Model: HYXE-VC01

7. Model: HYXE-VC01
7.1 Safety summary
● Please use this product properly after carefully reading are listed, and important safety-related contents are
this chapter given, please be sure to observe!
● Items in this chapter are identified as 「 Warning」. ● Please keep this manual properly after reading for
Serious consequences that may result from mis-operation reference at any time.

Installation · Electrical Construction

● For installation, please entrust the distributor or the professional installation personnel. Installation by
customers themselves may lead to water leakage, electric shock, a fire, unit falling and other injuries.
Warning

● Electrical constructors must be qualified for construction. Please entrust qualified distributors for
construction.
Installation by customers themselves may lead to electric shock, a fire and other accidents.

In Operation

● Please do not operate the controller with wet hands, which may lead to electric
shock.

● Please turn off the main power immediately when the safety device starts
repeatedly or the operation key acts abnormally.
Warning

Due to the possibility of electric leakage or overcurrent, accidents such as electric


shock, a fire and explosion may occur. Please contact the distributor or our
designated service center.

● In case of abnormality (smell of burning, etc.), please stop operation immediately


and cut off the main power supply. Operation under abnormal conditions may lead
to failure, electric shock, a fire and other accidents. Please contact the distributor
or our designated service center.

Servicing · Relocation

● Please contact the distributor or our designated service center for servicing of the air conditioner units.
Improper servicing or installation may lead to electric shock, a fire and other accidents.
Warning

● Please contact the distributor or our designated service center for servicing or relocation of the controller.
Improper servicing or installation may lead to electric shock, a fire and other accidents.

151
Model: HYXE-VC01

Other Warnings and Precautions

● Strictly prohibit the ingress of water during maintenance. Otherwise it may lead to electric shock.
Warning

● Do not alter the electrical wiring without permission, which may lead to major accident.

● Do not cut off the power supply within 3 minutes after pressing the key of the controller, which may lead to
misoperation.

152
Model: HYXE-VC01
7.2 Features

Features
Mode Cool/Heat/Auto/Fan/Dry

Timer Timing range is 0.5~72h.


Size: 86mm×86mm
Error code/parameter check/auto test run/indoor&outdoor
Maintenance
pcb checking / self diagnostic function Max.connectable indoor units:6

LCD DISPLAY
Louver Louver setting/louver controlled independently/3D-air flow
Language: English
Health/ECO/Sleep/Self-cleaning/Boost/Electric heater/
Special function
Quiet/Boost/Humidifying/Wind-free

Fan speed 6

Temperature control 0.5OC

Main-sub control ●

Air filter cleaning reminding ●

Back light ●

Built-in temperature sensor ●

7.3 Installation
7.3.1 Installation Site Selection
Cable section 0.3 mm2 ≥ 0.75 mm2
Cable length 30 m 500 m

7.3.2 Component List

Name Appearance Quantity

Wired Remote Control 1

Mounting Screw
4
(M4×25mm)

Operation Manual 1

Installation manual 1

153
Model: HYXE-VC01
7.3.3 Description of the parts
To proceed with below instructions, all the displays are listed. It is different from actual running.

32 33 34 35 36 37 38 39 40 41 42
9 10
12 13
14 15 11
20 21 22 23 24 25
19 18 17 16
26 27 28 29 30 31

1 2 3 4

5 6 7 8

A. Operation Buttons
1 Mode 4 Function 7 Temperature“-”
2 Fan 5 Timer 8 ON/OFF
3 Temperature“+” 6 Louver
B. Display on LED
9 Operation modes: "Cool""Dry" 20 Health 32 ON
"Heat" "Fan""Auto""Floor-heat" 21 ECO 33 Non-applicable
10 Fan 22 Sleep 34 Pre-heating
11 Louver 23 Self-cleaning 35 Anti-fungus
12 3D outlet 24 Boost 36 Emergency
13 Ultra-far 25 Electric heater 37 Test run
14 Set temp/humidity/room temperature 26 Quiet 38 Filter
15 Room/Set temp 27 Nature wind 39 Centralized controller
16 Timed power-on/off 28 Humidifying 40 Defrosting
17 Check 29 Water pump 41 Alarm
18 Service code 30 Leave home 42 Lock
19 On-site setting system address 31 Wind-free

● Please tap screen with finger.


Attention Do not touch the screen with objects with
sharp edges, or the screen may be damaged.

154
Model: HYXE-VC01
7.3.4 Dimension data
Unit: mm

43

155
Model: HYXE-VC01
7.3.5 Installation procedure
Check if the following items are available before installation:
remote controller×1 bolt (M4×25mm) ×2 expansion bolt(M3.5×25mm) ×2
manual×1 certificate of quality×1

Attention

● Separate the two parts by inserting and rotating a screwdriver. Pay attention when separation in case of damaging other
parts and the product.

