Professional Documents
Culture Documents
NORTH
CANAAN
LITCHFIELD
BLOOMFIELD
WINDHAM
SOUTH
TOLLAND
WINDSOR VERNON KILLINGLY
AVON
HARTFORD
DANIELSON
HARTFORD
CITY
FARMINGTON
ANDOVER WILLIMANTIC
NEWINGTON
MORRIS WETHERHILL CITY
BRISTOL
CITY WINDHAM
WASHINGTON THOMASTON PLAINVILLE NEW GLASTONBURY
COLUMBIA STERLING
PLYMOUTH BRITAIN SCOTLANDCANTERBURY PLAINFIELD
CITY
BETHLEHEM
ROCKYHILL HEBRON
NEW
MILFORD WATERTOWN SOUTHINGTON
BERLIN MARLBORO SPRAGUE
WOLCOTT CROMWELL LEBANON
SHERMAN SOUTHINGTON
(BORO) PORTLAND FRANKLIN JEWETT
ROXBURY WADBURY CITY
LISBON
WATERBURY EAST
BRIDGE- CITY HAMPTON GRISWOLD VOLUNTOWN
WATER COLCHESTER
MIDDLEBURY MERIDEN
CITY MIDDLETOWN NORWICH
M
CITY BOZRAH
ID
CHESHIRE
D
NEW
LE
FAIRFIELD PROSPECT NORWICH
CITY PRESTON
FI
NAUGATUCK
EL
BROOKFIELD SOUTHBURY WALLINGFORD
D
DANBURY OXFORD NEW HAVEN
BEACON
FALLS
WALLINGFORD
(BORO)
DURHAM MIDDLESEX HADDAM
EAST HADDAM SALEM
NEW LONDON
MONTVILLE NORTH
STONINGTON
DANBURY BETHANY LEDYARD
CITY NEWTOWN
N
CITY
VE
FAIRFIELD
SHELTON CITY GUIFFORD OLD
HA
WEST- OLD LYME
ORANGE CLINTON BROOK SAYBROOK
WEST BRANFORD
ST
HAVEN
EA
EASTON TRUMBULL
WESTON
ORD
MILFORD
FF
WILTON
BRIDGE-
STRA
MERIDEN, CT
PORT
FAIRFIELD CITY
NEW
CANAAN
WESTPORT
VICINITY MAP
NORWALK
STAMFORD
CITY
GREENWICH DARIEN
STAMFORD
CITY
Stantec
3 Columbia Circle Suite 6
Albany NY 12203-5158
Tel:(518) 452-4358
www.stantec.com
Copyright Reserved
D The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing
- any errors or omissions shall be reported to Stantec without delay.
The Copyrights to all designs and drawings are the property of Stantec. Reproduction or
use for any purpose other than that authorized by Stantec is forbidden.
Consultant
Notes
File Name:
50845_001_GENERAL NOTES CAM PVE PVE
Dwn. Dsgn. Chkd. YYYY.MM.DD
Permit/Seal
Client/Project Logo
Client/Project
Meridan-Markham Municipal Airport
Meriden, CT
A
Title
GENERAL NOTES
C-001
Revision Sheet Drawing No.
0 2 of 14
ORIGINAL SHEET - ANSI D
1 2 3 4 5
Stantec
3 Columbia Circle Suite 6
Albany NY 12203-5158
Tel:(518) 452-4358
www.stantec.com
· Copyright Reserved
D ·
The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing
- any errors or omissions shall be reported to Stantec without delay.
The Copyrights to all designs and drawings are the property of Stantec. Reproduction or
use for any purpose other than that authorized by Stantec is forbidden.
