Manual de Termostato Hisense Modelo Hyxe-Vc01
Manual de Termostato Hisense Modelo Hyxe-Vc01
7. Model: HYXE-VC01
7.1 Safety summary
● Please use this product properly after carefully reading are listed, and important safety-related contents are
this chapter given, please be sure to observe!
● Items in this chapter are identified as 「 Warning」. ● Please keep this manual properly after reading for
Serious consequences that may result from mis-operation reference at any time.
● For installation, please entrust the distributor or the professional installation personnel. Installation by
customers themselves may lead to water leakage, electric shock, a fire, unit falling and other injuries.
Warning
● Electrical constructors must be qualified for construction. Please entrust qualified distributors for
construction.
Installation by customers themselves may lead to electric shock, a fire and other accidents.
In Operation
● Please do not operate the controller with wet hands, which may lead to electric
shock.
● Please turn off the main power immediately when the safety device starts
repeatedly or the operation key acts abnormally.
Warning
Servicing · Relocation
● Please contact the distributor or our designated service center for servicing of the air conditioner units.
Improper servicing or installation may lead to electric shock, a fire and other accidents.
Warning
● Please contact the distributor or our designated service center for servicing or relocation of the controller.
Improper servicing or installation may lead to electric shock, a fire and other accidents.
151
Model: HYXE-VC01
● Strictly prohibit the ingress of water during maintenance. Otherwise it may lead to electric shock.
Warning
● Do not alter the electrical wiring without permission, which may lead to major accident.
● Do not cut off the power supply within 3 minutes after pressing the key of the controller, which may lead to
misoperation.
152
Model: HYXE-VC01
7.2 Features
Features
Mode Cool/Heat/Auto/Fan/Dry
LCD DISPLAY
Louver Louver setting/louver controlled independently/3D-air flow
Language: English
Health/ECO/Sleep/Self-cleaning/Boost/Electric heater/
Special function
Quiet/Boost/Humidifying/Wind-free
Fan speed 6
Main-sub control ●
Back light ●
7.3 Installation
7.3.1 Installation Site Selection
Cable section 0.3 mm2 ≥ 0.75 mm2
Cable length 30 m 500 m
Mounting Screw
4
(M4×25mm)
Operation Manual 1
Installation manual 1
153
Model: HYXE-VC01
7.3.3 Description of the parts
To proceed with below instructions, all the displays are listed. It is different from actual running.
32 33 34 35 36 37 38 39 40 41 42
9 10
12 13
14 15 11
20 21 22 23 24 25
19 18 17 16
26 27 28 29 30 31
1 2 3 4
5 6 7 8
A. Operation Buttons
1 Mode 4 Function 7 Temperature“-”
2 Fan 5 Timer 8 ON/OFF
3 Temperature“+” 6 Louver
B. Display on LED
9 Operation modes: "Cool""Dry" 20 Health 32 ON
"Heat" "Fan""Auto""Floor-heat" 21 ECO 33 Non-applicable
10 Fan 22 Sleep 34 Pre-heating
11 Louver 23 Self-cleaning 35 Anti-fungus
12 3D outlet 24 Boost 36 Emergency
13 Ultra-far 25 Electric heater 37 Test run
14 Set temp/humidity/room temperature 26 Quiet 38 Filter
15 Room/Set temp 27 Nature wind 39 Centralized controller
16 Timed power-on/off 28 Humidifying 40 Defrosting
17 Check 29 Water pump 41 Alarm
18 Service code 30 Leave home 42 Lock
19 On-site setting system address 31 Wind-free
154
Model: HYXE-VC01
7.3.4 Dimension data
Unit: mm
43
155
Model: HYXE-VC01
7.3.5 Installation procedure
Check if the following items are available before installation:
remote controller×1 bolt (M4×25mm) ×2 expansion bolt(M3.5×25mm) ×2
manual×1 certificate of quality×1
Attention
● Separate the two parts by inserting and rotating a screwdriver. Pay attention when separation in case of damaging other
parts and the product.
1. Insert into the bottom to separate the controller 2. Pass power source line through trough, and
by a slotted screwdriver with top width 6mm. fix the back cover onto the wall by screws (pay
attention to the arrow direction when installation).
3. Perform wiring work as per manual. 4. Press the controller onto the back cover.
Installation done.
