You are on page 1of 41

This is an ATEX/HAZ-LOC Document

CALDON® ULTRASONICS

®
LEFM 220Ci, 240Ci,
240CiRN, 280Ci and 280CiRN
Ultrasonic Flowmeters

Approvals – Installation and


Safe Operation Manual

Manual No. IB1008 Rev. 03


IB1008 Rev. 03 LEFM 2xxCi - Approvals – Installation and Safe Operation Manual
This is an ATEX/HAZ-LOC Document

Caldon is a trademark of Cameron International Corporation (“Cameron”).


LEFM is a registered trademark of Cameron.
Modbus is a registered trademark of Modbus Organization, Inc.

Copyright © 2010 Cameron International Corporation (“Cameron”). All information


contained in this publication is confidential and proprietary property of Cameron. Any
reproduction or use of these instructions, drawings, or photographs without the express
written permission of an officer of Cameron is forbidden.

All Rights Reserved


Printed in the United States of America

Manual No. IB1008, Rev. 03


November 2010
LEFM 2xxCi Approvals – Installation and Safe Operation Manual IB1008 Rev. 03
This is an ATEX/HAZ-LOC Document

Table of Contents
Important Safety Information ...................................................................................................... iii
Terms Used in this Manual .........................................................................................................iv
Section 1......................................................................................................................................... 5
Introduction.................................................................................................................................... 5
Equipment Description ................................................................................................................ 5
LEFM 2xxCi Meter Body ......................................................................................................... 7
LEFM 2xxCi Transmitter ......................................................................................................... 8
Flowmeter Identification .............................................................................................................. 9
Model Number....................................................................................................................... 11
Meter Body Part Code .......................................................................................................... 12
Flowmeter Specifications .......................................................................................................... 13
Section 2....................................................................................................................................... 19
Installing Transmitter Remotely from Meter Body–Only Models 2xxCi-R & 2xxCi LT-R ..... 19
Remote-Mount Terminations Procedure (External Junction Box Only) .................................... 20
Meter Body to Transmitter Terminations .............................................................................. 20
Section 3....................................................................................................................................... 23
Transmitter Connections – All Models ...................................................................................... 23
Transmitter Installation Procedure ............................................................................................ 23
Transmitter Terminations ...................................................................................................... 23
Section 4....................................................................................................................................... 27
Maintenance ................................................................................................................................. 27
Introduction................................................................................................................................ 27
Backplane Interface Board (BIB) Replacement .................................................................... 31
Transducer Installation.............................................................................................................. 35
Appendix A................................................................................................................................... 37
ATEX Certifications (Document IB1008-A) ........................................................................... 37

November 2010 Page i Table of Contents


IB1008 Rev. 03 LEFM 2xxCi Approvals – Installation and Safe Operation Manual
This is an ATEX/HAZ-LOC Document

Table of Contents Page ii November 2010


LEFM 2xxCi Approvals – Installation and Safe Operation Manual IB1008 Rev. 03
This is an ATEX/HAZ-LOC Document

Important Safety Information

OPERATORS SHOULD NOT REQUIRE ACCESS TO THE INTERIOR OF THE


FLOWMETER. ONLY QUALIFIED PERSONNEL SHOULD SERVICE THE LEFM
200Ci. DO NOT ATTEMPT TO DISASSEMBLE THE INSTRUMENT OR
CAUTION OTHERWISE SERVICE THE INSTRUMENT UNLESS YOU ARE A TRAINED
MAINTENANCE TECHNICIAN.

If the equipment is used in a manner not specified by the manufacturer, the


protection provided by the equipment’s safety features may be impaired.
Cameron is not responsible for damages or injuries sustained as a result of
inappropriate use.

Before performing system verification and repair procedures, contact Cameron’s


Measurement Systems division, Caldon Ultrasonics.

Note: Unless the topic is specific to only one particular model, this manual will typically
use the term “2xxCi”. As discussed in the manual, the 240CiRN (280CiRN) is a
special configuration of the 240Ci (280Ci) meter, but with a reduced bore for
improved accuracy at lower velocities and higher viscosities.

For additional information or assistance on the application, operation or servicing, write or


call the Cameron office nearest you or visit www.c-a-m.com.

November 2010 Page iii Important Safety Information


IB1008 Rev. 03 LEFM 2xxCi Approvals – Installation and Safe Operation Manual
This is an ATEX/HAZ-LOC Document
Terms Used in this Manual

This symbol identifies information about practices or circumstances that


can lead to personal injury or death, property damage, or economic loss.

WARNING

This symbol indicates actions or procedures which if not performed correctly


may lead to personal injury or incorrect function of the instrument or
connected equipment.
CAUTION

Note – Indicates actions or procedures which may affect instrument operation or may lead to
an instrument response which is not planned.