· Consultant
·
·
·
·
·
· Notes
·
N
·
·
N
·
·
Permit/Seal
Client/Project Logo
Client/Project
Meridan-Markham Municipal Airport
u:\179450845\aviation\9_drawing\sheet_files\50845_002_safety and phasing plan
CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ
CZ
CONSTRUCT 4 - UNIT HANGARS
CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ Meriden, CT
A
CZ
Title
CONSTRUCTION SAFETY AND
CZ
PHASING PLAN
CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ
CZ CZ CZ CZ CZ CZ CZ CZ Project No. Scale
179450845 AS SHOWN
2024.03.29 3:32:26 PM
C-002
Revision Sheet Drawing No.
0 3 of 14
ORIGINAL SHEET - ANSI D
1 2 3 4 5
N
Stantec
3 Columbia Circle Suite 6
Albany NY 12203-5158
Tel:(518) 452-4358
www.stantec.com
Copyright Reserved
D The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing
- any errors or omissions shall be reported to Stantec without delay.
The Copyrights to all designs and drawings are the property of Stantec. Reproduction or
use for any purpose other than that authorized by Stantec is forbidden.
Consultant
Notes
E
N
CZ
50845_100_EXISTING CONDITIONSCAM
File Name: PVE PVE
PLAN Dwn. Dsgn. Chkd. YYYY.MM.DD
Permit/Seal
Client/Project Logo
Client/Project
Meridan-Markham Municipal Airport
E E E E E E E E E E E E E E E E E
u:\179450845\aviation\9_drawing\sheet_files\50845_100_existing conditions plan
E E E E E
CONSTRUCT 4 - UNIT HANGARS
Meriden, CT
A
Title
E E E E E E E E E E E E E E E
CZ CZ CZ
EXISTING CONDITIONS PLAN
CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ
C-100
Revision Sheet Drawing No.
0 4 of 14
ORIGINAL SHEET - ANSI D
1 2 3 4 5
Stantec
3 Columbia Circle Suite 6
Albany NY 12203-5158
Tel:(518) 452-4358
www.stantec.com
Copyright Reserved
D The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing
- any errors or omissions shall be reported to Stantec without delay.
The Copyrights to all designs and drawings are the property of Stantec. Reproduction or
use for any purpose other than that authorized by Stantec is forbidden.
Consultant
Notes
E
N
CZ
File Name:
50845_101_LAYOUT PLAN CAM PVE PVE
Dwn. Dsgn. Chkd. YYYY.MM.DD
Permit/Seal
Client/Project Logo
N
Client/Project
Meridan-Markham Municipal Airport
E E E E E E E E E E E E E E E E E E E E
E E
CONSTRUCT 4 - UNIT HANGARS
u:\179450845\aviation\9_drawing\sheet_files\50845_101_layout plan
Meriden, CT
A
Title
E E E E E E E E E E E E E E E
CZ CZ CZ
LAYOUT PLAN
CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ
C-101
Revision Sheet Drawing No.
0 5 of 14
ORIGINAL SHEET - ANSI D
1 2 3 4 5
℄
Stantec
3 Columbia Circle Suite 6
Albany NY 12203-5158
Tel:(518) 452-4358
www.stantec.com
Copyright Reserved
D The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing
- any errors or omissions shall be reported to Stantec without delay.
The Copyrights to all designs and drawings are the property of Stantec. Reproduction or
use for any purpose other than that authorized by Stantec is forbidden.
Consultant
Notes
Permit/Seal
Client/Project Logo
Client/Project
Meridan-Markham Municipal Airport
u:\179450845\aviation\9_drawing\sheet_files\50845_102_typical section and details
Meriden, CT
A
Title
C-102
Revision Sheet Drawing No.
