You are on page 1of 59
© @% D779 MiniPurge® Manual ML 433 Important Note: It is essential for safety that the installer and user of the Expo system follow these instructions. Please refer to the standard for principles and definition. These instructions apply only to the pressurizing system. it is the responsibility of the manufacturer of the pressurized enclosure to provide instructions for the enclosure. Expo Technologies reserves the right to replace any component, with one ofthe equivalent functonalty M433 | v8 2eFeb-tT Section 1: System Specification MiniPurge® Control Unit Data - Reliof Valve Unit and Purge Outlet Valve with integral spark arrestor... Section 2: Quick User Guide Installation .. Operation of the System Section 3: Application Suitability Section 4: Description and Principle of Operation Section 5: Main Components Air Supply Filter / Regulator. Logic Air Supply Regulater... Minimum Pressure Sensor... Purge Flow Sensor Purge Timer Purge Complete Valve OR Gate Alarm Only Circuit (AO) Visual Indicators Power Interlock Switch ...... Alarm / Pressurized Switch... Purge Valve Purge Flow Restrictor CLAPS Sensor CLAPS Regulator Relief Valve Unit IPA Terminal Box. Section 6; Installation of the System.. Relief Valve Unit Air Supply Quality Pipe Work Multiple Enclosures Provision and Installation of Alarm Devices Power Supplies and their Isolation Power Interlock Switch Section 7: Commissioning .. Commissioning the System Normal Operation Section 8: Maintenance of the System... ssesesesnee 1 General maintenance 13 Additional maintenance checks.... stntntintsesenereinnetntntntatsenesesereneneees 13 Re-calibration of the Relief Valve Unit 13 Re-calibration of the Pressure Sensors .....sscitsitstieseneseesinnetintststntvese 14 Section 9: Fault Finding. 14 General Information 14 System purges correctly but trips and auto re-purges at the end of the purge time... 15 Relief Valve opens (continuously or intermittently) 15 System enters purging but purge indication does not occur. 16 Section 10: Recommended Spares List. 16 Section 11: Glossary.. Section 12: Drawings and Diagram: Section 13: Certifications... ML433 | vai i Section 1: System Specification 3X LCI ss/OV/ PC / PAIDI79 size PA = Power and Alarm Switches. 3= MiniPurge® Integral IPA Terminal Box Purge flow rate: 1500 Ni/min PC = Pressurized Control. Automatic leakage compensation (CLAPS} Approval / Certification 398 compensation (CLAPS) ATEX Certificate: ‘Sira 01ATEX1295X OV = Purge Outlet Valve is C€ 0518 © 1122) 60 pneumatically operated Ex [pxb] IIC TS Gb Ex [pxb] IIIC T85°C Db MiniPurge® Housing Tamp “20°C to +55°C 88 = Stainless Steel 316L IECEx Certificate: IECEx SIRO7.0027x Ex [pxb] IC T6 Gb Ex [pxb] IIIC T85°C Db Tamp -20°C to +55°C Pressurization Method LC = Leakage Compensation TUV INMETRO Certificate: TOV 12.1462x Ex [pxb] IC T6 Gb Ex [pxb] IIIC T85°C Db Tamb -20°C to +55°C ML433 | vai Page 1 MiniPurge® Control Unit Data Action on Pressure Failure: Type of Operation: Leakage Compensation Capacity: Enclosure Material: Mounting Method: Temperature Limits: Compressed Air Supply: Supply Pressure Main Regulator: Logic Regulator and Gauge: Process Connections: Visual Indicators: JPA Terminal Box: Power Interlock Switch: Alarm Switch: Minimum Pressure Sensor: Purge Flow Sensor: CLAPS Sensor: Alarm and Trip (isolate power to pressurized enclosure), user adjustable Alarm Only. ‘Automatic leakage compensation using the Closed Loop Automatic Pressurization System (CLAPS System) 500 Ni/min initial maximum pressurized enclosure leakage. Stainless Steel 316L. Wall mounting straps. Fixing holes as per drawing, -20°C to +55°C Clean, dry, oil free air or inert gas. Refer to Air Supply Quality section in installation of the System. 4 to 8 barg (60 to 120 psi). Set at 4 barg, 40 um automatic drain supply inlet filter. Fitted and set to 2.3 barg (33 psi). Purge supply and outlet to pressurized enclosure ‘/2’ NPT female. Minimum supply line 13 mm (“/2) ID tube, inlet sized appropriately for flow rate. Reference points & signals ‘/g’ NPT female, minimum 6 mm pipe to be used. Alarm (Red@) / Pressurized (Green@). System Purging (Yellow@). Glass reinforced polyester box with terminals and accessible cable glands. Certified to 2 Watts power dissipation: Ex e IIC T6 Gb / Ex tb IIIC T85°C Db IP67 Tamb : -65°C to +55°C. DPNO switch, contact ratings 250 Vac 4 Amps (AC-15) / 24V DC 4A, Exd IIC T6 Gb / Ex th IIIC T80°C Db. SPCO switch, contactratings 250 Vac4 Amps (AC-15)/24VDC4A, Ex d IIC T6 Gb / Ex tb IIIC T80°C Db. Minimum: 0.5 mbarg. Maximum: 5.0 mbarg, Default Setting: 1.5 mbarg. Tolerance -0, +0.7 mbarg. Set at 6.4 mbarg (Tolerance: -0, +10%). Minimum: 6.0 mbarg. Maximum:15 mbarg. Default Setting: 10 mbarg. Tolerance: -0, +10% Note: there must be a 2.5 mbarg difference between the intermediate and CLAPS sensor calibration point. For example: Minimum pressure = 5 mbarg, intermediate pressure = 6.5 mbarg, CLAPS sensor = 9 mbarg. Purge Time Weight: User selectable, 3-off time increments available. 10, 15 or 20 Minutes (-0 + 25%). Maximum available purge time of 45 minutes. Default Setting 45 minutes. 16 kg (351b) Relief Valve Unit and Purge Outlet Valve with integral spark arrestor Type: Page 2 RLV52iss/FS, Design number D779RLV. ML433 | véi Bore: Purge Outlet Valve @ 52 mm, Relief Valve @ 52 mm. Relief Valve Lif-Off Pressure: Minimum: 20 mbarg. Maximum: 50 mbarg. Default: 30 mbarg (+0, -20%). Flow Rate: Range: 1000 or 1500 Ni/min Default: 1500 Ni/min. Material: Housing: Stainless steel 316L. Gasket: Silicone. Spark arrestor: Stainless steel mesh. Mounting Method Rectangular cut-out and fixing holes as per drawing, Weight: 4 kg (8.8 Ib) Section 2: Quick User Guide Installation The MiniPurge® system must be installed by a competent engineer, in accordance with relevant standards, such as IEC / EN 60079-14 and any local codes or practice. + Mount the purge system in accordance with the hook-up drawing. + Ensure the system js installed according to the full instructions in the “Installation of the System” section of this manual. + Allpipings must be clean and free of dirt, condensation and debris prior to connection to the purge system or pressurized enclosure. + Itis strongly recommended that a local isolation valve is installed on the air supply upstream of the purge system. Note: Most faults are due to restricted air supply, Inadequate supply pipe work or drop in air supply pressure during the purge process. Operation of the System Once the system is installed correctly, turn on the air supply. Refer to Commissioning section. Indicator Colour Status Alarm / Pressurized Red @ Low pressure alarm (enclosure pressure too low) Purging Black @ Purge flow too low or not in purge mode The purge system commences the purge cycle: + The purge air will enter the enclosure + The pressurized enclosure will obtain a positive pressure. + The Purge Outlet Valve will open within the Relief Valve Unit. + The air will then exit the Relief Valve Unit housing via the spark arrestor. Indicator Colour Status ‘Alarm / Pressurized Green @ _| Pressurized (minimum enclosure pressure achieved) Purging Black @ | Purge flow too low ML433 | vai Page 3 Open the Purge Flow Restrictor Valve until the air flow reaches the required rate; the system will initiate the timed purge cycle. Start a stopwatch when the purging indicator turns yellow. Indicator Colour Status Alarm / Pressurized | Green @ Pressurized Purging Yellow @ Purge flow rate above minimum On completion of an uninterrupted purge cycle of the required length, the system will indicate purge complete. Stop the stopwatch when the purging indicator turns black Indicator Colour Status ‘Alarm / Pressurized Green @ —_| Pressurized and in leakage compensation mode Purging Black @ | No longer in purge mode Check stopwatch timing to verify that the actual purge time is equal to or greater than the required purge time. Note: The recorded purge time must never be less than the required purge time. ‘The system is now operating correctly in leakage compensation mode, If the system has not performed as expected, check the installation thoroughly and ensure it has been carried out according to the instructions. If an obvious problem has not been highlighted and corrected, follow the procedures in the Fault Finding section. Ifall checks have been carried out and the