankle and shoulder
to ensembles two or four from Table 3 depending on sleeve length
levels never varied by more than 2  C even on the hottest days. We
of the kameez. Extra insulation for a dupatta [30] was added when
believe this is due to the large height of the building. We also
found in use along with the salwarekameez. The minimum clo
observed that the measured globe temperature exactly matched up
value observed during the survey was 0.39 (ensemble 1) and the
with the calculated operative temperature (rounded up to the
maximum was 0.99 (ensemble 5 with sweat-shirt).
nearest whole number). Predicted mean vote values were calcu-
Experiments in the laboratory did not involve any heavy lifting
lated using Fanger’s methodology [33]. Maximum and minimum
or strenuous exertion. But since students had to take observa-
values during the survey days for outdoor conditions, indoor con-
tions, change settings on the instruments etc., they stood by their
ditions, average ensemble clo values, APD values, calculated TSI
experimental set-ups or intermittently moved around. We
values and calculated PMV, PPD values are given in Table 4. In the
assumed a metabolic rate of 1.6 met for this activity level, as given
same table, we also note maximum and minimum values for the
for “Standing, light activity (shopping, laboratory, light industry)” in
MTSV on ASHRAE seven point scale and the MTCV on the Bedford
ISO 7730-2005 [31]. Students generally walked or cycled from
scale. These values are the average votes of all respondents for a
their hostels to class. So we began our survey 75e90 min after
day. Number of respondents on different days varied between 23
beginning of class to let the subjects settle down to a stable ac-
and 32.
tivity level.
Maximum values for PMV, PPD, MTCV, and APD occurred on the
same survey day when both top and pa were at their maximum
2.2.4. Weather data
recorded values. However, MTSV had its highest recorded value on
Temperature data was collected from the Department of Physics
a different day. We think the higher MTSV value was because it was
and Meteorology’s weather station. Daily mean temperature was
the first day in the laboratory for that particular group of students
taken as an arithmetic average of the daily maximum and mini-
and as they were not used to the environment, they might have
mum temperatures. Running mean temperature for day ‘n’ was
judged it a bit harshly.
calculated from the daily mean temperature data using Equation
Maximum difference between average values for ta and tmrt is
(2) [32].
3  C. We believe such magnitude of variation is due to the large
n o number of windows present and the value would have been higher
trmt ¼ ð1  aÞ tm;n1 þ atm;n2 þ a2 tm;n3 / (2)
if not for all the windows being well protected from direct sunlight.
Both tmrt and tg were highly correlated to ta with R2 values of
Here, tm,nx is the daily mean temperature for the day ‘x’ days 0.98 and 0.99 respectively. The building’s large thermal mass
before day ‘n’. In keeping with EN15251, we take a value of 0.8 for a ensured that during hot summer days, indoor average DBT could be
and evaluate a seven day running mean. as much as 3  C below outdoor DBT even with open doors and
windows.
3. Results and analysis

A total of 342 responses were collected from the subjects. Out of Table 4
these, four responses were classified as ‘invalid’. A certain response Maximum and minimum values for observations.
was deemed invalid if: a subject wanted ‘no change’ in the envi- Parameter Maximum Minimum Parameter Maximum Minimum
ronment, yet found it ‘unacceptable’ or the subject voted an
Meteorological data
extreme thermal sensation but still preferred to have more of the Daily Minimum 25  C 9 C Daily 42  C 20  C
same thermal condition. Results discussed below are for the 338 Maximum
‘valid’ responses. Diurnal Range 18  C 7 C Daily Mean 33  C 14.5  C
RMT 32.8  C 16.9  C
Indoors
3.1. Indoor and outdoor conditions ta 34  C 22  C tmrt 37  C 22  C
top 35  C 22  C pa 3.04 kPa 1.06 kPa
As discussed in Section 2.2.1, we took one set of measurements va 0.6 m/s 0.05 m/s Average clo 0.91 clo 0.44 clo
for every group of students. When ceiling fans were not in use, a TSI 32  C 19  C PMV 3.06 0.50
PPD 99% 10% MTSV 1.74 0.73
0 air velocity was recorded. For such instances, instead of 0 m/s, we MTCV 1.48 0.48 APD 59% 0%
use a nominal value of 0.05 m/s for analysis and calculations. Once
228 A.K. Mishra, M. Ramgopal / Building and Environment 71 (2014) 223e232

3.2. Analysis of votes on ASHRAE and Bedford scales Table 5


Cross-tabulation of TSV and TCV.

