You are on page 1of 192

Declaration Of Compliance

We, The Manufacturer


SHENZHEN GROWATT NEW ENERGY CO.,LTD

Declare The Products:


MIC 1000TL-X, MIC 1500TL-X, MIC 2000TL-X, MIC 2500TL-X, MIC3000TL-X,
MIN 2500TL-X, MIN 3000TL-X, MIN 4200TL-X, MIN 5000TL-X, MIN 6000TL-X
MAX50KTL3 LV, MAX60KTL3 LV, MAX70KTL3 LV, MAX75KTL3 LV, MAX80KTL3 LV
MAX80KTL3 MV,MAX90KTL3 MV,MAX100KTL3 MV
MID15KTL3-X,MID17KTL3-X,MID20KTL3-X,MID22KTL3-X,MID25KTL3-X;
MID25KTL3-X1,MID30KTL3-X,MID33KTL3-X, MID36KTL3-X,MID40KTL3-X
MAC50KTL3-X LV/MAC50KTL3-X MV,MAC60KTL3-X LV/MAC60KTL3-X MV
MAC70KTL3-X MV
MAX 185KTL3-X HV,MAX 216KTL3-X HV, MAX 250KTL3-X HV,MAX 253KTL3-X HV,
MOD 10KTL3-X, MOD 11KTL3-X, MOD 12KTL3-X, MOD 13KTL3-X, MOD 15KTL3-X
MIN 7000TL-X(E),MIN 8000TL-X(E),MIN 9000TL-X ,MIN 10000TL-X
MAX100KTL3-X LV, MAX110KTL3-X LV ,MAX120KTL3-X LV ,MAX125KTL3-X LV
MAC 15KTL3-XL, MAC 20KTL3-XL, MAC 22KTL3-XL MAC 25KTL3-XL, MAC 30KTL3-XL,
MAC 36KTL3-XL
MID 10K TL3-XL, MID 12K TL3-XL, MID 15K TL3-XL, MID 20K TL3-XL
MAX 50 KTL3-XL2, MAX 60 KTL3-XL2, MAX 70 KTL3-XL2, MAX 75KTL3-XL2,
The Growatt inverters listed above comply with the relevant requirements of the Brazilian
standard:
ABNT NBR 16149:2013 Sistemas fotovoltaicos (FV) – Características da interface de
conexão com a rede elétrica de distribuição – Primeira edição (01.03.2013)
[Photovoltaic (PV) systems – Characteristics of the utility interface – first edition, March
01-2013]
As results after internal testing made in accordance to the applicable conformance test
protocol:
ABNT NBR 16150:2013 Sistemas fotovoltaicos (FV) — Características da interface de
conexão com a rede elétrica de distribuição — Procedimento de ensaio de conformida -
Primeira edição (04.03.2013)
[Photovoltaic (PV) systems – Characteristics of the utility interface – Conformity test
procedure. First edition, March 04-2013]
ABNT NBR 62116-2012 Procedimento de ensaio de anti-ilhamento para inversores de
sistemas fotovoltaico conectados à rede.

Please refer to the conditions and restriction of use specified in the table, as well as in the
following notes.
Inverter Model Power Nominal voltage/frequency Cos(phi)=f(p) Reactive FRT
No. of phase Power capability
Capability

MIC 1000TL-X 1kw 220V/60Hz,1-phase Yes Yes Yes


MIC 1500TL-X 1.5kw 220V/60Hz,1-phase Yes Yes Yes
MIC 2000TL-X 2kw 220V/60Hz,1-phase Yes Yes Yes
MIC 2500TL-X 2.5kw 220V/60Hz,1-phase Yes Yes Yes
MIC 3000TL-X 3kw 220V/60Hz,1-phase Yes Yes Yes
MIN 2500TL-X 2.5kw 220V/60Hz,1-phase Yes Yes Yes
MIN 3000TL-X 3kw 220V/60Hz,1-phase Yes Yes Yes
MIN 4200TL-X 4.2kw 220V/60Hz,1-phase Yes Yes Yes
MIN 5000TL-X 5kw 220V/60Hz,1-phase Yes Yes Yes
MIN 6000TL-X 6kw 220V/60Hz,1-phase Yes Yes Yes
MIN 7000TL-X(E) 7kw 220V/60Hz,1-phase Yes Yes Yes
MIN 8000TL-X(E) 8kw 220V/60Hz,1-phase Yes Yes Yes
MIN 9000TL-X 9kw 220V/60Hz,1-phase Yes Yes Yes
MIN 10000TL-X 10kw 220V/60Hz,1-phase Yes Yes Yes
MID 10K TL3-XL 10kw 220V/60Hz,3-phase Yes Yes Yes
MID 12K TL3-XL 12kw 220V/60Hz,3-phase Yes Yes Yes
MID 15K TL3-XL 15kw 220V/60Hz,3-phase Yes Yes Yes
MID 20K TL3-XL 20kw 220V/60Hz,3-phase Yes Yes Yes
MAC 15KTL3-XL 15kw 220V/60Hz,3-phase Yes Yes Yes
MAC 20KTL3-XL 20kw 220V/60Hz,3-phase Yes Yes Yes
MAC 22KTL3-XL 22kw 220V/60Hz,3-phase Yes Yes Yes
MAC 25KTL3-XL 25kw 220V/60Hz,3-phase Yes Yes Yes
MAC 30KTL3-XL 30kw 220V/60Hz,3-phase Yes Yes Yes
MAC 36KTL3-XL 36kw 220V/60Hz,3-phase Yes Yes Yes
MAX 50 KTL3-XL2 50kW 220V/60Hz,3-phase Yes Yes Yes
MAX 60 KTL3-XL2 60kW 220V/60Hz,3-phase Yes Yes Yes
MAX 70 KTL3-XL2 70kW 220V/60Hz,3-phase Yes Yes Yes
MAX 75 KTL3-XL2 75kW 220V/60Hz,3-phase Yes Yes Yes
MOD 10KTL3-X 10kw 380V/60Hz,3-phase Yes Yes Yes
MOD 11KTL3-X 11kw 380V/60Hz,3-phase Yes Yes Yes
MOD 12KTL3-X 12kw 380V/60Hz,3-phase Yes Yes Yes
MOD 13KTL3-X 13kw 380V/60Hz,3-phase Yes Yes Yes
MOD 15KTL3-X 15kw 380V/60Hz,3-phase Yes Yes Yes
MID17KTL3-X 17kw 380V/60Hz,3-phase Yes Yes Yes
MID20KTL3-X 20kw 380V/60Hz,3-phase Yes Yes Yes
MID22KTL3-X 22kw 380V/60Hz,3-phase Yes Yes Yes
MID25KTL3-X 25kw 380V/60Hz,3-phase Yes Yes Yes
MID25KTL3-X1 25kw 380V/60Hz,3-phase Yes Yes Yes
MID30KTL3-X 30kw 380V/60Hz,3-phase Yes Yes Yes
MID33KTL3-X 33kw 380V/60Hz,3-phase Yes Yes Yes
MID36KTL3-X 36kw 380V/60Hz,3-phase Yes Yes Yes
MID40KTL3-X 40kw 380V/60Hz,3-phase Yes Yes Yes
MAC50KTL3-X LV 50kw 380V/60Hz,3-phase Yes Yes Yes
MAC60KTL3-X LV 60kw 380V/60Hz,3-phase Yes Yes Yes
MAX50KTL3 LV 50kw 380V/60Hz,3-phase Yes Yes Yes
MAX60KTL3 LV 60kw 380V/60Hz,3-phase Yes Yes Yes
MAX70KTL3 LV 70kw 380V/60Hz,3-phase Yes Yes Yes
MAX75KTL3 LV 75kw 380V/60Hz,3-phase Yes Yes Yes
MAX80KTL3 LV 80kw 380V/60Hz,3-phase Yes Yes Yes
MAX100KTL3-X LV 100kw 380V/60Hz,3-phase Yes Yes Yes
MAX110KTL3-X LV 110kw 380V/60Hz,3-phase Yes Yes Yes
MAX120KTL3-X LV 120kw 380V/60Hz,3-phase Yes Yes Yes
MAX125KTL3-X LV 125kw 380V/60Hz,3-phase Yes Yes Yes
MAC50KTL3-X MV 50kw 480V/60Hz,3-phase Yes Yes Yes
MAC60KTL3-X MV 60kw 480V/60Hz,3-phase Yes Yes Yes
MAC70KTL3-X MV 70kw 480V/60Hz,3-phase Yes Yes Yes
MAX80KTL3 MV 80kw 480V/60Hz,3-phase Yes Yes Yes
MAX90KTL3 MV 90kw 480V/60Hz,3-phase Yes Yes Yes
MAX100KTL3 MV 100kw 480V/60Hz,3-phase Yes Yes Yes
MAX 185KTL3-X HV 185kw 800V/60Hz,3-phase Yes Yes Yes
MAX 216KTL3-X HV 216kw 800V/60Hz,3-phase Yes Yes Yes
MAX 250KTL3-X HV 250kw 800V/60Hz,3-phase Yes Yes Yes
MAX 253KTL3-X HV 253kw 800V/60Hz,3-phase Yes Yes Yes

Manufacturer:
Shenzhen Growatt New Energy CO., LTD

R&D Director
Mr.Woody Wu
Certificate of Conformity
Certificate Number: CN-PV-220113
On the basis of the tests undertaken, the samples of the below product have been found to comply with the
requirements of the referenced specifications /standards at the time the tests were carried out. It does not imply that
Intertek has performed any surveillance or control of the manufacture. The manufacturer shall ensure that the
manufacturing process assures compliance of the production units with the examined products mentioned in this
certificate.

Applicant: Shenzhen Growatt New Energy Co., Ltd.


4-13/F, Building A, Sino-German (Europe) Industrial Park, Hangcheng Ave, Bao’an
District, Shenzhen, China
Product: PV Grid inverter
Ratings & Principle See Appendix to Certificate of Conformity
Characteristics:
Model: MAX 50KTL3-XL2, MAX 60KTL3-XL2, MAX 70KTL3-XL2, MAX 73KTL3-XL2
MAX 75KTL3-XL2, MAX 50KTL3-XL1, MAX 60KTL3-XL1, MAX 70KTL3-XL1,
MAX 73KTL3-XL1, MAX 75KTL3-XL1
Brand Name<s>: GROWATT
Product Complies with: IEC 61727:2004. Photovoltaic (PV) systems – Characteristics of the utility interface
IEC 62116:2014. Test procedure of islanding prevention measures for utility-
interconnected photovoltaic inverters
Certificate Issuing Intertek Testing Services Ltd. Shanghai
Office Name & Address: West Area, 2nd Floor, No. 707, Zhangyang Road
China (Shanghai) Pilot Free Trade Zone, Shanghai, P. R. China
Accredited by China National Accreditation Service for Conformity Assessment
(CNAS C058-P) in accordance with ISO/IEC 17065:2012
Test Report No.<s>: 220308046GZU-001, 220308046GZU-002

Certification procedure: SMS-PV-OP-19


Product certification scheme type: Type test
Additional information in Appendix.

中国认可
Signature 国际互认
产品
PRODUCT
Certification Manager: Grady Ye CNAS C058-P
Date: 1 June 2022

This Certificate is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and
conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
Certificate. Only the Client is authorized to permit copying or distribution of this Certificate. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material,
product or service must first be approved in writing by Intertek.

Intertek Page 1 of 3 SFT-PV-OP-23a (16-December-2021)


APPENDIX: Certificate of Conformity
This is an Appendix to Certificate of Conformity Number: CN-PV-220113

Model MAX 50KTL3- MAX 60KTL3- MAX 70KTL3- MAX 73KTL3- MAX 75KTL3-
XL2 XL2 XL2 XL2 XL2
Max.PV voltage 1100Vdc
MPPT voltage 180-850Vdc
Max.input
8*45A
current
PV Isc 8*56.5A
Nominal output
voltage 3W/N/PE, 127/220Vac

Nominal output
50/60Hz
Frequency
Max.output current 144.3A 173.2A 183.7A 191.6A 196.9A
Max. output power 50KW 60KW 70KW 73KW 75KW
Max. apparent
55KVA 66KVA 70KVA 73KVA 75KVA
power
Power factor range 0.8Leading~0.8Lagging
Safety level Class I
Ingress Protection IP 66
Operation Ambient
-30℃ - +60℃
Temperature
Software version TN1.0

This Certificate is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and
conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
Certificate. Only the Client is authorized to permit copying or distribution of this Certificate. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material,
product or service must first be approved in writing by Intertek.

Intertek Page 2 of 3 SFT-PV-OP-23a (16-December-2021)


APPENDIX: Certificate of Conformity
This is an Appendix to Certificate of Conformity Number: CN-PV-220113

Model MAX 50KTL3- MAX 60KTL3- MAX 70KTL3- MAX 73KTL3- MAX 75KTL3-
XL1 XL1 XL1 XL1 XL1
Max.PV voltage 1100Vdc
MPPT voltage 180-850Vdc
Max.input
10*32A
current
PV Isc 10*40A
Nominal output
voltage 3W/N/PE, 127/220Vac

Nominal output
50/60Hz
Frequency
Max.output current 144.3A 173.2A 183.7A 191.6A 196.9A
Max. output power 50KW 60KW 70KW 73KW 75KW
Max. apparent
55KVA 66KVA 70KVA 73KVA 75KVA
power
Power factor range 0.8Leading~0.8Lagging
Safety level Class I
Ingress Protection IP 66
Operation Ambient
-30℃ - +60℃
Temperature
Software version TN1.0

This Certificate is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and
conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
Certificate. Only the Client is authorized to permit copying or distribution of this Certificate. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material,
product or service must first be approved in writing by Intertek.

Intertek Page 3 of 3 SFT-PV-OP-23a (16-December-2021)


Certificate of Conformity
Certificate Number: CN-PV-220127
On the basis of the tests undertaken, the samples of the below product have been found to comply with the
requirements of the referenced specifications /standards at the time the tests were carried out. It does not imply that
Intertek has performed any surveillance or control of the manufacture. The manufacturer shall ensure that the
manufacturing process assures compliance of the production units with the examined products mentioned in this
certificate.

Applicant: Shenzhen Growatt New Energy Co., Ltd.


4-13/F, Building A, Sino-German (Europe) Industrial Park, Hangcheng Ave, Bao’an
District, Shenzhen, China
Product: PV Grid inverter
Ratings & Principle See Appendix to Certificate of Conformity
Characteristics:
Model: MAX 50KTL3-XL2, MAX 60KTL3-XL2, MAX 70KTL3-XL2, MAX 73KTL3-XL2
MAX 75KTL3-XL2, MAX 50KTL3-XL1, MAX 60KTL3-XL1, MAX 70KTL3-XL1,
MAX 73KTL3-XL1, MAX 75KTL3-XL1
Brand Name<s>: GROWATT
Product Complies with: IEC/EN 62109-1:2010. Safety of Power Converter for use in Photovoltaic Power
Systems Part 1: General requirements
IEC/EN 62109-2:2011. Safety of Power Converter for use in Photovoltaic Power
Systems Part 2: Particular requirements for inverters
Certificate Issuing Intertek Testing Services Ltd. Shanghai
Office Name & Address: West Area, 2nd Floor, No. 707, Zhangyang Road
China (Shanghai) Pilot Free Trade Zone, Shanghai, P. R. China
Accredited by China National Accreditation Service for Conformity Assessment
(CNAS C058-P) in accordance with ISO/IEC 17065:2012
Test Report No.<s>: 220308046GZU-003, 220308046GZU-004

Certification procedure: SMS-PV-OP-19


Product certification scheme type: Type test
Additional information in Appendix.

中国认可
Signature 国际互认
产品
PRODUCT
Certification Manager: Grady Ye CNAS C058-P
Date: 28 June 2022

This Certificate is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and
conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
Certificate. Only the Client is authorized to permit copying or distribution of this Certificate. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material,
product or service must first be approved in writing by Intertek.

Intertek Page 1 of 3 SFT-PV-OP-23a (16-December-2021)


APPENDIX: Certificate of Conformity
This is an Appendix to Certificate of Conformity Number: CN-PV-220127

Model MAX 50KTL3- MAX 60KTL3- MAX 70KTL3- MAX 73KTL3- MAX 75KTL3-
XL2 XL2 XL2 XL2 XL2
Max.PV voltage 1100Vdc
MPPT voltage 180-850Vdc
Max.input
8*45A
current
PV Isc 8*56.5A
Nominal output
voltage 3W/N/PE, 127/220Vac

Nominal output
50/60Hz
Frequency
Max.output current 144.3A 173.2A 183.7A 191.6A 196.9A
Max. output power 50KW 60KW 70KW 73KW 75KW
Max. apparent
55KVA 66KVA 70KVA 73KVA 75KVA
power
Power factor range 0.8Leading~0.8Lagging
Safety level Class I
Ingress Protection IP 66
Operation Ambient
-30℃ - +60℃
Temperature
Software version TN1.0

This Certificate is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and
conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
Certificate. Only the Client is authorized to permit copying or distribution of this Certificate. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material,
product or service must first be approved in writing by Intertek.