1. Insert into the bottom to separate the controller 2. Pass power source line through trough, and
by a slotted screwdriver with top width 6mm. fix the back cover onto the wall by screws (pay
attention to the arrow direction when installation).

Slotted screwdriver with a


top width of approx. 6mm

3. Perform wiring work as per manual. 4. Press the controller onto the back cover.
Installation done.

Wiring

156
Model: HYXE-VC01
7.4 Electrical wiring

Attention

● Cut off power supply before wiring in case of an electric shock.


Up to 6 indoor units can be connected

Electric Box for Indoor Unit Electric Box for Indoor Unit Sub-remote-controller
Remote controller Terminal Block Terminal Block Remote controller

Bolt
M3.5

Twisted pair (1P-0.75mm2 above)

Cable Size of Additionally Purchased Cable for Elongation

Twisted pair (above 1P-0.75mm2)


Crimp Terminal (Type X)
O.D. 7mm, ivory
1.25-3X )

50 100

Attention

● Specification of communication cable: 0.3~0.75mm2(total length ≤30m), twisted cable of


1P-0.75mm2 (total length >30m) is also acceptable. Cables other than specified will lead to mis-operation due to clutter
● Wiring cable between remote controller and indoor unit shall keep a distance of at least 30cm from the power source
line. If within 30cm, iron conduit shall be applied to accommodate the cable, and a D type earthing shall be provided at
one side. Otherwise, failures may raised from mis-operation of air conditioners due to power source disturbance.
● Seal the gaps, if any, in cable conduit of remote controller box with vinyl tape. Otherwise, the ingress of water drop or
insects may raise failures.
● When installation keep the controller at a distance of at least 0.5m from the lamp.
● When installation remote controller should be located at eye-level. It is suggested at the height of around 1.3~1.5m, with
angle of viewing within 30°.
● When connecting with indoor units only, remote controllers can connect up to six units .

157
Model: HYXE-VC01
7.5 Checking procedure

● Test run duration is defaulted as 2h.


● Test run is to commission the air conditioner units, and guarantee a proper operation of refrigerant
Attention
system and water system. Once operation enters normal state, press 『 』 to exit from test run.
● In case of wrong quantity of the units, it may raised from improper connection or from the auto-
addressing due to disturbance. Please cut off power supply and check wiring connections.

Hold 『 』 and 『 』 simultaneously in usual state


for 5s to enter Test Run setting state. The icon of
Test Run display.
1
Quantity of 01 displays at the location of set
temperature.

Press『 』in the above interface to start test run.


2 The air conditioner turns off after the defaulted test run
duration of 2h.

For step 1:
Hold『 』 and 『 』 simultaneously for 5s to exit
from Test Run setting state
3 For step 2:
Stop test run when timing out or by pressing 『 』

158
Model: HYXE-VC01
7.6 Operation instruction

Basic Functions
Mode
Only units with Cool and Heat functions for shop/office and VRF with Cool and
Heat functions for building are capable of heating. Those with cooling function
only are not capable of heating.

Switch on.
Preparation

Power supply shall be available before


operation to protect compressor.
LCD is as shown on the right when
energized.
Do not cut off power supply in
operation season.

Press to select operation mode.


Each press of the button, the operation
mode will switch as the following
1 sequence.

● When connected with total heat exchanger, only air supply mode will display. Please contact the dealer for details.
● When connected with double-source indoor units, FAN and HEAT display. Please contact the dealer for details.
● Wired remote controller will display dry or auto-dry according to the actual condition that whether the connected ducted
type indoor units have equipped with humidity sensor or not.
● For the mode described in Item 1 will be skipped automatically when it is unavailable or the connected unit type does not
support.
● When connected a indoor unit with 3-Level dry, the wired remote controller can display three different levels of dry
operation: standard, C- Dry and S-Dry. Please contact the dealer for details.

159
Model: HYXE-VC01

Operation

Press『 』
The operation indicator light lits up and the
Start unit starts running.
The icon "ON" displays.

Press『 』
The operation indicator light goes out and
Stop the unit stops.
The icon "ON" disappeared.

● Once heating operation is stopped, the indoor unit will supply air for around 2 minutes.

Temperature

In usual mode, each press of


『 』will increase the temperature by 0.5℃ . And

1 rapid switching can be realized by holding this


button.

160
Model: HYXE-VC01

Temperature

In usual mode, each press of


『 』will increase the temperature by 0.5℃ . And
2 rapid switching can be realized by holding this
button.

● Room temperature can be displayed after special setting on controller. Please contact with the dealer for details.
● Hold 『 』 and 『 』for 3s to switch between Celsius and Fahrenheit.

Humidity

Each press of『 』will increase the


humidity by 1% (max. 90%). And rapid
1 switching can be realized by holding this
button.

Each press of『 』will decrease the


humidity by 1% (min. 35%). Rapid
2 switching can be realized by holding this
button.