system stil does not perform as expected, contact your local distributor or Expo Technologies. Page 4 ML433 | véi Section 3: Application Suitability MiniPurge® systems are certified for use in hazardous locations, where the hazardous location is non- mining (above ground) and the hazard is caused by flammable gasses, vapours or dust. Depending on the model the systems may be used in IECEx and ATEX Zone 1(21) and/or Zone 2(22) - Categories 2 and 3 respectively MiniPurge® systems may be used for hazards of any gas group. Apparatus associated with the MiniPurge® system, such as intrinsically safe signalling circuits and flameproof enclosures containing switching devices may be limited in their gas group. The certification documentation supplied with any such devices must be checked to ensure their suitability, This system is primarily designed for use with compressed air. Where other inert compressed gasses are used (Nitrogen, for example) the user must take suitable precautions so that the build up of the inert gas does not present a hazard to health. Consult the Control of Substances Hazardous to Health (COSHH) data sheet for the gas used. Where a risk of asphyxiation exists, a warning label must be fitted to the pressurized enclosure, The following materials are used in the construction of MiniPurge® systems. If substances that will adversely affect any of these materials are present in the surrounding environment, please consult Expo Technologies for further guidance. Materials of Construction Stainless Steel ‘Aluminium Acrylic Mild (Carbon) Steel Nylon Silicone Brass Polyurethane Neoprene ABS Polycarbonate Polyester (glass filled) Section 4: Description and Principle of Operation The MiniPurge® system is pneumatic in operation, with electrical interfaces. Purge and pressurization is a method of protection used in Zone 1 (21) and/or Zone 2 (22) hazardous locations to ensure that the interior of an enclosure is free of flammable gas. Addition of a MiniPurge” system allows the electrical equipment within the enclosure to be used safely in a hazardous location. The principle of purge and pressurization is as follows: + Clean compressed air or inert gas is drawn from a non-hazardous location. + The interior of the pressurized enclosure is flushed to remove any hazardous gas or dust. + This is introduced into the pressurized enclosure to keep the internal pressure at least 0.5 mbarg above the external pressure. + Whilst pressurized, flammable gas cannot enter the enclosure from the environment. Prior to switching on the power to the electrical equipment, the enclosure must be purged to remove any flammable gas that might have entered the enclosure before pressurization. Purging is the process of removal contaminated air and replacement with air (or inert gas) known to be free from flammable gas. The duration of this purge process is normally ascertained by performing a purge test At the end of the purge cycle the system automatically switches to leakage compensation mode. The Purge Outlet Valve is closed and the airflow is reduced but remains high enough to compensate for the leakage of air from the enclosure whilst maintaining the minimum over pressure state. In the event of pressure failure within the pressurized enclosure the system will raise an alarm in the form of visual indicators and a volt free contact depending on the specification of the system. The default action ML433 | vai Pages on loss of pressurization is alarm and automatic disconnect of power (A&T - Alarm and Trip). This can be changed by the customer to Alarm Only (/AO), please refer to section tiled Main Components. ‘The MiniPurge® system incorporates a Closed Loop Automatic Pressurization System (CLAPS). This allows the system to detect a rise or fall of the enclosure’s internal pressure and adjust the leakage compensation rate accordingly. Pressure variations are more likely during sudden start up of large rotating electrical machines but can also be caused by changes in running temperature. This system has been specifically designed to maintain a stable intemal pressure within the enclosure. Pressure characteristics during purge and pressurization of a pressurised enclosure using a MiniPurge® system that incorporates a CLAPS system: Powor interlock switeh \ Minin pressure sitch LAPS Regulator | Pressure fe or presse sens sends ‘stm 'neator ahows re alm oa} Alm tnictor shows td and poor” (3 isconnectod (Alarm and Tip) "Sensor Pressure Farge Tens) (RCA S (Normal Opwraion) (Faun Condton eer perm (Cope Tins) “outside of CLAPS re Section 5: Main Components Air Supply Filter / Regulator The unit is provided with a 40 um liquid / dust filter element as a precaution. The user of the MiniPurge® system must ensure that air supply is to the quality stated in Air Supply Quality paragraph found in the Installation of the System section. The regulator is factory set to 4 barg (60 psig) and regulates the pressure of an air supply between 4 and 8 barg (60 to 120 psig). A pressure gauge is fitted down stream of the fitter; this should indicate no less than 4 barg (60 psig). During the purge cycle a pressure drop will be indicated on the gauge. Logic Air Supply Regulator This device provides the system with a stable air supply pressure to the logic system and allows consistent operation. The pressure level is factory set to 2.3 barg (33 psig) and can be verified by means of the integral pressure gauge. Minimum Pressure Sensor This monitors the pressure inside the pressurized enclosure. When the pressure is below the minimum required for safe operation, the pressure sensor causes the system to reset and the Alarm / Pressurized indicator turns Red @. The sensor is factory calibrated and set to operate in falling pressure at or above the minimum specified pressure. Page o ML433 | véi Purge Flow Sensor The Purge Flow Sensor monitors flow through the Purge Outlet Valve. At correct purge flow rates, above the minimum specified for purging, the sensor sends a signal that activates the purge timer. This sensor is factory calibrated to operate on falling flow rate at or above the minimum specified purge flow rate. Purge Timer When both the enclosure pressure and the purge flow rate are correct, the Purge Flow Sensor activates the timer to start the timing period. The purge time is set by opening/closing the pinch valve so that the sum of the open valves times equals or exceeds the required purge time. At least one valve must be open, and the screws must be at the appropriate limit of travel. Do not over tighten. The purging indicator will turn yellow during timing Purge Complete Valve This valve receives a signal from the purge timer that indicates the completion of the purge cycle and verifies that the pressurization signal is still present. If both conditions are satisfied a signal is sent to indicate that the purge is complete. This performs two functions: to tum on the electrical supply to the pressurized enclosure and to reduce the high purge flow rate to leakage compensation mode. It also provides a hold-on signal that maintains the leakage compensation mode with the power switch on, even when the purge timer has reset ready for the next purge cycle. OR Gate This device provides the Purge Complete Valve with the hold-on function referred to previously. When either the timed-out signal or the purge complete signal is present it allows the pilot signal to be sent to the purge complete valve. Alarm Only Circuit (/AO) If the pressure in the pressurized enclosure is too low the system will normally cut off electrical power to it. In certain circumstances, where local codes of practice allow, the system can be altered to provide a hold- on circuit that will maintain the electrical power supply to the pressurized enclosure while also providing a pressure failure alarm. The user must respond to the alarm and either restore the pressure to the pressurized enclosure or otherwise make the installation safe; for example, cut off the electrical supply. The decision to use the Alarm Only facility, and the allowable length of time for non-pressurized operation, is the responsibility of the user. Warning: It is potentially dangerous to energise the pressurized enclosure in an non-pressurized condition when it is known that there is potentially explosive gas or dust in the hazardous