Important Safety Information Page iv November 2010


LEFM 2xxCi Approvals – Installation and Safe Operation Manual IB1008 Rev. 03
This is an ATEX/HAZ-LOC Document

Section 1

Introduction

Equipment Description

The LEFM 2xxCi ultrasonic flowmeters are highly sophisticated flow measurement systems
that employ ultrasonic transit time to measure fluid velocity and volumetric flow rate. They
use advanced signal and data processing circuitry that ensure high accuracy and repeatability.
The LEFM 2xxCi can be configured to indicate direction of flow via either a quadrature
pulse output or a digital signal.

The LEFM 2xxCi also contains automatic fault detection system for verifying performance
and alerting personnel when abnormal operating conditions are detected. For ease of
troubleshooting, the LEFM 2xxCi provides easy-to-interpret diagnostic information via
ModBus communications and the local display.

There are 3 categories of meters. These are:

 220Ci – 2 path ultrasonic flow meters

 240Ci – 4 path ultrasonic flow meters

 280Ci – 8 path ultrasonic flow meters

Note: Unless the topic is specific to only one particular model, this manual will typically
use the term “2xxCi”. As discussed in the manual, the 240CiRN (280CiRN) is a
special configuration of the 240Ci (280Ci) meter, but with a reduced bore for
improved accuracy at lower velocities and higher viscosities.

The LEFM 2xxCi flowmeter has two basic components or subsystems:

 a meter body, including up to eight pairs of transducers forming acoustic paths and a
temperature sensor.

 a transmitter(s) containing a readout display and acoustic data processing electronics.

Typically, the transmitter is mounted to the meter body at the factory and the assembly is
shipped as one instrument, ready for installation. Remote-mount units are available,
particularly when there are extreme temperatures at the meter itself.

This manual covers the following models or configurations. These models are described as
follows:

November 2010 Page 5 Section 1


IB1008 Rev. 03 LEFM 2xxCi Approvals – Installation and Safe Operation Manual
This is an ATEX/HAZ-LOC Document
Model 2xxCi: Transmitter mounted to the meter body. This model has a factory
installed seal between the transmitter and the meter body.

Model 2xxCiRN: Transmitter mounted to the meter body. This model has a factory
installed seal between the transmitter and the meter body. This model has a specially
designed bore that has a reduced diameter.

Model 2xxCi-R (2xxCiRN-R): Transmitter mounted remotely from the meter body
(see Section 2 for transmitter installation). This model has a factory installed seal
between the transmitter and a junction box for terminating cables from the meter
body.

Model 2xxCi LT-R (2xxCiRNLT-R): Transmitter mounted remotely from the


meter body. In this case, the meter body is likely to see extreme temperatures (see
Section 2 for transmitter installation). This model has a factory installed seal between
the transmitter and a junction box for terminating cables from the meter body.

Section 1 Page 6 November 2010


LEFM 2xxCi Approvals – Installation and Safe Operation Manual IB1008 Rev. 03
This is an ATEX/HAZ-LOC Document
Models 2xxCi-R and 2xxCiLT-R require that the transmitter be mounted separately from the
meter body. In those instances the transmitter(s) and meter body are shipped separately.

Transmitter
with Display

Meter Body

Transducer
8 typical

RTD

Figure 1.1: LEFM 2xxCi Components, (280Ci Shown as Typical)

LEFM 2xxCi Meter Body


The meter body or metering section, as it is sometimes referenced, contains up to eight pairs
of acoustic transducers and a temperature sensor (RTD).

The meter body is a specially designed section of pipe that contains pairs of housings that are
positioned to provide acoustic paths at an angle to the flow direction. They are spaced in
accordance with the Gaussian Method of flow integration. The transducers are installed
inside these housings.

Each transducer transmits and receives ultrasonic pulses (typically 1.0 MHz or 1.6 MHz).
The transducer modules contain piezoelectric crystals which transmit and receive acoustic
energy. The transducer modules may be removed from their housings for maintenance while
the meter body is in the pipeline without affecting the pressure boundary.

November 2010 Page 7 Section 1


IB1008 Rev. 03 LEFM 2xxCi Approvals – Installation and Safe Operation Manual
This is an ATEX/HAZ-LOC Document
LEFM 2xxCi Transmitter
The transmitter houses the display that provides a reading of flow data including flow rate,
total flow volume, fluid properties, analog input data, alarm indication, fault detection, and
acoustic diagnostic information.

Figure 1.2: LEFM 2xxCi Transmitter with Sunshield Shown (280CiRN Shown as Typical)

The transmitter performs all control and timing for the generation and measurement of
acoustic pulses. Acoustic processing is performed by specialized proprietary boards that are
designed to achieve high sampling rates, provide stable ultrasonic signals, and eliminate zero
drift.

The transmitter offers the following inputs/outputs:

Standard volume pulse output


The K-factors used to configure transmitters at the factory are listed in. The user may
configure the K-factor to meet its needs.
One analog input (optional; choose from 4-20 mA or 0-20 mA)
Choose from:
Product temperature
Product pressure
Product density
One analog output (optional; choose from 4-20 mA or 0-20 mA)
Flow
Any ModBus Register (See ModBus manual)

Note: If required, the analog output may be mapped to any variable.