● Auto-Dry mode is valid only when such function is available in the indoor unit. Please contact
the dealer for details.
● When connected a dehumidifier with 3-level Dry, the left lower corner shows target humidity value in Dry mode, and only
temperature value can be adjusted. Please contact with the dealer for details.

161
Model: HYXE-VC01

Louver
● Options of louver setting may vary along with the types of indoor units. Please refer to the manual of indoor unit for
details.
● When the louver is in operation, location display on LCD may not exactly match with the actual location.
● Sometimes the louver may not stop immediately after pressing the key.

● Louver setting when connected with 3D panel

Press『 』to start up the unit. Press『 』to


set louver direction. Each press of the button will
1 adjust the direction as the following sequence.

When is selected and flashing, Press『 』


and vertical louver swings or changes the angle at
stop. Each press of the button the vertical louver
will display in a flashing manner as the following
sequence.

2 Press『 』and vertical louver will display in a


reverse manner of the above sequence.
When flashes for 5s, the blades move and
vertical louver starts to swing. When other icons
flash and stop after 5s, vertical louver stops at set
location.

162
Model: HYXE-VC01

Louver

When is selected and flashing,


Press『 』and horizontal louver
swings or changes the angle at stop
Each press of the button the horizontal
louver will display in a flashing manner
as the following sequence.

3
Press『 』and horizontal louver will
display in a reverse manner of the above
sequence.
When flashes for 5s, the blades move
and horizontal louver starts to swing.
When other icons flash and stop after 5s,
horizontal louver stops at set location.

When is selected, it flashes


for 5s then keep ON.
4 Horizontal and vertical louvers are
in swing mode at present.

When is selected, it flashes for


5s then keep ON.

5 Louvers do not display at present.

163
Model: HYXE-VC01

Fan

Press to set air volume.


Each press of the button the adjust the air
volume as the following:
6-level: AUTO

1 (Breeze → SL → L → M → H → SH → AUTO)

4-level: AUTO

( L → M → H → SH → AUTO)

AUTO
3-level:
(L → M → H → AUTO)

● Air volume is adjustable during Dry operation, but it is defaulted at Low by indoor unit.
● Depending on the types of connected indoor units, Auto mode can display when controlling certain indoor units by wired
remote controller. Please contact the dealers for details.
● AUTO can be set only when this function is available in the indoor unit.

Fan

Attention ● Louver will not display when connected with an indoor unit without louver.

● Louver setting when connected with common 4-way cassette type indoor units.

Press『 』to start up the unit.


Press『 』to set louver direction. Each
press of the button will adjust the direction
1 as the following sequence.

164
Model: HYXE-VC01
Louver

● Louver setting when connected with 1-way cassette type or kitchen indoor units.

Press『 』to start up.


Press『 』to set louver direction.
Each press of the button will adjust the
1 direction as the following sequence.

When is selected and flashing,


Press『 』and vertical louver swings or
changes the angle at stop. Each press of
the button the vertical louver will display
in a flashing manner as the following
sequence.

2
Press『 』and vertical louver will
display in a reverse manner of the above
sequence.
When flashes for 5s, the blades move
and vertical louver starts to swing. After
other icons flash for 5s and stop, vertical
louver stops at set location.

165
Model: HYXE-VC01
Louver

When is selected and flashing,


Press『 』and horizontal louver swings
or changes the angle at stop. Each
press of the button the horizontal louver
will display in a flashing manner as the
following sequence.

3
Press『 』and horizontal louver will
display in a reverse manner of the above
sequence.
When flashes for 5s, the blades move
and horizontal louver starts to swing.
After other icons flash for 5s and stop,
horizontal louver stops at set location.

When flashes for 5s, the icon


keeps ON.
Horizontal and vertical louvers are
4 both in swing mode at present.

166
Model: HYXE-VC01

Louver
● Louver setting when connected with K3 4-way cassette type indoor units.

Press『 』to start up.


Press『 』 and icons of four louvers
flash simultaneously.
Press『 』and by each press of the
button the four louvers will display in a
flashing manner as the following sequence.

1
Press『 』and icons of four louvers will
display in a reverse manner of the above
sequence.
When flashes for 5s, or by pressing
『 』, the blades start to move and four
louvers starts to swing. After other icons
flash for 5s, or by pressing 『 』, four
louvers stop at set location.

● Louver setting when connected with K3 2-way cassette type in door units.

Press『 』to start up.


Press『 』 and icons of two louvers
flash simultaneously.
Press『 』and by each press of the
button the two louvers will display in a
flashing manner as the following sequence.

1
Press『 』and icons of two louvers will
display in a reverse manner of the above
sequence.
When flashes for 5s, or by pressing
『 』, the blades start to move and two
louvers starts to swing. After other icons
flash for 5s, or by pressing 『 』, two
louvers stop at set location.