Intertek Page 2 of 3 SFT-PV-OP-23a (16-December-2021)


APPENDIX: Certificate of Conformity
This is an Appendix to Certificate of Conformity Number: CN-PV-220127

Model MAX 50KTL3- MAX 60KTL3- MAX 70KTL3- MAX 73KTL3- MAX 75KTL3-
XL1 XL1 XL1 XL1 XL1
Max.PV voltage 1100Vdc
MPPT voltage 180-850Vdc
Max.input
10*32A
current
PV Isc 10*40A
Nominal output
voltage 3W/N/PE, 127/220Vac

Nominal output
50/60Hz
Frequency
Max.output current 144.3A 173.2A 183.7A 191.6A 196.9A
Max. output power 50KW 60KW 70KW 73KW 75KW
Max. apparent
55KVA 66KVA 70KVA 73KVA 75KVA
power
Power factor range 0.8Leading~0.8Lagging
Safety level Class I
Ingress Protection IP 66
Operation Ambient
-30℃ - +60℃
Temperature
Software version TN1.0

This Certificate is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and
conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
Certificate. Only the Client is authorized to permit copying or distribution of this Certificate. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material,
product or service must first be approved in writing by Intertek.

Intertek Page 3 of 3 SFT-PV-OP-23a (16-December-2021)


MAX50~75KTL3-XL2
··Até 8 MPPTs, design sem fusível
··Diagnóstico inteligente I/V
··Monitoramento inteligente por String
··SPD Tipo II no lado CC&CA
··Proteção C5 e IP65.

www.ginverter.com
Ficha de dados MAX50KTL3-XL2 MAX60KTL3-XL2 MAX70KTL3-XL2 MAX73KTL3-XL2 MAX75KTL3-XL2

Dados de entrada
Máxima potência CC 75000W 90000W 105000W 109500W 112500W

Máxima tensão CC 1100V


Tensão de partida 195V
Tensão nominal 370V
Faixa de tensão MPP 180V-850V
Números de MPP trackers 8
Número de Strings FV por MPP trackers 2
Máxima corrente de entrada
por MPP Tracker 45A
Máxima corrente de curto-circuito 56.5A
por MPP tracker
Saída
Potência nominal de saída CA 50000W 60000W 70000W 73000W 75000W
Potência máxima aparante CA. 55000VA 66000VA 70000VA 73000VA 75000VA
Tensão nominal de saída 127V/220V (101.6-139.7V)
Frequência da rede CA 50/60 Hz(45~55Hz/55-65 Hz)

Corrente máxima de saída. 145.8A @220V 175.0A @220V 183.7A @220V 191.6A @220V 196.9A @220V

Fator de potência ajustável 0.8leading ...0.8lagging

THDi <3%
Tipo de conexão da rede CA 3W/N/PE

Eficiência
Máx. Eficiência 98.80%
Eficiência europeia 98.30%
Eficiência MPPT 99.90%

Dispositivos de proteção
Proteção polaridade reversa CC Sim
Interruptor CC Sim
Proteção de surtos CA/CC Type II / Type II
Monitoramento de resistência Sim
de isolamento
Proteção de curto-circuito CA Sim
Monitoramento de falta à terra Sim

Detecção de string Sim


Função Anti-PID Opcional

Detecção de falha de arco Opcional

Dados gerais
Dimensões (L/A/P) 970/640/345mm
Peso 84kg
Temperatura de operação –30°C ... +65°C
Consumo noturno < 1W
Topologia Sem transformador
Resfriamento Refrigeração forçada
Grau de proteção Ip65
Humidade relativa 0~100%
Altitude 4000m
Conexão CC H4/MC4
Conexão CA Conector
Display LED/WIFI+APP
Interfaces: RS485 / USB / PLC Sim/Sim/Opc
Garantia : 10 anos Sim

CE,IEC62116, IEC61727, CQC, VDE0126, VFR2014, EN50549-1, C10/C11, UNE206007, G99


ROHS, CEI 0-21/0-16, N4105&N4110, UNE206006,MEA, PEA, KSC8565
* The AC voltage range and frequency range may var y depending on specific countr y grid standard.
All specifications are subject to change without notice.
Test Report issued under the responsibility of:

TEST REPORT
IEC 61727
Photovoltaic (PV) systems –
Characteristics of the utility interface

Report Number. .............................. : 220308046GZU-001


Date of issue ................................... : 30 May 2022
Total number of pages ................... 26 Pages

Name of Testing Laboratory Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
preparing the Report ..................... : Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of
Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD,
Guangzhou, Guangdong, China
Applicant’s name ........................... : Shenzhen Growatt New Energy Co., Ltd.
Address ........................................... : 4-13/F, Building A, Sino-German (Europe) Industrial Park,
Hangcheng Ave, Bao’an District, Shenzhen, China
Test specification:
Standard ......................................... : IEC 61727:2004
Test procedure ............................... : Type approval
Non-standard test method ............ : N/A
Test Report Form No. .................... : IEC61727B
Test Report Form(s) Originator .... : TÜV SÜD Product Service GmbH
Master TRF ..................................... : Dated 2017-11-03
Copyright © 2017 IEC System of Conformity Assessment Schemes for Electrotechnical
Equipment and Components (IECEE System). All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as
copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting
from the reader's interpretation of the reproduced material due to its placement and context.
If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the
CB Scheme procedure shall be removed.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory
and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.
General disclaimer:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing CB Testing
Laboratory. The authenticity of this Test Report and its contents can be verified by contacting the NCB,
responsible for this Test Report.
Page 2 of 26 Report No. 220308046GZU-001

Test item description . : PV Grid inverter


Trade Mark .................. : GROWATT
Manufacturer ............... : Same as applicant
Model/Type reference : MAX 50KTL3-XL2, MAX 60KTL3-XL2, MAX 70KTL3-XL2, MAX 73KTL3-XL2
MAX 75KTL3-XL2, MAX 50KTL3-XL1, MAX 60KTL3-XL1, MAX 70KTL3-XL1,
MAX 73KTL3-XL1, MAX 75KTL3-XL1
Ratings ........................ : Model MAX MAX MAX MAX MAX
50KTL3- 60KTL3- 70KTL3- 73KTL3- 75KTL3-
XL2 XL2 XL2 XL2 XL2
Max.PV
1100Vdc
voltage
MPPT
180-850Vdc
voltage
Max.input
8*45A
current
PV Isc 8*56.5A
Nominal
output 3W/N/PE, 127/220Vac
voltage

Nominal
output 50/60Hz
Frequency
Max.output
144.3A 173.2A 183.7A 191.6A 196.9A
current
Max. output
50KW 60KW 70KW 73KW 75KW
power
Max.
apparent 55KVA 66KVA 70KVA 73KVA 75KVA
power
Power factor
0.8Leading~0.8Lagging
range
Safety level Class I
Ingress
IP 66
Protection
Operation
Ambient -30℃ - +60℃
Temperature
Software
TN1.0
version
Model MAX MAX MAX MAX MAX
50KTL3- 60KTL3- 70KTL3- 73KTL3- 75KTL3-
XL1 XL1 XL1 XL1 XL1

TRF No. IEC 61727B


Page 3 of 26 Report No. 220308046GZU-001

Max.PV
1100Vdc
voltage
MPPT
180-850Vdc
voltage
Max.input
10*32A
current
PV Isc 10*40A
Nominal
output 3W/N/PE, 127/220Vac
voltage

Nominal
output 50/60Hz
Frequency
Max.output
144.3A 173.2A 183.7A 191.6A 196.9A
current
Max. output
50KW 60KW 70KW 73KW 75KW
power
Max.
apparent 55KVA 66KVA 70KVA 73KVA 75KVA
power
Power factor
0.8Leading~0.8Lagging
range
Safety level Class I
Ingress
IP 66
Protection
Operation
Ambient -30℃ - +60℃
Temperature
Software
TN1.0
version

TRF No. IEC 61727B


Page 4 of 26 Report No. 220308046GZU-001

Responsible Testing Laboratory (as applicable), testing procedure and testing location(s):

Testing Laboratory: Intertek Testing Services Shenzhen Ltd. Guangzhou


Branch
Testing location/ address ............................. : Room 02, & 101/E201/E301/E401/E501/E601/E701/E801
of Room 01 1-8/F., No. 7-2. Caipin Road, Science City,
GETDD, Guangzhou, Guangdong, China
Associated CB Testing Laboratory: N/A
Testing location/ address ............................. : N/A

Tested by (name, function, signature) ........ : Joss Huang


Engineer
Approved by (name, function, signature) ... : Jason Fu
Supervisor

Testing procedure: TMP/CTF Stage 1: N/A


Testing location/ address ............................. : N/A

Tested by (name, function, signature) ........ : N/A


Approved by (name, function, signature) ... : N/A

Testing procedure: WMT/CTF Stage 2: N/A


Testing location/ address ............................. : N/A

Tested by (name + signature) ...................... : N/A


Witnessed by (name, function, signature) . : N/A
Approved by (name, function, signature) ... : N/A

Testing procedure: N/A


SMT/CTF Stage 3 or 4:
Testing location/ address ............................. : N/A

Tested by (name, function, signature) ........ : N/A


Witnessed by (name, function, signature) . : N/A
Approved by (name, function, signature) ... : N/A
Supervised by (name, function, signature) : N/A

TRF No. IEC 61727B


Page 5 of 26 Report No. 220308046GZU-001

List of Attachments (including a total number of pages in each attachment):


Appendix 1: photos (3 pages)

Summary of testing:

Tests performed (name of test and test Testing location:


clause): Intertek Testing Services Shenzhen Ltd.
All applicable tests Guangzhou Branch
Room 02, &
101/E201/E301/E401/E501/E601/E701/E801 of
Room 01 1-8/F., No. 7-2. Caipin Road, Science
City, GETDD, Guangzhou, Guangdong, China

Summary of compliance with National Differences:


List of countries addressed
N/A

The product fulfils the requirements of IEC 61727:2004

TRF No. IEC 61727B


Page 6 of 26 Report No. 220308046GZU-001

Copy of marking plate:


The artwork below may be only a draft. The use of certification marks on a product must be
authorized by the respective NCBs that own these marks.

Note:
1. The above markings are the minimum requirements required by the safety standard. For the final
production samples, the additional markings which do not give rise to misunderstanding may be
added.
2. Label is attached on the side surface of enclosure and visible after installation.
3. Other labels are identical to above, except the model’s name and ratings

TRF No. IEC 61727B


Page 7 of 26 Report No. 220308046GZU-001

Test item particulars...................................................:


Classification of installation and use.......................: Fixed and outdoor use
Supply Connection .....................................................: Permanent connection
.......................................................................................:
Possible test case verdicts:
- test case does not apply to the test object ........... : N/A
- test object does meet the requirement.................. : P (Pass)
- test object does not meet the requirement ........... : F (Fail)
Testing.......................................................................... :
Date of receipt of test item ........................................ : 06 April 2022
Date (s) of performance of tests ............................... : 06 April 2022 to 10 May 2022

General remarks:
"(See Enclosure #)" refers to additional information appended to the report.
"(See appended table)" refers to a table appended to the report.
Throughout this report a comma / point is used as the decimal separator.
Determination of the test conclusion is based on IEC Guide 115 in consideration of measurement
uncertainty.
This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between
Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the
agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the
agreement, for any loss, expense or damage occasioned by the use of this report. Only the Client is
authorized to permit copying or distribution of this report and then only in its entirety. Any use of the
Intertek name or one of its marks for the sale or advertisement of the tested material, product or service
must first be approved in writing by Intertek. The observations and test results in this report are relevant
only to the sample tested. This report by itself does not imply that the material, product, or service is or
has ever been under an Intertek certification program.
The test report only allows to be revised only within the report defined retention period unless standard or
regulation was withdrawn or invalid.
This report shall be used together with the report 220308046GZU-002.
Manufacturer’s Declaration per sub-clause 4.2.5 of IECEE 02:
The application for obtaining a CB Test Certificate Yes
includes more than one factory location and a Not applicable
declaration from the Manufacturer stating that the
sample(s) submitted for evaluation is (are)
representative of the products from each factory has
been provided ............................................................... :

When differences exist; they shall be identified in the General product information section.
Name and address of factory (ies) .......................... : Guangdong Growatt New Energy Co., Ltd.
Growatt Industrial Park,No.17 Pingheng Road
Pingtan Town,Huiyang District,Huizhou,Guangdong,
China

TRF No. IEC 61727B


Page 8 of 26 Report No. 220308046GZU-001

General product information:


The unit is a three-phase PV Grid inverter, it can convert the high PV voltage to Grid voltage and feed into
Grid network.
The unit is providing EMC filtering at the PV side and AC side. It is transformerless between the PV circuit
and AC circuit.
The unit has three controllers. The master controller DSP A measure the PV voltage and current, AFCI,
PV ISO and also communicate with the slave controller B and slave controller ARM and etc; The slave
controller DSP B is used to INV control and PV ISO measurement and etc.
The slave controller ARM monitor AC voltage, GFCI and communicate with the master controller DSP
The relays are designed to redundant structure that controlled by separately.
The master controller A and slave controller B are used together to control relay open or close, if the
single fault on one controller, the other controller can be capable to open the relay, so that still providing
safety means.
The topology diagram as following:

Difference of models:
All models are identical, except the number of MPPT and the output power derating in software.

Other than special notice, the model MAX 75KTL3-XL2 is as the representative test model in this report.

TRF No. IEC 61727B


Page 9 of 26 Report No. 220308046GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

4 UTILITY COMPATIBILITY P
The quality of power provided by the PV system for P
the on-site AC loads and for power delivered to the
utility is governed by practices and standards on
voltage, flicker, frequency, harmonics and power
factor.
Deviation from these standards represents out-of- P
bounds conditions and may require the PV system
to sense the deviation and properly disconnect from
the utility system.
4.1 Voltage, current and frequency P
The PV system AC voltage, current and frequency P
are compatible with the utility system.
4.2 Normal voltage operating range P
Utility-interconnected PV systems do not normally P
regulate voltage, they inject current into the utility.
Therefore, the voltage operating range for PV
inverters is selected as a protection function that
responds to abnormal utility conditions, not as a
voltage regulation function.
4.3 Flicker P
The operation of the PV system is not cause voltage P
flicker in excess of limits stated in the relevant
sections of IEC 61000-3-3 for systems less than 16
A or IEC 61000-3-5 for systems with current of 16 A
and above.
4.4 DC injection P
The PV system is not inject DC current greater than (See appended table) P
1 % of the rated inverter output current, into the
utility AC interface under any operating condition.
4.5 Normal frequency operating range P
The PV system operates in synchronism with the P
utility system, and within the frequency
trip limits defined in 5.2.2.
4.6 Harmonics and waveform distortion P
Total harmonic current distortion is less than 5 % at (See appended table) P
rated inverter output. Each individual harmonic is
limited to the percentages listed in Table 1.
Even harmonics in these ranges is less than 25 % of P
the lower odd harmonic limits listed.

TRF No. IEC 61727B


Page 10 of 26 Report No. 220308046GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

4.7 The PV system has a lagging power factor greater P


than 0,9 when the output is greater than 50 % of the
rated inverter output power.
5 PERSONNEL SAFETY AND EQUIPMENT PROTECTION P
This Clause provides information and considerations P
for the safe and proper operation of the utility-
connected PV systems.
5.1 Loss of utility voltage P
To prevent islanding, a utility connected PV system Complied with IEC 62116, See P
ceases to energize the utility system from a de- the separate report for
energized distribution line irrespective of connected reference
loads or other generators within specified time limits.
A utility distribution line can become de-energized P
for several reasons. For example, a substation
breaker opening due to fault conditions or the
distribution line switched out during maintenance.
5.2 Over/under voltage and frequency P
The abnormal utility conditions of concern are P
voltage and frequency excursions above or below
the values stated in this Clause, and the complete
disconnection of the utility, presenting the potential
for a distributed resource island.
5.2.1 Over/under voltage P
When the interface voltage deviates outside the (See appended table) P
conditions specified in Table 2, the photovoltaic
system ceases to energize the utility distribution
system. This applies to any phase of a multiphase
system.

TRF No. IEC 61727B


Page 11 of 26 Report No. 220308046GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

5.2.2 Over/under frequency P


When the utility frequency deviates outside the (See appended table) P
specified conditions the photovoltaic system ceases
to energize the utility line. The unit does not have to
cease to energize if the frequency returns to the
normal utility continuous operation condition within
the specified trip time.
When the utility frequency is outside the range of ±1 P
Hz, the system ceases to energize the utility line
within 0,2 s. The purpose of the allowed range and
time delay is to allow continued operation for short-
term disturbances and to avoid excessive nuisance
tripping in weak-utility system conditions.
5.3 Islanding protection P
The PV system must cease to energize the utility P
line within 2 s of loss of utility.
5.4 Response to utility recovery P
Following an out-of-range utility condition that has (See appended table) P
caused the photovoltaic system to cease energizing,
the photovoltaic system is not energize the utility line
for 20 s to 5 min after the utility service voltage and
frequency have recovered to within the specified
ranges.
5.5 Earthing P
The utility interface equipment is earthed/grounded P
in accordance with IEC 60364-7-712.
5.6 Short circuit protection N/A
The photovoltaic system has short-circuit protection Should consider in the end use N/A
in accordance with IEC 60364-7-712.
5.7 Isolation and switching N/A
A method of isolation and switching is provided in Should consider in the end use N/A
accordance with IEC 60364-7-712.