Section 1 Page 8 November 2010


LEFM 2xxCi Approvals – Installation and Safe Operation Manual IB1008 Rev. 03
This is an ATEX/HAZ-LOC Document
Flowmeter Identification

Both the transmitter and the meter body have nameplates that identify and define the
subcomponents.

Fi
Figure 1.3: LEFM Meter Body Nameplate, 2xxCi Typical

Figure 1.4: LEFM Meter Body Nameplate, 2xxCi –LT-R or 2xxCi -R Typical

November 2010 Page 9 Section 1


IB1008 Rev. 03 LEFM 2xxCi Approvals – Installation and Safe Operation Manual
This is an ATEX/HAZ-LOC Document

Figure 1.5: LEFM 2xxCi Transmitter Nameplate, Typical

Section 1 Page 10 November 2010


LEFM 2xxCi Approvals – Installation and Safe Operation Manual IB1008 Rev. 03
This is an ATEX/HAZ-LOC Document

Model Number
The model number defines construction and features. From the model number, a user can
identify and verify the component type, meter size, piping thickness, construction material,
ANSI rating, and enclosure type.

LEFM2xxCi - 6 -40 -SS - 150 - C


C = Custom
Meter Type
Ci = Integral Electronics ANSI Flange Rating
CiRN = Integral Electronics with Reduced Bore 150
300
Ci-R (or CiRN-R) = Remote Electronics
600
Ci LT-R (or CiRN-R) = Remote Electronics
900
with Cryogenic Meter Body
Meter Size, Inches 1500

Schedule: Material
40 160 SS = Stainless Steel
STD XXS CS = Carbon Steel
80 0.625 wall thickness DS = Duplex Stainless Steel
100 0.750 wall thickness
120 0.875 wall thickness

November 2010 Page 11 Section 1


IB1008 Rev. 03 LEFM 2xxCi Approvals – Installation and Safe Operation Manual
This is an ATEX/HAZ-LOC Document

Meter Body Part Code


Each LEFM 2xxCi meter body is assigned a part code that defines its construction and
features. A sample part code is illustrated below.
Meter Body Part Code Key

H 4 C 0 6 4 S A W A 1 6 A A C
Product Line: 0 = Standard / C = Custom
H = Hydrocarbon
W = Hydroelectric Approvals (Pressure Boundary/Electrical)
N = Nuclear A = ASME/CSA
B = ASME/ATEX
Product Type: C = PED/ATEX
2 = LEFM220C
4 = LEFM240C Enclosure Material
8 = LEFM280C A = Aluminum
S = SoundTrack S = Stainless Steel (Pending)
E = LEFM200E
Transducer Frequency (10*MHz)
Meter Type
C = Integral Compact Electronics Housing Size:
R = Remote Compact Electronics A = 0.5"
B = 1"
Size (Inches) C = 0.62"
D = 1.05"
Schedule: E = 0.75"
4 = Sch. 40
S = Standard Flange Type
8 = Sch. 80 W = Weld Neck Raised Face
0 = 100 R = Weld Neck RTJ Face
2 = 120
6 = 160 Flange Class:
X = XXS A = ANSI Class 150
T = 0.625 for 26" Meter B = ANSI Class 300
T = 0.750 for 28" and 32" Meter C = ANSI Class 600
T = 0.875 for 34" and 36" Meter D = ANSI Class 900
E = ANSI Class 1500
Material:
S = Stainless Steel
C = Carbon Steel
D = Duplex Stainless Steel

Section 1 Page 12 November 2010


LEFM 2xxCi Approvals – Installation and Safe Operation Manual IB1008 Rev. 03
This is an ATEX/HAZ-LOC Document
Flowmeter Specifications
Table 1.1: LEFM 2xxCi Transmitter Specifications
Material
Standard Aluminum
Custom Stainless Steel
Weight (if delivered separate from the meter body)
Net Weight 13.5 lb. (6.1 kg) Aluminum
35 lb. (15.9 kg) Stainless Steel
Power Requirements
Voltage Req’d 24 VDC (18 VDC to 30 VDC)
Current Draw 24 VDC at 0.45A
Power Consumption 10 W
Pulse Outputs/Communications
Pulse Output 0-5 V or 0-12 V
Alarm Status 5V (for 0-5V output) = normal operation
12V (for 0-12V output) = normal operation
0V = alarm condition
Communications
RS-485 Two COM ports or One COM port and one Ethernet
port

See ModBus specifications


Wireless Communications
Accessibility via PocketPC (see Pocket Link
IR Port
literature)
Analog Output
4-20 mA or 0-20 mA
(max load 650 Ohms)
Analog Input
4-20 mA or 0-20 mA
Meter body RTD is standard
Temperature Range
Storage Temperature -58°F (-50°C) to 185°F (85°C)
Operating Temperature -40°F (-40°C) to 140°F (60°C)
Hazardous Area
Approvals -40°F (-40°C) to 140°F (60°C)
Ambient Temperature

November 2010 Page 13 Section 1


IB1008 Rev. 03 LEFM 2xxCi Approvals – Installation and Safe Operation Manual
This is an ATEX/HAZ-LOC Document

Table 1.1: LEFM 2xxCi Transmitter Specifications (Cont’d.)