● When connected with K3 2-way and 4-way cassette types of indoor units, louver can be switched to individual control
when the unit is ON by holding FAN button. Please contact with the dealer for details.

167
Model: HYXE-VC01

Additional Functions
● If an indoor unit without any additional functions is connected in,
Attention
"N.A. (non-applicable)" will display when pressing button.

Press『 』to start up the unit.


Press『 』to set additional
1 functions, and the selected
additional function flashes.

When icon of additional function is


flashing, press『 』to switch.
Each press of the button the icons
of additional functions will display as
the following sequence.

2
When icon of additional function is
flashing, press『 』to switch.
Each press of the button will change
the icons of additional functions
in a reverse manner of the above
sequence.

168
Model: HYXE-VC01

Health
● The icon of Health does not display when connected with an indoor unit without this
Attention
function.

Press『 』to enter additional


function setting interface.
1 Press『 』or『 』to switch to
Health, if the icon of Health flashes it
is in setting state.

When Heath function is in setting


state, if it hasn't been set before,
this function will be valid after
flashing for 5s or by pressing『 』.
2 If it has been set, the function will be
canceled after flashing for 5 seconds
or by pressing『 』.

● When the unit is switched from ON to OFF, the Health mode is canceled.
● When operation mode is changed, the Health function does not cancel.
● When the unit is OFF, the User can set if Health function will be auto-on or off when starts up by holding『 』for over
5s.

169
Model: HYXE-VC01

ECO
Attention ● The icon of ECO does not display when connected with an indoor unit without this
function. ECO is not available when air volume or temperature is restricted, and if
ECO function has been set, the function will be canceled automatically by then.

Press『 』to enter additional


function setting interface.
1 Press『 』or『 』to switch to
ECO, if the icon of ECO flashes it is in
setting state.

When ECO is in setting state, if it


hasn't been set before, this function
will be valid after flashing for 5s or
by pressing 『 』.
2 If it has been set, this function will
be canceled after flashing for 5s or
by pressing『 』.

● When setting ECO function by wired remote controller, set air volume and temperature are non-adjustable. Indoor unit
will set air volume and temperature automatically.
● ECO mode is canceled when the air conditioner is switched OFF.
● ECO mode is canceled when the operation mode is changed.

170
Model: HYXE-VC01

Sleep
Attention ● The icon of Sleep does not display when connected with an indoor unit without this
function. Sleep function invalids when temperature or air volume is restricted.

Press『 』to enter additional


function setting interface.
1 Press『 』or『 』to select Sleep,
if the icon of Sleep flashes it is in
setting state.

When Sleep function is in setting


state, if it hasn't been set before, this
function will be valid after flashing for
5s or by pressing『 』button.
2 Then Sleep icon will display on
the LED, and there's an automatic
dimming of screen and operation
indicator light. The timer power-off of
8h flashes, which can be adjusted by
pressing『 』or『 』.

When Sleep function is in setting


state, if it has been set before, this
function will be canceled after flashing
3 for 5s or by pressing『 』.
Then timer will be canceled, screen
and operation indicator light come
back to normal brightness.

● When setting to Sleep mode by remote controller, the air volume is at Low, which can be adjusted during Sleep mode.
● Sleep mode is canceled when the air conditioner is switched OFF.
● Sleep mode is canceled when operation mode is changed.
● Sleep mode is canceled when timer power-off is canceled.
● In Sleep mode, timing duration can be adjusted.

171
Model: HYXE-VC01

Self-cleaning
Attention ● The icon of Self-cleaning does not display when connected with an indoor unit
without this function.

Press『 』in OFF state,


1 if the icon of Self-cleaning flashes it is
in setting state.

When Self-cleaning is in setting state,


press『 』and run indicator is
ON, indicating the function works. At
present, only the icon of Self-cleaning
and『ON』 display.
2
In Self-cleaning mode, no button
works except for『 』.

Self-cleaning will stop automatically


after 16~33 minutes' operation. Or
3 cancel this function by pressing 『 』
during operation.

● When setting to Sleep mode by remote controller, the air volume is at Low, which can be adjusted during Sleep mode.
● Sleep mode is canceled when the air conditioner is switched OFF.
● Sleep mode is canceled when operation mode is changed.
● Sleep mode is canceled when timer power-off is canceled.
● In Sleep mode, timing duration can be adjusted.

172
Model: HYXE-VC01

Electric Heater
Attention ● The icon of Electric Heater does not display when connected with an indoor unit
without this function.

Press『 』to enter additional


function setting interface.
1 Press『 』or『 』to switch to
Electric Heater, if the icon of Electric
Heater flashes it is in setting state.

When Electric Heater is in setting


state, if it hasn't been set before, this
function will be valid after flashing for
5s or by pressing『 』.
2 If it has seen set, this function will be
canceled after flashing for 5s or by
pressing『 』.