TRF No. IEC 61727B


Page 12 of 26 Report No. 220308046GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

4.3 TABLE: Flicker P


Model: MAX 75KTL3-XL2
Starting Stopping Running
Limit 4% 4% Pst = 1.0 Plt = 0.65

Test value L1-N 1.61 2.99 0.58 0.54

Test value L2-N 0.73 2.86 0.59 0.55

Test value L3-N 1.56 2.97 0.59 0.55


Supplementary information:

4.4 TABLE: Direct current injection P


Rated Ratio of Measured DC output current between terminals Isolated Limit
output rated transformer ?
L1-L2 L1-L3 L2-L3 L1-N L2-N L3-N (mA)
current output
(mA) (mA) (mA) (mA) (mA) (mA) (Yes/No)
(A) power
(VA)
Model: MAX 75KTL3-XL2
-- -- -- 215.7 109.0 120.0 No 1969
196.9 25%
-- -- -- 152.4 129.9 109.7 No 1969
196.9 50%
-- -- -- 582.2 565.3 517.7 No 1969
196.9 100%
Model: MAX 50KTL3-XL2
-- -- -- 486.6 543.9 607.8 No 1312
131.2 25%
-- -- -- 497.2 458.9 442.7 No 1312
131.2 50%
-- -- -- 535.9 523.3 473.4 No 1312
131.2 100%
Supplementary information:

4.6 TABLE: Harmonics and waveform distortion P


Model: MAX 75KTL3-XL2
Harmonic % of % of % of Harmonic
fundamen fundamen fundamen
fundamen fundamen fundamen Current
tal L1 (A) tal L2 (A) tal L3 (A)
tal) tal) tal) Limits (%)

02 0.2266 0.1150 0.3814 0.1950 0.1367 0.0700 1.0%

03 0.1721 0.0870 0.2336 0.1190 0.0611 0.0310 4.0%

TRF No. IEC 61727B


Page 13 of 26 Report No. 220308046GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

04 0.0808 0.0410 0.2005 0.1020 0.1947 0.0990 1.0%

05 3.2068 1.6260 3.3086 1.6870 3.1664 1.6140 4.0%

06 0.0604 0.0310 0.1152 0.0590 0.0354 0.0180 1.0%

07 1.4608 0.7410 1.5422 0.7870 1.3969 0.7120 4.0%

08 0.1153 0.0580 0.1279 0.0650 0.0400 0.0200 1.0%

09 0.0739 0.0370 0.0337 0.0170 0.0909 0.0460 4.0%

10 0.1132 0.0570 0.1368 0.0700 0.1026 0.0520 0.5%

11 0.9060 0.4590 0.8268 0.4220 0.7467 0.3810 2.0%

12 0.0852 0.0430 0.0994 0.0510 0.0952 0.0490 0.5%

13 0.8945 0.4530 0.9354 0.4770 0.9098 0.4640 2.0%

14 0.0512 0.0260 0.0207 0.0110 0.0606 0.0310 0.5%

15 0.0663 0.0340 0.1000 0.0510 0.0634 0.0320 2.0%

16 0.1032 0.0520 0.0936 0.0480 0.1050 0.0540 0.5%


17 0.7812 0.3960 0.7098 0.3620 0.6849 0.3490 1.5%
18 0.0544 0.0280 0.0094 0.0050 0.0707 0.0360 0.5%
19 0.2055 0.1040 0.2316 0.1180 0.2439 0.1240 1.5%
20 0.0586 0.0300 0.0806 0.0410 0.0215 0.0110 0.5%
21 0.0418 0.0210 0.0337 0.0170 0.0346 0.0180 1.5%
22 0.0145 0.0070 0.0337 0.0170 0.0080 0.0040 0.5%
23 0.3791 0.1920 0.3900 0.1990 0.3871 0.1970 0.6%
24 0.0016 0.0010 0.0067 0.0030 0.0073 0.0040 0.5%
25 0.0967 0.0490 0.0858 0.0440 0.0925 0.0470 0.6%
26 0.0475 0.0240 0.0413 0.0210 0.0308 0.0160 0.5%
27 0.0184 0.0090 0.0134 0.0070 0.0085 0.0040 0.6%
28 0.0467 0.0240 0.0219 0.0110 0.0285 0.0150 0.5%
29 0.0642 0.0330 0.0830 0.0420 0.0721 0.0370 0.6%
30 0.0283 0.0140 0.0387 0.0200 0.0091 0.0050 0.5%
31 0.1072 0.0540 0.0982 0.0500 0.1058 0.0540 0.6%
32 0.0075 0.0040 0.0290 0.0150 0.0159 0.0080 0.5%
33 0.0407 0.0210 0.0262 0.0130 0.0203 0.0100 0.6%
THD 1.967 2.039 1.922 5%
Supplementary information:

TRF No. IEC 61727B


Page 14 of 26 Report No. 220308046GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

4.6 TABLE: Harmonics and waveform distortion P


Model: MAX 50KTL3-XL2
Harmonic % of % of % of Harmonic
fundamen fundamen fundamen
fundamen fundamen fundamen Current
tal L1 (A) tal L2 (A) tal L3 (A)
tal) tal) tal) Limits (%)
02 0.1085 0.0820 0.2345 0.1790 0.1366 0.1040 1.0%
03 0.0724 0.0550 0.1052 0.0800 0.0461 0.0350 4.0%
04 0.0952 0.0720 0.1341 0.1020 0.1260 0.0960 1.0%
05 1.4840 1.1230 1.5372 1.1700 1.4581 1.1090 4.0%
06 0.0435 0.0330 0.0754 0.0570 0.0588 0.0450 1.0%
07 0.8371 0.6330 0.9378 0.7140 0.8570 0.6520 4.0%
08 0.0433 0.0330 0.0692 0.0530 0.0332 0.0250 1.0%
09 0.0361 0.0270 0.0271 0.0210 0.0675 0.0510 4.0%
10 0.0115 0.0090 0.0566 0.0430 0.0654 0.0500 0.5%
11 0.5575 0.4220 0.5276 0.4020 0.4949 0.3770 2.0%
12 0.0673 0.0510 0.0855 0.0650 0.0683 0.0520 0.5%
13 0.4533 0.3430 0.4605 0.3510 0.4722 0.3590 2.0%
14 0.0546 0.0410 0.0302 0.0230 0.0387 0.0290 0.5%
15 0.0280 0.0210 0.0137 0.0100 0.0343 0.0260 2.0%
16 0.0411 0.0310 0.0446 0.0340 0.0077 0.0060 0.5%
17 0.6799 0.5140 0.6253 0.4760 0.6337 0.4820 1.5%
18 0.0280 0.0210 0.0309 0.0240 0.0342 0.0260 0.5%
19 0.1276 0.0970 0.1231 0.0940 0.1045 0.0800 1.5%
20 0.0406 0.0310 0.0573 0.0440 0.0133 0.0100 0.5%
21 0.0252 0.0190 0.0189 0.0140 0.0069 0.0050 1.5%
22 0.0167 0.0130 0.0219 0.0170 0.0280 0.0210 0.5%
23 0.2891 0.2190 0.2797 0.2130 0.2477 0.1880 0.6%
24 0.0251 0.0190 0.0264 0.0200 0.0378 0.0290 0.5%
25 0.0961 0.0730 0.1082 0.0820 0.0522 0.0400 0.6%
26 0.0131 0.0100 0.0431 0.0330 0.0266 0.0200 0.5%
27 0.0304 0.0230 0.0084 0.0060 0.0198 0.0150 0.6%
28 0.0420 0.0320 0.0503 0.0380 0.0717 0.0550 0.5%
29 0.0451 0.0340 0.0461 0.0350 0.0670 0.0510 0.6%

TRF No. IEC 61727B


Page 15 of 26 Report No. 220308046GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

30 0.0197 0.0150 0.0246 0.0190 0.0189 0.0140 0.5%


31 0.0624 0.0470 0.1120 0.0850 0.0753 0.0570 0.6%
32 0.0039 0.0030 0.0193 0.0150 0.0355 0.0270 0.5%
33 0.0189 0.0140 0.0162 0.0120 0.0378 0.0290 0.6%
THD 1.530 1.596 1.507 5%
Supplementary information:

4.7 TABLE: Power factor P


Model: MAX 75KTL3-XL2
Input Output
Curre
Voltage Power Voltage Current Power Power Rated output
No nt (A
(V d.c.) (W) (V a.c.) (A a.c.) (W) factor (+/-) (V.A)
d.c.)
1 362.38 44.59 16155.43 126.32 40.16 15163.87 0.9963 (20±5)%
2 362.15 66.08 23929.70 126.51 60.00 22707.25 0.9972 (30±5)%
3 361.78 87.82 31769.51 126.70 79.81 30263.72 0.9977 (40±5)%
4 127.04 99.78 12650.93 126.88 99.40 37755.57 0.9979 (50±5)%
5 361.15 131.34 47431.11 127.07 118.83 45212.32 0.9981 (60±5)%
6 360.94 153.26 55315.67 127.26 138.35 52717.43 0.9981 (70±5)%
7 360.57 175.43 63254.93 127.44 157.83 60225.20 0.9980 (80±5)%
8 360.26 197.81 71260.83 127.64 177.29 67762.75 0.9982 (90±5)%
9 360.00 220.18 79262.55 127.84 196.57 75255.32 0.9982 (100±5)%
Supplementary information:
Power factor with “+” indicating leading and “-“ indicating lagging.

4.7 TABLE: Power factor P


Model: MAX 50KTL3-XL2
Input Output
Curre
Voltage Power Voltage Current Power Power Rated output
No nt (A
(V d.c.) (W) (V a.c.) (A a.c.) (W) factor (+/-) (V.A)
d.c.)
1 362.62 29.90 10841.99 126.19 26.54 9994.20 0.9947 (20±5)%
2 362.38 44.33 16063.72 126.33 39.93 15079.91 0.9965 (30±5)%

TRF No. IEC 61727B


Page 16 of 26 Report No. 220308046GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

3 362.19 58.82 21304.75 126.45 53.11 20088.39 0.9970 (40±5)%


4 361.95 73.20 26493.21 126.58 66.31 25113.15 0.9974 (50±5)%
5 361.76 87.67 31715.18 126.71 79.46 30135.95 0.9977 (60±5)%
6 361.62 102.15 36939.44 126.84 92.61 35160.84 0.9978 (70±5)%
7 361.43 116.69 42175.56 126.97 105.70 40180.35 0.9979 (80±5)%
8 361.24 131.35 47446.70 126.89 119.01 45215.89 0.9981 (90±5)%
9 361.01 145.54 52541.17 127.01 131.64 50063.54 0.9982 (100±5)%
Supplementary information:
Power factor with “+” indicating leading and “-“ indicating lagging.

TRF No. IEC 61727B


Page 17 of 26 Report No. 220308046GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

5.2.1 & 5.4 TABLE: Under-and over-voltage trip settings and reconnection test P
(1) Under voltage disconnection procedure
Rated Output Required Value of Ratio of Interva Measured Measured
output power min. voltage PCE trip decreased l time tripped disconnectio
voltage (VA) (V) settings (V / s) (s) voltage n time (s)
(V) (V) (V)
127 75K 107.95 108.0 0.10 4 106.98 1.49
Rated Output Required Value of Ratio of Interval Measured Measured
output power min. voltage PCE trip decreased time tripped voltage disconnection
voltage (VA) (V) settings (V / s) (s) (V) time (s)
(V) (V)
127 75K 63.5 63.0 0.10 0.1 63.90 0.063
(2) Under voltage reconnection procedure
Ratio of voltage rapidly Reconnection voltage (V) Reconnection time (s)
decreased
(V / s)
0.10 >108 81.2
(3) Over voltage disconnection procedure
Rated Output Required Value of Ratio of Interva Measured Measured
output power max. voltage PCE trip increased l time tripped disconnectio
voltage (VA) (V) settings (V / s) (s) voltage n time (s)
(V) (V) (V)
127 75K 139.7 140 0.10 4 139.7 1.50
Rated Output Required Value of Ratio of Interval Measured Measured
output power max. voltage PCE trip increased time tripped voltage disconnection
voltage (VA) (V) settings (V / s) (s) (V) time (s)
(V) (V)
127 75K 171.5 172 0.10 0.1 172.2 0.032
(4) Over voltage reconnection procedure
Ratio of voltage rapidly Reconnection voltage (V) Reconnection time (s)
decreased
(V / s)
0.10 <139 80.90
Supplementary information:
Tested on model MAX 75KTL3-XL2

TRF No. IEC 61727B


Page 18 of 26 Report No. 220308046GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

5.2.2 & 5.4 TABLE: Over/under frequency trip settings and reconnection test P
(1) Under frequency disconnection procedure
Rated Output Required Value of Ratio of Interva Measured Measured
output power min. PCE trip decreased l time tripped disconnectio
frequency (VA) frequency settings (Hz / s) (s) frequency n time (s)
(Hz) (Hz) (Hz) (Hz)
60 75K 59 59 0.01 0.3 59.01 0.185

(2) Under frequency reconnection procedure


Ratio of frequency rapidly Reconnection frequency (Hz) Reconnection time (s)
decreased (Hz / s)
0.01 >59 82.2
(3) Over frequency disconnection procedure
Rated Output Required Value of Ratio of Interva Measured Measured
output power max. PCE trip increased l time tripped disconnectio
frequency (VA) frequency settings (Hz / s) (s) frequency n time (s)
(Hz) (Hz) (Hz) (Hz)
60 75K 61 61 0.01 0.3 60.96 0.182
(4) Over frequency reconnection procedure
Ratio of frequency rapidly Reconnection frequency (Hz) Reconnection time (s)
decreased (Hz / s)
0.01 <61 80.8
Supplementary information:
Tested on model MAX 75KTL3-XL2 with frequency 60Hz

TRF No. IEC 61727B


Page 19 of 26 Report No. 220308046GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

5.2.2 & 5.4 TABLE: Over/under frequency trip settings and reconnection test P
(1) Under frequency disconnection procedure
Rated Output Required Value of Ratio of Interva Measured Measured
output power min. PCE trip decreased l time tripped disconnectio
frequency (VA) frequency settings (Hz / s) (s) frequency n time (s)
(Hz) (Hz) (Hz) (Hz)
50 75K 49 49 0.01 0.3 49.01 0.176

(2) Under frequency reconnection procedure


Ratio of frequency rapidly Reconnection frequency (Hz) Reconnection time (s)
decreased (Hz / s)
0.01 >49 79.0
(3) Over frequency disconnection procedure
Rated Output Required Value of Ratio of Interva Measured Measured
output power max. PCE trip increased l time tripped disconnectio
frequency (VA) frequency settings (Hz / s) (s) frequency n time (s)
(Hz) (Hz) (Hz) (Hz)
50 75K 51 51 0.01 0.3 50.99 0.193
(4) Over frequency reconnection procedure
Ratio of frequency rapidly Reconnection frequency (Hz) Reconnection time (s)
decreased (Hz / s)
0.01 <51 79.0
Supplementary information:
Tested on model MAX 75KTL3-XL2 with frequency 50Hz

TRF No. IEC 61727B


Page 20 of 26 Report No. 220308046GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

5.3 TABLE: tested condition and run-on time P


Model: Tested on model MAX 75KTL3-XL2 with frequency 50Hz
No. PEUT (% Reactiv PAC QAC Run-on PEUT Actual VDC Which
of EUT e load time(ms) (KW) Qf (V) load is
rating) (% of (Var) selected
normal) to be
adjusted
(R or L)
Test condition A
1 100 100 0 0 459.5 75.11 1.00 800 /
2 100 100 -5 -5 332.5 75.11 0.98 800 /
3 100 100 -5 0 279.5 75.11 0.95 800 /
4 100 100 -5 +5 305.0 75.11 0.93 800 /
5 100 100 0 -5 401.0 75.11 1.03 800 /
6 100 100 0 +5 311.5 75.11 0.98 800 /
7 100 100 +5 -5 258.5 75.11 1.08 800 /
8 100 100 +5 0 279.5 75.11 1.06 800 /
9 100 100 +5 +5 157.5 75.11 1.03 800 /
Test condition B
10 66 66 0 0 299.5 49.68 1.00 520 /
11 66 66 0 -5 196.0 49.68 1.03 520 L
12 66 66 0 -4 292.0 49.68 1.02 520 L
13 66 66 0 -3 287.5 49.68 1.02 520 L
14 66 66 0 -2 243.5 49.68 1.01 520 L
15 66 66 0 -1 242.0 49.68 1.01 520 L
16 66 66 0 1 308.0 49.68 0.99 520 L
17 66 66 0 2 464.0 49.68 0.99 520 L
18 66 66 0 3 415.5 49.68 0.98 520 L
19 66 66 0 4 409.5 49.68 0.98 520 L
20 66 66 0 5 311.5 49.68 0.97 520 L
Test condition C
21 33 33 0 0 838.0 24.81 1.00 309 /
22 33 33 0 -5 529.0 24.81 1.03 309 L
23 33 33 0 -4 668.0 24.81 1.02 309 L
24 33 33 0 -3 832.0 24.81 1.02 309 L
25 33 33 0 -2 652.0 24.81 1.01 309 L
26 33 33 0 -1 770.0 24.81 1.01 309 L
27 33 33 0 1 716.0 24.81 0.99 309 L
28 33 33 0 2 600.0 24.81 0.99 309 L
29 33 33 0 3 858.0 24.81 0.98 309 L
30 33 33 0 4 612.0 24.81 0.98 309 L
31 33 33 0 5 460.0 24.81 0.97 309 L

TRF No. IEC 61727B


Page 21 of 26 Report No. 220308046GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

Supplementary information:
For test condition A:
If any of the recorded run-on times are longer than the one recorded for the rated balance condition, then
the non-shaded parameter combinations also require testing.
For test condition B and C:
If run-on times are still increasing at the 95 % or 105 % points, additional 1 % increments is taken until
run-on times begin decreasing.