0 6 of 14
ORIGINAL SHEET - ANSI D
1 2 3 4 5
ELECTRICAL GENERAL NOTES GENERAL ABBREVIATIONS PANEL & CIRCUIT SYMBOLS RECEPTACLE OUTLET SYMBOLS
ABBREVIATIONS DESCRIPTIONS SYMBOLS DESCRIPTIONS DESCRIPTIONS SYMBOLS DESCRIPTIONS Stantec
1. ALL GENERAL NOTES, SYMBOL LIST & DETAILS ARE TO BE CONSIDERED AS
SYMBOLS 3 Columbia Circle Suite 6
APPLICABLE TO ALL ELECTRICAL DRAWINGS FOR THIS PROJECT. SYMBOLS AND LETTER IS CIRCUIT CONTROL GROUP. Albany NY 12203-5158
ABBREVIATIONS SHOWN ON THIS SHEET ARE FOR REFERENCE ONLY AND DO ACU AIR CONDITIONING UNIT PANELBOARD - FLUSH MOUNTED AT 6'-6" TO TOP. "42"" INDICATES MOUNTED AT 42" A.F.F. Tel:(518) 452-4358
"GFCI" / "GFI" INDICATES GFI OUTLET
NOT INDICATE THEIR INCORPORATION IN THE DESIGN. AFF ABOVE FINISHED FLOOR www.stantec.com
PANELBOARD - SURFACE MOUNTED AT 6'-6" TO TOP. (PROTECTS DOWNSTREAM RECEPTACLES ON SAME CIRCUIT.)
AFG ABOVE FINISHED GRADE "WM" INDICATES DEVICE MOUNTED IN "WIREMOLD"
2. ALL WORK PERFORMED ON THIS CONTRACT SHALL BE DONE IN A NEAT AND
AHU AIR HANDLING UNIT LP1-3 (PAR) "E" INDICATES EXISTING Copyright Reserved
D WORKMANLIKE MANNER AND SHALL BE IN COMPLIANCE WITH NEC, NFPA,
IBC, OSHA, AND ALL APPLICABLE STATE AND LOCAL CODES AND ORDINANCES. AIC AMPERE INTERRUPTING CAPACITY "TR" INDICATES TAMPER RESISTANT The Contractor shall verify and be responsible for all dimensions. DO NOT scale the dra
INDICATES PARTIAL CIRCUIT - any errors or omissions shall be reported to Stantec without delay.
"OC" INDICATES OVER COUNTER
C CONDUIT INDICATES CIRCUIT NUMBER The Copyrights to all designs and drawings are the property of Stantec. Reproduction
3. THESE DRAWINGS ARE, IN GENERAL, MADE TO SCALE BUT ALL MEASUREMENTS "WP" INDICATES WEATHER RESISTANT DEVICE IN A WEATHER PROOF IN-USE use for any purpose other than that authorized by Stantec is forbidden.
CS CONDUIT SLEEVE INDICATES PANEL
SHALL BE TAKEN FROM FIGURED DIMENSIONS, AND NOT BY SCALING. COVER
ELECTRICAL FEED TO EQUIPMENT; ARROW INDICATES HOMERUN TO
CB
CL
CIRCUIT BREAKER
PANELBOARD OR AS NOTED.
MOUNT WITH GROUND TERMINAL AT TOP. DEVICES SHALL BE HOSPITAL GRADE, SEE
SPEC.
Consultant
4. THE ELECTRICAL CONTRACTOR SHALL CONFER WITH ALL OTHER TRADES CENTER LINE
INDICATES CIRCUIT IN CONDUIT RUN IN FLOOR OR UNDERGROUND.
RELATIVE TO THE LOCATION OF APPARATUS AND EQUIPMENT AND SELECT CR CASEWORK RECESSED OUTLET SIMPLEX CONVENIENCE RECEPTACLE MOUNTED AT +18" OR AS NOTED.
LOCATIONS SO AS NOT TO CONFLICT WITH WORK OF OTHER TRADES. INDICATES CONTROL WIRING BY ELECTRICAL
CLF CURRENT LIMITING FUSE
CT CURRENT TRANSFORMER DUPLEX RECEPTACLE OUTLET NEMA 5-20R, HEAVY DUTY.