ATEX Approvals:

Ex d IIB T6 (Ta: -40°C to 60°C)


ITS07ATEX15465X
Hazardous Area Approvals:
(USA and Canada)
Class I Div I Groups C and D, Conforms to UL Std 1203,
Std UL 61010-1, CSA Std 22.2 No. 30, CSA Std 22.2 No.
61010.1

The ATEX certificates that define the conditions for safe use of the meter manifold and
transmitter are located in Appendix A of this manual. See the meter nameplate for the
temperature limit of an assembled system.

Section 1 Page 14 November 2010


LEFM 2xxCi Approvals – Installation and Safe Operation Manual IB1008 Rev. 03
This is an ATEX/HAZ-LOC Document

Table 1.2: Meter Body Specifications including -R and LT options


Material
Standard Stainless steel, carbon steel, or duplex steel

Storage Temperature -40°F (-40°C) to 140°F (60°C)


Note: For storage temperature, the meter body
limits have been set by the limiting ambient rating
of any seal/gland or J-box that could be used
with the flow meter. The operating temperatures
are defined in the previous section.

Operating Pressure Maximum working pressure is listed on the meter


nameplate (Surge pressures in excess of the
flange maximum working pressure rating must be
evaluated.)

ATEX Approvals
Model 2xxCi - Direct Mount
(Part Number
202B524HYY)

EEx d IIB T6 (Ta: -40°C to 60°C)


TRL04ATEX11068X

HYY Defines different sizes (“YY” can be any value between 21 and 36)

Or
(Part Number 202B761-W-DXX-M)

Ex d IIB T6 (Ta: -40°C to 60°C)


TRAC09ATEX21211X

Explanation of Part Number

D”XX” Defines different sizes (“XX” can be any value from 01 to 07)
M Defines material type
M = C means carbon steel,
M = S means stainless steel,
M = D means duplex steel

November 2010 Page 15 Section 1


IB1008 Rev. 03 LEFM 2xxCi Approvals – Installation and Safe Operation Manual
This is an ATEX/HAZ-LOC Document
Table 1.2 - Meter Body Specifications (Cont’d.)

Approvals (Cont’d.)
Model 2xxCi (280CiRN)-R Remote Mount

(Manifold Part Number 202B264-W-HXX)

EEx d II B T5 (Ta: See Below)


TRL04ATEX11068X
Explanation of Part Number Code and Temperature Range (ATEX only)

“W” Defines the different glands/seals used with device


Where:
“W” set to D – temperature range is: TA = -50°C to 93°C
“W” set to E – temperature range is: TA = -50°C to 80°C
“W” set to F – temperature range is: TA = -50°C to 93°C
“W” set to G – temperature range is: TA = -50°C to 105°C

H”XX” Defines different sizes (“XX” can be any value from 01 to 16)

Section 1 Page 16 November 2010


LEFM 2xxCi Approvals – Installation and Safe Operation Manual IB1008 Rev. 03
This is an ATEX/HAZ-LOC Document

Table 1.2: Meter Body Specifications (Cont’d.)

Approvals (Cont’d.)
Model 2xxCi LT (Wide Range Temperature)

Remote Mount
(Manifold Part
Number
202B582-WYZ-
H**)
EEx d IIB T3 (Ta: -170°C to 130°C)
TRL04ATEX11068X

Explanation of Part Number Code


“W” Defines the different glands/seals used with device
“Y” Defines whether device has an elbow in fittings
“Y” set to R – There is an elbow in the fittings
“Y” set to S – There is no elbow in the fittings
“Z” Defines whether device has a Tee or an adaptor in fittings
“Z” set to T – There is a tee in the fittings
“Z” set to F – There is an adaptor used in the fittings

H”**” Defines different sizes (“**” can be any value from 01 to 40)

Hazardous Class I Div I Groups C and D, Conforms to UL Std 1203,


Area Approvals Std UL 61010-1, CSA Std 22.2 No. 30, CSA Std 22.2 No.
(USA and 61010.1
Canada)

Note: The ambient temperature range for the ATEX approved glands is
limited to -50°C. The 2xxCi-LT meter body is rated to -170°C and must be
under thermal insulation.
WARNING

The ATEX certificates that define the conditions for safe use of the meter manifold and
transmitter are located in Appendix A of this manual. See the meter nameplate for the
temperature limit of the system as assembled.

November 2010 Page 17 Section 1


IB1008 Rev. 03 LEFM 2xxCi Approvals – Installation and Safe Operation Manual
This is an ATEX/HAZ-LOC Document

Figure 1.6: 2xxCi-R (202B264 ATEX Only)


Construction of Manifold to Junction Box Connection

Note: The specific ATEX approved cable gland, as specified on ATEX Certificate, must be
used. (See Appendix A of this manual for a copy of the ATEX Certificate).