TRF No. IEC 61727B


Page 22 of 26 Report No. 220308046GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

5.3 TABLE: tested condition and run-on time P


Model: Tested on model MAX 75KTL3-XL2 with frequency 60Hz
No. PEUT (% Reactiv PAC QAC Run-on PEUT Actual VDC Which
of EUT e load time(ms) (KW) Qf (V) load is
rating) (% of (Var) selected
normal) to be
adjusted
(R or L)
Test condition A
1 100 100 0 0 730.0 75.11 1.00 800 /
2 100 100 -5 -5 330.0 75.11 0.97 800 /
3 100 100 -5 0 484.0 75.11 0.95 800 /
4 100 100 -5 +5 414.0 75.11 0.93 800 /
5 100 100 0 -5 322.0 75.11 1.03 800 /
6 100 100 0 +5 256.0 75.11 0.98 800 /
7 100 100 +5 -5 260.0 75.11 1.08 800 /
8 100 100 +5 0 648.0 75.11 1.06 800 /
9 100 100 +5 +5 588.0 75.11 1.04 800 /
Test condition B
10 66 66 0 0 335.5 49.68 1.00 520 /
11 66 66 0 -5 259.0 49.68 1.03 520 L
12 66 66 0 -4 327.0 49.68 1.02 520 L
13 66 66 0 -3 373.5 49.68 1.02 520 L
14 66 66 0 -2 327.5 49.68 1.01 520 L
15 66 66 0 -1 285.5 49.68 1.01 520 L
16 66 66 0 1 313.0 49.68 0.99 520 L
17 66 66 0 2 629.0 49.68 0.99 520 L
18 66 66 0 3 327.0 49.68 0.98 520 L
19 66 66 0 4 411.0 49.68 0.98 520 L
20 66 66 0 5 299.0 49.68 0.97 520 L
Test condition C
21 33 33 0 0 530.0 24.81 1.00 309 /
22 33 33 0 -5 134.5 24.81 1.03 309 L
23 33 33 0 -4 192.5 24.81 1.02 309 L
24 33 33 0 -3 178.5 24.81 1.02 309 L
25 33 33 0 -2 226.5 24.81 1.01 309 L
26 33 33 0 -1 234.5 24.81 1.01 309 L
27 33 33 0 1 235.5 24.81 0.99 309 L
28 33 33 0 2 153.5 24.81 0.99 309 L
29 33 33 0 3 182.5 24.81 0.98 309 L
30 33 33 0 4 176.5 24.81 0.98 309 L
31 33 33 0 5 175.5 24.81 0.97 309 L

TRF No. IEC 61727B


Page 23 of 26 Report No. 220308046GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

Supplementary information:
For test condition A:
If any of the recorded run-on times are longer than the one recorded for the rated balance condition, then
the non-shaded parameter combinations also require testing.
For test condition B and C:
If run-on times are still increasing at the 95 % or 105 % points, additional 1 % increments is taken until
run-on times begin decreasing.

TRF No. IEC 61727B


Page 24 of 26 Report No. 220308046GZU-001

Appendix 1: Photos

Top view of the unit

Back view of the unit

TRF No. IEC 61727B


Page 25 of 26 Report No. 220308046GZU-001

Appendix 1: Photos

PV Input Terminal view

Side view

TRF No. IEC 61727B


Page 26 of 26 Report No. 220308046GZU-001

Appendix 1: Photos

Internal view

Internal view

--- End of test report---

TRF No. IEC 61727B


Test Report issued under the responsibility of:

TEST REPORT
IEC 62109-1
Safety of Power Converter for use in Photovoltaic Power Systems
Part 1: General requirements

Report Number. ........................... : 220308046GZU-003


Date of issue ................................ : 22 Jun 2022
Total number of pages .................. 110 pages

Name of Testing Laboratory Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
preparing the Report.................... : Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of
Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD,
Guangzhou, Guangdong, China
Applicant’s name ......................... : Shenzhen Growatt New Energy Co., Ltd.
Address ....................................... : 4-13/F, Building A, Sino-German (Europe) Industrial Park,
Hangcheng Ave, Bao’an District, Shenzhen, China
Test specification:
Standard ...................................... : IEC/EN 62109-1:2010 (First Edition)
Test procedure............................. : Type approval
Non-standard test method ........... : N/A
Test Report Form No.................... : IEC62109_1B
Test Report Form (s) Originator .... : VDE Testing and Certif ication Institute
Master TRF .................................. : Dated 2016-04
Copyright © 2016 IEC System of Conformity Assessment Schemes for Electrotechnical Equipment
and Components (IECEE System). All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as
copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from
the reader's interpretation of the reproduced material due to its placement and context.
If this Test Report Form is used b y non-IECEE members, the IECEE/IEC logo and the ref erence to the CB
Scheme procedure shall be removed.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory
and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.
General disclaimer:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in f ull, without the written approval of the Issuing CB Testing
Laboratory. The authenticity of this Test Report and its contents can be verified by contacting the NCB,
responsible f or this Test Report.
Page 2 of 110 Report No. 220308046GZU-003
Test item description .....................
PV: Grid inverter
Trade Mark .....................................
GROWATT
:
Manufacturer .................................
Same: as applicant
MAX
Model/Type reference .................... : 50KTL3-XL2, MAX 60KTL3-XL2, MAX 70KTL3-XL2, MAX
73KTL3-XL2, MAX 75KTL3-XL2, MAX 50KTL3-XL1, MAX 60KTL3-
XL1, MAX 70KTL3-XL1, MAX 73KTL3-XL1, MAX 75KTL3-XL1
Ratings ..........................................Model
: MAX MAX MAX MAX MAX
50KTL3- 60KTL3- 70KTL3- 73KTL3- 75KTL3-
XL2 XL2 XL2 XL2 XL2
Max.PV
1100Vdc
voltage
MPPT
180-850Vdc
voltage
Max.input
8*45A
current
PV Isc 8*56.5A
Nominal
output 3W/N/PE, 127/220Vac
voltage

Nominal
output 50/60Hz
Frequency
Max.output
144.3A 173.2A 183.7A 191.6A 196.9A
current
Max. output
50KW 60KW 70KW 73KW 75KW
power
Max.
apparent 55KVA 66KVA 70KVA 73KVA 75KVA
power
Power f actor
0.8Leading~0.8Lagging
range
Saf ety level Class I
Ingress
IP 66
Protection
Operation
Ambient -30℃ - +60℃
Temperature
Sof tware
TN1.0
version
Model MAX MAX MAX MAX MAX
50KTL3- 60KTL3- 70KTL3- 73KTL3- 75KTL3-
XL1 XL1 XL1 XL1 XL1
Max.PV 1100Vdc

TRF No. IEC62109_1B


Page 3 of 110 Report No. 220308046GZU-003
voltage
MPPT
180-850Vdc
voltage
Max.input
10*32A
current
PV Isc 10*40A
Nominal
output 3W/N/PE, 127/220Vac
voltage

Nominal
output 50/60Hz
Frequency
Max.output
144.3A 173.2A 183.7A 191.6A 196.9A
current
Max. output
50KW 60KW 70KW 73KW 75KW
power
Max.
apparent 55KVA 66KVA 70KVA 73KVA 75KVA
power
Power f actor
0.8Leading~0.8Lagging
range
Saf ety level Class I
Ingress
IP 66
Protection
Operation
Ambient -30℃ - +60℃
Temperature
Sof tware
TN1.0
version

TRF No. IEC62109_1B


Page 4 of 110 Report No. 220308046GZU-003

Responsible Testing Laboratory (as applicable), testing procedure and testing location(s):

Testing Laboratory: Intertek Testing Services Shenzhen Ltd. Guangzhou


Branch
Testing location/ address ........................... : Room 02, & 101/E201/E301/E401/E501/E601/E701/E801
of Room 01 1-8/F., No. 7-2. Caipin Road, Science City,
GETDD, Guangzhou, Guangdong, China
Associated CB Testing Laboratory: N/A
Testing location/ address ........................... : N/A

Tested by (name, function, signature) ........ : Jason Fu


Supervisor
Approved by (name, function, signature) ... : Tommy Zhong
Technical Manager

Testing procedure: CTF Stage 1: N/A


Testing location/ address ........................... : N/A

Tested by (name, function, signature) ........ : N/A


Approved by (name, function, signature) ... : N/A

Testing procedure: CTF Stage 2: N/A


Testing location/ address ........................... : N/A

Tested by (name + signature) ..................... : N/A


Witnessed by (name, function, signature) .. : N/A
Approved by (name, function, signature) ... : N/A

Testing procedure: CTF Stage 3: N/A


Testing procedure: CTF Stage 4: N/A
Testing location/ address ........................... : N/A

Tested by (name, function, signature) ........ : N/A


Witnessed by (name, function, signature) .. : N/A
Approved by (name, function, signature) ... : N/A
Supervised by (name, function, signature). : N/A

TRF No. IEC62109_1B


Page 5 of 110 Report No. 220308046GZU-003

List of Attachments (including a total number of pages in each attachment):


Appendix 1: photos (16 pages)

Summary of testing:

Tests performed (name of test and test Testing location:


clause): Intertek Testing Services Shenzhen Ltd.
All applicable tests Guangzhou Branch
Room 02, &
101/E201/E301/E401/E501/E601/E701/E801 of
Room 01 1-8/F., No. 7-2. Caipin Road, Science
City, GETDD, Guangzhou, Guangdong, China

Summary of compliance with National Differences (List of countries addressed):


N/A

The product fulfils the requirements of IEC/EN 62109-1:2010 (First Edition)

TRF No. IEC62109_1B


Page 6 of 110 Report No. 220308046GZU-003

Copy of marking plate:


The artwork below may be only a draft. The use of certification marks on a product must be
authorized by the respective NCBs that own these marks.

Note:
1. The above markings are the minimum requirements required by the saf ety standard. For the f inal
production samples, the additional markings which do not give rise to misunderstanding may be
added.
2. Label is attached on the side surf ace of enclosure and visible af ter installation.
3. Other labels are identical to above, except the model’s name and ratings

TRF No. IEC62109_1B


Page 7 of 110 Report No. 220308046GZU-003

Test item particulars.............................................:


Equipment mobility ..............................................: movable hand-held stationary
f ixed transportable f or building-in
Connection to the mains ......................................: pluggable equipment direct plug-in
permanent connection f or building-in
Environmental category........................................: outdoor indoor indoor
unconditional conditional
Over voltage category Mains ................................: OVC I OVC II OVC III OVC IV
Over voltage category DC.....................................: OVC I OVC II OVC III OVC IV
Mains supply tolerance (%)...................................: -90 / +110 %
Tested for power systems ....................................: TN systems
IT testing, phase-phase voltage (V).......................: - - -
Class of equipment ..............................................: Class I Class II Class III
Not classif ied
Mass of equipment (kg) ........................................: Approx. 84Kg
Pollution degree ...................................................: Outside PD3; Inside PD2
IP protection class................................................: IP 66
............................................................................:
Possible test case verdicts:
- test case does not apply to the test object ......... : N/A
- test object does meet the requirement ............... : P (Pass)
- test object was not evaluated for the
requirement ......................................................... : N/E

- test object does not meet the requirement ......... : F (Fail)


Testing ................................................................. :
Date of receipt of test item ................................... : 06 April 2022
Date (s) of performance of tests ........................... : 06 April 2022 to 08 Jun 2022

TRF No. IEC62109_1B


Page 8 of 110 Report No. 220308046GZU-003

General remarks:
"(See Enclosure #)" ref ers to additional inf ormation appended to the report.
"(See appended table)" ref ers to a table appended to the report.

Throughout this report a comma / point is used as the decimal separator.

This report shall be used together with report No.220308046GZU-004


Manufacturer’s Declaration per sub-clause 4.2.5 of IECEE 02:
The application f or obtaining a CB Test Certif icate Yes
includes more than one f actory location and a Not applicable
declaration f rom the Manuf acturer stating that the
sample(s) submitted f or evaluation is (are)
representative of the products f rom each f actory has
been provided........................................................ :

When differences exist; they shall be identified in the General product information section.
Name and address of factory (ies) ....................... : Guangdong Growatt New Energy Co., Ltd .
Growatt Industrial Park,No.17 Pingheng Road Pingt
an Town,Huiyang District,Huizhou,Guangdong,
China

TRF No. IEC62109_1B


Page 9 of 110 Report No. 220308046GZU-003

General product information:


The unit is a three-phase PV Grid inverter, it can convert the high PV voltage to Grid voltage and f eed into
Grid network.
The unit is providing EMC f iltering at the PV side and AC side. It is transf ormerless between the PV circuit
and AC circuit.
The unit has three controllers. The master controller DSP A measure the PV voltage and current, AFCI,
PV ISO and also communicate with the slave controller B and slave controller ARM and etc; The slave
controller DSP B is used to INV control and PV ISO measurement and etc.
The slave controller ARM monitor AC voltage, GFCI and communicate with the master controller DSP
The relays are designed to redundant structure that controlled by separately.
The master controller A and slave controller B are used together to control relay open or close, if the
single f ault on one controller, the other controller can be capable to open the relay, so that still providing
saf ety means.
The topology diagram as f ollowing:

Model differences:
All models are identical, except the number of MPPT and the output power derating in sof tware.

The product was tested on:


The Sof tware version: TN1.0
The Hardware version: V1.0

Other than special notes, typical model MAX 75KTL3-XL2 is used as representative f or testing in this
report.

TRF No. IEC62109_1B


Page 10 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

4 GENERAL TESTING REQUIREMENTS P


4.1 General P
4.2 General conditions f or testing P
4.2.1 Sequence of tests P
4.2.2 Ref erence test conditions P
4.2.2.1 Environmental conditions Max. 60°C rated ambient P
temperature tested.
4.2.2.2 State of equipment P
4.2.2.3 Position of equipment Be f ixed in accordance with P
the manuf acturer’s instruction
4.2.2.4 Accessories P
4.2.2.5 Covers and removable parts N/A
4.2.2.6 Mains supply (see appended table 4.2.2.6) P
a) Voltage:
b) Frequency:
c) Polarity:
d) Earthing:
e) Over-current Protection:
4.2.2.7 Supply ports other than the mains P
4.2.2.7.1 Photovoltaic supply sources (see appended table 4.2.2.7) P
a) Open circuit voltage:
b) Short-circuit current:
4.2.2.7.2 Battery inputs N/A
4.2.2.8 Conditions of loading f or output ports P
4.2.2.9 Earthing terminals P
4.2.2.10 Controls N/A
4.2.2.11 Available short circuit current P
4.3 Thermal testing (see appended table 4.3) P
4.3.1 General P
4.3.2 Maximum temperatures P
4.3.2.1 General P
4.3.2.2 Touch temperatures P
4.3.2.3 Temperature limits f or mounting surf aces P
4.4 Testing in single f ault condition (see appended table 4.4) P
4.4.1 General P
4.4.2 Test conditions and duration f or testing under f ault P
conditions

TRF No. IEC62109_1B


Page 11 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

4.4.2.1 General P
4.4.2.2 Duration of tests P
4.4.3 Pass/f ail criteria f or testing under f ault conditions P
4.4.3.1 Protection against shock hazard P
4.4.3.2 Protection against the spread of f ire P
4.4.3.3 Protection against other hazards P
4.4.3.4 Protection against parts expulsion hazards P
4.4.4 Single f ault conditions to be applied (See appended tables) P
4.4.4.1 Component f ault tests P
4.4.4.2 Equipment or parts f or short-term or intermittent Not f or short-term or N/A
operation intermittent operation
4.4.4.3 Motors P
4.4.4.4 Transf ormer short circuit tests P
4.4.4.5 Output short circuit P
4.4.4.6 Backf eed current test f or equipment with more than Considered P
one source of supply
4.4.4.7 Output overload P
4.4.4.8 Cooling system f ailure Blanketing test f or the P
heatsink according to IEC
62109-2 Clause 4.4.4.17
4.4.4.9 Heating devices No heating devices N/A
4.4.4.10 Saf ety interlock systems No saf ety interlock N/A
4.4.4.11 Reverse d.c. connections Reverse DC+ and DC-, the P
PCE cannot start-up. No
damaged.
4.4.4.12 Voltage selector mismatch No voltage selector N/A
4.4.4.13 Mis-wiring with incorrect phase sequence or polarity P
4.4.4.14 Printed wiring board short-circuit test P
4.5 Humidity preconditioning (see appended table 7.5) P
4.5.1 General P
4.5.2 Conditions 95% R.H. 40℃. 48H P

4.6 Backf eed voltage protection P


4.6.1 Backf eed tests under normal conditions The max. DC input and output P
are less than 60V,
disconnected DC inputs and
main
4.6.2 Backf eed tests under single-f ault conditions PV input is separated f rom P
Main with basic insulation
under normal and single-f ault
conditions with disconnection