5. LIGHTING FIXTURE MANUFACTURERS NAME & MODEL NUMBER ARE USED FOR T T MOUNTED AT +18" OR AS NOTED, SELF-ILLUMINATING, AND
CTV CABLE TELEVISION TRANSFORMER, SIZE & TYPE AS INDICATED
DESCRIPTIVE PURPOSES ONLY AND ARE INTENDED TO INDICATE THE STANDARD BACKPLATE. DEVICES
OF MATERIAL OR ARTICLES REQUIRED. CU CONDENSING UNIT SHALL BE RED WHEN CONNECTED TO CRITICAL OR EQUIPMENT
J J JUNCTION BOX - SIZED IN ACCORDANCE WITH NEC - "C"
CUH CABINET UNIT HEATER C C INDICATES MOUNTING IN CEILING SPACE. PANELS.
6. ALL EQUIPMENT SHOWN ON THESE DRAWINGS IS INTENDED TO BE GENERALLY QUADRUPLEX RECEPTACLE OUTLET (DOUBLE DUPLEX) NEMA 5-
CWP CONDENSER WATER PUMP
REPRESENTATIVE OF THE EQUIPMENT WHICH WILL BE INSTALLED UNDER THIS 3 POLE, NON-FUSIBLE DISCONNECT SWITCH 20R, HEAVY DUTY. MOUNTED AT +18" OR AS NOTED, SELF-
DT DISTRIBUTION TRANSFORMER 30NF 30 = AMPACITY. VOLTAGE AS REQ'D. ILLUMINATING, AND BACKPLATE. DEVICES SHALL BE RED WHEN
CONTRACT, BUT IT SHALL NOT BE ASSUMED THAT THE DRAWINGS INDICATE
THE SPECIFIC CONFIGURATION, ARRANGEMENT OR POINTS OF CONNECTION OF DW DISHWASHER 40 CONNECTED TO CRITICAL OR EQUIPMENT PANELS.
THE ACTUAL EQUIPMENT UNLESS NOTED OTHERWISE. DWG DRAWING 60
3 POLE FUSIBLE DISCONNECT SWITCH
60 = CLIP SIZE, 40 = FUSE SIZE
Notes
EBB ELECTRIC BASEBOARD HEATER VOLTAGE AS REQ'D GF GFCI DUPLEX RECEPTACLE OUTLET
7. CIRCUIT BREAKERS USED FOR LIGHTING CIRCUITS SHALL BE SWITCH DUTY E.C. ELECTRICAL CONTRACTOR
3R 3 POLE WEATHERPROOF DISCONNECT SWITCH SIZE & CONFIGURATION RANGE OUTLET NEMA 14-50R ("D" INDICATES DRYER OUTLET NEMA 14-30R)
RATED AND APPROVED FOR USE WITH FIXTURES. CIRCUIT BREAKERS EDH ELECTRIC DUCT HEATER R
AS NOTED ABOVE
USED FOR HVAC AND REFRIGERATION EQUIPMENT SHALL BE "HACR" RATED.
EF EXHAUST FAN SPECIAL PURPOSE CONNECTION.
MS MANUAL STARTER - SIZE AS REQUIRED
8. ALL HOME RUNS FOR LIGHTING OR POWER CIRCUITS LONGER THAN 150 FEET EUH ELECTRIC UNIT HEATER
EUROPEAN 220V DUPLEX RECEPTACLE
SHALL BE INCREASED ONE SIZE. (IE: #12 TO #10). EWC ELECTRIC WATER COOLER MOTOR, HP AS INDICATED COORDINATE W/ ACTUAL EQUIPMENT
1
EX EXISTING EQUIPMENT (AS NOTED) FURNISHED. FLOOR SINGLE RECEPTACLE OUTLET W/ COVER. NEMA 5-20R
9. ALL BRANCH CIRCUIT AND FEEDER CONDUCTORS SHALL BE SIZED FOR THE
FACP FIRE ALARM CONTROL PANEL
O.C.D. RATING FOR THAT CIRCUIT ACCORDING TO NEC ART 310 UNLESS COMBINATION MAGNETIC STARTER - NEMA SIZE AS REQUIRED
OTHERWISE INDICATED ON THESE DRAWINGS. IN NO CASE SHALL CONDUCTORS FBO FURNISHED BY OWNER FLOOR DUPLEX RECEPTACLE OUTLET W/ COVER. NEMA 5-20R
(MINIMUM SIZE 1) PROVIDE W/ H-O-A SWITCH AND GREEN RUN LIGHT
SMALLER THAN NO. 12 AWG BE USED FOR POWER OR LIGHTING CIRCUITS. FC FAN COIL
ON COVER. DW FLOOR SPECIAL PURPOSE OUTLET LETTER(S)
FLA FULL LOAD AMPS
MAGNETIC STARTER - NEMA SIZE AS REQUIRED (MINIMUM SIZE 1) BESIDE SYMBOL INDICATES ACTUAL EQUIPMENT SERVED.