● Electric Heater is available only in Heat mode.


● Electric Heater is canceled when the air conditioner is switched OFF.
● Electric Heater is canceled when the operation mode is changed.
● This function is not available when connected with an indoor unit without electric heater.

173
Model: HYXE-VC01

Quiet
Attention ● The icon of Quiet does not display when connected with an indoor unit without this
function. Quiet may be invalid when air volume is restricted.

Press『 』to enter additional


function setting interface.
1 Press『 』or『 』to switch to
Quiet and if it flashes it is in setting
state.

When Quiet is in setting state, if it


hasn't been set, this function will
be valid after flashing for 5s or by
pressing『 』.
2 If it has been set, this function will be
canceled after flashing for 5s or by
pressing『 』.

● When setting to Quiet by remote controller, the air volume is remains at current level and non-adjustable. Indoor unit will
set volume.
● Quiet mode is canceled when the air conditioner is switched OFF.
● Quite mode is canceled when operation mode is changed.

174
Model: HYXE-VC01

Nature Wind
Attention ● Icon of Nature Wind does not display when connecting with an indoor unit without
this function. Nature Wind may be invalid when air volume is restricted.

Press『 』to enter additional


function setting interface.
1 Press『 』or『 』to switch to
Nature Wind, and if it flashes it is in
setting state.

When Nature Wind is in setting state,


if it hasn't been set, this function will
be valid after flashing for 5s or by
pressing『 』.
2 If it has been set, this function will be
canceled after flashing for 5s or by
pressing『 』.

● Nature Wind is available only in Cool mode.


● Nature Wind is canceled when the air conditioner is switched OFF.
● Nature Wind is canceled when the operation mode is changed.
● When setting Nature Wind, both set air volume and direction are non-adjustable, indoor unit will take control over the air
volume and direction.
● When connected with an indoor unit has Nature Wind function and equipped with 3D panel, once it is set to Nature Wind,
the louver will be in swing state.

175
Model: HYXE-VC01

Wind Free
Attention ● The icon of Wind Free does not display when connected with an indoor unit without
this function.

Press『 』to enter additional


function setting interface.
1 Press『 』or『 』to switch to Wind
Free and if it flashes it is in setting
state.

When Wind Free is in setting state, if


it hasn't been set, this function will be
valid after flashing for 5s or by
pressing『 』. And FAN and LOUV
icons do not display.
2
If it has been set, this function will be
canceled after flashing for 5s or by
pressing『 』. And FAN and LOUV
icons display.

● Wind Free is available only in FAN, COOL, HEAT, and DRY modes.
● Wind Free is canceled when the air conditioner is switched OFF.
● Wind Free is canceled when setting of FAN or LOUV is changed.

176
Model: HYXE-VC01
Timer
● Timer power-on: unit operates when timer ends
● Timer power-off: unit stops when timer ends
Timer power-on

Press『 』to enter timer setting


interface.
Then『ON』displays and timer『 』
flashes.
Timer power-on

When Timer power-on is in setting


state, Each press of『 』will
increase the timing by 0.5h.
Each press of『 』will decrease the
timing by 0.5h.
Timer power-on

When Timer power-on is in setting


state, and the time is adjusted
according to demand, this function is
successfully set after the time flashes
for 5s or by press『 』and flashing
stops.
Timer power-on

When Timer power-on is in setting


state, this function will be canceled by
setting time to 0 and flashes for 5s.
Or in usual state, cancel this function
by holding『 』for 3s. Then both
time and 『ON』disappear.

● Timer power-on is available only when the air ● When timing range is 0~10h, the adjustment accuracy is 0.5h.
conditioner is OFF. ● When timing range is 10~72h, the adjustment accuracy is 1h.
● Timing range is 0.5~72h.

177
Model: HYXE-VC01

Timer
Timer power-on

Press『 』to enter timer setting


interface.
Then『OFF』displays and timer『 』
flashes.
Timer power-on

When Timer power-off is in setting


state, Each press of『 』will
increase the timing by 0.5h.
Each press of『 』will decrease the
timing by 0.5h.
Timer power-on

When Timer power-off is in setting


state, and the time is adjusted
according to demand, this function is
successfully set after the time flashes
for 5s or by press『 』and flashing
stops.
Timer power-on

When Timer power-off is in setting


state, this function will be canceled by
setting time to 0 and flashes for 5s.
Or in usual state, cancel this function
by holding『 』for 3s. Then both
time and 『OFF』disappear.

● Timer power-on is available only when the air ● When timing range is 0~10h, the adjustment accuracy is 0.5h.
conditioner is ON. ● When timing range is 10~72h, the adjustment accuracy is 1h..
● Timing range is 0.5~72h.

178
Model: HYXE-VC01
Other Displays
State
Central Controller

When voiding remote controller through


central controller, the remote controller
is not able to set operation, temperature,
mode, air volume ,louver.