location. Visual Indicators Visual indicators are fitted to provide status information to the operator. Alarm / Pressurized Indicator Green" @ Pressurized Red @ Pressure Alarm (enclosure pressure low) ‘System Purging Indicator Black” @ Purge flow too low (not in purge mode) Yellow @ Purging (flow above minimum) * The Green @/ Black @ combination indicates normal operation of the pressurized enclosure after the initial purging cycle has been completed ML433 | vai Page7 Power Interlock Switch This flameproof power switch is activated by the signal from the Purge Complete Valve. This activation can be used to tum on the electrical supply to the pressurized enclosure. The cable from the switch is terminated in the /PA terminal box. Alarm / Pressurized Switch This flameproof switch is operated by the pressurized signal. It allows a remote electrical system status indicator to show either pressurized or a pressure failure alarm. The cable from the switch is terminated in the /PA terminal box. Purge Valve This changeover valve selects between purge air flow or leakage compensation. Itis sized to allow sufficient air into the enclosure during purging based on: the specified air supply pressure range, the minimum specified purging outlet flow rate +10% and the expected leakage rate from the pressurized enclosure. At the end of the purge cycle, the purge valve closes in response to the “Purge Complete” signal, it remains in the closed position until the next purge cycle is initiated. Purge Flow Restrictor This valve restricts the purge flow to the minimum required flow rate. The Purge Flow Restrictor must be readjusted during commissioning. CLAPS Sensor This sensor monitors the pressure within the pressurized enclosure and sends a control signal to the CLAPS Regulator. The normal running pressure must be determined prior to system start-up so that the CLAPS Sensor may be set to the level required to control the CLAPS Regulator. CLAPS Regulator This is the regulator that controls the leakage compensation air flow into the enclosure after the purging is complete. It either increases or decreases the air flow into the enclosure as appropriate to maintain a stable Tunning pressure. The CLAPS Regulator must be set at the time of commissioning. Relief Valve Unit ‘The Relief Valve Unit allows the purge air to exit the enclosure safely via a built-in spark arrestor. This spark arrestor is designed to prevent the emission of arcs, sparks and incandescent particles produced within the pressurized enclosure Purge air passes through the Relief Valve Unit; the preset pressure differential across the appropriate orifice ensures that the purge flow sensor is activated once the selected purge flow has been attained. During the purge cycle a pneumatic cylinder operates the Purge Outlet Valve that lets the air from inside the enclosure exhaust through the Relief Valve Unit. When the system changes to leakage compensation mode, the Purge Outlet Valve is closed and the enclosure sealed ‘The Relief Valve Unit has an in-built relief valve. This is sized to ensure that, if the air supply pressure rises up from the specified maximum, the internal enclosure pressure will not exceed the specified maximum. working pressure of the pressurized enclosure. IPA Terminal Box ‘The Terminal Box is increased safety (Ex e) certified and incorporates the terminal connection points for the alarm and interlock switches. All contacts provided are volt free (dry), Page 8 ML433 | véi Cable entry methods (for example conduit or cable glands) must be certified to IECEx, ATEX or INMETRO standards. The main requirement is that IP66 (or better) ingress protection must be provided by use of seals or washers. Section 6: Installation of the System The MiniPurge® is designed for use under normal industrial conditions of ambient temperature, humidity and vibration, Please consult Expo before installing this equipment in conditions thet may cause stresses beyond normal industrial conditions. The MiniPurge® system must be installed by a competent person in accordance with relevant standards, such as IEC / EN 60079-14, and any local codes of practice. The MiniPurge® control unit should be installed either directly on, or close to the pressurized enclosure. It should be installed such that the system indicators and certification labels are in view. All parts of the system carry a common serial number. If installing more than one system, ensure that this, ‘commonality is maintained within each system installed Relief Valve Unit To achieve effective purging, the points where air enters and exits the pressurized enclosure should normally be at opposite ends of the enclosure. The RLV unit must be mounted vertically and there should bea minimum clearance of 300 mm (12") around the spark arrestor (purge outlet) It is important that the interior and exterior of the spark arrestor is kept clean and debris is not allowed to accumulate; this might affect the calibration of the device. In particular the exterior of the spark arrestor should not be painted or blocked in any way. Air Supply Quality The MiniPurge® system should be connected to a protective gas supply, which is suitable for purging and pressurization. The supply pipe connection to the MiniPurge® must be appropriate for the maximum input flow rate for the application The air supply must be regulated at a pressure less than the maximum stated inlet pressure. The air supply must be: clean, non-flammable and from a non-hazardous location. The air should be of Instrument Air Quality. Although the purge control system will operate with lower air quality, its operational life will be adversely affected. The equipment that is being protected by the MiniPurge® may also suffer because of poor air quality With reference to BS ISO 8573-1: 2010, Instrument Air is typically specified as: Particle Class 1 In each cubic metre of compressed air, the particulate count should not exceed 20,000 particles in the 0.1 to 0.5 micron size range, 400 particles in the 0.5 to 1 micron size range and 10 particles in the 1 to 5 micron size range. Humidity or pressure dew point The dew point, at line pressure, shall be at least 10 °C below the minimum local recorded ambient temperature at the plant site. In no case, should the dew point at line pressure exceed +3 °C. Oil Class 2 In each cubic metre of compressed air, not more than 0.1mg of oil is allowed. This is @ total level for liquid oil, oil aerosol and oil vapour. ML433 | vai Page ‘When an inert gas is being used to supply the purge system, risk of asphyxiation exists. Refer to Application Suitability section. Before connection of the air supply to the purge system, the supply pipe work should be flushed through with instrument quality air to remove any debris that may remain in the pipes. This must be carried out for at least 10 seconds for every meter of supply pipe. Unless a supply shut-off valve has been fitted to the MiniPurge® system, an external shut-off valve with the same, or larger, thread size as the Control Unit inlet fitting should be fitted by the installer to prevent any restriction of purge flow. The purge air from the MiniPurge® Control Unit should be piped within the pressurized enclosure to ensure purging of potential dead air spots. The purge system is fitted with an internal regulator factory set to 3 bar feeding the logic. Pipe Work If the MiniPurge® is not connected directly to the pressurized enclosure, pipe work and fittings used to connect the Control Unit to the pressurized enclosure should be either metallic or appropriate to the environment into which the system is installed. No valve may be fitted in any signal pipe connecting the Control Unit to the pressurized enclosure. This pipe work must be fitted in accordance with local codes of practice where relevant. Multiple Enclosures This system is suitable for the purge and pressurization of the primary pressurized enclosure and its associated terminal boxes. Provision and Installation of Alarm Devices When the pressure inside the pressurized enclosure is above the minimum, the Minimum Pressure Sensor returns a positive (pressurized) signal causing the alarm indicator on the control unit to change from red to green. ‘When the pressure falls below the minimum permissible the positive (pressurized) signal is removed. This absence of