10. PROVIDE 3/8" NYLON ROPE IN ALL EMPTY SERVICE RACEWAYS. GD GARBAGE DISPOSER PROVIDE W/ H-O-A SWITCH AND GREEN RUN LIGHT ON COVER. -
GFCI GROUND FAULT CIRCUIT INTERRUPTING FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR. SIZE AS
C 11. ALL SLEEVES AND OTHER PENETRATIONS THRU FIRE RATED ASSEMBLIES SHALL
LIGHTING SYMBOLS
CONDUCTORS WITH ALL FEEDERS AND BRANCH CIRCUITS. S SINGLE POLE SWITCH MOUNTED AT +48" OR AS NOTED.
HWP HOT WATER CIRC. PUMP
ALL WIRING SHALL BE IN CONDUIT. IBC INTERNATIONAL BUILDING CODE 3
THREE WAY SWITCH MOUNTED AT +48" OR AS NOTED.
15. SA
IG ISOLATED GROUND Revision By Appd YYYY.MM.DD
16. REMOVE EQUIPMENT, FIXTURES AND DEVICES THAT ARE NOT BEING REUSED IR INFRA-RED S
DM SLIDE CONTROL DIMMER AT +48" OR AS NOTED, PROVIDE
AND DISCARD. OWNER HAS THE OPTION TO KEEP ANY MATERIAL DESIRED. SYMBOLS DESCRIPTIONS SWITCH FOR FIXTURES ACTUALLY SERVED.
KW KILOWATT
EXISTING FIXTURES SCHEDULED FOR REUSE SHALL BE CLEANED. SA
LXXX
LOW VOLTAGE SWITCH LIGHT MOUNTED AT +48" OR AS NOTED.
KWH KILOWATT HOUR
17. PROVIDE ARC FLASH LABELS ON EQUIPMENT AS REQUIRED BY NPFA 70 - ART. LIG LONG/INSTANTANEOUS/GROUND FAULT SEE DETAILS FOR SWITCH CONFIGURATION(S)
WALL MOUNTED EXTERIOR LIGHT
110.16. LTG LIGHTING S
P
SINGLE POLE SWITCH W/ PILOT LIGHT MOUNTED AT +48" OR AS NOTED.
18. PROVIDE AVAILABLE FAULT CURRENT VALUES AND DATE AS REQUIRED BY NFPA MB MAIN BREAKER S
M H.P. RATED MANUAL MOTOR STARTER (WEATHERPROOF WHERE Issued for Bid CAM PVE 2024.04.04
OUTSIDE).
70 - ART. 110.24. UTILITY SHALL PROVIDE THESE VALUES (21 CYCLE SYMMETRICAL
RMS.)
MC METAL CLAD LENSED LED STRIP - AS NOTED ON DRAWINGS
ON DRAWINGS.