The icon lits up when filter requires


Filter

cleaning. Holding 『 』for over 3s


will clear the icon.
Defrosting

The icon lits up when outdoor unit is


performing auto-defrosting operation,
and goes out when completed.
Pre-heating

PREH.
To protect air conditioning system and
improve comfort level, when the air
conditioner is preparing for operation
after startup, this icon will lit up for a
while and then goes out.

179
Model: HYXE-VC01

Other Displays

This icon lits up when holding『 』


Button Lock

+『 』simultaneously for over 5s,


indicating the remote controller is in button
locking, and buttons does not work. When
locked, hold『 』+『 』 simultaneously
for over 5s to unlock. And buttons work
again.

This icon lits up when holding『 』


Function Lock

+『 』simultaneously for over 5s,


indicating the remote controller is in
function locking, and MODE, FAN,
LOUV, TIMER are locked.
When locked, hold『 』+『 』
simultaneously for over 5s to unlock. And
buttons work again.

180
Model: HYXE-VC01

Other Functions

This function is needed when display of


exception appears (CHEC., SERV., TEST RUN
One-key Reset

etc.),or when effect of Heat/Cool failed to reach


the expectations after startup.
When the air conditioner is OFF, hold 『 』
for over 5s to reset the remote controller to
factory settings.
At present the wired controller is in usual
interface and all the parameters are reset to
initial settings.

● If installation engineer has perform setting on the air conditioner before installation, please use this function with caution.
Please contact with the dealer for details.

This remote controller is defaulted as tone-off


Key Tone

When tone-off, hold 『 』+『 』for over 2s to turn on.


When tone-on, hold 『 』+『 』for over 2s to turn off .
Protocol

This remote controller has infrared receiving function, and can realize remote controller by using
with wireless controller. Please contact the dealer for details.

181
Model: HYXE-VC01
7.7 Alarm indication
Abnormality

(i) alarm code


System abnormality triggers the icon.
Operation indicator light flashes. Indoor
unit address, system No. and alarm (ii) indoor unit
code display on the screen and flash. add.and
refrigerant
system with
abnormality

All icons disappear.


Power Failure

The air conditioner remains out of


operation after recovery of power
source supply if the shutdown is due
to power failure. Please re-perform
running operation.
Instantaneous power failure of around
2s will not interrupt operation of air
conditioner after recovery of power
source supply.
Disturbance

All icons disappear.


Operation may also stop. This is due
to the protection actions from micro-
processor against disturbance.
Please re-perform running operation.
Commu.Abnormality

Flashing operation indicator


light indicating a communication
abnormality. Please contact with the
dealer for details.

182
Model: HYXE-VC01
7.8 Check mode

● Check mode including 『Check 1』and『Check 2』with differences as below:


Attention Check 1: display data of sensors that has to be updated every 30s.
Check 2: display data before alarm triggered, because data are saved in EEPROM

Check 1:

Hold『 』and『 』for 5s in usual


state to enter Check 1, and the icon

1
CHEC displays.
The latest alarm code displays at the
location of set temperature.

Press『 』in the above interface to


2 enter item selecting state of Check 1.

Press『 』or『 』to select the


required check item.

3
Check item displays at the location of
set temperature. Value of check item
displays at the location of timer.

183
Model: HYXE-VC01

Table D: Data Code of Check Mode 1 (following table described all the information can be displayed, and only part of the
information will display in actual operation)

No. Items Mark


1 Set temp b1
2 Return air temp b2
3 Outlet air temp b3
4 Liquid pipe temp b4
5 Remote controller sensor temp b5
6 Ambient temp b6
7 Gas pipe temp b7
8 Evaporation temp b8
9 Compressor quantity in operation b9
10 Exhaust gas temp bA
11 Wired remote controller sensor temp bb
12 Current humidity bv
13 Inlet water temp Twi bF
14 Outlet water temp Two bh
15 Liquid pipe temp b0
16 Indoor chip I/O state C1
17 Outdoor chip I/O state C2
18 Cause of stoppage d1
19 Occurrence times of alarm E1
20 Instantaneous stop times of indoor unit E2
21 Commu. error times between controller and indoor unit E3
22 Failure times of frequency converter E4
23 State of auto-louver F1
24 Exhaust pressure H1
25 Suction pressure H2
26 Required frequency H3
27 Actual operation frequency H4
28 Indoor unit capacity J1
29 Outdoor unit type code J2
30 Refrigerant system (display method 1) J3
31 Refrigerant system (display method 2) J4
32 Indoor expansion valve opening L1
33 Outdoor expansion valve 1 opening L2
34 Outdoor expansion valve 2 opening L3
35 Outdoor expansion valve B opening L4
36 Compressor current P1
37 Software version Pq

184
Model: HYXE-VC01

Check 2:

Hold『 』and『 』for 5s in Check


1 mode to enter Check 2, and the icon
1 CHEC displays.
The latest alarm code displays at the
location of set temperature.