Fig. 3 shows a scatter plot of TSV. It is easy to observe from the TSV TCV
figure how widely spread out individual thermal sensations are L3 L2 L1 0 1 2 3
even on the same day. Cross-tabulation of all TCV and TSV is given
L3 0 0 1 0 0 0 0
in Table 5 and Fig. 4 represents a bar graph for the number of votes
L2 0 1 19 3 0 0 0
under different categories for thermal sensation and thermal L1 0 1 41 14 5 0 0
comfort. 0 0 0 14 31 21 0 0
There is match of TSV and TCV 52% of the times. Maximum 1 0 0 4 19 79 7 1
2 0 0 0 1 39 19 0
number of matches occur at voting level ‘1’, followed by ‘1’ and ‘0’.
3 0 0 0 0 3 10 5
Most disagreements for votes on the two scales occur at extreme
sensation values (3,2,2,3) with 30% votes in extreme values of
TSV compared to only 13% in TCV (Fig. 4). The students appear to be
more stringent while voting for thermal sensation than when
amongst the occupants. This was expected since over course of the
voting for thermal comfort at the extreme scale points. But in the
survey, we examined occupant responses both in the hottest and
central three categories (1,0,1), there is a high degree of corre-
coolest month they face during their semesters. The neutral tem-
spondence for votes on the two scales: 96% who voted in the central
perature found in this study is close to that found by Kwok in the
three for TSV also voted in the central three for TCV. There were
study of NV classrooms in Hawaii [13] as well as that found by
only nine instances when the signs of TSV and TCV were different
Ogbonna and Harris in university classrooms in Jos, Nigeria [15].
with all such instances being for votes of 1/1. This similarity in
Though both these study locations have Type A climate, similar to
voting pattern is also observed by Wong and Khoo [14].
Kharagpur, the similarity with results from Kwok’s study is more
A Wilcoxon signed rank test (two-sided, paired) for TSV and TCV
pertinent as it was conducted across both cool and hot seasons, like
(p ¼ 0.24); MTSV and MTCV (p ¼ 0.75) revealed that the votes are
the current study.
not statistically significantly different. So it would seem that using
In view of the similarity of voting pattern for MTSV and MTCV,
TCV or TSV values for analysis should not give us significantly
we also give here the regression equation between MTCV and top.
different results. We further discuss this in the following section.

MTCV ¼ 0:14top  3:72; R2 ¼ 0:87; p < 0:001 (4)


3.3. Regression analysis for neutral temperature C
Equation (4) yields a neutral temperature of 26.6 and a
comfort zone between 19.4 and 33.7  C. There is a close resem-
We regressed MTSV against three different indices for indoors
blance between comfort zones obtained from regression of MTSV
viz. ta, top, and TSI. Regression correlation came to be strongest with
and MTCV vs top while the two neutral temperatures are practically
TSI (R2 ¼ 0.88) followed by top (R2 ¼ 0.86), and ta (R2 ¼ 0.84). We feel
same. Pellegrino et al. have also observed a similar result [23].
TSI has an unfair advantage in this situation, having been developed
As a check of our decision to take average values of environ-
in Indian conditions and for Indian subjects. So, to allow for com-
mental parameters for the whole building, we also do a regression
parison with other works and in keeping with observations made
analysis between the individual’s TSV and top measured in vicinity
regarding utility of top in certain seminal works on adaptive com-
of his/her group. Equation (5) gives the resulting regression
fort [32,34], we use top as the index for indoor environment.
relation.
Regression equation between top and MTSV is given in Equation (3)

MTSV ¼ 0:18top  4:77; R2 ¼ 0:86; p < 0:001 (3) TSV ¼ 0:184top  4:866; R2 ¼ 0:39; p < 0:001 (5)
This equation yields a neutral temperature of 26.5 and a C In validation of our approach, Equation (5) yields neutral tem-
comfort zone (based on votes of 1) between 20.9 and 32  C. The perature and comfort zone (26.4  C, 21e31.9  C) near identical to
small slope of the equation implies a high degree of adaptation those found from Equation (3). The individual thermal sensation

Fig. 3. Scatter plot of thermal sensation votes.