signal indicates a low pressure alarm condition and causes the alarm indicator on the control Unit to go from green to red. ‘There are volt free (dry) contacts available within the terminal box for remote usage. ‘The user must make use of this alarm facility in accordance with the local code of practice for Action on Pres- sure or Flow Failure. Most codes include the following recommendations: + Zone 1 Installations: Alarm and Automatic Trip of Power. + Zone 2 Installations: Alarm Only on pressure or flow failure with power being removed manually. Power Supplies and their Isolation All power entering the pressurized enclosure should have a means of isolation. This requirement also applies to any external power sources that are connected to the equipment such as volt-free (dry) contacts within the pressurized enclosure. This is commonly achieved using the Power Interlock Switch. Power Interlock Switch This switch is a Double Pole Normally Open, double-break switch: it provides two independent contacts that should be connected in series and used to isolate the power. This can be achieved using switchgear or other suitable switching device. These contacts are terminated and accessible to the user in the Ex e terminal box. Itis the responsibility of the user to ensure that the switch is only operated within appropriate technical limits. Page 10 ML433 | véi The switch must be replaced after any short circuit that occurs within the main circuit; the switch is a piece of encapsulated equipment and as such it is not possible to check the state of the contacts. Technical modifications to the switch are not permitted. Prior to commissioning, check that the Ex e terminal box is clean, the connections have been made properly, the cables laid correctly and all screws in the terminals are secure. In all cases the application and isolation of power must be controlled by the MiniPurge® system using the power interlock signal. No switches are permitted between the power switch and the MiniPurg manual override circuit. system other than an authorized The safe use of this switch is the responsibility of the user, all electrical installations must conform to local codes of practice. Exception Power to apparatus that is already suitable for use in hazardous locations need not be isolated by the MiniPurge® system, Section 7: Commissioning Commissioning the System Note: The steps 11 and 15 to 21 represent detailed commissioning tests The following equipment is needed for this process: = Continuity meter = Gauge manometer (0 to 200 mbarg) + Differential manometer If, after commissioning, the system does not perform as expected, refer to the Fault Finding Section. Follow the steps as outlined: 1, Check all connections and that the Relief Valve Unit is fitted correctly with an unobstructed path to the purge exhaust. Close the Purge Flow Restriclor Valve. Fully open external supply shut-off valve where fitted Check that the internal logic pressure gauge reads 2.3 barg / 33 psi / 230 kPag Check that the pressure gauge on main air supply reads 4 barg / 60 psi / 400 kPag. Check that the Pressure Relief Valve is correctly set by disconnecting the minimum pressure sensing pipe at the bulkhead fitting on the input to the MiniPurge®. This will disable all of the pressure sensors. + Using a4 mm nylon tube, connect a manometer to the bulkhead fitting from which the minimum pressure sensing pipe was removed. + Open the Purge Flow Restrictor Valve very slowly, until the Pressure Relief Valve opens + Check the opening pressure is within calibration limits. Sa kON + This test can be carried out several times to ensure repeatability and compliance. Refer to the Maintenance of the System section if the Relief Valve needs recalibrating. 7. Close the Purge Flow Restrictor Valve. 8. Remove the manometer and reconnect the minimum pressure sensing pipe to the bulkhead fitting. 9. Remove red plug from the top of the Minimum Pressure Sensor and connect a gauge manometer. 10.Connect a differential manometer to the test points on the flow sensor. ML433 | vai Page 11 11.To check sensor calibration + The internal pressure in the pressurized enclosure must be below Relief Valve lift off pressure and above the CLAPS pressure + At this time the pressurized indicator should be green. + gradually open Purge Flow Restrictor Valve until purging indicator turns yellow. Note: For large volumes it may take a long time for the purge flow to start. + very slowly close Purge Fiow Restrictor Valve until the purging indicator turns back to black. + Take a reading from pressure gauge. 12.To set the purge flow rate: + Turn on the compressed air to the MiniPurge®. + Gradually open the Purge Flow Restrictor Valve until the black / yellow indicator changes to yellow. + The yellow indicator confirms the correct flow rate. + The differential pressure should be greater than 6.4 mbarg. + The relief valve is supplied with different orifice plates for the specified flow rate. This orifice plate is held in position by two M3 screws and can easily be changed by removing the large cover plate from over the outlet valve assembly and screws. Warning: When opening the Purge Flow Restrictor Valve, ensure the over pressure within the pres- surized enclosure does not exceed the pressure relief vaive setting. 13.The purge timer will start as soon as the Purging Indicator turns yellow. Check that the time delay between the indicator turning to yellow and returning to black is not less than the minimum time required for complete purging of the pressurized enclosure. Times in excess of minimum are permitted. 14.After the purge has been completed, the Purge Valve will close and the air flow into the pressurized enclosure will be controlled by the CLAPS Regulator. The initial setting may be too high or too low. 15.Gradually turn the CLAPS Regulator anti-clockwise to reduce enclosure pressure. 16.Reduce regulator until intermediate sensor causes contacts to open. 17.Check the manometer on the minimum pressure sensor. 18.Continue to reduce the CLAPS Regulator to test the minimum pressure sensor. 19.To check operation of Minimum Pressure Sensor, check readings on manometer as system will automatically re-purge when it reaches minimum pressure. 20.While the system re-purges, return the CLAPS Regulator to the initial setting. 21./f minimum pressure is below the set point, refer to the Recalibration section 2.1 the setting is too high, continual rising and falling of the enclosure pressure will be seen as the CLAPS Regulator automatically shuts off and reinstates the flow. The CLAPS Regulator should be adjusted to reduce the flow into the pressurized enclosure by turning the adjuster screw anti-clockwise. 23.If the initial setting is too low the CLAPS Regulator may not provide enough air flow causing a gradual decline in enclosure pressure. To increase the flow into the pressurized enclosure, adjust the CLAPS Regulator Relief Valve unit by turning the adjuster screw clockwise. 24.To test the CLAPS settings, create a leak in the system by removing a bolt or losening a gland plate in order to create a 15mm hole. Remember to replace bolt or retighten gland plate after testing 25.The setting of the CLAPS Sensor is factory calibrated to the normal working pressure expected in the pressurized enclosure, typically 10 mbarg. The pressure in the pressurized enclosure should be stabilized as close as possible to this figure. This can be checked by a manometer attached to the minimum pressure sensor. 