ATEX Gland

Figure 1.7: LEFM 2xxCiLT-R – 202B582 (Low/High Temperature Configurations)


Note: Approved Seal at the End of the Tee/Fitting is required. The specific ATEX approved
cable gland, as specified on ATEX Certificate, must be used. (See Appendix A of this
manual for a copy of the ATEX Certificate).

Section 1 Page 18 November 2010


LEFM 2xxCi Approvals – Installation and Safe Operation Manual IB1008 Rev. 03
This is an ATEX/HAZ-LOC Document

Section 2

Installing Transmitter Remotely from Meter Body–Only


Models 2xxCi-R & 2xxCi LT-R

The physical properties, acoustic properties, and calibration of the meter


body are pre-programmed into the transmitter; therefore, the meter body and
transmitter are manufactured as a matched set and must be installed as a
CAUTION pair. Failure to install transmitters and meter bodies as matched sets can
result in erroneous flow measurements.

Should a customer receive multiple meter bodies and transmitters in one


shipment, the installer must verify that each transmitter is installed with the
meter body for which it was programmed.

Note All wiring between the transmitter and the meter body must be routed
through grounded metal conduit or equivalent according to site guidelines.
All wiring to the transmitter is to be routed in shielded conduit that meets site
environment specifications.

This section addresses the installation procedure for a transmitter separate from the meter
body. The following figure illustrates that configuration. The transmitter may be mounted
according to this section within 100 meters (300 feet). For distances further than 100 meters,
contact Cameron.

November 2010 Page 19 Section 2


IB1008 Rev. 03 LEFM 2xxCi Approvals – Installation and Safe Operation Manual
This is an ATEX/HAZ-LOC Document

J-Box at the
Transmitter

Field J-Box
Upstream box
shown.
Downstream
box is behind
pipe
Hazardous Area
Seal within 18
inches (45 cm)
Figure 2.1: Remote Installation of Transmitter from Meter Body

The installation requires field wiring to connect the meter body terminations to the
transmitter. Both the meter body and transmitter are installed with junction boxes (J-Box) for
the field terminations. The transmitter and its junction box must be mounted according to
site seismic rules/guidelines.

Remote-Mount Terminations Procedure (External Junction Box Only)

The terminations discussed in this section are within the junction boxes associated with the
meter body and transmitter. For all other terminations (e.g., power, serial communications
etc.), go to Section 3, “Transmitter Installation Procedure.”

Meter Body to Transmitter Terminations

Before terminating wires, open the power supply circuit breaker. Failure to
do so can result in electrical shock and/or explosion.

WARNING

Section 2 Page 20 November 2010


LEFM 2xxCi Approvals – Installation and Safe Operation Manual IB1008 Rev. 03
This is an ATEX/HAZ-LOC Document
Install hazardous area seals within 18 inches (45 cm) of the meter body junction boxes. (For
ATEX see the certificate for the conditions for safe use). Install hazardous area seals at the
entry point to transmitter junction box. There is a factory installed hazardous area seal
installed between the factory delivered junction box and the transmitter.

If ATEX approved glands are to be used, they shall be types that include
compound filled seals around individual cores. (Refer to EN 60079-14 clause
10.4.2).
WARNING

In the following figures, the location of the hazardous area seals is only nominal. Site
Note: geometrics, electrical codes and criteria may change the seal selection and affect the
configuration.

Transmitter with
sunshield shown

Factory installed seal is


used between transmitter
and junction box.

Remote mount junction


box for connections to
the meter body (Junction
box may vary between
sites)

Figure 2.2: Illustration of Installation of Transmitter/Junction Box

Important All equipment should be installed by a licensed electrician in accordance with


NEC/CEC or local codes. At a minimum, install a disconnect switch in series with
the transmitter power input.

November 2010 Page 21 Section 2


IB1008 Rev. 03 LEFM 2xxCi Approvals – Installation and Safe Operation Manual
This is an ATEX/HAZ-LOC Document

Section 2 Page 22 November 2010


LEFM 2xxCi Approvals – Installation and Safe Operation Manual IB1008 Rev. 03
This is an ATEX/HAZ-LOC Document

Section 3

Transmitter Connections – All Models


Models 2xxCi-R and 2xxCi LT-R Only: The physical properties, acoustic
properties, and calibration of the meter body are pre-programmed into the
transmitter; therefore, the meter body and transmitter are manufactured as a
CAUTION matched set and must be installed as a pair. Failure to install transmitters and
meter bodies as matched sets can result in erroneous flow measurements.

Transmitter Installation Procedure

Important All equipment should be installed by a licensed electrician in accordance with


NEC/CEC or local codes. At a minimum, install a disconnect switch in series with
the transmitter power input.

Note All wiring to and from the transmitter must be routed through grounded metal
conduit or equivalent.

Transmitter Terminations

Before inspecting components, open the power supply circuit breaker.


Failure to do so can result in electrical shock and/or explosion.

WARNING
User Conduit
These Conduit Entries Entries:
are NOT to be used. (3/4 Inch NPT)
One Used: A
seal is required
within 18 inches
(45 cm).
Both Used: A
seal is required
immediately at
This conduit entry is the device.
sealed at the factory
for the connection to
the meter body or
junction box.