Press『 』in the above


2 interface to enter item selecting
state of Check 2.

Press『 』or『 』to select the


required check item.
3 Check item displays at the location of
set temperature. Value of check item
displays at the location of timer.

185
Model: HYXE-VC01

Hold『 』and『 』for 5s in Check


4 2 mode to exit from Check.

Table E: Reference Table of "Check 2" Data


No. Check Item Mark
1 Return air temp q1
2 Outlet air temp q2
3 Indoor heat exchanger liquid pipe freezing temp q3
4 Outdoor unit gas pipe temp q4
5 Indoor heat exchanger gas pipe temp q5
6 Heat evaporation temp q6
7 Quantity of compressors in operation q7
8 Compressor top temp q8
9 Exhaust (high) pressure q9
10 Suction (low) pressure qA
11 Required frequency qb
12 Operation frequency qC
13 Indoor unit expansion valve opening qd
14 Outdoor unit expansion valve opening 1 qe
15 Current (compressor) qF

● Tables of "Check 1 and 2" indicate that more marks will show up during checking but not applicable to this type of air
conditioner, and thus no further explanations are given. Please note when using.

186
Model: HYXE-VC01
7.9 Change indoor unit address

● Indoor unit address (number) can be changed through remote controller.


Attention ● When two remote controls (master/sub) are adopted for controlling, address changing and verification
cannot be performed.
● Address of some indoor units cannot be changed.
● In address verification and address changing modes, please do not operate on central controller.

Verify the indoor unit that changed address; When not Take (1) address verification mode
sure about the indoor unit address that to be changed Take (2) address change mode
1 (verification required); Get indoor unit's address that
Take (3) auto-addressing initialization mode
changed; Initialize the address set by auto-addressing;

(1) Address verification

● When one remote controller controls over 2 or more indoor units, and not sure about the address, please
Attention
specify indoor unit address and run individual to verify.

Hold『 』and『 』for 5s to enter


On-site Setting mode when the air
conditioner is turned OFF. Service No.
1 flashes at frequency of 1Hz. Then press
『 』or『 』to select Service 05, and
press『 』to enter address selection
interface.

Press『 』or『 』to select the address


2 for the target indoor unit.

187
Model: HYXE-VC01

When an indoor unit is selected,


press『 』and the one with
3 address displayed on the screen
starts to operate.

When indoor unit address is confirmed


and air conditioner is turned off, hold
4 『 』+『 』for 5s to exit from
On-site Setting and return to usual
mode.

Change indoor unit address after confirming the address of indoor unit that will be changed. Step to (2) Address change
mode.
(2) Address change mode ( change indoor unit address and refrigerant No.)

Hold『 』and『 』』for 5s when


the air conditioner is turned off to enter
On-site Setting mode, and service No.
1 flashes at the frequency of 1Hz.
Press『 』or『 』to switch to Service
04, and press『 』 to enter address
selection interface.

188
Model: HYXE-VC01

Press『 』or『 』to select


the address of indoor unit to be
changed.
2 If the address of an indoor unit
without address changing function
is selected, "N.A." will display.

When an indoor unit is selected, press


『 』and the address flashes.
Press『 』or『 』to switch indoor
unit address.
3 (range: 00~63)
Then press『 』, the address will
stop flashing, and indoor unit system
starts to flash.

When indoor unit system flashes as


described above, press『 』or『 』
to change refrigerant system number of
indoor unit.
(range: 00~63)
4 Then press『 』, the indoor
unit system will stop flashing, and
AH displays at the location of set
temperature. indicating that the change
is completed.

● When an address is changed, AH will display for a while.


Attention ● When an address cannot be changed, EE will display for a while. Please select another address and
system that can be changed.
● No. 99 is used as a temporary system number when all the system numbers are running out, but it
actually doesn't exist.
● Once a system number is set to 99, it is a must to change to a number between 00 and 63.

189
Model: HYXE-VC01

When indoor unit address is changed,


hold『 』+『 』for 5s to exit from
On-site Setting and return to usual
5 mode.
Once the address change is completed,
wiring verification starts.

Please cut off the power supply to


indoor unit after 3 to 5 minutes from the
6 completion of the above operations.
And re-connect power supply when the
screen of wired controller is blank.

● It is a must to cut off power supply to indoor unit after changing of indoor unit address. If not, it may lead
Attention
to improper operation of auto-addressing.

(3) Auto-addressing function will initialize the indoor unit address.

Hold『 』and『 』』for 5s to enter


On-site Setting mode when the air

1 conditioner is turned OFF. Service No.


flashes at frequency of 1Hz.
Press『 』or『 』to select Service
06, and press『 』 to enter address
selection interface selection interface.