TRF No. IEC62109_1B


Page 12 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

method evaluated to IEC


62109-2

Also, is
presented on the marking
label means that “Af ter
disconnect must wait f or 5
mins can touch with PCE
terminal”
4.6.3 Compliance with backf eed tests P
4.7 Electrical ratings tests (see appended table 4.2.2.6) P
4.7.1 Input ratings P
4.7.1.1 Measurement requirements f or DC input ports P
4.7.2 Output ratings P

5 MARKING AND DOCUMENTATION P


5.1 Marking P
5.1.1 General P
Equipment shall bear markings as specif ied in 5.1 Label are marked on PCE and P
and 5.2 graphic symbol is explained in
user manual
Graphic symbols may be used and shall be in P
accordance with Annex C or IEC 60417 as
applicable.
Graphic symbols shall be explained in the P
documentation provided with the PCE.
5.1.2 Durability of markings P
Markings required by this clause to be located on Af ter this test, the markings P
the PCE shall remain clear and legible under are clearly legible. There was
conditions of NORMAL USE and resist the ef f ects neither loose nor curling on
of cleaning agents specif ied by the manuf acturer the edge of label.
5.1.3 Identif ication P
The equipment shall, as a minimum, be P
permanently marked with:
a) the name or trade mark of the manuf acturer or Trade mark: P
supplier GROWATT
b) model number, name or other means to identif y P
the equipment
c) a serial number, code or other marking allowing Within three months P
identif ication of manuf acturing location and the
manuf acturing batch or date within a three
month time period.
5.1.4 Equipment ratings See below P

TRF No. IEC62109_1B


Page 13 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

Unless otherwise specif ied in another part of IEC P


62109, the f ollowing ratings, as applicable shall be
marked on the equipment:
− input voltage, type of voltage (a.c. or d.c.), Ref er to the marking label P
f requency, and max. continuous current f or
each input
– output voltage, type of voltage (a.c. or d.c.), Ref er to the marking label P
f requency, max. continuous current, and f or a.c.
outputs, either the power or power f actor f or
each output
– the ingress protection (IP) rating as in 6.3 below IP 66 P
5.1.5 Fuse identif ication N/A
Marking shall be located adjacent to each f use or N/A
f useholder, or on the f useholder, or in another
location provided that it is obvious to which f use the
marking applies, giving the f use current rating and
where f uses of different voltage rating value could
be f itted, the f use voltage rating.
Where f uses with special f using characteristics N/A
such as time delay or breaking capacity are
necessary, the type shall also be indicated
For f uses not located in operator access areas and N/A
f or soldered-in fuses located in operator access
areas, it is permitted to provide an unambiguous
cross-ref erence (f or example, F1, F2, etc.) to the
servicing instructions which shall contain the relevant
inf ormation.
5.1.6 Terminals, Connections, and Controls P
If necessary f or saf ety, an indication shall be given The indications were provided P
of the purpose of Terminals, connectors, controls, adjacent to PV connector,
and indicators, and their various positions, including AC terminal and DC quick
any connections f or coolant f luids such as water Connector.
and drainage. The symbols in Annex C may be
used, and where there is insuf f icient space, symbol
9 of Annex C may be used.
Push-buttons and actuators of emergency stop P
devices, and indicator lamps used only to indicate a
warning of danger or the need f or urgent action
shall be coloured red.
A multiple-voltage unit shall be marked to indicate The PCE is not intended to N/A
the particular voltage f or which it is set when connect to multiple-voltage
shipped f rom the f actory. The marking is allowed to and there is no voltage setting
be in the f orm of a paper tag or any other non- device.
permanent material.
A unit with d.c. terminals shall be plainly marked The “+” and “-” marking were P
indicating the polarity of the connections, with: provided adjacent to the PV
input terminals
− the sign “+“ f or positive and “-„ f or negative; or P

TRF No. IEC62109_1B


Page 14 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

− a pictorial representation illustrating the proper Not provided N/A


polarity where the correct polarity can be
unambiguously determined f rom the
representation
5.1.6.1 Protective Conductor Terminals P
The means of connection f or the protective earthing P
conductor shall be marked with:
− symbol 7 of Annex C; or P
− the letters “PE“; or N/A
− the colour coding green-yellow. P

5.1.7 Switches and circuit-breakers Approved switch was used f or P


all models.
The on and of f -positions of switches and circuits “ON” indicated the on-position P
breakers shall be clearly marked. If a push-button of DC switch.
switch is used as the power switch, symbols 10 and
“OFF” indicated the of f-
16 of Annex C may be used to indicate the on-
position, or symbols 11 and 17 to indicate the of f - position of DC switch
position, with the pair of symbols (10 and 16, or 11
and 17) close together.
5.1.8 Class ‫ ׀׀‬Equipment Class I N/A
Equipment using Class ‫ ׀׀‬protective means N/A
throughout shall be marked with symbol 12 of
Annex C. Equipment which is only partially
protected by DOUBLE INSULATION or
REINFORCED INSULATION shall not bear symbol
12 of Table Annex C.
Where such equipment has provision f or the N/A
connection of an earthing conductor f or f unctional
reasons (see 7.3.6.4) it shall be marked with
symbol 6 of Annex C
5.1.9 Terminal boxes f or External Connections No such parts N/A
Where required by note 1 of Table 2 as a result of N/A
high temperatures of terminals or parts in the wiring
compartment, there shall be a marking, visible
beside the terminal bef ore connection, of either:
a) the minimum temperature Rating and size of N/A
the cable to be connected to the TERMINALS;
or
b) a marking to warn the installer to consult the N/A
installation instruction. Symbol 9 of Table D -1 is
an acceptable marking
5.2 Warning markings P
5.2.1 Visibility and legibility requirements f or warning P
markings
Warning markings shall be legible, and shall have P

TRF No. IEC62109_1B


Page 15 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

minimum dimensions as f ollows:


− Printed symbols shall be at least 2,75 mm high P
− Printed text characters shall be at least 1.5 mm P
high and shall contrast in colour with the
background
− Symbols or text that are moulded, stamped or P
engraved in a material shall have a character
height of at least 2,0 mm, and if not contrasting
in colour f rom the background, shall have a
depth or raised height of at least 0,5 mm.
If it is necessary to ref er to the instruction manual to The manual provides P
preserve the protection af f orded by the equipment, necessary inf ormation f or
the equipment shall be marked with symbol 9 of warning marking
Annex C
Symbol 9 of Annex C is not required to be used P
adjacent to symbols that are explained in the
manual
5.2.2 Content f or warning markings P
5.2.2.1 Ungrounded heat sinks and similar parts Grounded heatsink N/A
An ungrounded heat sink or other part that may be N/A
mistaken f or a grounded part and involves a risk of
electric shock in accordance with 7.3 shall be
marked with symbol 13 of Annex C, or equivalent.
The marking may be on or adjacent to the heat sink
and shall be clearly visible when the PCE is
disassembled to the extent that a risk of contact
with the heat sink exists.
5.2.2.2 Hot Surf aces P
A part of the PCE that exceeds the temperature The symbol 14 of Annex C P
limits specif ied in 4.3.2 shall be marked with symbol provided on the warning label
14 of Annex C or equivalent. which located on the surf ace
of enclosure
5.2.2.3 Coolant Coolant is not used N/A
A unit containing coolant that exceeds 70 °C shall N/A
be legibly marked externally where readily visible
af ter installation with symbol 15 of Annex C. The
documentation shall provide a warning regarding
the risk of burns f rom hot coolant, and either:
a) statement that coolant system servicing is to be N/A
done only by SERVICE PERSONNEL, or
b) instructions f or saf e venting, draining, or N/A
otherwise working on the cooling system, if
these operations can be perf ormed without
OPERATOR access to HAZARDS internal to
the equipment
5.2.2.4 Stored energy P

TRF No. IEC62109_1B


Page 16 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

Where required by 7.3.9.2 or 7.4.2 the PCE shall P


be marked with Symbol 21 of Annex C and the time
to discharge capacitors to saf e voltage and energy
levels shall accompany the symbol.
5.2.2.5 Motor guarding N/A
Where required by 8.2 a marking shall be provided N/A
where it is visible to service personnel bef ore
removal of a guard, warning of the hazard and
giving instructions f or saf e servicing (f or example
disconnection of the source bef ore removing the
guard).
5.2.3 Sonic hazard markings and instructions Hazardous noise is not N/A
produced
If required by 10.2.1 a PCE shall: N/A
a) be marked to warn the operator of the sonic N/A
pressure hazard; or
b) be provided with installation instructions that N/A
specif y how the installer can ensure that the
sound pressure level f rom equipment at its
point of use af ter installation, will not reach a
value, which could cause a hazard. These
instructions shall include the measured sound
pressure level, and shall identif y readily
available and practicable protective materials or
measures which may be used.
5.2.4 Equipment with multiple sources of supply P
A PCE with connections f or multiple energy Marked with symbol 13 of P
sources shall be marked with symbol 13 of Annex Annex C and explained in
C and the manual shall contain the inf ormation User manual.
required in 5.3.4.
The symbol shall be located on the outside of the P
unit or shall be prominently visible behind any cover
giving access to hazardous parts.
5.2.5 Excessive touch current N/A
Where required by 7.3.6.3.7 the PCE shall be The touch current does not N/A
marked with symbol 15 of Annex C. See also 5.3.2 exceed limited
f or inf ormation to be provided in the installation
manual.
5.3 Documentation P
5.3.1 General P
The documentation provided with the PCE shall P
provide the inf ormation needed f or the saf e
operation, installation, and (where applicable)
maintenance of the equipment. The documentation
shall include the items required in 5.3.2 through
5.3.4, and the f ollowing:

TRF No. IEC62109_1B


Page 17 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

a) explanations of equipment makings, including P


symbols used
b) location and f unction of terminals and controls P
c) all ratings or specif ications that are necessary P
to saf ely install and operate the PCE, including
the f ollowing environmental ratings along with
an explanation of their meaning and any
resulting installation requirements:
– ENVIRONMENTAL CATEGORY as per 6.1 Outdoor P
– WET LOCATIONS classif ication f ort he Suitable f or wet location P
intended external environment as per 6.1
– POLLUTION DEGREE classif ication f or the Outside: PD3, Inside: PD2 P
intended external environment as per 6.2
– INGRESS PROTECTION rating as per 6.3 IP 66 P
– Ambient temperature and relative humidity Max. +60℃ and 100% R.H. P
ratings
– MAXIMUM altitude rating 4000m P
– OVERVOLTAGE CATEGORY assigned to OVC II(PV), OVC III(Mains) P
each input and output port as per
7.3.7.1.2, accompanied by guidance
regarding how to ensure that the installation
complies with the required overvoltage
categories;
d) a warning that when the photovoltaic array is P
exposed to light, it supplies a d.c. voltage to the
PCE
5.3.1.1 Language English provide P
Instructions related to saf ety shall be in a language For other country language N/A
that is acceptable in the country where the f urther evaluated is needed
equipment is to be installed.
5.3.1.2 Format P
In general, the documentation must be provided in Printed f orm provided P
printed f orm and is to be delivered with the
equipment.
For equipment which requires the use of a N/A
computer f or both installation and operation,
documentation may be provided in electronic
f ormat without accompanying printed f ormat.
5.3.2 Inf ormation related to installation P
The documentation shall include installation and P
where applicable, specif ic commissioning
instructions and, if necessary f or saf ety, warnings
against hazards which could arise during
installation or commissioning of the equipment. The
inf ormation provided shall include:

TRF No. IEC62109_1B


Page 18 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

a) assembly, location, and mounting P


requirements:
b) ratings and means of connection to each P
source of supply and any requirements related
to wiring and external controls, colour coding of
leads, disconnection means, or overcurrent
protection needed, including instructions that
the installation position shall not prevent access
to the disconnection means;
c) ratings and means of connection of any outputs P
f rom the PCE, and any requirements related
to wiring and externals controls, colour coding
of leads, or overcurrent protection needed;
d) explanation of the pin-out of connectors f or P
external connections, unless the connector is
used f or a standard purpose (e.g. RS 232)
e) ventilation requirements; P
f) requirements f or special services, f o r example N/A
cooling liquid;
g) instructions and inf ormation relating to sound N/A
pressure level if required by 10.2.1;
h) where required by 14.8.1.3, instructions f or the N/A
adequate ventilation of the room or location in
which PCE containing vented or valve-
regulated batteries is located, to prevent the
accumulation of hazardous gases;
i) tightening torque to be applied to wiring P
terminals;
j) values of backf eed short-circuit currents The backf eed current N/A
available f rom the PCE on input and output was prevented.
conductors under f ault conditions, if those
currents exceed the max. rated current of the
circuit, as per 4.4.4.6;
k) f or each input to the PCE, the max value of P
short-circuit current available f rom the source,
f or which the PCE is designed; and
l) compatibility with RCD and RCM; Internal RCM is used N/A
m) instructions f or protective earthing, including the Touch current is not N/A
inf ormation required by 7.3.6.3.7 if a second exceeding limit
protective earthing conductor is to be installed:
n) where required by 7.3.8, the installation N/A
instructions shall include the f ollowing or
equivalent wording:
“This product can cause a d.c. current in the Internal RCM is used N/A
external protective earthing conductor. Where a
residual current-operated protective (RCD) or
monitoring (RCM) device is used f or protection

TRF No. IEC62109_1B


Page 19 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

in a case of direct or indirect contact, only an


RCD or RCM of Type B is allowed on the
supply side of this product.“
o) f or PCE intended to charge batteries, the N/A
battery nominal voltage rating, size, and type
p) PV array conf iguration inf ormation, such as PV array should be f loating P
ratings, whether the array is to be grounded or conf iguration to be connected
f loating, any external protection devices to PCE, relevant inf ormation h
needed, etc. ad shown on the installation
manual.
5.3.3 Inf ormation related to operation P
Instructions f or use shall include any operating P
instructions necessary to ensure saf e operation,
including the f ollowing, as applicable:
− Instructions f or adjustment of controls including P
the ef f ects of adjustment;
− Instructions f or interconnection to accessories P
and other equipment, including indication of
suitable accessories, detachable p arts and any
special materials;
− Warnings regarding the risk of burns f rom P
surf aces permitted to exceed the temperature
limits of 4.3.2 and required operator actions to
reduce the risk; and
− Instructions, that if the equipment is used in a P
manner not specif ied by the manuf acturer, the
protection provided by the equipment may be
impaired.
5.3.4 Inf ormation related to maintenance P
Maintenance instructions shall include the P
f ollowing:
− Intervals and instructions f or any preventive P
maintenance that is required to maintain saf ety
(f or example air f ilter replacement or periodic
re-tightening of terminals);
− Instructions f or accessing operator access No such part P
areas, if any are present, including a warning
not to enter other areas of the equipment;
− Part numbers and instructions f or obtaining any N/A
required operator replaceable parts;
− Instructions f or saf e cleaning (if recommended) N/A
− Where there is more than one source of supply P
energizing the PCE, inf ormation shall be
provided in the manual to indicate which
disconnect device or devices are required to be
operated in order to completely isolate the

TRF No. IEC62109_1B


Page 20 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

equipment.
5.3.4.1 Battery maintenance No such parts N/A
Where required by 14.8.5, the documentation shall N/A
include the applicable items f rom the f ollowing list
of instructions regarding maintenance of batteries:
− Servicing of batteries should be perf ormed or N/A
supervised by personnel knowledgeable about
batteries and the required precautions
− When replacing batteries, replace with the N/A
same type and number of batteries or battery
packs
− General instructions regarding removal and N/A
installation of batteries
− CAUTION: Do not dispose of batteries in a f ire. N/A
The batteries may explode.
− CAUTION: Do not open or damage batteries. N/A
Released electrolyte is harmf ul to the skin and
eyes. It may be toxic.
− CAUTION: A battery can present a risk of N/A
electrical shock and high short-circuit current.
The f ollowing precautions should be observed
when working on batteries:
a) Remove watches, rings, or other metal objects. N/A
b) Use tools with insulated handles. N/A
c) Wear rubber gloves and boots. N/A
d) Do not lay tools or metal parts on top of N/A
batteries
e) Disconnect charging source prior to connecting N/A
or disconnecting battery terminals
f) Determine if battery is inadvertently grounded. N/A
If inadvertently grounded, remove source f rom
ground. Contact with any part of a grounded
battery can result in electrical shock. The
likelihood of such shock can be reduced if such
grounds are removed during installation and
maintenance (applicable to equipment and
remote battery supplies not having a grounded
supply circuit).
6 ENVIRONMENTAL REQUIREMENTS AND CONDITIONS P
The manuf acturer shall rate the PCE f or the P
f ollowing environmental conditions:
– ENVIRONMENTAL CATEGORY, as in 6.1 Outdoor used P
below
– Suitability f or WET LOCATIONS or not Yes P