A.K. Mishra, M. Ramgopal / Building and Environment 71 (2014) 223e232 229

Fig. 4. Thermal sensation and thermal comfort votes.

Fig. 5. Thermal sensation votes on ASHRAE seven point scale and their regression lines with operative temperature. (a) Thermal Sensation Votes vs Operative temperature. (b) Mean
Thermal Sensation Vote vs Operative temperature.
230 A.K. Mishra, M. Ramgopal / Building and Environment 71 (2014) 223e232

votes and the MTSV values, along with their corresponding e Votes that answer ‘Yes’ to the direct question of acceptability.
regression fits, are shown in Fig. 5(a) and Fig. 5(b) respectively. e Votes that answer ‘No change’ to the question on thermal
Since the regression between TSV and top comes with inter- preference.
individual variability of rating same environments differently as
well as all votes having integral values only, R2 value of Equation (5) Fig. 6 shows the total number of students (out of 338) who gave
is much smaller than that of Equation 3. However, in behavioural acceptable votes under the different assumptions. We see that the
studies, R2 values of even 0.25 would indicate strong correlations first three criteria give similar, though not exactly the same, results.
[35]. As Kenny further states, “. Correlations of this size (0.81) are Votes on the Bedford scale give a higher acceptability than even the
often between two different measures of the same variable.” [35]. direct acceptability question. This might be due to some subjects
This statement has great import for field studies of thermal com- not being able to separate their feelings for overall acceptability of
fort. As in the current work, often other authors have also found R2 the class from their perception of thermal comfort alone. The
values of the order 0.8 when relating mean votes of a space and acceptability pattern we find using different criteria, highest from
mean indoor temperatures [30,36]. This implies that while inter- Bedford scale to lowest from thermal preference, is similar to that
individual perception may vary a lot, average perception of a found by Wong and Khoo in their study of school classrooms in
large enough group regarding a thermal environment may be taken Singapore [14]. A comparison of acceptability found using the first,
as an unbiased estimate of the ambient temperature. third, and fourth criteria also bears good resemblance to the results
Equation (6) gives the regression relation between PMV values of Kwok from NV classrooms [13], with direct acceptability giving
(calculated using room average conditions) and the corresponding the highest percentage and thermal preference the least.
top. Use of the preference question to determine acceptability seems
to be a rather stringent criteria with only 33% finding their envi-
PMV ¼ 0:18top  3:57; R2 ¼ 0:95; p < 0:001 (6) ronment acceptable. As observed by Humphreys et al., votes on the
 C,
preference scale may be more about “lifestyle aspirations” than
This correlation yields a neutral temperature of 19.8 i.e.
about acceptability of the current environment [38]. Responses to
about 7  C smaller than the neutral temperature obtained from the
the preference question are also affected by thermal experience of
occupant votes. Analysing this discrepancy further, we regress
the occupants [39]. Since the study location has a tropical climate, a
MTSV against PMV values (Equation (7)).
majority wanted to feel ‘cooler’ (60%). During the summer months
of March and April, there were zero votes for the ‘warmer’ prefer-
MTSV ¼ 0:996PMV  1:154; R2 ¼ 0:88; p < 0:001 (7)
ence where as even on the coolest day, three subjects wanted to be
Equation (7) shows that an MTSV of 0 (neutral) would occur for ‘cooler’.
PMV value of 1.2, indicating the high degree of adaptation occu-
pants have developed to local weather and NV buildings. However, 3.4.1. Acceptable zones of thermal comfort
we must note here that some of the temperature and humidity Using the first three criteria set up for measuring acceptability of
values measured in this survey are beyond the standard range for occupants in Section 3.4, we analyse possible zones of thermal
application of PMV d as specified by ISO 7730 [31]. comfort over which students are likely to accept their thermal
environment. We examine the percentage of occupants that
3.4. Assessment of acceptability accepted their thermal environment on each day and then a second
order polynomial fit is obtained between percentage of acceptable
As Brager et al. have observed, different criteria for determining votes and average operative temperature on a day. Results are
acceptability levels of occupants are likely to give very different shown in Fig. 7. From Fig. 7, a sharp decline in acceptability per-
results [37]. We analyse acceptability levels assuming the following centage at room temperatures beyond 30  C is observed. This is also
four types of votes to be accepting of their environment: reflected in the nature of fitted polynomial curve. Similar trend of a
‘threshold’ has been observed by Zhang et al. from their analysis of
e Votes in central three categories of ASHRAE scale. the ASHRAE database for acceptability in summer time in NV and
e Votes in central three categories of Bedford scale. mixed mode buildings [40]. Unlike Zhang et al., we do not

Fig. 6. Acceptability assessment using different criteria.