Issued By Appd YYYY.MM.DD
M.C. MECHANICAL CONTRACTOR S OS OS2 OS - DUAL TECH. OCCUPANCY SENSOR WALL SWITCH
MCA MINIMUM CIRCUIT AMPACITY OS2 - DUAL TECH. OCCUPANCY SENSOR TWO BUTTON/LOAD WALL
19. WHERE THE FAA AND CSI SPECIFICATIONS DIFFER, THE MORE STRINGENT File Name:
50845_E-501_ELEC_DTLS HAB MLC MK
LENSED LED STRIP - AS NOTED ON DRAWINGS SWITCH
REQUIREMENT SHALL BE REQUIRED. MD MAIN DISCONNECT Dwn. Dsgn. Chkd. YYYY.MM.DD
ON DRAWINGS. SHADING DENOTES BATTERY BACKUP.
MDP MAIN DISTRIBUTION PANEL OS OCCUPANCY SENSOR (CEILING MOUNT) . COMPATIBLE WITH ROOM
MH MAN HOLE / METAL HALIDE EMERGENCY EXIT SIGN, SEE LIGHTING CONTROLLER/ SWITCHING SYSTEM OR/AND LIGHTING CONTROL PANEL.
MI MINERAL INSULATED
SCHEDULE FOR SPECIFICATION. 'H' DENOTES HIGH CEILING TYPE. 'R' DENOTES HVAC RELAY Permit/Seal
MLO MAIN LUGS ONLY TYPE ROOM CONTROLLER (ABOVE CEILING MOUNT)
MMC MAINE MEDICAL CENTER # LRC - LOCAL SWITCH CONTROL. LDC - LOCAL DIMMING CONTROL.
MTD MOUNTED NRC - NETWORK SWITCH CONTROL. NDC - NETWORK DIMMING CONTROL.
B MW MICROWAVE
THE # INDICATES NUMBER OF LOADS. SEE DETAILS.
RECP RECEPTACLE
REF REFRIGERATOR
REQ'D REQUIRED
RF RETURN FAN
Client/Project
RGE RANGE Meridan-Markham Municipal Airport
RGS RIGID GALVANIZED STEEL CONDUIT
RH RANGE HOOD
SF SUPPLY FAN CONSTRUCT 4 - UNIT HANGARS
S/N SOLID NEUTRAL
TBD TO BE DETERMINED
TP TAMPER PROOF
TV TELEVISION
Meriden, CT
A
TYP TYPICAL
UC UNDER COUNTER Title
UH
UNO
UNIT HEATER
UNLESS NOTED OTHERWISE
ELECTRICAL LEGEND AND GENERAL
WP WEATHERPROOF NOTES
WM INSTALL WITH "WIREMOLD"
XFMR TRANSFORMER
E.001
Revision Sheet Drawing No.
0 10of 14
ORIGINAL SHEET - ANSI D
1 2 3 4 5
Stantec
3 Columbia Circle Suite 6
Albany NY 12203-5158
Tel:(518) 452-4358
www.stantec.com
Copyright Reserved
D The Contractor shall verify and be responsible for all dimensions. DO NOT scale the dra
- any errors or omissions shall be reported to Stantec without delay.
The Copyrights to all designs and drawings are the property of Stantec. Reproduction
use for any purpose other than that authorized by Stantec is forbidden.
Consultant
E
CZ E CZ CZ E CZ CZ E CZ CZ E CZ CZ E CZ E
CZ CZ E CZ CZ E CZ CZ E CZ CZ E CZ CZ E CZ E
CZ CZ E
CZ CZ E CZ CZ E CZ CZ E CZ CZ E CZ CZ E CZ E
CZ CZ E CZ CZ E CZ CZ E
Notes
CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ
E E E CZ
E E E E E E E E E
CZ
E E
E E E
E
CZ
C
CZ
ECZ E E CZ
CZ CZ CZ CZ CZ CZ CZ CZ CZ
CZE CZ E
CZ CZ E
CZ CZ CZ CZ CZ E CZ CZ CZ CZ CZ
CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ CZ
E E E E E E E E E E E E E E E E E E E E
E E CZ
E
Issued for Bid CAM PVE 2024.04.04
File Name:
50845_E-101_ELEC_SITE_PLAN HAB MLC MK
E
Dwn. Dsgn. Chkd. YYYY.MM.DD
E
Permit/Seal
B E
E
Client/Project Logo
E
E E E E
E E E E
E
E E
E
\\us0258-ppfss01\shared_projects\179450845\building_services\9_drawing\electrical\50845_e-101_elec_site_plan
E E E E
E E
E E
E
E E
E
E Client/Project
E
EE EE EE E Meridan-Markham Municipal Airport
E
E E
E E E
CONSTRUCT 4 - UNIT HANGARS
Meriden, CT
A
Title
ELECTRICAL SITE PLAN
N
Stantec
3 Columbia Circle Suite 6
Albany NY 12203-5158
Tel:(518) 452-4358
www.stantec.com
Copyright Reserved
D The Contractor shall verify and be responsible for all dimensions. DO NOT scale the dra
- any errors or omissions shall be reported to Stantec without delay.