TRF No. IEC62109_1B


Page 21 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

– POLLUTION DEGREE rating in 6.2 below Outside PD3, Inside PD2 P


– INGRESS PROTECTION (IP) rating, as in 6.3 IP 66 P
below
– Ultraviolet (UV) exposure rating, as in 6.4 belo w P
– Ambient temperature and relative humidity Max. 60℃, 100%R.H. P
ratings, as in 6.5 below
6.1 Environmental categories and minimum environmental conditions P
6.1.1 Outdoor P
6.1.2 Indoor, unconditioned N/A
6.1.3 Indoor, conditioned N/A
6.2 Pollution degree PD3 P
6.3 Ingress Protection IP66 P
6.4 UV exposure P
6.5 Temperature and humidity -30°C~+60°C, 0%~100% R.H. P
7 PROTECTION AGAINST ELECTRIC SHOCK AND ENERGY HAZARDS P
7.1 General P
7.2 Fault conditions Normal and single f ault P
condition are considered
7.3 Protection against electric shock P
7.3.1 General In the PCE the earthed metal P
enclosure is evaluated by
means of basic insulation f rom
DVC C circuit
DVC A circuit and unearthed
accessible parts are evaluated
by means of reinf orced
insulation f rom DVC C or
protective impedance
DVC C circuit: The PV input
and the Main output
DVC A circuit: The signal
communication output port.
7.3.2 Decisive voltage classif ication P
7.3.2.1 Use of decisive voltage class (DVC) Working voltage and P
protective measure and
considered
7.3.2.2 Limits of DVC (according table 6) Wet location is considered f or P
PCE outside only
7.3.2.3 Short-terms limits of accessible voltages under f ault P
conditions
7.3.2.4 Requirements f or protection (according table 7) Single f ault condition is P
considered
7.3.2.5 Connection to PELV and SELV circuits The external signal P

TRF No. IEC62109_1B


Page 22 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

communication ports are


considered as SELV
7.3.2.6 Working voltage and DVC P
7.3.2.6.1 General Transients and voltage P
f luctuation are disregarded.
And worst-case normal
operation condition is
considered
7.3.2.6.2 AC working voltage (see Figure 2) P
7.3.2.6.3 DC working voltage (see Figure 3) P
7.3.2.6.4 Pulsating working voltage (see Figure 4) P
7.3.3 protective separation In the PCE the earthed metal P
enclosure is evaluated by
means of basic insulation f rom
DVC C circuit
DVC A circuit and unearthed
accessible parts are evaluated
by means of reinf orced
insulation f rom DVC C or
protective impedance
DVC C circuit: The PV input
and the Main output
DVC A circuit: The signal
communication output port
Protective separation shall be achieved by: P
▪ double or reinf orced insulation, or The double or reinf orced P
insulation was provided
between: 1) PV input circuits
and communication circuits;
2) AC output circuits and
communication circuits.
▪ protective screening, i.e. by a conductive P
screen connected to earth by protective
bonding in the PCE, or connected to the
protective earth conductor itself , whereby the
screen is separated f rom live parts by at least
basic insulation, or
▪ protective impedance comprising limitation of P
current per 7.3.5.3 and of discharged energy
per 7.3.5.4, or
▪ limitation of voltage according to 7.3.5.4. N/A
The protective separation shall be f ully and P
ef f ectively maintained under all conditions of
intended use of the PCE
7.3.4 Protection against direct contact P
7.3.4.1 General P
Protection against direct contact is employed to Metal enclosure provides P

TRF No. IEC62109_1B


Page 23 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

prevent persons f rom touching live parts that do not basic insulation and PE
meet the requirements of 7.3.5 and shall be
provided by one or more of the measure given in
7.3.4.2 (enclosures and barriers) and 7.3.4.3
(insulation).
Open type sub-assemblies and devices do not N/A
require protective measures against direct contact
but the instruction provided with the equipment
must indicate that such measures must be provided
in the end equipment or in the installation.
Product intended f or installation in CLOSED Not use under this condition N/A
ELECTRICAL OPERATING AREAS, (see 3.9)
need not have protective measures against direct
contact, except as required by 7.3.4.2.4.
7.3.4.2 Protection by means of enclosures and barriers P
The f ollowing requirements apply where protection Enclosure provided to prevent P
against contact with live parts is provided by access to inside live parts
enclosures or barriers, not by insulation in
accordance with 7.3.4.3.
7.3.4.2.1 General P
Parts of enclosures and barriers that provide Secured by screws P
protection in accordance with these requirements
shall not be removable without the use of a tool
(see 7.3.4.2.3).
Polymeric materials used to meet these N/A
requirements shall also meet the requirements of
13.6
7.3.4.2.2 Access probe criteria P
Protection is considered to be achieved when the P
separation between the test probes and live parts,
when tested as described below, is as f ollows:
a) decisive voltage classif ication A, (DVC A) - the The signal is considered as P
probe may touch the live parts DVC A

b) decisive voltage classif ication B, (DVC B) - the The DVC B circuit is not P
probe must not touch bare live parts accessible by probe

c) decisive voltage classif ication C, (DVC C) – the The DVC C circuit is not P
probe must have adequate clearance to live accessible by probe
parts, based on the clearance f or Basic
insulation using the recurring peak working
voltage involved,
7.3.4.2.3 Access probe tests P
Compliance with 7.3.4.2.1 is checked by all of the P
f ollowing:
a) Inspection; and P
b) Tests with the test f inger (Figure D.1) and test P
pin (Figure D.2) of 0E, the results of which shall

TRF No. IEC62109_1B


Page 24 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

comply with the requirements of 7.3.4.2.1 a), b),


and c) as applicable. Probe tests are perf ormed
on openings in the enclosures af ter removal of
parts that can be detached or opened by an
operator without the use of a tool, including
f useholders, and with operator access doors
and covers open. It is permitted to leave lamps
in place f or this test. Connectors that can be
separated by an operator without use of a tool,
shall also be tested during and af ter
disconnection. Any movable parts are to be put
in the most unf avourable position.
The test f inger and the test pin are applied as P
above, without appreciable f orce, in every
possible position, except that f lo or-standing
equipment having a mass exceeding 40 kg is
not tilted.
Equipment intended f or building-in or rack N/A
mounting, or f or incorporation in larger
equipment, is tested with access to the
equipment limited according to the method of
mounting detailed in the installation
instructions.
c) Openings preventing the entry of the jointed No openings N/A
test f inger ( Figure E-1 of 0E) during test b)
above, are f urther tested by means of straight
unjointed test f inger (Figure E-3 of 0E), applied
with a f orce of 30 N. If the unjointed f inger
enters, the test with the jointed f inger is
repeated except that the f inger is applied using
any necessary f orce up to 30 N.
d) In addition to a) – c) above, top surf aces of N/A
enclosure shall be tested with the IP3X probe of
IEC 60529. The test probe shall not penetrate
the top surf ace of the enclosure when probed
f rom the vertical direction ±5 °only.
7.3.4.2.4 Service access areas Inside PCE are not P
intentionally touched with
energized part when
installation and maintenance.
Symbol 21 of Annex C are
marked on PCE and explained
in user manual
7.3.4.3 Protection by means of insulation of live parts The earthed enclosure is with N/A
basic insulation f rom the live
parts inside

Where the requirements of 7.3.4.2 are not met, live N/A


parts shall be provided with insulation if :
– their working voltage is greater than the N/A

TRF No. IEC62109_1B


Page 25 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

maximum limit of decisive voltage class A, or


– f or a DVC A or B circuit, protective separation N/A
f rom adjacent circuit of DVC C is not provided
(see note “‡“ under Table 7)
7.3.5 Protection in case of direct contact The single communication P
ports are direct contact and
evaluated with reinf orced
insulation f rom live part
7.3.5.1 General P
Protection in case of direct contact is required to P
ensure that contact with live parts does not produce
a shock hazard.
The protection against direct contact according to Considered P
7.3.4 is not required if the circuit contacted is
separated f rom other circuits according to 7.3.2.3,
and:
– is of decisive voltage class A and complies with The single communication P
7.3.5.2, or port is DVC A and reinf orced
insulation f rom the live part by
means of isolation transf ormer
and optocoupler
– is provided with protective impedance N/A
according to 7.3.5.3, or
– is limited in voltage according to 7.3.5.4 N/A
In addition to the measures as given in 7.3.5.2 to Considered P
7.3.5.4, it shall be ensured that in the event of error
or polarity reversal of connectors no voltages that
exceed DVC A can be connected into a circuit with
protective separation. This applies f or example to
plug-in-sub-assemblies or other plug-in devices
which can be plugged-in without the use of a tool
(key) or which are accessible without the use of a
tool.
Conf ormity is checked by visual inspection and trial P
insertion.
7.3.5.2 Protection using decisive voltage class A The communication port is P
DVC A and reinf orced
insulation f rom the live part by
means of isolation transf ormer
and optocoupler
7.3.5.3 Protection by means of protective impedance Protective impedance not N/A
used as protective separation
in the PCE
Circuits and conductive parts do not require N/A
protection against direct contact if any connection
to circuits of DVC-B or DVC-C is through protective
impedance, and the accessible circuit or part is
otherwise provided with protective separation f rom

TRF No. IEC62109_1B


Page 26 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

circuits of DVC-B or DVC-C according 7.3.3.


7.3.5.3.1 Limitation of current through protective imped ance N/A
The current available through protective imped ance N/A
to earth and between simultaneously accessible
parts, measured at the accessible live parts, shall
not exceed a value of 3,5 mA a.c. or 10 mA d.c.
under normal and single-f ault conditions.
7.3.5.3.2 Limitation of discharging energy through protective N/A
impedance
The discharging energy available between N/A
simultaneously accessible parts protected by
protective impedance shall not exceed the charging
voltage and capacitance limits given in Table 9,
which applies to both wet and dry locations, under
normal and single f ault conditions. Ref er to f igure 8.
7.3.5.4 Protection by means of limited voltages No such design N/A
That portion of a circuit that has its voltage reduced N/A
to DVC-A by a voltage divider that complies with
the f ollowing requirements, and that is otherwise
provided with protective separation f rom circuits of
DVC-B or DVC-C according to 7.3.3, does not
require protection against direct contact.
The voltage divider shall be designed so that under N/A
normal and single f ault conditions, including f aults
in the voltage division circuit, the voltage across the
output of the voltage divider does not exceed the
limit f or DVC-A.
This type of protection shall not be used in case of N/A
protective class II or unearthed circuits, because it
relies on protective earth being connected.
7.3.6 Protection against indirect contact P
7.3.6.1 General P
Protection against indirect contact is required to The earthing metal enclosure P
prevent shock- hazardous current being accessible is complied with protective
f rom conductive parts during an insulation f ailure. class I and the circuit of
This protection shall comply with the requirements communication is complied
f or protective class I (basic insulation plus with protective class II f or
protective earthing), class II (double or reinf orced accessible communication
insulation) or class III (limitation of voltages) ports

That part of a PCE meets the requirements of The earthed metal enclosure P
7.3.6.2 and 7.3.6.3 is def ined as protective class I meets this requirement
That part of a PCE meets the requirements of P
7.3.6.4 is def ined as protective class II.
That part of PCE which meets the requirements of N/A
decisive voltage class A and in which no hazardous
voltages are derived, is def ined as protective class
III. No shock hazard is present in such circuits.

TRF No. IEC62109_1B


Page 27 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

Where protection against indirect contact is The manual requires the PCE P
dependent on means provided during installation, must be securely earthed
the installation instructions shall provide details of
the required means and shall indicate the
associated hazards.
7.3.6.2 Insulation between live parts and accessible P
conductive parts
Accessible conductive parts of equipment shall be See Cl. 7.3.7.4 and Cl. 7.3.7.5 P
separated f rom live parts by insulation meeting the
requirements of Table 7 or by clearances as
specif ied in 7.3.7.4 and creepages as sp ecif ied in
7.3.7.5
7.3.6.3 Protective class I – Protective bonding and earthing P
7.3.6.3.1 General P
Equipment of protective class I shall be provided P
with protective earthing, and with protective
bonding to ensure electrical contact between
accessible conductive parts and the means of
connection f or the external protective earthing
conductor, except bonding is not required f or:
a) accessible conductive parts that are protected P
by one of the measures in 7.3.5.2 to 7.3.5.4, or
b) accessible conductive parts are separated f rom Communication circuits are P
live parts of DVC-B or -C using double or separated f rom live parts used
reinf orced insulation. double or reinf orced insulation

7.3.6.3.2 Requirements f or protective bonding P


Electrical contact with the means of connection of P
the external protective earthing conductor shall be
achieved by one or more of the f ollowing means:
a) through direct metallic contact; The connection of external P
protective earthing conductor
is direct metal contact via a
terminal with screw.
b) through other conductive parts which are not N/A
removed when the PCE or sub-units are used
as intended ;
c) through a dedicated protective bonding P
conductor;
d) through other metallic components of the PCE N/A
Where direct metallic contact is used and one or The metal enclosure is reliably P
both of the parts involved is painted or coated, the penetrated earthed
paint or coating shall be removed in the area of
contact, or reliably penetrated, to ensure metal to
metal contact.
For moving or removable parts, hinges or sliding No such design N/A
contacts designed and maintained to have a low
resistance are examples of acceptable means if

TRF No. IEC62109_1B


Page 28 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

they comply with the requirements of 7.3.6.3.3.


Metal ducts of f lexible or rigid construction and No such design N/A
metallic sheaths shall not be used as protective
bonding conductors, unless the device or material
has been investigated as suitable f or protective
bonding purposes.
7.3.6.3.3 Rating of protective bonding The alternative of 7.3.6.3.5 is P
considered.
Protective bonding shall withstand the highest P
thermal and dynamic stresses that can occur to the
PCE item(s) concerned when they are subjected to
a f ault connecting live parts to accessible
conductive parts.
The protective bonding shall remain ef f ective f or as
long as a f ault to the accessible conductive parts
persists or until an upstream protective device
removes power f rom the part.
Protective bonding shall meet f ollowing P
requirements:
a) For PCE with an overcurrent protective device N/A
rating of 16 A or less, the impedance of the
protective bonding means shall not exceed 0,1
Ω during or at the end of the test below.
b) For PCE with an overcurrent protective device N/A
rating of more than 16 A, the voltage drop in
the protective bonding test shall not exceed 2,5
V during or at the end of the test below.
As alternative to a) and b) the protective bonding The alternative of 7.3.6.3.5 is P
may designed according to the requirements f or the considered.
external protective earthing conductor in 7.3.6.3.5,
in which case no testing is required.
The impedance of protective bonding means shall N/A
be checked by passing a test current through the
bond f or a period of time as specif ied below. The
test current is based on the rating of the
overcurrent protection f or the equipment or part of
the equipment under consideration, as f ollows:
a) For pluggable equipment type A, the N/A
overcurrent protective device is that provided
external to the equipment (f or example, in the
building wiring, in the mains plug or in an
equipment rack);
b) For pluggable equipment type B and f ixed N/A
equipment, the maximum rating of the
overcurrent protective device specif ied in the
equipment installation instructions to be
provided external to the equipment;
c) For a circuit or part of the equipment f or which N/A
an overcurrent protective device is provided as

TRF No. IEC62109_1B


Page 29 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

part of the equipment, the rating of the provided


overcurrent device.
Voltages are measured f rom the pro tective earthing N/A
terminal to all parts whose protective bonding
means are being considered. The imp edance of the
protective earthing conductor is not included in the
measurement. However, if the protective earthing
conductor is supplied with the equipment, it is
permitted to include the conductor in the test circuit
but the measurement of the voltage drop is made
only f rom the main protective earthing terminal to
the accessible part required to be earthed.
On equipment where the protective earth N/A
connection to a subassembly or to a separate unit
is part of a cable that also supplies power to that
subassembly or unit, the resistance of the
protective bonding conductor in that cable is not
included in the protective bond impedance
measurements f or the subassembly or separate
unit, as shown in Figure 11. However, this option is
only permitted if the cab le is protected by a
suitably rated protective device that takes into
account the size of the conductor. Otherwise the
impedance of the protective bonding conductor
between the separate units is to be included, by
measuring to the protective earthing terminal where
the power source enters the f irst unit in the system,
as shown in Figure 12.
7.3.6.3.3.1 Test current, duration, and acceptance criteria P
The test current, duration of the test and P
acceptance criteria are as f ollows:
a) For PCE with an overcurrent protective device N/A
rating of 16 A or less, the test current is 200%
of the overcurrent protective device rating, but
not less than 32 A, applied f or 120s. The
impedance of the protective bonding means
during and at the end of the test shall not
exceed 0,1 Ω.
b) For PCE with an overcurrent protective device N/A
rating of more than 16 A, the test current is
200% of the overcurrent protective device
rating and the duration of the test is as shown
in Table 10 below. The voltage drop in the
protective bonding means, during and at the
end of the test, shall not exceed 2,5 V.
c) During and af ter the test, there shall be no P
melting, loosening, or other damage that would
impair the ef f ectiveness of the protective
bonding means.
The test current is derived f rom an a.c or d.c supply P

TRF No. IEC62109_1B


Page 30 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

source, the output of which is not earthed.