A.K. Mishra, M. Ramgopal / Building and Environment 71 (2014) 223e232 231

Fig. 7. Percentage of acceptable votes vs operative temperature.

encounter a sharply declining acceptability threshold on cool side For the 12 survey days, we compare average values of Dtc be-
as our lowest recorded temperature was 22  C. tween tc calculated using Equation (8) and using other adaptive
Solving the fitted polynomials for an 80% acceptability yields the models: Standard 55-2010 [24], EN15251 [32], the work by Hum-
following thermal comfort zones: phreys et al. [41], and a recent ACE proposed for South-East Asia by
Nguyen et al. [42]. For outdoor temperature, we use PMOAT based
e Votes in central three categories of ASHRAE scale: 22.7e28.9  C on a seven day average for ASHRAE equation, RMT for EN15251 and
e Votes in central three categories of Bedford scale: 17.9e32.8  C Humphreys’ model, and current monthly mean temperature (tmm)
e Votes that answer ‘Yes’ to the direct question of acceptability: for Nguyen’s model.
19.4e30.9  C We also consider values of tc found using corrections suggested
in ASHRAE and EN15251 models for higher air velocities, using
All three of the above zones are broader than those recom- average velocities recorded during the survey for correction. Since
mended for conditioned spaces in NBC [11]. Assuming direct average velocities recorded are always 0.6 m/s, for the ASHRAE
acceptability votes as the reliable indicator of an occupant’s overall values of tc we include a correction 1.2  C for all days recording an
comfort level, a comfort zone of 20e31  C may be assumed for the average velocity greater than 0.3 m/s. Summary results are pre-
laboratory building. The comfort zone we find is similar to what sented in Table 6.
Nicol et al. found from their field studies in Pakistan [30]. This is of An important observation from Table 6 is that though there are
course the range of temperatures occupants can adapt to over differences in the predicted (tc) values, the differences are not very
different seasons and not drifts that would be tolerated over a day. stark. The maximum Dt c value found is 3.3  C. For perspective,
ASHRAE recommended 80% comfort zone itself has a width of 7  C.
3.5. An adaptive comfort equation Considering velocity correction in tc decreases Dt c for both ASHRAE
and EN15251 models. Models of both Nguyen et al. and Humphreys
Adaptive comfort equations recommended by both ASHRAE et al. give reasonably close predictions. We believe this is because
Standard 55 and EN15251 were developed using database of oc- Nguyen et al. gave the model based on meta-analysis of a group of
cupants engaged in near sedentary activities. A question naturally studies done in Type A climate and due to the similarity of slope
arises as to how the comfort temperature (tc) estimates of an ACE between our and Humphreys’ et al.’s equations. Least deviations are
developed from the current observations would compare with observed with the EN15251 model after taking into account ve-
those from the standard ACEs. Using Griffiths’ equation along with locity correction. This shows the necessity for adaptive models to
a slope of 0.5/ C d as suggested by Humphreys et al. in a recent take into account enhanced air velocities especially in tropical cli-
work [41] d we calculate tc on each day of the survey. Following the mates with widespread use of fans. We observe that there are
recent addenda to ASHRAE Standard 55-2010 [24], we use a seven differences between the predictions from different models, though
day mean of daily mean temperatures as the PMOAT (to). not very large ones. Models developed for similar climates have
A regression between PMOAT and tc yields the following ACE: lesser differences and bringing effect of enhanced air velocity into
consideration also helps reduce difference between model
tc ¼ 0:53to þ 15:23; R2 ¼ 0:93; p < 0:001 (8) predictions.

Table 6
A comparison with standard adaptive comfort models.

ASHRAE EN15251 Humphreys et al. Nguyen et al.