The Copyrights to all designs and drawings are the property of Stantec. Reproduction
use for any purpose other than that authorized by Stantec is forbidden.
Consultant
Notes
50845_E-201_ELEC_HNGR_PLANS HAB
File Name: MLC MK
Dwn. Dsgn. Chkd. YYYY.MM.DD
Permit/Seal
Client/Project Logo
\\us0258-ppfss01\shared_projects\179450845\building_services\9_drawing\electrical\50845_e-201_elec_hngr_plans
Client/Project
Meridan-Markham Municipal Airport
Meriden, CT
A
Title
HANGAR POWER AND LIGHTING PLA
E.201
Revision Sheet Drawing No.
0 12of 14
ORIGINAL SHEET - ANSI D
1 2 3 4 5
Stantec
3 Columbia Circle Suite 6
Albany NY 12203-5158
Tel:(518) 452-4358
www.stantec.com
Copyright Reserved
D The Contractor shall verify and be responsible for all dimensions. DO NOT scale the dra
- any errors or omissions shall be reported to Stantec without delay.
The Copyrights to all designs and drawings are the property of Stantec. Reproduction
use for any purpose other than that authorized by Stantec is forbidden.
Consultant
Notes
File Name:
50845_E-501_ELEC_DTLS HAB MLC MK
Dwn. Dsgn. Chkd. YYYY.MM.DD
Permit/Seal
Client/Project Logo
\\us0258-ppfss01\shared_projects\179450845\building_services\9_drawing\electrical\50845_e-501_elec_dtls
Client/Project
Meridan-Markham Municipal Airport
KEEP 5 FOOT CLEAR
OF AIRCRAFT ENGINE CONSTRUCT 4 - UNIT HANGARS
& FUEL TANK AREA Meriden, CT
A FROM ALL ELECTRICAL
Title
EQUIPMENT & CONNECTIONS
ELECTRICAL ONE-LINE AND DETAILS
E.501
Revision Sheet Drawing No.
0 13of 14
ORIGINAL SHEET - ANSI D
1 2 3 4 5
Stantec
3 Columbia Circle Suite 6
Albany NY 12203-5158
Tel:(518) 452-4358
www.stantec.com
Copyright Reserved
D The Contractor shall verify and be responsible for all dimensions. DO NOT scale the dra
- any errors or omissions shall be reported to Stantec without delay.
The Copyrights to all designs and drawings are the property of Stantec. Reproduction
use for any purpose other than that authorized by Stantec is forbidden.
Consultant
Notes
File Name:
50845_E-501_ELEC_DTLS HAB MLC MK
Dwn. Dsgn. Chkd. YYYY.MM.DD
Permit/Seal
Client/Project Logo
\\us0258-ppfss01\shared_projects\179450845\building_services\9_drawing\electrical\50845_e-501_elec_dtls
Client/Project
Meridan-Markham Municipal Airport
Meriden, CT
A
Title
ELECTRICAL SCHEDULES
E.601
Revision Sheet Drawing No.
0 14of 14
ORIGINAL SHEET - ANSI D