26.Remove the air supply to the system, remove all test equipment and replace all plugs. Page 12 ML433 | véi Normal Operation For normal operation of the system, after commissioning has been carried out it is possible to turn the air supply valve on or off to start or stop the system. After this, the purge and pressurization sequence is automatic. Section 8: Maintenance of the System General maintenance The maintenance of the system outlined in this manual should be supplemented with any additional requirements set out in appropriate local codes of practice. The following checks should be carried out every 6 - 36 months dependent on environment according to IEC / EN 60079-17 + Tests outlined in the Detailed Commissioning section. + Ensure that the Relief Valve Unit is free from contamination prior to making any adjustment. To do this: + Remove large cover plate using a 8 mm spanner (wrench). + Check that the interior and all components are clean and free from contamination. + Replace large cover plate. + Check the condition of the air supply filter element. Clean or replace as necessary. Additional maintenance checks The following additional checks are recommended at least every 3 years: Cheek that: + Apparatus is suitable for use in the hazardous location. + There are no unauthorised modifications. + The air supply is uncontaminated. + The interlocks and alarms function correctly. + Approval labels are legible and undamaged. + Adequate spares are carried. + The action on pressure failure is correct. Re-calibration of the Relief Valve Unit Warning Incorrect adjustment of the Relief Valve Unit can lead to significant over pressure and result in damage to the enclosure. If maximum pressure setting Is reached, stop adjustment and reduce the pressure. To perform the following adjustments, an 8 mm spanner (wrench) and a 2.5 mm hex key will be required Ensure that the Relief Valve Unit is free from contamination prior to making any adjustment. To do this: + Remove large cover plate using a 8 mm spanner (wrench), + Check that the interior and all components are clean and free from contamination. + Replace large cover plate To adjust the lift off pressure of the Relief Valve: + Attach test equipment as described in the Commissioning Section. + Remove small cover plate. + Whilst holding the central adjustment screw in position using the hex key, loosen the retaining nut. + Adjust the hex key clockwise to increase, or anti-clockwise to reduce the lift off pressure, ML433 | vai Page 13 + Before testing, retighten the locking nut whilst holding the adjustment screw in place + Carry out the commissioning tests to check the correct setting of the relief valve after adjustment + The adjustment is sensitive and it is recommended that a */, turn (maximum) adjustments are applied between tests. Allen screw and locknut Re-calibration of the Pressure Sensors ‘The brass nozzle on the sensor is sealed into position using Loctite thread sealant. If the thread has seized up, remove to a safe area and heat slightly to soften prior to making any adjustment. This prevents potential damage to the brass of the nozzle. + Disconnect pipe work from the sensor, including pipe located below the sensor. + Remove sensor by unscrewing anti-clockwise. + The nozzle is located under the sensor. + The adjustment is sensitive, turn the nozzle in '/g of a turn steps. + Turn clockwise to reduce the pressure setting and anti-clockwise to increase. = Replace sensor, screwing clockwise. + Reconnect all pipe work Section 9: Fault Finding General Information Ifyou are having problems that cannot be corrected using one of the methods described, please call Expo or your supplier for further assistance. If the system is less than 12 months old, parts under warranty should be returned to Expo for investigation. A full report of the fault and the system serial number should accompany the parts. Itis common for problems with the MiniPurge® system to be caused by contamination of the air supply with cil, water or dirt, To prevent these problems, the air supply must contain a dust filter and a water filter. This will ensure that the air is instrument quality and protect both the purge system and the equipment being purged. This filtration system is not provided by Expo and must be sourced separately. Contamination can enter the system from a number of sources. To prevent this, it is essential that the procedures described in the installation section are carried out prior to first use of the system. These procedures should also be carried out following any disconnection and re-connection of the pipe work. Failure to perform these procedures may cause damage to the system that will not be covered by the warranty. ‘The system has been designed for ease of fault finding and many of the components fitted are plug-in or chassis mounted. Check components by substitution only after establishing that such action is necessary. Before carrying out the fault finding procedures, ensure that: + Both the main air pressure to the system and for Motor Purge Systems, the regulated pressure to the logic manifold are as specified on the settings sheet, Page 14 ML433 | véi + Air pressure does not drop below the minimum supply pressure during purging: the majority of faults reported are due to insufficient air supply during the purge cycle. System purges correctly but trips and auto re-purges at the end of the purge time. This is a result of the pressure within the pressurized enclosure being below the minimum pressure sensor setting. The pressure can be checked using a manometer. The most common causes of this problem are outlined below. Fault Location Cause Solution Pressurised Enclosure There is debris on the face of the Relief Valve disk held in place by the magnet + Remove debris and ensure RLV disk is clean Enclosure leaking excessively. + Ensure all doors and covers are closed and that all conduit and cable glands are properly sealed + Seal any other leaks. Pressure sensing tube damaged, + Replace tubing. CLAPS Regulator The CLAPS Regulator setting is too low. + Increase the setting of the CLAPS regulator to raise the pressure in the pressurised enclosure after purging + Todo this, turn clockwise. MiniPurge® Control Unit the Minimum Pressure Sensor setting has drifted above the CLAPS setting The Minimum Pressure Sensor needs re-calibrating, + Refer to Re-calibration of Pressure Sensors in the Maintenance section Relief Valve opens (continuously or intermittently) Fault Location Cause Solution Pressurised Enclosure Enclosure pressure is too high due to CLAPS Regulator being open to far Adjust the CLAPS Regulator. Relief Valve Unit Debris on the Relief Valve disk allowing air to leak from the valve. Remove Relief Valve cover and clean the valve disk, ML433 | vai Page 15 System enters purging but purge indication does not occur. Fault Location Cause Solution Air Supply Insufficient flow rate due to inadequate air supply pressure. Often due to pressure drop in the supply pipe. Sialic pressure of 5 barg must be maintained during purge + Check air supply pressure at the inlet to the control unit + Ensure that the supply pipe bore is suitable for the flow rate Pressurized Enclosure Excessive leakage from the pressurized enclosure. + Check around the enclosure while purging is taking place. + Total leakage at purge outlet valve should not exceed 10% of purge flow sensor setting. + Check for leakage down cables and conduit Pipe Work Tubing from Relief Valve flow sensing point not air tight. + Ensure fitting nuts are tightened + Check for tube damage. + Repair as necessary. Relief Valve Unit Relief Valve opening during purge + Check enclosure pressure on start up is less than Relief Valve lift off pressure. MiniPurge Control Unit Flow sensor setting incorrect, + Check the pressure is correct on the flow sensor. Section 10: Recommended Spares List Part Number Description $0016/250 Filter kit for main air supply filter/regulator $0030/606 Purge flow sensor factory set to 6.4 mbarg $0030/016 Minimum Pressure sensor, must be factory set to the value as stated on the Customer Test and Inspection Sheet s0030/588 CLAPS Sensor must be factory set to the value as stated on the Customer Test and Inspection Sheet $0015/018 Pressure gauge (Air Supply Pressure), 0 - 10 barg $0015/135 Miniature gauge (Logic Pressure), 0-4 barg Note. The system's Pneumatic Timer may be replaced with the Expo Electronic Timer. Please contact Expo Technologies’ Sales Team for further details. Page 10 ML433 | véi Section 11: Glossary Acronym Definition AT Alarm and Trip AO Alarm Only CLAPS Closed Loop Automatic Pressurization System cu Control Unit, ET Electronic Timer FcV Flow Control Valve Is Intrinsically Safe Lc Leakage Compensation PA Power and Alarm RLV Relief Valve Unit Section 12: Drawings and Diagrams Title Drawing Number Number of Sheets D779 Control Unit D779-GA 2 Typical Claps Hook-up Diagram SYS-M000-007 1 P and | Diagram D779-Pl 1 Circuit Diagram AGM-PA00-019 1 D779 EEx e Box Layout AGE-WC00-120 1 Manual Override Switch Hook-up ‘AGE-WC00-117 1 ‘Size 3 MotorPurge Relief Valve XBR-RTDO-010 1 MiniPurge® X LC Sequence Diagram XBR-7TDO-040 1 System Status