Comfort equation tc ¼ 0.31to þ 17.38 tc ¼ 0.33trmt þ 18.8 tc ¼ 0.53trmt þ 13.8 tc ¼ 0.341tmm þ 18.83
tc correction for air velocity 1.2  C 7  4 þ 50 pffiffiffiffi  n.a. n.a.
10 va C (va>0.1 m/s)
Dt c 3.3  C 1.3  C 1.2  C 1.2  C
Dt c for velocity corrected values 2.4  C 0.5  C n.a. n.a.
232 A.K. Mishra, M. Ramgopal / Building and Environment 71 (2014) 223e232

4. Conclusion [13] Kwok AG. Thermal comfort in tropical classrooms. ASHRAE Trans
1998;104(1):1031e50.
[14] Wong NH, Khoo SS. Thermal comfort in classrooms in the tropics. Energy
This survey was a first step towards classroom thermal comfort Buildings 2003;35(4):337e51.
research in tropical climate of India. Results show a comfort zone [15] Ogbonna A, Harris D. Thermal comfort in Sub-Saharan Africa: field study
broader than 10  C as well as a high correlation between indoor report in Jos-Nigeria. Appl Energy 2008;85(1):1e11.
[16] Cândido C, de Dear R, Lamberts R. Combined thermal acceptability and air
comfort temperature and outdoor conditions. Even though the movement assessments in a hot humid climate. Building Environ 2011;46(2):
study was conducted on occupants having sustained metabolic rate 379e85.
of 1.6 met, adaptive comfort principle was found to be very much [17] Rao MN. Comfort range in tropical Calcutta. A preliminary experiment. Indian
J Med Res 1952;40(1):45e52.
applicable. This would suggest that with further complimentary [18] Sharma MR, Ali S. Tropical summer index e a study of thermal comfort of
research, the metabolic rate limits set for application of adaptive Indian subjects. Building Environ 1986;21(1):11e24.
models in current standards may be broadened. [19] Indraganti M. Using the adaptive model of thermal comfort for obtaining
indoor neutral temperature: findings from a field study in Hyderabad, India.
One thing to note here is that the subjects in this study are not Building Environ 2010;45(3):519e36.
strangers to AC. Most of their larger lecture theatres and labora- [20] Deb C, Ramachandraiah A. Evaluation of thermal comfort in a rail terminal
tories dealing with computation/simulation are air-conditioned. So location in India. Building Environ 2010;45(11):2571e80.
[21] Indraganti M, Ooka R, Rijal HB. Field investigation of comfort temperature in
the results are not entirely due to low expectations. India, with its Indian office buildings: a case of Chennai and Hyderabad. Building Environ
varied climatic zones, economic growth, population size and 2013;65:195e214.
number of buildings, and looming energy crisis, could greatly [22] Dhaka S, Mathur J, Wagnerb A, Agrawal GD, Garg V. Evaluation of thermal
environmental conditions and thermal perception at naturally ventilated
benefit from development and implementation of an adaptive
hostels of undergraduate students in composite climate. Building Environ
comfort standard. Until an ACE tailor made for Indian conditions is 2013;66:42e53.
developed, our results indicate that use of EN15251 model (with [23] Pellegrino M, Simonetti M, Fournier L. A field survey in Calcutta. Architectural
velocity correction) could give good results. issues, thermal comfort and adaptive mechanisms in hot humid climates. In:
Proceedings of 7th Windsor Conference: the changing context of comfort in
an unpredictable world. Windsor, UK: NCEUB; 2012.
[24] ANSI/ASHRAE, Standard 55e2010. Thermal comfort conditions for human
Acknowledgements occupancy. Atlanta: ASHRAE; 2010.
[25] ASHRAE. ASHRAE handbook: fundamentals. SI ed. Atlanta, GA: American So-
We appreciate the cooperation of all our subjects. We are ciety of Heating, Refrigerating and Air-conditioning Engineers; 2009.
[26] Vaisala humidity calculator for windows, version 2.2www.vaisala.com/
grateful for the cooperation of Mr. Ranendranath Dey and Mr.
humiditycalculator; Nov 2009.
Pradip Roychowdhury during the survey and set up of equipments. [27] R Core Team. R: a language and environment for statistical computing.
We are thankful to Prof. B. K. Mathur of the Department of Physics Vienna, Austria: R Foundation for Statistical Computing; 2012. http://www.R-
and Meteorology for making available to us historical and current project.org.
[28] Humphreys MA. An adaptive approach to the thermal comfort of office