Figure 3.1: Fully Assembled Transmitter – Rear View

November 2010 Page 23 Section 3


IB1008 Rev. 03 LEFM 2xxCi Approvals – Installation and Safe Operation Manual
This is an ATEX/HAZ-LOC Document
The two conduit entries (3/4 inch NPT) at the rear of the transmitter are for user connections.
If one entry is used, then a hazardous area conduit seal must be installed within 18 inches (45
cm) of the device. If both entries need to be used, a hazardous area conduit seal is required
on both entries immediately at the device.

If ATEX approved glands are to be used, they shall be types that include
compound filled seals around individual cores. (Refer to EN 60079-14 clause
10.4.2).
WARNING

The wires should then be routed so that the termination can be made. The terminations are
made under the rear cover at the terminal blocks (see Figures 3.2 and 3.3).

Figure 3.2: Transmitter with Rear Cover Removed

Section 3 Page 24 November 2010


LEFM 2xxCi Approvals – Installation and Safe Operation Manual IB1008 Rev. 03
This is an ATEX/HAZ-LOC Document

Figure 3.3: User Terminations, Cover Off

November 2010 Page 25 Section 3


IB1008 Rev. 03 LEFM 2xxCi Approvals – Installation and Safe Operation Manual
This is an ATEX/HAZ-LOC Document

TB2 TB4

TB3
TB1

Power supply fuses


Serial Output Protocol Jumpers

Figure 3.4: User Terminations, Close Up

Figures 3.3 and 3.4 show the locations of the transmitter terminations. Inside the rear cover
of the transmitter, there is a diagram of the user connections. All connections are to be per
the “Operation and Maintenance Manual”.

There are grounding points on the inside of the junction box at the meter body (if remote
mount) and on the outside of the junction box and the manifold. There are grounding points
on the inside and outside of the transmitter enclosure. For ATEX applications, both
grounding points must be used. Follow all other site guidelines regarding
grounding/earthing. See Figure 3.4 for the external ground point on the transmitter body.
TB3, Pin 3 is the internal ground connection.

1. Verify all field terminations have proper continuity and isolation from each other and
earth. Verify connections are good with respect to insulation.
2. Verify electronics turn on. On the display, only the top two LEDs (LED1 and LED2)
should be lit and the display is working.
3. Verify ModBus communications are operational. (Use LEFMLink software to test
ModBus communications via the IR port or RS-485 connection.)
4. Verify meter operation according to the “Operation and Maintenance Manual”.

Section 3 Page 26 November 2010


LEFM 2xxCi Approvals – Installation and Safe Operation Manual IB1008 Rev. 03
This is an ATEX/HAZ-LOC Document

Section 4

Maintenance

Service should be performed on the LEFM 2xxCi only by qualified personnel.

WARNING
Introduction

The troubleshooting and maintenance procedures must comply with the safety and hazardous
area requirements of this section. The typical maintenance procedures are discussed in the
“Operation and Maintenance Manual”.

Never open the transmitter or the meter body manifold when the instrument
is energized. Before inspecting components, open the power supply circuit
breaker. Failure to do so may result in electrical shock and/or an explosion.
WARNING

Wear an ESD protective wrist strap to avoid damaging any components.

CAUTION

Power Supply/Display Replacement

To open and close the transmitter, perform the following steps to comply with hazardous
location requirements:

To replace the Power Supply and Display assembly, perform the following steps:

1. Unscrew and remove the lid from the display end of the enclosure (Figure 4.1).
2. Grasp the edges of the Display cover and gently pull to lift it from three hex standoffs
(Figure 4.2). The Power Supply and Display assembly will be visible.
3. Unscrew the three standoffs to free the Power Supply and Display assembly from the
transmitter body, and lift the assembly from the enclosure (Figure 4.3). Unscrew the
power regulator that is attached by wire to the display assembly. The power regulator has
a plastic (non-conductive screw) and an insulator (typically mica material) between it and
the enclosure. Save these parts.

November 2010 Page 27 Section 4


IB1008 Rev. 03 LEFM 2xxCi Approvals – Installation and Safe Operation Manual
This is an ATEX/HAZ-LOC Document
4. Remove the new assembly from its packaging. Connect the new power regulator to the
enclosure with the original screw and insulator. Align the mounting holes with the
standoffs that remain inside the enclosure.
5. Reinstall the three hex standoffs that were removed in step 3, screwing them into the
holes provided in the power supply board (the large board at the back of the assembly).
6. Align the plastic connectors on the back of the display cover with the three hex standoffs
and snap the display cover into place.
7. Replace the lid on the enclosure.