Indication TP-518-058-WD 1 Section 13: Certifications Download the certificates at www.expoworldwide.com/downloads. Component Certificate Number Purge System ATEX Certificate SIRA O1ATEX1295X MlU/e Ex e Terminal Box Electronic Switches ML433 | vai IECEx Certificate INMETRO/TUV Certificate ATEX Certificate IECEx Certificate Ex d limit switch Ex d limit switch IECEx SIRO7.0027X TOV 12.1462x Sira 99ATEX3173X IECEx SIR 06.0087X IECEx EPS 14.0092x EPS 14 ATEX 1766 X Page 17 z TO NER TIVES Te) snivisoMmvea Ao — ‘eouN aa ‘ear ‘aha ‘ganowad® | san Vor6HO LINN TOMLNOD 6440 cu sand Saree | ore mera] v0 aha | ovo votre [ava [oor SIN sos rove aaa PaNUUIT] SeiBojouyse) odxy SNIDER evsaval t Zz T Tear] OP] Gals co" | see) D4/no/warss/37XE “ON 7300K oF l/ — fst uietan 2 \ whos aon aM aLATON 38 SH BEATE“ 68 661+ mR aaa J : senaoul posuere an of [Seni ean nae g i ANHOTIEWEION og ouay NO MIA sd a g an ft y “|8 anwasanay woud ot a : andrea wont = in Le 3 4 ava ati og mow gs | | | ve SEE ‘No main q | q re) |b | / ee TT | || foo tyes are) L if | 4 __ = a ehhnnand rma Lewstl ob Lewelee weet tomas /30 \ uaae9 7 " MOLVDIONT ONIDUNE WELSAS \__ (nario 7.038) woLvorant : vo SEAR ean 2 (se'st] oo» C.p0'O#.9't] OO'T#9"Ty Tro 02 1] 09 19-08 sry emis nme me raguapan nc ERRa aa WR STRHSGTENETESayos tN OD f=5,@) soussoes Io a opt Smut topopaee, co © oad saownuaTo wwisnoisvana LE ony ae ML433 | véi Page 18 207 NaBH wanoisno] neon] BLV734 1430 ‘shuvis oNNvEO| yy | masa = Br] ea [wat | —carousay vorseo LINN TOULNO 6440 so sami Borsa [cree] aver | aoe vate [one [| av con SIN sos POEMSaNg Peyu seiBojouysa, odx3g awreaivn| t z “rosr] Pat | aay \WaLSAS 40 YOOG ZOISNI O3LLI4 HET NOLLYOISLIMED 2 nn span aon Fal, Panu anos LON OG. +E Nowisod 3AUMNREITY Nowsaroud “SONY IE Page 19 ML433 | vai a moe xe EV S| oa J : wa [war] ova ao LOG-O00H SAS WVYDVIO 4N-HOOH SVD WIIdAL | snl gersoni| Geran | Zon sa] ove | aw SIN sven ENS payWy SeiBojouyse, odxs swat eet “re [ove | caav caro syNourenusiou 30una-, \ \ YOLOW nse una stutd Sunseon sent non oye uo ¥57000 YOLOW unse3e ONNGO (ATS 3HL ONS HOS _ /BLV7d N3A00 TYWS- oo BATA 43173e—/ = a ae ee ML433 | véi Page 20 Geanenssreaioaew bao ONLESHS) ‘wawousn9| on gor] ‘GUN | NMA a swan 'dr6Ll0 WVBOVIC I ONY d ul a4 Bree wn ano] 7 | aw = swoel ENS paw SeiBojouyse, odxs swe Sofa Fara eae Taar ouvsnaaioo 390031 at dl sa i WOMINEM “O° [WWUOS) 2 avenassy 7 deh 2fT “T Ad ei SYD LMANE/HIY \ sersoms eon mg at ext SORT TTT aa — iputbna EE SST aT by Nousarous Page 21 ML433 | vai ve ‘amis ta] TEE TED SEO HS can S10-00vd HRY WVEB¥IO LIND oul oval exo SIN poywily seiBojouyses odxy ove| oar saniatess @ von @® MLA33 | véi Page 2 be) visas noel conser GELVBY 18D ‘shivis oxino | gy yy = “ wa] wat | ova | caousw cous] OE vixoes sul — Pal FOTIA Sve] ova] coro voor [eve | a SIN vod era PEMWIT Se[Bojouyse, odxy synsus oe oval caer mee 1 cataL¥39 S34A1 37@V0 2AILWNRAL TW {Ins 04, aul GaAOedY ATAVAINS HAIM GOV" 38 Avi SaNv19 SS3H1 S2v G=HNOMeVNON GO Wp Le300¥ ‘$318¥9 ONION 3HL wos x08 TNL - ss8v0 HLM GBOINOUd SEY SATMLNS ONY BYRVO d8 1 ¥ CRA HO ° © 2326066000002 3S © ° Row BLUE 20 TIMeL suov4noo supvaNoo WooTHAINNOLON — aazENeeauaNNW Ey HSSaNINIRT SORT oo og BS 6 ~eieaee Page 23 ML433 | vai 130) ONS anon usar GENEE TEED sts own] gy yaa 009M war ae Tm [os cnouy eN-000M 2 df-HOOH HOLIMS 3OIHYIAO TWANVH | sean | ae | ao [eon | so] od [aoa oT TnoaoNts GLI a CJ Ld con SIN sos} feecyrgune Pawwy7 serBojouyse, odxy swessivnl 8 i 2 r ‘anesi] Od | Gav) WALSAS YOLOM 01 ONIGHOOOY BAEMAN WHINY « adds LON 3a SaNvT9 Sav (O3TIRIONN SI H31SAS 3ORINd NI SLVId ONYIO 35001 O3/Idd!'6 HOLIMS 3ORUIAO TWnNYWN =o nana fy! w— nan ‘ams f [saz caw Saw xe Cr Ss ML433 | véi Page 24 Tao T eKuRiS sunous0a| on aor com www [oue | epee [ ee | mame [ wwe fe Or0-0dLu-uaXx AATVA 4372Y DYNdYOLOW € 3ZIS vistuts Naiwar]| GDH | sew “on ontnva uu aL wN aT vonanp0id_snuvis oma vay] ST aos neozorstaraPeMUUN] SeBojouyse, Odxa | PETMAN sauyn | 6002/20/0T avzmmne| anoatr| mreoasr | uncon | noun (ual yx) tu § 40 anbyol y 01 aaNatHoU ANAS WY vr 1108 SABE ERAS NSHP BN NSS 201-8250-naW '3009 Luvd “5 oer g 5)» ATALYHIXOUddY SI LHOI3M - . Be Ee -aMOHS NoMYNaT¥O aH > Re SF NE oauNnon 39 1Sfie 3A SITE ORL a “igpnassy rung bo mou a0und o1 aut st Sivigsoiaie "2 ER avy iors 584,135 04 auynd aousnio FAVS iS SSNS SIRI ane ot 8H 1Ins OL SINIOg ONIX! 430 9 ‘S2L0N = 431un0 wiv 30une aStino iv 358ne (39914) ANIOs 1s3L Sanssaed LAW Td 39T4T¥O JHL ONIONYHD “aS uw $60 Sa10H ONLINAOWS30 9, Jnanassy ana sansy [zunssave SHO FAASGTONS BOLOW ‘WOd ALWId YBAOD BDU) RUNSOTONA HOLM > sanassy 131100 \ Oo ° MOTs 39UNd: \ oO oO Oo 5 SI wBPRRURE al ; H © eo 8 oO jojo oO ofo a —aynais arava } GING dene o ° ® Loa aunssaud 01 ° ° AwNBIS MOTs 4310 poor 3YNSSIYd ONINIdO ATY SHL ve ONILLAS ¥Od LV Id B3AOD TWAS aoe we “paws pan aooase; soruny | LAE LARSE WSO CUT ONML SER TOLER Sy AGREES. RASS? SPP Seat ING oy Ban a wt wumieersiance > SAREE Page 25 ML433 | vai ML433 | véi oro-cous-wex | 5 8O novia sowanbas 31 xS5unaiin ssn [ese [aa |r oe fe ee nu eS ray | TT sos weserguss PONT] SeJBojouyse, odxy ‘wrvaivn | OF0Z/90/E2 aire wneva) arceccr | sive Gruscr | wanna | va €-€-66d9 SI ONIMVUA NOLVOISLLYRD OdXS LNVARTIY SHL Toma seenaescrmen evmivannenuint sieere a WMT TTR 00 fav au0 Ou GEE we msncrsantg Page 20 C0 HHS nanousno] ‘ow aor gua | 38a M-850-8TS-dL Hsiwta| Nave | @>Ho coronal NOLLVOIGNI SNLVIS WALSAS | wae] \nccono. spay] SE{BOjOUYda| OdxX] wre | 6007/E0/6T ge 4 A ih (oe)(@) | oem 3, 5 i von vary. as QO | mm slelee [gale lelele | GG] | meee svouvoraNt sruvis wausis Page 27 ML433 | vai zr zabeg yee: core ses seven vopeayniag Ando faa139 Siar ‘9h1— suo}sn 13 /aumesodusoa Oi paypnds 5 ca.ig wopeuen aoe hae poe aude Sul ° s co ‘ebungque-sodng “98nd "903 " ’ TE onset XS6ZTXGLVTO eS :2qum € rons Ja sor04tsouny 9950 ur a XS6CTXaLYTO E15 LVOTATLMaD NOLIVNIWVXG 34AL-Na inasrtoz anba4a se 24ssouay 298013 Mena WI 9 40) PP z LVOISLLNGO NOLLVNIWWXG adAL-' sinaaHs 3 ML433 | véi Page 28 zi opa0eg ‘sopoo vendo acueg uw soq@ 5, ML vo WON WSssa © o1xT UN OH rronsst XS6CEXALYTO es UWOIsILNGD NOLLYNIMWG 3dAL-na sinaaHos mM ere obea \wop0upj pain ‘ne SHO ‘UeBuenehs "leg ean Uepreus @9]MaS UONINUED BIS ‘eon ponerse aL so.on 09t Xz 0.06 p36 1am nad sony + wed} ea + ‘sack ovond naj 8 up Y>|M Jo SAE ied WL pany S| NEA PIR YP YO BRNO MUL ‘ncane ue OSTA ‘SCUATH “POAT SLT “SE 2A ‘AT ‘SCAT 'GIAT ‘ZEAT NT SAT ENTE soo} as on LAUER ‘910129 ayen jane uoneussop au ‘an lao Sepa py ae aL “smeaace a Jo ue waists aun Jo 38m aun 9d oF ansepia pane ung ope aq KEL! ILM ALD BMA AL, (uo vogenvrssaié 2) voasenid ng - 60 aug 30 au0 apne un ey juanapad © 0} S20 bine Jo es woy Law € aot pape a un Sava ped Kroteunet Be open aNa ronsst xSecreaivto es SUVOTALLUED NOLIVNIWWXa 3dAL-1 ainaaHos Page 29 ML433 | vai ‘zr yogabed trp § a6eq sererooneuns “ea 9asrpU Uepenes@ An ad|Mag UoeoyIUE9 AIS @01Meg UONeayTED EMIS perl rory “Nbupesse pep a0 7 ves say 9 107246009 UE ZTOT-LaNS 1a Aq pooedos aan son’ to7T9 Na pt LonpaTooe-Te7T9 at L0022-62009N3 77020-6008 Ne Biponwy supe Hae} aun IAM SUAUED aeaURAD Causes sexdo.dde BUMOIES ‘Spowouy jenna yom aig AM ZUBIN apaRCuAD ch yaussoe adage Cua} wk *.09-012.05- oy paiano, sen sw9sin heme, No] pue area NOT a 0} EKA HIME UTIL OU, A "jes uosorbo {uenap ae ana nrpoid ajo sede aye 20 0pm amensiowpe aie suaLpLBLI asm 39 (vost amsae stupuew aap wove 9 pue sou o vogppe aut SuoqeypoW GujeD ouR yo uaODe BULA (soso sme ps “eRPoULcD Camus Ny tg 0 LORY sg RLERCO UR NOUS POBUELD eM LORELED ATHOUL (Gvojsan araeiocun ‘rpaqu sex uenGo (S165 INTY pouaue 0.25) {5 ms mapa NE = mt EUR ee Bi a EM AL :98ue\ Buywo}9) 349 poonpoaM LoRaLeN Su z WOREHEA -aos stn aun eum. uo Anau aur seq. ods Pau wants Mayes vane, obs 2b) Aauns ‘uowia Sees ‘peoy ulus wot sou MON ‘aueN PIO jonu0> a.nd an 0 paxye age paroxlde aun uo aueu 0 ‘2a 9) auau mou ata Jo Vonruisans aut pe BiEDYUSD 2A vo aWeL saURD|acy Bajo a6UeD yy) afvel angeseusy “posn aq Aew pun jgeopanoxide z obareD ALY AeA A 1D siieodusy. owes aut ancy pu apo> LoneayaiaD Sues aA :wajgue ata way pasn ag Ue nay ‘eds sd ‘ave Buwoie} at paonpaa UoReLeA fu myn pers 8 iron pue S06 0) ua ees ae SL spe E04 ih jo LDOUUED 4 NSO LEW aA URN PpHOAE 8 09 eA @ xa Uy ansopue sonics fund a aps pue von yo e249 OF PON 2x SOL om spe Ao opin Baan 90 A OOS) 18243, [105-9 uve pasn 26 0, _yswoye se ainsopse aa SsaUIES ‘pawey eUoRPHE Ue Spsu pay ad 6} eYOUE SBiNG