Wiring
156
Model: HYXE-VC01
7.4 Electrical wiring
Attention
Electric Box for Indoor Unit Electric Box for Indoor Unit Sub-remote-controller
Remote controller Terminal Block Terminal Block Remote controller
Bolt
M3.5
50 100
Attention
157
Model: HYXE-VC01
7.5 Checking procedure
For step 1:
Hold『 』 and 『 』 simultaneously for 5s to exit
from Test Run setting state
3 For step 2:
Stop test run when timing out or by pressing 『 』
158
Model: HYXE-VC01
7.6 Operation instruction
Basic Functions
Mode
Only units with Cool and Heat functions for shop/office and VRF with Cool and
Heat functions for building are capable of heating. Those with cooling function
only are not capable of heating.
Switch on.
Preparation
● When connected with total heat exchanger, only air supply mode will display. Please contact the dealer for details.
● When connected with double-source indoor units, FAN and HEAT display. Please contact the dealer for details.
● Wired remote controller will display dry or auto-dry according to the actual condition that whether the connected ducted
type indoor units have equipped with humidity sensor or not.
● For the mode described in Item 1 will be skipped automatically when it is unavailable or the connected unit type does not
support.
● When connected a indoor unit with 3-Level dry, the wired remote controller can display three different levels of dry
operation: standard, C- Dry and S-Dry. Please contact the dealer for details.
159
Model: HYXE-VC01
Operation
Press『 』
The operation indicator light lits up and the
Start unit starts running.
The icon "ON" displays.
Press『 』
The operation indicator light goes out and
Stop the unit stops.
The icon "ON" disappeared.
● Once heating operation is stopped, the indoor unit will supply air for around 2 minutes.
Temperature
160
Model: HYXE-VC01
Temperature
● Room temperature can be displayed after special setting on controller. Please contact with the dealer for details.
● Hold 『 』 and 『 』for 3s to switch between Celsius and Fahrenheit.
Humidity
● Auto-Dry mode is valid only when such function is available in the indoor unit. Please contact
the dealer for details.
● When connected a dehumidifier with 3-level Dry, the left lower corner shows target humidity value in Dry mode, and only
temperature value can be adjusted. Please contact with the dealer for details.
161
Model: HYXE-VC01
Louver
● Options of louver setting may vary along with the types of indoor units. Please refer to the manual of indoor unit for
details.
● When the louver is in operation, location display on LCD may not exactly match with the actual location.
● Sometimes the louver may not stop immediately after pressing the key.
162
Model: HYXE-VC01
Louver
3
Press『 』and horizontal louver will
display in a reverse manner of the above
sequence.
When flashes for 5s, the blades move
and horizontal louver starts to swing.
When other icons flash and stop after 5s,
horizontal louver stops at set location.
163
Model: HYXE-VC01
Fan
1 (Breeze → SL → L → M → H → SH → AUTO)
4-level: AUTO
( L → M → H → SH → AUTO)
AUTO
3-level:
(L → M → H → AUTO)
● Air volume is adjustable during Dry operation, but it is defaulted at Low by indoor unit.
● Depending on the types of connected indoor units, Auto mode can display when controlling certain indoor units by wired
remote controller. Please contact the dealers for details.
● AUTO can be set only when this function is available in the indoor unit.
Fan
Attention ● Louver will not display when connected with an indoor unit without louver.
● Louver setting when connected with common 4-way cassette type indoor units.
164
Model: HYXE-VC01
Louver
● Louver setting when connected with 1-way cassette type or kitchen indoor units.
2
Press『 』and vertical louver will
display in a reverse manner of the above
sequence.
When flashes for 5s, the blades move
and vertical louver starts to swing. After
other icons flash for 5s and stop, vertical
louver stops at set location.
165
Model: HYXE-VC01
Louver
3
Press『 』and horizontal louver will
display in a reverse manner of the above
sequence.
When flashes for 5s, the blades move
and horizontal louver starts to swing.
After other icons flash for 5s and stop,
horizontal louver stops at set location.
166
Model: HYXE-VC01
Louver
● Louver setting when connected with K3 4-way cassette type indoor units.
1
Press『 』and icons of four louvers will
display in a reverse manner of the above
sequence.
When flashes for 5s, or by pressing
『 』, the blades start to move and four
louvers starts to swing. After other icons
flash for 5s, or by pressing 『 』, four
louvers stop at set location.
● Louver setting when connected with K3 2-way cassette type in door units.