Figure 4.1: Front Cover Removal (Installation)

Section 4 Page 28 November 2010


LEFM 2xxCi Approvals – Installation and Safe Operation Manual IB1008 Rev. 03
This is an ATEX/HAZ-LOC Document

Figure 4.2: Display Cover Removal (Installation)

Figure 4.3: Power Supply/Display Removal (Installation)

November 2010 Page 29 Section 4


IB1008 Rev. 03 LEFM 2xxCi Approvals – Installation and Safe Operation Manual
This is an ATEX/HAZ-LOC Document

Backplane Interface Board (BIB) Fuse Replacement


Never open the transmitter when the instrument is energized. Before
inspecting components, open the power supply circuit breaker. Failure to do
so may result in electrical shock and/or an explosion if in a hazardous area.
WARNING

Wear an ESD protective wrist strap to avoid damaging any components.

CAUTION

The fuses of the BIB (incoming power) are replaceable. The fuses are designed to fail if
120VAC or 230VAC are ever inadvertently put into the input power. These fuses are located
in the lower right side of the BIB. To replace the fuse, remove fuse with an IC puller or
tweezers. Press replacement fuse into the fuse holder.

Power supply fuses

Figure 4.4: Backplane Interface Board (BIB) Fuse Location

Section 4 Page 30 November 2010


LEFM 2xxCi Approvals – Installation and Safe Operation Manual IB1008 Rev. 03
This is an ATEX/HAZ-LOC Document

Backplane Interface Board (BIB) Replacement

Never open the transmitter when the instrument is energized. Before


inspecting components, open the power supply circuit breaker. Failure to do
so may result in electrical shock and/or an explosion if in a hazardous area.
WARNING

Wear an ESD protective wrist strap to avoid damaging any components.

CAUTION

The Backplane Interface Board (BIB) is located just beneath the rear cover. To replace the
BIB, perform the following steps:

1. Unscrew and remove the rear cover to reveal the BIB and the user terminations (Figure
4.5).
2. Remove the connections to TB1, TB2, TB3 and TB4.
3. Remove the three Phillips head screws connecting the BIB to the rear access panel
(Figure 4.6).
4. Carefully lift the BIB board from the enclosure. In doing so, you will detach the
connector on the back of the BIB that connects the BIB to the underlying Input/Output
board. The IOB is hidden from view by the rear access panel; only the IOB connector
that fits through a cutout in the rear access panel is visible when the BIB is removed.
5. Remove the new BIB from its packaging and attach it to the rear access panel with the
three screws removed in step 3.
6. Replace the connections to TB1, TB2, TB3 and TB4.
7. Replace the rear cover on the transmitter.

November 2010 Page 31 Section 4


IB1008 Rev. 03 LEFM 2xxCi Approvals – Installation and Safe Operation Manual
This is an ATEX/HAZ-LOC Document

Figure 4.5: Rear Cover Removal

Figure 4.6: Backplane Interface Board (BIB) Removal

Section 4 Page 32 November 2010


LEFM 2xxCi Approvals – Installation and Safe Operation Manual IB1008 Rev. 03
This is an ATEX/HAZ-LOC Document
Acoustic Processor Board (IOB, CTC & MXR) Replacement

Never open the transmitter when the instrument is energized. Before


inspecting components, open the power supply circuit breaker. Failure to do
so may result in electrical shock and/or an explosion if in a hazardous area.
WARNING

The transmitter has a real time clock that has battery backup. It is
recommended to replace the complete circuit board if the battery ever fails.
Do not replace the battery alone. It must be replaced with the identical
WARNING battery (Panasonic CR1632 coin battery) and it must never be changed in a
hazardous location area.

Wear an ESD protective wrist strap to avoid damaging any components.

CAUTION

1. Remove the rear cover from the transmitter and remove the backplane interface board
(BIB) according to the procedure above. The BIB has incoming power protection circuits
that could possibly be damaged by extreme power excursions.
2. Place the BIB in an ESD resistant jacket/packaging and store it in a safe location.
3. Push site cabling aside as required. (Note: It is assumed that the conduit and site cabling
will be installed.) Remove the three hex standoffs holding the rear access panel in place
(Figure 4.7) and lift the panel from the enclosure. The three acoustic processing boards
(IOB, CTC, and MXR as installed left to right) are now visible.
4. Identify the board requiring replacement. The end of the board farthest from the operator
is attached to a connector deep inside the transmitter body. To remove a board, simply
grasp the board and gently pull in a back-and-forth motion until it releases from the
connector (Figure 4.8).

Note the orientation of the board removed, as the new board must be inserted in the same
position, since the connector is keyed.

5. Remove the new board from its packaging, determine the proper orientation for
installation, and carefully guide it into the connector inside the transmitter.
6. Repeat steps 4 and 5 if necessary, to install multiple boards.
7. Carefully replace the rear access panel that was removed in step 3, adjusting the position
of the interior boards as necessary until the rear access panel fits snugly against them.
When the rear access panel is positioned properly, the middle and bottom interior boards
(the CTC and MXR boards) will lock into the thin cutouts in the rear access panel.
8. Re-install the three hex standoffs in the rear access panel.
9. Replace the BIB and attach it to the rear access panel with the three screws removed in step 1.
10. Replace the connections to TB1, TB2, TB3 and TB4.
11. Replace the rear cover on the transmitter. Tighten securely.