190
Model: HYXE-VC01

Press『 』or『 』to select the


address of indoor unit that requires
auto-addressing initialization.
2 If the address of an indoor unit without
address changing function is selected,
"N.A." will display.

Press 『 』to start address


initialization of the selected indoor
unit. Address and system No. flash for
3 around 10s and stop, then enter re-
communication step.

After auto-addressing initialization,


4 remote controller re-communicates and
step into usual state.

● If an indoor unit without auto-addressining initialization function is selected, "N.A." will display.
Attention ● If the address of selected indoor unit is "AA", indoor unit without auto-addressing initialization function will
not clear up auto-addressing.
● When auto-addressing initialization proceeding properly, re-communication will begin.
● For indoor unit that auto-addressing has been initialized or without auto-addressing initialization function,
the address of target unit and refrigerant system will switch from flashing to ON.

191
Model: HYXE-VC01
7.10 Address check operation

Setting Mode Selection

Address Check Operation Mode Selection Address Check Mode

Indoor Unit Selection

Temperature Temperature
Adjustment Adjustment

Minimum Address of Minimum System +1

Temperature Temperature
Adjustment Adjustment

Maximum Address of Maximum System

Function + " "

Common Mode

● Operation and display


(1) Switch to address check
When setting mode, 7-segment display for displaying service function No. shows [05] in a flashing manner, press [Func]
to switch to address check mode.
However, when main-slave wired remote control is adopted, address check mode is not accessbile, and [Function not
available] will display on screen and flash for 5s.

(2) Indoor unit selection


When switched to address check mode, the target
indoor unit will enter the selected state immediately.
After switching, the display will be as below.

192
Model: HYXE-VC01
(i) [05] shows at the 7-segment display for service function No.
(ii) Display address and refrigerant system of target indoor unit .
When switched to indoor unit selection state, following information will show up immediately: indoor unit with min.
refrigerant system and min. address among the indoor units performing group setting via wired remote control.
In addition, when no indoor unit in group setting via wired remote control, address and refrigerant system will display as
[00].
(iii) 7-segment display for set temp will not display [Set temp], [°C], [QTY].

(3) Indoor unit selection


(i) In the state of indoor unit selection, select target indoor unit as below.
Each press of [ ∨ ] or [ ∧ ] to switch address

[∧] temp adjustment key


min. ref. system min. ref. system max. ref. system
min. address min. address +1 max. address

[∨] temp adjustment key

(ii) Press [Run/Stop] to start the selected indoor unit.


In addition, other operation demands other than [Run/Stop] will not be received, and maintain at state of stop.
If switched to address check operation, proceed as below.
(1) During address check operation, [Basic format] will be sent from wired remote control to target indoor unit only.
(2) During address check operation, address does not change when pressing [ ∨ ] or [ ∧ ].

● Exit from mode of address check


(1) In the mode of address check, press [Func]+[ ∧ ] for 5s to switch to common mode. However, it will not exit from
address check mode when pressing [Reset] when in address check mode.
(2) In the mode of address check, commands of OFF and commands of changing of operation mode, set temp, Fan, louver
will be received. However, when these commands cannot be handled when they are in prohibited state.

● Others
(1) In the mode of address check, it will return to common mode when power outage regardless of instantaneous outage or
a long one.
(2) In the mode of address check, commands of OFF and commands of changing of operation mode, set temp, Fan, louver
will be received. However, when these commands cannot be handled when they are in prohibited state.
(3) In the mode of address check, timer cannot be set.
(4) In the mode of address check, temperature will not change when pressing [ ∨ ] or [ ∧ ].
(5) In the mode of address check, when the state or target of ON/OFF, operation mode, set temp, Fan, Louver is changed,
the state remains even when returned to common mode.

193
Model: HYXE-VC01
7.11 Address initialization
Auto-addressing function will initialize the indoor unit address.

Hold『 』and『 』for 5s to enter


On-site Setting mode when the air
conditioner is turned OFF. Service No.
1 flashes at frequency of 1Hz.
Then press『 』or『 』to select
Service 06, and press『 』to enter
address selection interface.

Press『 』or『 』to select the


address of indoor unit that requires
auto-addressing initialization.
2 If the address of an indoor unit without
address changing function is selected,
"N.A." will display.

Press『 』to start address


initialization of the selected indoor
3 unit. Address and system No. flash for
around 10s and stop, then enter
recommunication step.

194
Model: HYXE-VC01

After auto-addressing initialization,


remote controller re-communicates
4 and step into usual state.

● If an indoor unit without auto-addressing initialization function is selected, "N.A." will display.
Attention ● If the address of selected indoor unit is "AA", indoor unit without auto-addressing initialization function will
not clear up auto-addressing.
● When auto-addressing initialization proceeding properly, re-communication will begin.
● For indoor unit that auto-addressing has been initialized or without auto-addressing initialization function,
the address of target unit and refrigerant system will switch from flashing to ON.

195