temperature data. We are also grateful for insights on statistical workers in North West Pakistan. Renew Energy 1994;5(5e8):985e92.
methods from Prof. P. K. J. Mohapatra, Department of Industrial [29] Morgan C, de Dear R. Weather, clothing and thermal adaptation to indoor
Engineering. climate. Clim Res 2003;24(3):267e84.
[30] Nicol JF, Raja IA, Allaudin A, Jamy GN. Climatic variations in comfortable
temperatures: the Pakistan projects. Energy Buildings 1999;30(3):261e79.
[31] ISO. ISO 7730: Ergonomics of the thermal environment e analytical deter-
References
mination and interpretation of thermal comfort using calculation of the PMV
and PPD indices and local thermal comfort criteria. 3rd ed.; 2005. Geneva.
[1] Auliciems A. Classroom performance as a function of thermal comfort. Int J [32] Nicol F, Humphreys M. Derivation of the adaptive equations for thermal
Biometeorol 1972;16(3):233e46. comfort in free-running buildings in European standard EN15251. Building
[2] Wyon DP, Andersen I, Lundqvist GR. The effects of moderate heat stress on Environ 2010;45(1):11e7.
mental performance. Scand J Work Environ Health 1979;5(4):352e61. [33] Fanger PO. Thermal comfort. Analysis and applications in environmental en-
[3] Mendell MJ, Heath GA. Do indoor pollutants and thermal conditions in schools gineering. Copenhagen: Danish Technical Press; 1970.
influence student performance? A critical review of the literature. Indoor Air [34] de Dear RJ, Brager GS. Developing an adaptive model of thermal comfort and
2005;15(1):27e52. preference. ASHRAE Trans 1998;104(1):145e67.
[4] Leyten JL, Kurvers SR, Raue AK. Temperature, thermal sensation and workers’ [35] Kenny DA. Statistics for the social and behavioral sciences. Boston: Little
performance in air-conditioned and free-running environments. Architectural Brown; 1987.
Sci Rev 2012;56(1):14e21. [36] Rijal HB, Yoshida H, Umemiya N. Seasonal and regional differences in neutral
[5] UGC, Higher education in India d Issues related to expansion, inclusiveness, temperatures in Nepalese traditional vernacular houses. Building Environ
quality and finance, secretary. University Grants Commission: New Delhi. 2010;45(12):2743e53.
[6] Annual report 2010e11. Department of School Education & Literacy and [37] Brager G, Fountain M, Benton C, Arens E, Bauman F. A comparison of methods
Department of Higher Education, Ministry of Human Resource Development, for assessing thermal sensation and acceptability in the field. In: Oseland N,
Government of India; 2012. editor. Proceedings of thermal comfort: past, present and future. Watford, UK:
[7] Isaac M, Van Vuuren DP. Modeling global residential sector energy demand for British Research Establishment; 1993.
heating and aireconditioning in the context of climate change. Energy Policy [38] Humphreys MA, Nicol JF, Raja IA. Field studies of indoor thermal comfort and
2009;37(2):507e21. the progress of the adaptive approach. Adv Building Energy Res 2007;1(1):
[8] IEA. Energy balances of non-OECD countries. Paris, France: International En- 55e88.
ergy Agency; 2011. [39] Humphreys MA, Hancock M. Do people like to feel ‘neutral’?: exploring the
[9] CSO. Energy statistics. 19th ed. New Delhi, India: Central Statistics Office. variation of the desired thermal sensation on the ASHRAE scale. Energy
Ministry of Statistics and Programme Implementation. Government of India; Buildings 2007;39(7):867e74.
2012. [40] Zhang H, Arens E, Pasut W. Air temperature thresholds for indoor comfort and
[10] Kumar S, Kapoor R, Rawal R, Seth S, Walia A. Developing an energy conser- perceived air quality. Building Res Inf 2011;39(2):134e44.
vation building code implementation strategy in India; May 2010. Tech. rep., [41] Humphreys MA, Rijal HB, Nicol JF. Updating the adaptive relation between
ECO-III. climate and comfort indoors; new insights and an extended database.
[11] BIS. National building code of India 2005. New Delhi, India: Bureau of Indian Building Environ 63:40e55.
Standards; 2005. [42] Nguyen AT, Singh MK, Reiter S. An adaptive thermal comfort model for hot
[12] BEE. Energy conservation building code user guide. New Delhi, India: Bureau humid South-East Asia. Building Environ 2012;56(0):291e300.
of Energy Efficiency; 2009.

You might also like