November 2010 Page 33 Section 4


IB1008 Rev. 03 LEFM 2xxCi Approvals – Installation and Safe Operation Manual
This is an ATEX/HAZ-LOC Document

Figure 4.7: Rear Access Panel Removal

Figure 4.8: IOB, CTC, MXR Board Removal

Following replacement of the CTC board, the “safe mode” readout may
appear in the transmitter display. This is an indicator that the configuration
data has not been uploaded to the transmitter. See Error! Reference source not
CAUTION found. in the LEFMLink (or PocketLink) manual, for downloading the
configuration file.

Section 4 Page 34 November 2010


LEFM 2xxCi Approvals – Installation and Safe Operation Manual IB1008 Rev. 03
This is an ATEX/HAZ-LOC Document
Transducer Installation

Never open the manifold when the instrument is energized. Before


inspecting components, open the power supply circuit breaker. Failure to do
so may result in electrical shock and/or an explosion.
WARNING

If re-installing the manifold cover, all socket head screws must be installed
with a torque of 30 in-lbs (3.4nm).

WARNING

1. Power down the LEFM and disconnect the failed transducer from the terminals in the
junction box (note upstream and downstream junction boxes).
2. Remove the M8 socket head screws from the manifold cover and remove the manifold
cover to reveal the transducer internals.

Figure 4.2: Manifold Cover Removal (Installation) – M8 Fasteners Shown

November 2010 Page 35 Section 4


IB1008 Rev. 03 LEFM 2xxCi Approvals – Installation and Safe Operation Manual
This is an ATEX/HAZ-LOC Document

Temperature Sensor

Manifold Cover Fasteners – M8

For carbon
steel meter
bodies (model
9A-202B761-
Transducer Z-Dxx-C) all
unpainted
Spacer Spring surfaces shall
Manifold Cover Manifold have lithium
Cover Compression grease.
O-ring Screw
Figure 4.3: Transducer Replacement
3. Remove the socket head screws from the manifold cover and remove the manifold cover
to reveal the transducer internals.
4. Remove the transducer internals using an O-ratchet T-socket head (½-in. socket for the
½-in. or 12.5-mm transducer housing and ¾-in. socket for the 1-in. or 25-mm transducer
housing).
5. Replace the transducer.
6. Verify the transducer housing is clean and free from dirt.
7. Re-install the transducer internals as follows.
a. Thread the wires of the transducer though the compression spring and the spacer.
b. Apply silicone lubricant to the transducer face or metal foil for cryogenic/high
temperature applications.
c. Insert the transducer and components into the housing until the parts bottom out.
d. Route the wires though the compression screw and then apply lubricant to the threads.
e. Screw into the transducer housing and tighten. This will load the compression spring.
8. Connect the new transducer to the terminals.
9. Re-install the manifold and junction box cover, if applicable.
10. Torque the socket head screws to 30 in-lbs (3.4 nm).

Section 4 Page 36 November 2010


LEFM 2xxCi Approvals – Installation and Safe Operation Manual IB1008 Rev. 03
This is an ATEX/HAZ-LOC Document

Appendix A

ATEX Certifications (Document IB1008-A)


The following ATEX certifications describe the conditions for safe use of the meter manifold
and the transmitter. The temperature ranges listed are for the enclosures indicated on the
certificate. The temperature limit of the meter assembly is dependent on the temperature
limits for the components used to connect the meter to the electronics. Components with
temperature limits that are more stringent than those of the meter assembly may limit the
temperatures under which the assembled meter may be operated safely. See the meter
nameplate for the temperature limit of an assembled system.

November 2010 Page 37 Appendix A


This is an ATEX/HAZ-LOC Document
WARRANTY - LIMITATION OF LIABILITY: Seller warrants only title to the products,
software, supplies and materials and that, except as to software, the same are free from
defects in workmanship and materials for a period of one (1) year from the date of delivery.
Seller does not warranty that software is free from error or that software will run in an
uninterrupted fashion. Seller provides all software "as is". THERE ARE NO
WARRANTIES, EXPRESS OR IMPLIED, OF MERCHANTABILITY, FITNESS OR
OTHERWISE WHICH EXTEND BEYOND THOSE STATED IN THE IMMEDIATELY
PRECEDING SENTENCE. Seller's liability and Buyer's exclusive remedy in any case of
action (whether in contract, tort, breach of warranty or otherwise) arising out of the sale or
use of any products, software, supplies, or materials is expressly limited to the replacement
of such products, software, supplies, or materials on their return to Seller or, at Seller's
option, to the allowance to the customer of credit for the cost of such items. In no event shall
Seller be liable for special, incidental, indirect, punitive or consequential damages. Seller
does not warrant in any way products, software, supplies and materials not manufactured by
Seller, and such will be sold only with the warranties that are given by the manufacturer
thereof. Seller will pass only through to its purchaser of such items the warranty granted to it
by the manufacturer.
Caldon Ultrasonics
Customer Service & Technical Support

1000 McClaren Woods Drive


Coraopolis, PA 15108 USA
Tel 724-273-9300

The ultrasonic measurement


group of Cameron

www.c-a-m.com

You might also like