1
Press『 』and icons of two louvers will
display in a reverse manner of the above
sequence.
When flashes for 5s, or by pressing
『 』, the blades start to move and two
louvers starts to swing. After other icons
flash for 5s, or by pressing 『 』, two
louvers stop at set location.
● When connected with K3 2-way and 4-way cassette types of indoor units, louver can be switched to individual control
when the unit is ON by holding FAN button. Please contact with the dealer for details.
167
Model: HYXE-VC01
Additional Functions
● If an indoor unit without any additional functions is connected in,
Attention
"N.A. (non-applicable)" will display when pressing button.
2
When icon of additional function is
flashing, press『 』to switch.
Each press of the button will change
the icons of additional functions
in a reverse manner of the above
sequence.
168
Model: HYXE-VC01
Health
● The icon of Health does not display when connected with an indoor unit without this
Attention
function.
● When the unit is switched from ON to OFF, the Health mode is canceled.
● When operation mode is changed, the Health function does not cancel.
● When the unit is OFF, the User can set if Health function will be auto-on or off when starts up by holding『 』for over
5s.
169
Model: HYXE-VC01
ECO
Attention ● The icon of ECO does not display when connected with an indoor unit without this
function. ECO is not available when air volume or temperature is restricted, and if
ECO function has been set, the function will be canceled automatically by then.
● When setting ECO function by wired remote controller, set air volume and temperature are non-adjustable. Indoor unit
will set air volume and temperature automatically.
● ECO mode is canceled when the air conditioner is switched OFF.
● ECO mode is canceled when the operation mode is changed.
170
Model: HYXE-VC01
Sleep
Attention ● The icon of Sleep does not display when connected with an indoor unit without this
function. Sleep function invalids when temperature or air volume is restricted.
● When setting to Sleep mode by remote controller, the air volume is at Low, which can be adjusted during Sleep mode.
● Sleep mode is canceled when the air conditioner is switched OFF.
● Sleep mode is canceled when operation mode is changed.
● Sleep mode is canceled when timer power-off is canceled.
● In Sleep mode, timing duration can be adjusted.
171
Model: HYXE-VC01
Self-cleaning
Attention ● The icon of Self-cleaning does not display when connected with an indoor unit
without this function.
● When setting to Sleep mode by remote controller, the air volume is at Low, which can be adjusted during Sleep mode.
● Sleep mode is canceled when the air conditioner is switched OFF.
● Sleep mode is canceled when operation mode is changed.
● Sleep mode is canceled when timer power-off is canceled.
● In Sleep mode, timing duration can be adjusted.
172
Model: HYXE-VC01
Electric Heater
Attention ● The icon of Electric Heater does not display when connected with an indoor unit
without this function.
173
Model: HYXE-VC01
Quiet
Attention ● The icon of Quiet does not display when connected with an indoor unit without this
function. Quiet may be invalid when air volume is restricted.
● When setting to Quiet by remote controller, the air volume is remains at current level and non-adjustable. Indoor unit will
set volume.
● Quiet mode is canceled when the air conditioner is switched OFF.
● Quite mode is canceled when operation mode is changed.
174
Model: HYXE-VC01
Nature Wind
Attention ● Icon of Nature Wind does not display when connecting with an indoor unit without
this function. Nature Wind may be invalid when air volume is restricted.
175
Model: HYXE-VC01
Wind Free
Attention ● The icon of Wind Free does not display when connected with an indoor unit without
this function.
● Wind Free is available only in FAN, COOL, HEAT, and DRY modes.
● Wind Free is canceled when the air conditioner is switched OFF.
● Wind Free is canceled when setting of FAN or LOUV is changed.
176
Model: HYXE-VC01
Timer
● Timer power-on: unit operates when timer ends
● Timer power-off: unit stops when timer ends
Timer power-on
● Timer power-on is available only when the air ● When timing range is 0~10h, the adjustment accuracy is 0.5h.
conditioner is OFF. ● When timing range is 10~72h, the adjustment accuracy is 1h.
● Timing range is 0.5~72h.
177
Model: HYXE-VC01
Timer
Timer power-on
● Timer power-on is available only when the air ● When timing range is 0~10h, the adjustment accuracy is 0.5h.
conditioner is ON. ● When timing range is 10~72h, the adjustment accuracy is 1h..
● Timing range is 0.5~72h.