As an alternative to Table 10, where the time- N/A
current characteristic of the overcurrent protective
device that limits the f ault current in the protective
bonding means is known because the device is
either provided in the equipment or f ully specif ied in
the installation instructions, the test duration may
be based on that specif ic device’s time-current
characteristic,. The tests are cond ucted f or a
duration corresponding to the 200% current value
on the time-current characteristic.
7.3.6.3.4 Protective bonding impedance (routine test) Manuf acture declaration f or N/A
this
If the continuity of the protective bonding is N/A
achieved at any point by a single means only (f or
example a single conductor or single f astener), or if
the PCE is assembled at the installation location,
then the impedance of the protective bonding shall
also be tested as a routine test.
The test shall be as in 7.3.6.3.3, except f or the
f ollowing:
▪ the test current may be reduced to any N/A
convenient value greater than 10 A suf f icient to
allow measurement or calculation of the
impedance of the protective bonding means:
▪ the test duration may be reduced to no less N/A
than 2 s
For equipment subject to the type test in N/A
7.3.6.3.3.1a), the impedance during the routine test
shall not exceed 0,1Ω.
For equipment subject to the type test in N/A
7.3.6.3.3.1b) the impedance during the routine test
shall not exceed 2,5 V divided by the test current
required by 7.3.6.3.3.1b).
7.3.6.3.5 External protective earthing conductor P
A protective earthing conductor shall be connected The protective earthing P
at all times when power is supplied to PCE of conductor is f ixed permanently
protective class I. Unless local wiring regulations and the minimum cross-
state otherwise, the protective earthing conductor sectional area is 35mm2 f or
cross-sectional area shall be determined f rom copper or 35mm2 or 50mm2 for
Table 11 or by calculation according to IEC 60364- aluminium. Only qualif ied
5-54. personnel can install the
protective earthing.
If the external protective earthing conductor is Permanently connected N/A
routed through a plug and socket or similar means
of disconnection, it shall not be possible to
disconnect it unless power is simultaneously
removed f rom the part to be protected.
The cross-sectional area of every external P

TRF No. IEC62109_1B


Page 31 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

protective earthing conductor which does not f orm


part of the supply cable or cable enclosure shall, in
any case, be not less than:
▪ 2,5 mm²if mechanical protection is provided; N/A
▪ 4 mm²if mechanical protection is not provided. P
For cord-connected equipment, provisions shall be Not cord-connected N/A
made so that the external protective earthing equipment.
conductor in the cord shall, in the case of f ailure of
the strain-relief mechanism, be the last conductor
to be interrupted.
7.3.6.3.6 Means of connection f or the external protective External protective earthing P
earthing conductor conductors connect to the
enclosure body.
7.3.6.3.6.1 General P
The means of connection f or the external protective Considered P
earthing conductor shall be located near the
terminals f or the respective live conductors. The
means of connections shall be corrosio n-resistant
and shall be suitable f or the connection of cables
according to 7.3.6.3.5.
The means of connection f or the protective earthing
conductor shall not be used as a part of the
mechanical assembly of the equipment or f or other
connections.
A separate means of connection shall be provided
f or each external protective earthing conductor.
Connection and bonding points shall be so
designed that their current-carrying capacity is not
impaired by mechanical, chemical, or
electrochemical inf luences. Where enclosures
and/or conductors of aluminium or aluminium alloys
are used, particular attention should be given to the
problems of electrolytic corrosion.
The means of connection f or the protective earthing P
conductor shall be permanently marked with:
• symbol 7 of Annex C; or P
• the colour coding green-yellow P
Marking shall not be done on easily changeable P
parts such as screws.
7.3.6.3.7 Touch current in case of f ailure of the protective P
earthing conductor
The requirements of this sub-clause shall be P
satisf ied to maintain saf ety in case of damage to or
disconnection of the protective earthing conductor.
For pluggable equipment type A, the touch current N/A
measured in accordance with 7.5.4 shall not
exceed 3,5 mA a.c. or mA d.c.

TRF No. IEC62109_1B


Page 32 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

For all other PCE, one or more of the f ollowing Accessible parts and earthing P
measure shall be applied, unless the touch current terminal: 1.152mAac
measured in accordance with 7.5.4 using the test
network of IEC 60990 test f igure 4 shall not exceed
3,5 mA a.c. or 10 mA d.c.
a) Permanently connected wiring, and: Not exceed 3.5mA a.c. N/A
• a cross-section of the protective earthing N/A
conductor of at least 10 mm²Cu or 16 mm²
Al; or
• automatic disconnection of the supply in N/A
case of discontinuity of the protective
earthing conductor; or
• provision of an additional terminal f or a N/A
second protective earthing conductor of the
same cross-sectional area as the original
protective earthing conductor and
installation instruction requiring a second
protective earthing conductor to be
installed or
b) Connection with an industrial connector N/A
according to IEC 60309 and a minimum
protective earthing conductor cross-section of
2,5 mm²as part of a multi-conductor power
cable. Adequate strain relief shall be provided.
In addition, the caution symbol 15 of Annex C N/A
shall be f ixed to the product and the installation
manual shall provide details of the protective
earthing measures required in the installation
as required in 5.3.2.
When it is intended and allowed to connect two N/A
or more PCEs in parallel using one common PE
conductor, the above touch current
requirements apply to the maximum number of
the PCEs to be connected in parallel, unless
one of the measures in a)
or b) above is used. The maximum number of N/A
parallel PCEs is used in the testing and has to
be stated in the installation manual.
7.3.6.4 Protective Class II – Double or Reinf orced Class I N/A
Insulation
Equipment or parts of equipment designed f or Signal communication ports N/A
protective class II shall have insulation between live are evaluated with reinf orced
parts and accessible surf aces in accordance with insulation f orm live parts
7.3.4.3. The f ollowing requirements also apply: inside
• Equipment designed to protective class II shall N/A
not have means of connection f or the external
protective earthing conductor. However this
does not apply if the external protective

TRF No. IEC62109_1B


Page 33 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

earthing conductor is passed through the


equipment to equipment series-connected
beyond it. In the latter event, the external
protective earthing conductor and its means f or
connection shall be insulated with basic
insulation f rom the accessible surf ace of the
equipment and f rom circuits that employ
protective separation, extra-low voltage,
protective impedance and limited discharging
energy, according to 7.3.5. This basic insulation
shall correspond to the rated voltage of the
series-connected equipment;
• metal-encased equipment of protective class II N/A
may have provision on its enclosure f or the
connection of an equipotential bonding
conductor;
• equipment of protective class II may have N/A
provision f or the connection of an earthing
conductor f or f unctional reasons or f or damping
of overvoltages; it shall, however, be insulated
as though it is a live part;
• equipment employing protective class II shall N/A
be marked according to 5.1.8.
7.3.7 Insulation Including Clearance and Creepage P
Distance
7.3.7.1 General P
This subclause gives minimum requirements f or Considered P
insulation, based on the principles of IEC 60664.
Manuf acturing tolerances shall be taken into Considered P
account during measurement of creepage,
clearance, and insulation distance in the PCE.
Insulation shall be selected af ter consideration of Considered P
the f ollowing inf luences:
• pollution degree PD3 outside, PD2 inside P

• overvoltage category The mains circuits: OVC III P


The PV circuits: OVC II
• supply earthing system TN P
• insulation voltage PV input: max. 1100Vdc and P
Main:277Vac
• location of insulation See table 7.3.7.4 and 7.3.7.5 P
f or detail
• type of insulation See table 7.3.7.4 and 7.3.7.5 P
f or detail
Compliance of insulation, creepage distances, and P
clearance distances, shall be verif ied by
measurement or visual inspection, and the tests of
7.5.

TRF No. IEC62109_1B


Page 34 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

7.3.7.1.3 Supply earthing systems P


Three basic types of earthing system are described Inverter is intended to install in P
in IEC 60364-1. They are: TN system
• TN system: has one point directly earthed, the P
accessible conductive parts of the installation
being connected to that point by protective
conductors. Three types of TN systems, TN-C,
TN-S and TN-C-S, are def ined according to the
arrangement of the neutral and protective
conductor.
• TT system: has one point directly earthed, the N/A
accessible conductive parts of the installation
being connected to earth electrodes electrically
independent of the earth electrodes of the
power system;
• IT system: has all live parts isolated f rom earth N/A
or one point connected to earth through an
impedance, the accessible conductive parts of
the installation being earthed independently or
collectively to the earthing system.
7.3.7.1.4 Insulation voltages See table 7.3.7.4 and 7.3.7.5 P
f or detail
Table 12 makes use of the circuit system voltage P
and overvoltage category to def ine the impulse
withstands voltage and the temporary overvoltage.
7.3.7.2 Insulation between a circuit and its surroundings P
7.3.7.2.1 General P
7.3.7.2.2 Circuits connected directly to the mains System voltage f or mains is P
300Vrms according to table 1
7.3.7.2.3 Circuits other than mains circuits P
7.3.7.2.4 Insulation between circuits P
7.3.7.3 Functional insulating P
7.3.7.4 Clearance distances (see appended table 7.3.7) P
7.3.7.4.1 Determination Designed f or use in altitudes P
4000m and below.
7.3.7.4.2 Electric f ield homogeneity Inhomogeneous electric f ield N/A
is considered f or PCE
7.3.7.4.3 Clearance to conductive enclosures P
7.3.7.5 Creepage distances (see appended table 7.3.7) P
7.3.7.5.1 General P
7.3.7.5.2 Voltage If Working voltage less than P
system voltage, system
voltage is used f or creepage
according to IEC60664-1

TRF No. IEC62109_1B


Page 35 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

7.3.7.5.3 Materials Certif ied PWB used. Other P


materials are considered IIIb.
The inside parts are
considered Pollution degree 2
7.3.7.6 Coating N/A
7.3.7.7 PWB spacings f or f unctional insulating V-0 and short circuit test are P
considered
7.3.7.8 Solid insulating (see appended table 7.3.7) P
7.3.7.8.1 General P
7.3.7.8.2 Requirements f or electrical withstand capab ility of P
solid insulation
7.3.7.8.2.1 Basic, supplemental, reinf orced, and double P
insulation
7.3.7.8.2.2 Functional insulation P
7.3.7.8.3 Thin sheet or tape material P
7.3.7.8.3.1 General P
7.3.7.8.3.2 Material thickness not less than 0,2 mm Impulse test and voltage test P
are considered f or insulation
on IGBT as basic insulation
7.3.7.8.3.3 Material thickness less than 0,2 mm N/A
7.3.7.8.3.4 Compliance N/A
7.3.7.8.4 Printed wiring boards P
7.3.7.8.4.1 General P
7.3.7.8.4.2 Use of coating materials N/A
7.3.7.8.5 Wound components Varnish is not considered as P
insulation and voltage test
perf ormed as routine test.
7.3.7.8.6 Potting materials N/A
7.3.7.9 Insulation requirements above 30 kHz N/A
7.3.8 Residual Current-operated protective (RCD) or Internal RCM is used. An P
monitoring (RCM) device compatibility external built RCD is not
necessary
RCD and RCM are used to provide protection N/A
against insulation f aults in some domestic and
industrial installations, additional to that provided by
the installed equipment.
7.3.9 Capacitor discharge P
7.3.9.1 Operator access area Accessible signal P
communication ports are
DVC-A circuit.
Equipment shall be so designed that there is no risk P
of electric shock in operator access areas f rom

TRF No. IEC62109_1B


Page 36 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

charge stored on capacitors af ter disconnection of


the PCE.
7.3.9.2 Service access areas Inside capacitor discharge to P
DVC A and no energy hazard
level within 300s
Capacitors located behind panels that are Warning symbol 21 of annex P
removable f or servicing, installation, or C is marked on PCE with
disconnection shall present no risk of electric shock 5min.
or energy hazard f rom charge stored on capacitors
af ter disconnection of the PCE.
7.4 Protection against energy hazards P
7.4.1 Determination of hazardous energy level No such high energy level P
presented in the operator
access area.
A hazardous energy level is considered to exist if P
a) The voltage is 2 V or more, and power available Considered P
af ter 60 s exceeds 240 VA.
b) The stored energy in a capacitor is at a voltage. Considered P
U of 2 V or more, and the stored energy. E,
calculated f rom the f ollowing equation, exceeds
20J:

E = 0,5 CU²
7.4.2 Operator Access Areas No energized parts accessible P
to user
Equipment shall be so designed that there is no risk P
of energy hazard in operator access areas f rom
accessible circuits.
7.4.3 Services Access Areas The capacitor inside the P
equipment stored hazardous
energy. A symbol 21 of Annex
C is provided.
7.5 Electrical tests related to shock hazard (see appended table 7.5) P
7.5.1 Impulse voltage test (type test) P
7.5.2 Voltage test (dielectric strength test) P
7.5.2.1 Purpose of test P
7.5.2.2 Value and type of test voltage P
7.5.2.3 Humidity pre-conditioning P
7.5.2.4 Perf orming the voltage test P
7.5.2.5 Duration of the a.c. or d.c. voltage test P
7.5.2.6 Verif ication of the a.c. or d.c. voltage test P
7.5.3 Partial discharge test P
7.5.4 Touch current measurement (type test) P

TRF No. IEC62109_1B


Page 37 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

The touch current shall be measured if required by (see appended table P


7.3.6.3.7 and shall not be greater than 3.5 mA a.c. 7.3.6.3.7)
or 10 mA d.c. or special measures of protection as
given in 7.3.6.3.7 are required.
For type tests on PCE f or which wet locations P
requirements apply according to 6.1, the humidity
pre-conditioning of 4.5 shall be perf ormed
immediately prior to the touch current test.
7.5.5 Equipment with multiple sources of supply P
8 PROTECTION AGAINST MECHANICAL HAZARDS P
8.1 General P
Operation shall not lead to a mechanical HAZARD No mechanical hazards under P
in NORMAL CONDITION or SINGLE FAULT the normal or single f ault
CONDITION. condition.
Edges, projections, corners, openings, guards,
handles and the like, that are accessible to the
operator shall be smooth and rounded so as not to
cause injury during normal use of the equipment.
Conf ormity is checked as specif ied in 8.2 to 8.6. P
8.2 Moving parts P
Moving parts shall not be able to crush, cut or P
pierce parts of the body of an OPERATOR likely to
contact them, nor severely pinch the OPERATOR's
skin. Hazardous moving parts of equipment, that is
moving parts which have the potential to cause
injury, shall be so arranged, enclosed or guarded
as to provide adequate protection against the risk
of personal injury.
8.2.1 Protection of service persons P
Protection shall be provided such that unintentional P
contact with hazardous moving parts is unlikely
during servicing operations. If a guard over a
hazardous moving part may need to be removed
f or servicing, the marking of symbol 15 of Table D-1
shall be applied on or near the guard.
8.3 Stability N/A
Equipment and assemblies of equipment not Wall mounted N/A
secured to the building structure bef ore operation
shall be physically stable in NORMAL USE.
8.4 Provisions f or lif ting and carrying P
If carrying handles or grips are f itted to, or supplied P
with, the equipment, they shall be capable of
withstanding a f orce of f our times the weight of the
equipment.
Equipment or parts having a mass of 18 kg or more P
shall be provided with a means f or lif ting and

TRF No. IEC62109_1B


Page 38 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

carrying or directions shall be given in the


manuf acturer's documentation.
8.5 Wall mounting P
Mounting brackets on equipment intended to be P
mounted on a wall or ceiling shall withstand a f orce
of f our times the weight of the equipment.
8.6 Expelled parts N/A
Equipment shall contain or limit the energy of parts N/A
that could cause a HAZARD if expelled in the event
of a f ault.
9 PROTECTION AGAINST FIRE HAZARDS P
9.1 Resistance to f ire P
This subclause specif ies requirements intended to Considered P
reduce the risk of ignition and the spread of f lame,
both within the equipment and to the outside, by the
appropriate use of materials and components and
by suitable construction.
9.1.1 Reducing the risk of ignition and spread of f lame P
For equipment or a portion of equipment, there are Method 1 used P
two alternative methods of providing protection
against ignition and spread of f lame that could
af f ect materials, wiring, wound components and
electronic components such as integrated circuits,
transistors, thyristors, diodes, resistors and
capacitors.
9.1.2 Conditions f or a f ire enclosure P
A FIRE ENCLOSURE is required f or equipment or P
parts of equipment f or which Method 2 is not f ully
applied and complied with.
9.1.2.1 Parts requiring a f ire enclosure P
Except where Method 2 is used, or as permitted in P
9.1.2.2, the f ollowing are considered to have a risk
of ignition and, theref ore, require a FIRE
ENCLOSURE:
– components in PRIMARY CIRCUITS P
– components in SECONDARY CIRCUITS P
supplied by power sources which exceed the
limits f or a LIMITED POWER SOURCE as
specif ied in 9.2;
– components in SECONDARY CIRCUITS N/A
supplied by a LIMITED POWER SOURCE as
specif ied in 9.2, but not mounted on a material
of FLAMMABILITY CLASS V-1;
– components within a power supply unit or N/A
assembly having a limited power output