ALL”) s96Ut0 Bulojoj aa peonpay woReVeN SL T WORELER e6uel Bugvogey 89 peorpna LOREEN ALE UOREEA rr onssr rranest XS6CTXGLYTO WIS AMVOIHILUa9 NOLLYNINWxa adAL-3 XS6ZEXALVTO eas AUVOTILLvaD NOLLYNINWG 3dAL-na ainaaHos ainaaHos &) ML433 | vai Page 30 zr peetee aolAlag uo} eayNa9 BAIS ‘3.21 pany 6 an 29 ul 2 2 insopL oun ‘Bunun 901) sW9d tun 90 Aue UO Bue ad bao te Oy TALON oa HM SHLePUEDS 24) Jo vogeucwog ~ suoado (GH/) amenduy YB Pue CL) eumelecuD]. ey PaUILCD ssvoaso (ail © 94N aimeradui Yi pue (1) ameiaduey Mor pevqucD aA Jo voRDMpOA 34 _sofueu> Bumojo) 219 poonPOgu UeRBUEA SL - OF UORELEA aimeiaauay uuu @ yh (Qa09+ 08 2302) aBues snzeacUDy 0 STUDI ‘p23 20339 PRBS Fey oleRN Aue 59 eu (@/L) ones XSecPGLYTO eS SLVOLSTLNED NOLLYNINWIG 3dAL-n3 ‘s1naaH3s eils aw cate, a 99|Aag UOHEDIs9D BAIS ert -yroip 26) yun oavon wah fungi aun BuAIdns adi se os Xap ap pany aq AjeURdE Kew 2BURIXS IU sau09 ue 2,05 Ye sieo 01385 5 1]009 BLO BL. Dnaunauc argu a 000 a psn (137 2un a4on29 jes Ajensuny ve 2pnou Ae 2.04 y execs se abine unueau Bumuued pue ‘ureradin awaque ve tm soyoaUeD 6. aBingN aud Jo UAE BTeMRUD YBN - CH + ‘GaSet) hyo 2 2a 1) gens ua euoNgo Bu roaucs wasshs ‘fungi aun uAlddns ad se yoo> xan op u peny oq AjevoNdo Kew OUR 124 pd vo] saeuraud a6sngut 243 0D oi pasn si pue >,0¢+ 4 aes 6b 3955 Jf00D XOLOA SAL. “sue arwedway uray e yan (2.09% 08 2402) a6 21 11 Ba 109 PaULaD GL Beans Aue oq dats ‘3a voamnpedul au, so6uo\> 6uiojoj 9a psonponu Logue SL - 6 UORELEA rroneer XS6zTXALYTO es AVOISLLID NOLIVNIWWG 3dAL-na annaakos Bis Page 31 ML433 | vai 21 0F ea "yea feist veneneH awn e9/Mag UOReOYIUED BAIS (9 Vonevea yo voronpeau au | veereto0cw ‘opieso6ce 8 (oWvER6Sz8 “ ooisgsezy oroesequecaa zz | 9 vyseserTise S002 Aeniaay et sest158 doozanee) yezssrvisy 9002 squares 61 YVosOrTVisw ”Fo0e sauandos ogg YORTIAESH HOC WIN EL) ‘y>yuo0 a 0 800101 UL YEBLLVESS ‘aoe Ate) ‘20514 2,e2UHE9 pue SuOdDY ex's poye)D055y ‘pauy mOyRED OOP ‘sSumera sinanno0d aaniérosaa ‘uote snide pas ou sem Lu Gump passes snjaid eo uoRppe aA 8d OA SLVOISTLMaD NOLLYNIWYXa adAL-na. snnaaHos 801s UONeDINIUED BIS hia! zr 63teg S380 aumeiadumy nw © yu {2,094 0} 2.09) abu aur 291 SDI BG 20 9 3 Poggio NADAL age Aue og Ae (GL) HO FURL FeLORED Od), ‘ese 3 sex ‘oiass amessduay ‘oy oi Baan 249 0% ep! 51 LOI “RED HBR ‘ayo wg 33 3 un nice amt abinaui ata Suen se oo xav0K aA Up 99 A moro OY ‘ayn. 280) ageunoud aGungui au ocd 1 pasn s puE 2.054 3 meso oi 395 51-9609 MADEN BU ‘eS 38 oi Su “oI amseocu9 9951 OM 0a a TY 5 auNSODLE aA o wOROG OY 2yorp afer yun pice uumsis afinguy ta Buns a6 ooo xayon ayn pony 9g yeuondo fe aBuR IU Y oy ag pas 249 rons XS6UEXaLYTO C45 LVDTATLWaD NOLLYNIWWXa adAL-13 ainaaH9s, eis ML433 | véi Page 32 er pot 2605 ‘weg eusspuy uBaseneH 9h e/Meag uoReoy!We9 BAIS tuys payaso 2yerau-u0U e wy setsoune snp ays | 950} gE Se poYeU! Og L| xonoc{onazlo0sE/0er a6ingupiadng e6nanan-adn eBid ofingue-cns ‘ajonu0D ang ‘ansoouo jas ks pawed 0 es sss Jao o paede Bupyews Mpa ayy ul sacle Jeys UO ZH 10 95 Bimelodu. uw puP amelodue) oy Sojanuoy ae aeudo.dde se apo wONEYTLAD UL, Uwonsar01d aunssaudiang GuyGang Jo wone>y 0A ‘ssa: ue andi ayeudo.cde 4 sop)0.dsjoqu0> a1 28 aya ag yes ‘Sup 1 un yonuoy aBsnanIN a BI PARAM 9g YS BYE) Aen ey ‘ua yun pon aq un este abingM AR {Wong eunss9i4s9n0 usmpejnuew iq 4 pauuoyid aq 2 Aosa19 0} payne Agnins 3g yuan og ‘pr uonD9g u pas) 30d, oyavsp)useq neu seni sia U pa sbepuet a fa see (6sSv8) IE XANNY 40 SuNaHiTAIND A ALAS ONY HLTWaH THINGS. rons xseznGuvto es ALVDITLUSD NOLLYNIWYXG 3dAL-n, annaakos eiIS dno 21 11 960s (2H '9H pur suezensrpeeduy YOu cHh'9H) AaUoD GuUORDUN 1 pose 990 18 ‘a6e-poa pve suoransco wy a1 2 9 yes add nro e204 a ‘enyzeo Su “alee fbtoe aNDaHG Aq pauLep se quwoniny auddde 24) pue waueinba thu pawesodxou eq jeys Wun ae seinau SL "un nue Bing pue(sunsoove psunssau a Jo voreURUO? 2 aeoyus0 ay ye x Ag preuep) gM HO SNOLLTANGD 2141>3eS ‘Or uoneven jo uotonponul | a6seCneN STOR CEI sz] TT {GuoReLeh JO LOR>reaAN aL ‘na/re/otoe ana2010 0 1 opt au sourpaDe up) “naive anpaia csOuep 008 Ut sjeayuny vonecuers odAL 13 0 pap 2a/6)¥G un sauepiee y ayRen voneUWeS SAL 23° abun. Bua) a9 snven sss UL YezeBHOOL sto euNEST | _Or rronssr XSezrxauvro es BIVOLITLWGO NOLLYNIWWG 34AL-N'3 aingakos eis est ost Page 33 ML433 | vai eno rateg uogag Busv85 wooT| sr une ze st60s sruneze ‘rca STUN 361805 oe sre zazeas [Part uonesyiue9 sana | —g1une ee ‘szcas Bupnoy ainieacuas wor) stun zz Bria sibs gH aBirawW | ——oF sate] t]_TeT | —_sTecos orseatz | t} tet | etecas orseaiz| Fert] aceas orsgez| 3) cat] —_tazcos TURTON SEROUR]FOTSETIU, Teaco ae] voneLED DaLY abindun | —tazcos sonst TZ new To]_zioz] 968105) these 31 AR2 See To) eiot)—9eév0s| TES WIRY PIETY SNE DIM Hood SEGA O59 OY WseY Bue KuD my = ayes "woe S1oAURWOD Y BUHL ~ WesbeD 2ueTERS WO sOnUWLe AO ZL TTS WoReBVaCUGD BOI! A107 aeAL — ITAURUES Tol eat fist ep 13624 “Sie Tal toponeta pow aL mee] ol ar 2 @0|M9g UORLOYIHED BAIS -pous wee woRAUHT 5]2m0 [ste UoRe>I=D ‘usnoy armeiedua WOT ‘soiag Bu0D 39910 38170 | ines Ney = We.B20 B14A ‘BILD WO NO SOT SOO}, nO IAIN BUGS, Teccas BhrLO8 toscos bbvces ESCO "SW 7 WN Wo SOTTO) — SHES Tae Tueputos pue WaIBKS WAUUIENND = MRED RAST (Gre bp 4 poRG aM SS Sa I HEE SSOMEP A) ONBET 002 awax Bey uoRRSYRIT BUEN BURTON ameIICH MOT] —EO~G | eevee poe wien 600 cr 182008. (sre pas sens q tents sen es a gy see one) Z OMEET Aa pune » (eet i coms a T T T z é (erst bi pons a EE SBE a) ONEST ean s9/60youN>=1 O4xa 0002/0002 /005¢/009t =8:naquin-rodng ‘a8ingiuin-iodn ‘eBsnaiuin ‘a8ungin-as BiIS ou avennddy auewdinba ON oyeoyn199 @ReFHED, uur eiaeup=Looa wey oon/oas/ne aor oSnae ens te oe zt qe as aunt sno wuss ssecnavreens sions 2 ells axouuy aye2yi00 ML433 | véi Page 34 ete eo/Mes UONBOYNHED BAIS “Wa lasfoncecr ae aL (iam wy we aR] wo peo 005 (a aR, BH DOR LT A, HoT PUD sas SEG RH SEPA Tess = WR ea MGT, Ds eau WH sp2s08 Us Tozcas BS CRO SIO watcas anata sF ane | ay | sus | Bumeia | rr onser oeag ROH SERA 152505 ‘T= WORD DeaL wy MG AUA, 3s ave WH svisas SH ado 208 av aBn/ee 309 rea LOH 0s sees] 9001 § oa ao, emaesdu2| UH Sess oun) sendin | Woy st toecas (sn arsine [ayes | tone) Pen srFooNee. Oa x0004/000¢/00s¢/008r sfunawinodns ‘abingitnsodns bangin ‘Bundi ans nono 96mg sou aneutuas XSSrHALYTO MS “oN eHeURIOD Bis oxauy sen Page 35 ML433 | vai sumuaermaiey uta seeuiouseenanéa spa ams ae 0 : prune puc umes ig oan. og payout Basico seose fx pe Sunda tee el Aylwuojuog jo B}EDIIH9ID XAIDAl ‘uopbey pan antain speta noone, Te ee aratatt Uaawsacmonemtet 7 ome 7 ao 0.0) sn tee org hoa seve ong aro) fama soa: puogro ae pe vouysqa.9y nen esto mcg snag sing gt ‘ease sosaydsouny enjsojdxg 104 auleyog uoneo|sR109 Dal NOISSINWO9 TWOINHO31 0419373 TVNOLLYNUALNI AyuoyuoD Jo oa] fed SJOWIH9D XADAl ML433 | véi Page 36 10210991 /apemsa ae sen ‘Sy eSieatfeon eee sons yrneeaun mo pu ecu) mo 22 yu ata ‘one oh os bueus opt oe es {ot0ge poe sane 30ND YOUN HO EWI Ayui10juog Jo Coil ayeOyIMED XO be suena ss nogaere eta spear ae Lao stots ue i ens Byun 9 mes caearsd eu, sop 5 yu 4 pat suns pow waar “ina Ayuuoyuog jo ayeOI9D XFDAl Page 37 ML433 | vai spesses sroz mono se ea sere srocsgeose =a Sr ewes sayoniog #6ing pawn seitoouypas ox ueouaay (6 anest x2z00°40 WIS 3931 ‘oyromy Poin sour, o4xa aueondty (6 anest x2200°20 WIS *303r or xouuy ML433 | véi Page 38 spyoquep 26nd Panu sy60y0uy>04 Oaxa 6 2nss1 x2z00'20 WIS *a93I gupeesaumesiocyen Page 39 ML433 | vai ‘woptunt pewun sre SHO epee "yea eusrpuuBpmene oN eojAleg UoAeoYTUED 11S spsotes orormepose oa sayonven 96ing ssmereddy emir seioouNps1 o4xa aweondey (onset xcz00'40 91S 3931 souxouuy ML433 | véi Page 40 Sez (au) sete 9p exes, ‘rd eng eb (40g) eptonbos epembos opsemunte op ope ‘02TH au ud SeuRLOU SogSOUAp Sens 5 sopeUGDE a ORS e/NNPA AP SHUTS 592004 HT 0 unui op eau_osraner ep aioe suns cyan un imho te 3am cid opsa1d0005 2p OW BP NAPA Eu Ld OPDEUE} 9 aBinaHAA efurd =p JoP=ENUED O own 2p ernaen, sei yw Secu (one eu) me AD ona “een s6inaran an yond 3a xoavioain0> 4 er07/60/8z ‘7 omnea Too =X ZON ‘8107/60/87 oon To oreney apepluuiosuod ap opery!ya5 1yBiy Aresio0s oPUeIUIEUHANL vy ApeplUUosuoD ap opesyyad ayBiy Ajesio014 PUE|UIOUYANL V Page at ML433 | vai ue uu Bs i sity on (expequnesand ayowos)exsod env oxsraid = 4a Pet e6und sce orn (veg iu) oxre = > APepIULIoJUO> ap Opedy!ED apeplwiojuod ap operyiieD MLARS | v8i ‘openyso © given ‘puewUH ATL ep engad ogee wes ‘osseD1d esp OBSENALITON eu sounsep ssanbop SmuaRyp seuaiau 8 seuouodwa> ap ean no plo! 2p oxeaypou senbeNd ‘opevesio ednptad ee eORUEP edn © eppEw Sp SOMPaI sO EI BIN 9 APEPRULOLAD OP OPEDYRAD MEI -Z T07/60/8z 8 omren To eenew oPUEIUIEUYANL - (epemoiped cesar) -eensqo uo 0 ops. sua> we 5 opus ‘oben eoqmo! opuaIeP ‘sepeope seu sep sow, sou ‘aypue 9 so sou opetide fo aN Oopou eland ap JopeLNND sosenuen 1027/60/97 8 opm ‘BrOz/60/8¢ 8 omen TOSeey XX TOPETT AML wHoPmUENO apepluiojuod ap operyize9 TYBIY Ajes!9e4g_ »PURIUIEYYANL bh Page 43 ML433 | vai siozateg ‘S.x0 yoann cna uy pecgod mae ncaa um poyne> Aes fp wouaBeue ve guy ewoyie "iq! poms ansosus Ogg e sest 504 Anawainda Jo NonaRos3a—¢t XEcTeKaLv6s ens ‘BAYDTUTLNG NOLLYNIWWX-34AL.93 snnaaos NOlAvOlsi4wa9 3 = 9p 195te ‘Srerainguges seems revoou gunn zee DAS UDIAUNND OS ‘paves vara suaunse 2 pur yan sig cL ampapE aA y payneds 9 BNR UaRIN pAEEOTE fue ponsLaUdnDS LL Tr ess -afses aupava somytsounyensee Aenea BIVOISILYGD NOLLVNINWXG-3dAL 2a NOlLvolsi4uad 3) 7 ML433 | véi Page 44 pp yatey srowwy N83 0-ORy stuymera 190 onedsp sound wnunau pnapese aun e001 Jo modus) aye 3,65" 1sqUE sath Jeu psn dq ot FONG|e 2m Soe ooiverzzeu “spepues os) 9a 2100-6008 ha Aa pose se 1100-64009°31 ieunuayna uogppe aa ussau eonpou se sr 385 0, vin eons @ s95un0 6uNo40, aa peorp0Ru vonee Sl -9 UORELEA onset XECTEXaLV6 es BLVOIATINGD NOLLYNIWWXG-3dAL 23 snnaatos NOlLvOIsILya9 3} 7 spestes sf13 Ws wo mon eer a Om DOWNS UORBDYIWED BIS sing roan ue ni tga XELTOGLv66 es ALyOTATINGD NOLLYNIWWXG-34AL 2 sinaaHos NOILVOISILNa9 &} Page 45 ML433 | vai a osesed 2p Aajes uns ag oth abut “arospuna a buena om anaes en ea co va 119004941990 62509 12 SB IN sede? sue ainsapue 24 SuEROKS inp ayo pany 39 fot bis wouarba ef poy Aes Sct ERTS OEE SEBO Tan 300r SIE vo 2430 ups 39 pop pation yeenantie! ca loaves vornpaid a ay Aeie> «1 pone “san as sep 8 age Sua ou ata aeayD Ba JoeEN BML Et NouoIsEL¥ID 40 SNOLIGNGD —&t rons, XELTEXALVES C15 BIVOIUTIAGD NOLLYNTHWXG-24AL 92 annaaios NOILVOISILYaO 3) 7. 9405 0604 ot unas up soc og afey syne sia UBER SHIDUER A He (susie) aNNW 4o SuNaHERUINDU ALZAVS GN HLWWaH THLNSS2 ot IBR RAC OE VEzrOROCE | — FOE AAT cowtiore | srozwdv0| 6 comrsre | rive goo yz] ouNsessey | eve veo] 3 waeevise| —eoozoewor| —s [wwerotnese | —soae wa ae | —F ep aun oseTar a facie sunyieg pue Runde es peweposEY 741 XecTOxaves es BIVDIJTIMGD NOLLYNINYXG-24AL 93. anaawos NOILVOIsIL¥a9 3) 7 ML433 | véi Page 40 rye rateg BOIA9g UONBOYIUED BUS, sno yogntas kag niu penpnce oo/vewezeu Been son Sa] ——er BOT array st ree [ee Sus | Suweaal) oorerrcoce onset THOS TDA TET Toad Bune Das TT pune = iecsueh TET oN) nest eS OSA Tae TB] Yad SHUEY BE ‘rapt 1a Tae SUSE Sue O00 ay Soy TEIN — oT Be ‘3201 a7 9 onssy RETESET] —— SURI ‘rar ey) aREoRS BUINDERUN baa] ee] — ‘conser (BPS; pes asus Aa psleuene aN Sans esas Lk paeDEseSEuNasP 247 0 0 BNET Nolavolsisys9 aan HoaLaV ‘sex09 voroune jo a6uey 948 el is XECTOKALYG6 ws uBqUNN mEDUIOD = exeuuy 27294119) Page 47 ML433 | vai pen "Sone TEL poprous wa veya ol pt voneuue os Arpsecos 84 ey auto i owe Y “anoge pay spuepuers ox) pope feaidee oie ue soy suowaynbar eotousaiod pu Mijas faite mn osuayaucs CHU OU B80p aE SUL 9, Mies peseanu fa vomoios woud 1 wea 40° 002 4- 6100 931 tones 1 einsopue fa uoqperon! uonubenp woud 16 Bed 002 46 €200 531 of ueaes le ayes om fa Monsees Wau 44 Yee 102 b1-"6z00 931, 102 0-'6200 931, ‘wowarnas esoue5 19 veg 144 2049x3051 uno 98 se suopUED eum ck sens pewesD ea LSS (Buco Senay teat ofoaoes uu ka Bosanos ‘uowneog ruonssedo ove zo 49 oreo Suurioeyruyy [LORE septa on meer oiwin HoaLay see; Ayu10jyuoy Jo BzEdIWWID XAOAl vouveaas worn eis ES sever voreoun2 fandoa 1303) 9 0 yoo vo opie) ponent fo09 umen, ‘toesec00 ung seedy 010913 oni oatay sen rover uso 0 ue aOR en snouts MHHED Dal NOISSIWINOD WWOINHD3SLOYNLO313 TWNOLLYNYSLNI Ajlwsojyuoyg jo Zz 97BSIH9D XAOAl ML433 | véi Page 43 ‘eno8 pur seme} 0} $3ONVHO ZLVONLNSD 0 $V130. riaretes on ena, oe-uo-ri0e. ‘ones 00160 AjIW1OJUOD JO SJEIIIWID XADAl Page 49 101 wes siow ou jo wou inate ows anpcodo.t 10} pms 99 015} wswdne oa 1 Arne sone tn wREDIade fed) eH da ww UL PORN UKIA—L oreuuy oqeoy e019) “sfeuuuo) un pany ‘once ronpaxd 19 eats @ season aakog Uotout Ses oul ‘(9990090 us x30 Ee pouneo NlevodtueD ITO sswoj0/ 86 010 ceo sus Ka pasoroo swash pu WoO ommpeuos MLA33 [vai A}IWUOJUOD JO ayeoIWW9D XAOAl Aylwu10JU09 Jo eyeOyIED XFOII ames seo 8 nevweas08 one oe ws cox riave enon Tam aOS oN mem seomoys euaa0H sereydsouny eusojdea Jj eweLDg LOMEDNIIED D1 NOISSIMINOO TWOINHOSLO¢LO3TS TNOLLYNAALNI ‘AyUutoyUo9 Jo ayeoyme xG03I MLARS | v8i poreupesoi6a3e931 oy aa tupsose me tena pay cee nfs a cseny sachs ota ae enue irae sen mae etmenn en ee persia pepone Shes es Ose ems on sue cusunep rapa apn tgp sie fete cra canon ete oa pCR a Ayuuoyuog jo aye0ymeg X3OAl Page 5t ML433 | vai cL oLbuepnd oon aO8 BL ON “max 229 WIE Habe a NTU Li) youd sa Aine ue enrqpecu a ule nang exo suouaurbas gins yng amen soup we ‘Pets ogy woenns pus cheapo ot Anos aomeD wmeouae BONO ae) ‘ogc ot abi pyc vn oe 0909 out polo pacts a fa ea Fog nS we le oes HBO RCO) (uszs100 oa) ‘novse-uo09 wa ‘eunyaues fa pareve ney ery simuanrbny eg PUN aay ees OM am sue) C@) ®) aqeoyyye9 uoneuUexy edk|-03 O°AeH X91 F XALV PE Sa3 eveONNIOD UOHeUIUIEXS OdhL-o3 ML433 | vai . With EU-Declaration of European Conformity Directives Issued under the sole responsibilty of Expo Technologies Ltd Unit 2, The Summit, Hanworth Road ‘Sunbury on Thames TW16 5DB, UK This is to declare that “Purge Controllers: Sub-MiniPurge, MiniPurge, Super-MiniPurge, Super-MiniPurge 1800/3500/7000/7000X”, are manufactured in conformity with the following European Directives and standards: Electromagnetic Compatibility Directive 2014/30/EU MiniPurge Systems with a /PO suffix in the type number are non-electrical and are outside the scope of the EMC Directive. MiniPurge Systems with suffices /PA or /IS incorporate one or more volt-ree (‘dry’) contacts which work in Circuits Specified by others. In normal operation these circuits are “benign” and no CE mark is appropriate. MiniPurge Systems with Electronic Timer (Option JET) are designed to conform to the EMC Directive, in compliance with EN 61000-6-4:2007 and EN 61000-6-2:2005 (Intertek Report EM10048000). MiniPurge Systems are intended for use in potentially explosive atmospheres (Hazardous Areas) and are therefore excluded from the Low Voltage Directive. Pressure Equipment Directive 97/23/EC. MiniPurge Systems are classified as not higher than category | under Article 9 of this Directive and intended for use in potentially explosive atmospheres (Hazardous Areas) and are therefore excluded from the Pressure Equipment Directive. ATEX Directive 2014/34/EU Equipment for explosive atmospheres MiniPurge Systems are designed to conform to the ATEX Directive in fulfilment of the essential health and safely requirements set out in Annex Il, and in compliance with: EN 60079-0; 2012 +A11:2013 EN 60079-2: 2014 MiniPurge Systems are certified by SIRA Certification Service, Hawarden Industrial Park, Hawarden CHS 3US, England, under EC Type-Examination Certificate SIRA 01ATEX1295X, in compliance wit EN 60079-0: 2012 EN 60079-2: 2014 According to the model, MiniPurge Systems are rated and shall be marked as follows: MiniPurge, Type X & Type Y models Group II Category 26 & 2D. ©) 1122) GD MiniPurge, Type Z models Group II Category 36.&3D 1123) GD MiniPurge systems are manufactured under Production Quality Assurance Notification SIRA 99 ATEX M043, issued by SIRA Certification Service, Notified Body No 0518. Signed for and on behalf of Expo Technologies Lid., John Paul de Beer Date 16/08/2016 Managing Director Confidential Assessment file reference SCO04 S\Files\QA\CERTSIC-OF-C\Minipurge CE $C004 Issue9.doc Page 54 ML433 | vai Expo Technologies USA Expo Technologies UK Expo Technologies China Expo Technologies Inc. Expo Technologies Lid. Qingdao Expo M&E Technologies Co. Lid 9140 Ravenna Road Unit #3 Unit 2 The Summit, Hanworth Road 329 Huashan Er Lu Twinsburg, Sunbury-On-Thames, Jimo City, Qingdao, OH 440878, USA TW16 5DB, UK 266200 China T: +1 440 247 5314 T: #44 20 8398 6011 T: +86 532 8906 9858 F: +4 330 487 0011 F: +44 20 8398 8014 F: +86 532 8906 9858 E: sales.na@expoworldwide.com E: sales@expoworldwide.com E: gingdao@expoworldwide.com www.expoworldwide.com

You might also like