178
Model: HYXE-VC01
Other Displays
State
Central Controller
PREH.
To protect air conditioning system and
improve comfort level, when the air
conditioner is preparing for operation
after startup, this icon will lit up for a
while and then goes out.
179
Model: HYXE-VC01
Other Displays
180
Model: HYXE-VC01
Other Functions
● If installation engineer has perform setting on the air conditioner before installation, please use this function with caution.
Please contact with the dealer for details.
This remote controller has infrared receiving function, and can realize remote controller by using
with wireless controller. Please contact the dealer for details.
181
Model: HYXE-VC01
7.7 Alarm indication
Abnormality
182
Model: HYXE-VC01
7.8 Check mode
Check 1:
1
CHEC displays.
The latest alarm code displays at the
location of set temperature.
3
Check item displays at the location of
set temperature. Value of check item
displays at the location of timer.
183
Model: HYXE-VC01
Table D: Data Code of Check Mode 1 (following table described all the information can be displayed, and only part of the
information will display in actual operation)
184
Model: HYXE-VC01
Check 2:
185
Model: HYXE-VC01
● Tables of "Check 1 and 2" indicate that more marks will show up during checking but not applicable to this type of air
conditioner, and thus no further explanations are given. Please note when using.
186
Model: HYXE-VC01
7.9 Change indoor unit address
Verify the indoor unit that changed address; When not Take (1) address verification mode
sure about the indoor unit address that to be changed Take (2) address change mode
1 (verification required); Get indoor unit's address that
Take (3) auto-addressing initialization mode
changed; Initialize the address set by auto-addressing;
● When one remote controller controls over 2 or more indoor units, and not sure about the address, please
Attention
specify indoor unit address and run individual to verify.
187
Model: HYXE-VC01
Change indoor unit address after confirming the address of indoor unit that will be changed. Step to (2) Address change
mode.
(2) Address change mode ( change indoor unit address and refrigerant No.)
188
Model: HYXE-VC01
189
Model: HYXE-VC01
● It is a must to cut off power supply to indoor unit after changing of indoor unit address. If not, it may lead
Attention
to improper operation of auto-addressing.
190
Model: HYXE-VC01
● If an indoor unit without auto-addressining initialization function is selected, "N.A." will display.
Attention ● If the address of selected indoor unit is "AA", indoor unit without auto-addressing initialization function will
not clear up auto-addressing.
● When auto-addressing initialization proceeding properly, re-communication will begin.
● For indoor unit that auto-addressing has been initialized or without auto-addressing initialization function,
the address of target unit and refrigerant system will switch from flashing to ON.
191
Model: HYXE-VC01
7.10 Address check operation
Temperature Temperature
Adjustment Adjustment
Temperature Temperature
Adjustment Adjustment
Common Mode
192
Model: HYXE-VC01
(i) [05] shows at the 7-segment display for service function No.
(ii) Display address and refrigerant system of target indoor unit .
When switched to indoor unit selection state, following information will show up immediately: indoor unit with min.
refrigerant system and min. address among the indoor units performing group setting via wired remote control.
In addition, when no indoor unit in group setting via wired remote control, address and refrigerant system will display as
[00].
(iii) 7-segment display for set temp will not display [Set temp], [°C], [QTY].
● Others
(1) In the mode of address check, it will return to common mode when power outage regardless of instantaneous outage or
a long one.
(2) In the mode of address check, commands of OFF and commands of changing of operation mode, set temp, Fan, louver
will be received. However, when these commands cannot be handled when they are in prohibited state.
(3) In the mode of address check, timer cannot be set.
(4) In the mode of address check, temperature will not change when pressing [ ∨ ] or [ ∧ ].
(5) In the mode of address check, when the state or target of ON/OFF, operation mode, set temp, Fan, Louver is changed,
the state remains even when returned to common mode.
193
Model: HYXE-VC01
7.11 Address initialization
Auto-addressing function will initialize the indoor unit address.
194
Model: HYXE-VC01
● If an indoor unit without auto-addressing initialization function is selected, "N.A." will display.
Attention ● If the address of selected indoor unit is "AA", indoor unit without auto-addressing initialization function will
not clear up auto-addressing.
● When auto-addressing initialization proceeding properly, re-communication will begin.
● For indoor unit that auto-addressing has been initialized or without auto-addressing initialization function,
the address of target unit and refrigerant system will switch from flashing to ON.
195