TRF No. IEC62109_1B


Page 39 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

complying with the criteria f or a LIMITED


POWER SOURCE as specif ied in 9.2, including
overcurrent protective devices, limiting
impedances, regulating networks and wiring, up
to the point where the LIMITED POWER
SOURCE output criteria are met;
– components having unenclosed arcing parts, Enclosed relay N/A
such as open switch and relay contacts and
commutators, in a circuit at HAZARDOUS
VOLTAGE or at a HAZARDOUS ENERGY
LEVEL; and
– insulated wiring, except as permitted in 9.1.2.2. PVC wire N/A
9.1.2.2 Parts not requiring a f ire enclosure N/A
9.1.3 Materials requirements f or protection against f ire P
hazard
9.1.3.1 General P
ENCLOSURES, components and other parts shall P
be so constructed, or shall make use of such
materials, that the propagation of fire is limited.
9.1.3.2 Materials f or f ire enclosures P
If an enclosure material is not classif ied as Metal enclosure P
specif ied below, a test may be perf ormed on the
f inal enclosure or part of the enclosure, in which
case the material shall additionally be subjected to
periodic SAMPLE testing.
9.1.3.3 Materials f or components and other parts outside P
f ire enclosures
Except as otherwise noted below, materials f or P
components and other parts (including
MECHANICAL ENCLOSURES, ELECTRICAL
ENCLOSURES and DECORATIVE PARTS);
located outside FIRE ENCLOSURES, shall be of
FLAMMABILITY CLASS HB.
9.1.3.4 Materials f or components and other parts inside f ire P
enclosures
9.1.3.5 Materials f or air f ilter assemblies N/A
9.1.4 Openings in f ire enclosures No openings N/A
9.1.4.1 General N/A
For equipment that is intended to be used or N/A
installed in more than one orientation as specif ied
in the product documentation, the f ollowing
requirements apply in each orientation.
These requirements are in addition to those in the N/A
f ollowing sections:
– 7.3.4, Protection against direct contact; N/A

TRF No. IEC62109_1B


Page 40 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

– 7.4, Protection against energy hazards; N/A


– 13.5, Openings in enclosures N/A
9.1.4.2 Side openings treated as bottom openings N/A
9.1.4.3 Openings in the bottom of a f ire enclosure N/A
The bottom of a FIRE ENCLOSURE or individual N/A
barriers, shall provide protection against emission
of f laming or molten material under all internal
parts, including partially enclosed components or
assemblies, f or which Method 2 of 9.1.1 has not
been f ully applied and complied with.
9.1.4.4 Equipment f or use in a CLOSED ELECTRICAL N/A
OPERATING AREA
The requirements of 9.1.4.3 do not apply to FIXED N/A
EQUIPMENT intended only f or use in a CLOSED
ELECTRICAL OPERATING AREA and to be
mounted on a concrete f loor or other non-
combustible surf ace. Such equipment shall be
marked as f ollows:
WARNING: FIRE HAZARD SUITABLE FOR N/A
MOUNTING ON CONCRETE OR OTHER NON-
COMBUSTIBLE SURFACE ONLY
9.1.4.5 Doors or covers in f ire enclosures N/A
9.1.4.6 Additional requirements f or openings in N/A
transportable equipment
9.2 LIMITED POWER SOURCES N/A
9.2.1 General N/A
9.2.2 Limited power source tests N/A
9.3 Short-circuit and overcurrent protection P
9.3.1 General P
The PCE shall not present a hazard, under short- The circumstances of short- P
circuit or overcurrent conditions at any port, circuit and overcurrent are
including phase-to-phase, phase-to-earth and protected by the circuits
phase-to-neutral, and adequate inf ormation shall be design. When short-circuit
provided to allow proper selection of external wiring or overcurrent of components
and external protective devices. occurred, the PCE will
shutdown and
disconnect f rom the grid
immediately.
9.3.2 Protection against short-circuits and overcurrents DC wire are designed f or the P
shall be provided f or all input circuits, and f or output short circuit rating of the array
circuits that do not comply with the requirements f or Short-circuit was occurred at
limited power sources in 9.2, except f or circuits in PV input and DC terminal
which no overcurrent hazard is presented by short-
circuits and overloads.
9.3.3 Protective devices provided or specif ied shall have P
adequate breaking capacity to interrupt the

TRF No. IEC62109_1B


Page 41 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

maximum short circuit current specif ied f or the port


to which they are connected. If protection that is
provided integral to the PCE f o r an input port is not
rated f or the short-circuit current of the circuit in
which it is used, the installation instructions shall
specif y that an upstream protective device, rated
f or the prospective short-circuit current of that port,
shall be used to provide backup protection.
10 PROTECTION AGAINST SONIC PRESSURE HAZARDS N/A
10.1 General N/A
The equipment shall provide protection against the No sonic pressure hazards. N/A
ef f ect of sonic pressure. Conf ormity tests are
carried out if the equipment is likely to cause such
HAZARDS.
10.2 Sonic pressure and Sound level N/A
10.2.1 Hazardous Noise Levels N/A
11 PROTECTION AGAINST LIQUID HAZARDS N/A
11.1 Liquid Containment, Pressure and Leakage N/A
The liquid containment system components shall N/A
be compatible with the liquid to be used.
There shall be no leakage of liquid onto live parts N/A
as a result of :
a) Normal operation, including condensation; N/A
b) Servicing of the equipment; or N/A
c) Inadvertent loosening or detachment of hoses N/A
or other cooling system parts over time.
11.2 Fluid pressure and leakage N/A
11.2.1 Maximum pressure N/A
11.2.2 Leakage f rom parts N/A
11.2.3 Overpressure saf ety device N/A
11.3 Oil and grease N/A
12 CHEMICAL HAZARDS N/A
12.1 General N/A
13 PHYSICAL REQUIREMENTS P
13.1 Handles and manual controls P
Handles, knobs, grips, levers and the like shall be DC breaker holder f or manual P
reliably f ixed so that they will not work loose in controls.
normal use, if this might result in a hazard. Sealing
compounds and the like, other than self -hardening
resins, shall not be used to prevent loosening. If
handles, knobs and the like are used to indicate the
position of switches or similar components, it shall
not be possible to f ix them in a wrong position if this

TRF No. IEC62109_1B


Page 42 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

might result in hazard.


13.1.1 Adjustable controls No such setting control N/A
13.2 Securing of parts P
13.3 Provisions f or external connections P
13.3.1 General Certif ied PV connectors are P
used. AC terminal provided for
grid connection and secured
by a cable gland. Installation
manual provide inf ormation f or
the disconnection means
13.3.2 Connection to an a.c. Mains supply An industrial AC terminal P
used, and it is detachable with
tool
13.3.2.1 General P
For saf e and reliable connection to a MAINS See above P
supply, equipment shall be provided with one of the
f ollowing:
– terminals or leads or a non-detachable power P
supply cord f or permanent connection to the
supply; or
– a non-detachable power supply cord f or N/A
connection to the supply by means of a plug
– an appliance inlet f or connection of a N/A
detachable power supply cord; or
– a mains plug that is part of direct plug -in N/A
equipment as in 13.3.8
13.3.2.2 Permanently connected equipment P
13.3.2.3 Appliance inlets N/A
13.3.2.4 Power supply cord N/A
13.3.2.5 Cord anchorages and strain relief Cable gland used N/A
For equipment with a non-detachable power supply N/A
cord, a cord anchorage shall be supplied such that:
– the connecting points of the cord conductors N/A
are relieved f rom strain; and
– the outer covering of the cord is protected f rom N/A
abrasion.
13.3.2.6 Protection against mechanical damage N/A
13.3.3 Wiring terminals f or connection of external AC terminals P
conductors f or connection of external
conductors.
13.3.3.1 Wiring terminals P
13.3.3.2 Screw terminals P

TRF No. IEC62109_1B


Page 43 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

13.3.3.3 Wiring terminal sizes P


13.3.3.4 Wiring terminal design P
13.3.3.5 Grouping of wiring terminals P
13.3.3.6 Stranded wire P
13.3.4 Supply wiring space P
13.3.5 Wire bending space f or wires 10 mm²and greater P
13.3.6 Disconnection f rom supply sources The explanations are provided P
in the installation manual.
13.3.7 Connectors plugs and sockets The misconnection is unlikely P
f or PV connectors.
13.3.8 Direct plug-in equipment Permanently equipment. N/A
13.4 Internal wiring and connections P
13.4.1 General All wires were used suitably P
and are f ixed well to prevent
mechanical damage during
installation.
13.4.2 Routing Internal wire is routed to avoid P
sharp edge and overheat
13.4.3 Colour coding Green-yellow wire used as P
protective bonding only
13.4.4 Splices and connections P
13.4.5 Interconnections between parts of the PCE P
13.5 Openings in enclosures N/A
13.5.1 Top and side openings N/A
Openings in the top and sides of ENCLOSURES N/A
shall be so located or constructed that it is unlikely
that objects will enter the openings and create
hazards by contacting bare cond uctive parts.
13.6 Polymeric Materials P
13.6.1 General P
13.6.1.1 Thermal index or capability P
13.6.2 Polymers serving as enclosures or barriers P
preventing access to hazards
13.6.2.1 Stress relief test 72℃ P

13.6.3 Polymers serving as solid insulation P


13.6.3.1 Resistance to arcing N/A
13.6.4 UV resistance P
Polymeric parts of an OUTDOOR ENCLOSURE The LCD panel rated UV P
required f or compliance with this standard shall be resistance according to UL
suf f iciently resistance to degradation by ultra-violet 746C

TRF No. IEC62109_1B


Page 44 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

(UV) radiation
13.7 Mechanical resistance to def lection, impact, or drop P
13.7.1 General P
13.7.2 250-N def lection test f or metal enclosures P
13.7.3 7-J impact test f or polymeric enclo sures P
13.7.4 Drop test N/A
13.8 Thickness requirements f or metal enclosures N/A
13.8.1 General The enclosure complied P
with13.7.
13.8.2 Cast metal N/A
13.8.3 Sheet metal P

14 COMPONENTS P
14.1 General (see appended table 14) P
Where saf ety is involved, components shall be P
used in accordance with their specif ied RATINGS
unless a specif ic exception is made. They shall
conf orm to one of the f ollowing:
a) applicable saf ety requirements of a relevant P
IEC standard. Conf ormity with other
requirements of the component standard is not
required. If necessary f or the application,
components shall be subjected to the test of
this standard, except that it is not necessary to
carry out identical or equivalent tests already
perf ormed to check conf ormity with the
component standard;
b) the requirements of this standard and, where P
necessary f or the application, any additional
applicable saf ety requirements of the relevant
IEC component standard;
c) if there is no relevant IEC standard, the P
requirements of this standard;
d) applicable saf ety requirements of a non-IEC P
standard which are at least as high as those of
the applicable IEC standard, provided that the
component has been approved to the non-IEC
standard by a recognized testing authority.
Components such as optocouplers, capacitors, P
transf ormers, and relays connected across basic,
supplemental, reinf orced, or double insulation shall
comply with the requirements applicable f or the
grade of insulation being bridged, and if not
previously certif ied to the applicable component
saf ety standard shall be subjected to the voltage

TRF No. IEC62109_1B


Page 45 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

test of 7.5.2 as routine test.


14.2 Motor Over temperature Protection N/A
Motors which, when stopped or prevented f rom N/A
starting (see 4.4.4.3), would present an electric
shock HAZARD, a temperature HAZARD, or a f ire
HAZARD, shall be protected by an over
temperature or thermal protection device meeting
the requirements of 14.3.
14.3 Over temperature protection devices N/A
14.4 Fuse holders N/A
14.5 MAINS voltage selecting devices N/A
14.6 Printed circuit boards P
Printed circuit boards shall be made of material with V-0 P
a f lammability classif ication of V-1 of IEC 60707 or
better.
This requirement does not apply to thin-f ilm f lexible P
printed circuit boards that contain only circuits
powered f rom limited power sources meeting the
requirements of 9.2.
Conf ormity of the f lammability RATING is checked P
by inspection of data on the materials. Alternatively,
conf ormity is checked by perf orming the V-1 tests
specif ied in IEC 60707 on three samples of the
relevant parts.
14.7 Circuits or components used as transient overvoltage limiting devices N/A
If control of transient overvoltage is employed in the N/A
equipment, any overvoltage limiting component or
circuit shall be tested with the applicable impulse
withstand voltage of Table 7-10 using the test
method f rom 7.5.1 except 10 positive and 10
negative impulses are to be applied and may be
spaced up to 1 min apart.
14.8 Batteries N/A
Equipment containing batteries shall be designed to N/A
reduce the risk of f ire, explosion and chemical leaks
under normal conditions and af ter a single f ault in
the equipment including a f ault in circuitry within the
equipment battery pack.
14.8.1 Battery Enclosure Ventilation N/A
14.8.1.1 Ventilation requirements N/A
14.8.1.2 Ventilation testing N/A
14.8.1.3 Ventilation instructions N/A
14.8.2 Battery Mounting N/A
Compliance is verif ied by the application of the N/A

TRF No. IEC62109_1B


Page 46 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

f orce to the battery's mounting surf ace. The test


f orce is to be increased gradually so as to reach the
required value in 5 to 10 s, and is to be maintained
at that value f or 1 min. A non-metallic rack or tray
shall be tested at the highest normal condition
operating temperature.
14.8.3 Electrolyte spillage N/A
Battery trays and cabinets shall have an electrolyte- N/A
resistant coating.
The ENCLOSURE or compartment housing a N/A
VENTED BATTERY shall be constructed so that
spillage or leakage of the electrolyte f rom one
battery will be contained within the ENCLOSURE
and be prevented f rom:
a) reaching the PCE outer surf aces that can be N/A
contacted by the USER
b) contaminating adjacent electrical components N/A
or materials; and
c) bridging required electrical distances N/A
14.8.4 Battery Connections N/A
Reverse battery connection of the terminals shall N/A
be prevented if reverse connection could result in a
hazard within the meaning of this Standard
14.8.5 Battery maintenance instructions N/A
The inf ormation and instructions listed in 5.3.4.1 N/A
shall be included in the operator manual f or
equipment in which battery maintenance is
perf ormed by the operator, or in the service manual
if battery maintenance is to be perf ormed by
service personnel only.
14.8.6 Battery accessibility and maintainability N/A
Battery terminals and connectors shall be N/A
accessible f or maintenance with the correct
TOOLS. Batteries with liquid electrolyte, requiring
maintained shall be so located that the battery cell
caps are accessible f or electrolyte tests and
readjusting of electrolyte levels.
15 Sof tware and f irmware perf orming saf ety f unctions Ref er to annex B f or details P

TRF No. IEC62109_1B


Page 47 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

Annex A Measurement of clearances and creepage P


distances (see 7.3.7.4 and 7.3.7.5)

Annex B Programmable Equipment P


B.1 Sof tware or f irmware that perf orm saf ety critical P
f unctions
B.1.1 Firmware or sof tware that perf orms a critical saf ety P
f unction/s, the f ailure of which can result in a risk of
f ire, electric shock or other hazard as specif ied by
this standard, shall be evaluated by one of the
f ollowing means.
a) All sof tware or f irmware limits or controls shall be P
disabled bef ore the test to evaluate the hardware
circuitry during the abnormal test condition related
to the saf ety f unction.
b) Protective controls employing software or N/A
f irmware to perf orm their f unction(s), shall be so
constructed that they comply with IEC 60730-1
Annex H to address the risks identif ied in B.2.1.
B.2 Evaluation of controls employing software P

Annex C Symbols to be used in equipment markings P

Annex D Test Probes f or Determining Access P

Annex E RCDs Integrated RCM used N/A

Annex F Altitude correction f or clearances N/A

Annex G Clearance and creepage distance determination f or Only clock f or IC P


f requencies greater than 30 kHz

Annex H Measuring Instrument f or Touch Current P


Measurements
H.1 Measuring instrument P
H.2 Alternative measuring instrument N/A

Annex I Examples of Protection, Insulation, and P


Overvoltage Category Requirements f or PCE

Annex J Ultraviolet light conditioning test N/A

TRF No. IEC62109_1B


Page 48 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

4.2.2.6/4.7 TABLE: mains supply electrical data in normal condition/ Electrical ratings P
test
Type U (V) I (A) DC P (W) DC U (V) I (A) AC P (W) AC
114.00 132.60
MAX 50KTL3-XL2 185.29 259.30 48045.74 114.30 50Hz 131.87 45254.20
114.92 131.65
114.02 132.63
MAX 50KTL3-XL2 185.30 259.28 48043.35 114.31 60Hz 131.89 45252.19
114.98 131.68
126.55 132.65
MAX 50KTL3-XL2 185.23 286.87 53137.57 126.85 50Hz 131.91 50239.09
127.44 131.70
126.19 132.68
MAX 50KTL3-XL2 185.23 285.98 52972.26 126.50 60Hz 131.94 50081.78
127.12 131.73
139.01 121.70
MAX 50KTL3-XL2 185.22 288.06 53356.11 139.23 50Hz 121.02 50596.75
139.88 120.82
139.04 121.82
MAX 50KTL3-XL2 185.22 288.29 53397.62 139.27 60Hz 121.13 50635.52
139.96 120.93
114.61 132.13
MAX 50KTL3-XL2 361.46 131.70 47602.50 114.43 50Hz 131.35 45114.12
114.29 131.35
114.67 132.11
MAX 50KTL3-XL2 361.41 131.71 47599.11 114.46 60Hz 131.33 45100.19
114.31 131.34
127.22 132.18
MAX 50KTL3-XL2 361.32 145.58 52601.28 127.03 50Hz 131.38 50107.73
126.91 131.40
127.28 132.14
MAX 50KTL3-XL2 361.27 145.56 52585.16 127.06 60Hz 131.35 50088.38
126.91 131.37
139.89 119.69
MAX 50KTL3-XL2 361.26 144.48 52196.50 139.71 50Hz 118.98 49916.95
139.57 119.01
139.89 119.85
MAX 50KTL3-XL2 361.23 144.60 52232.59 139.69 60Hz 119.13 49945.51
139.53 119.14
114.61 132.14
MAX 50KTL3-XL2 652.18 73.54 47958.37 114.42 50Hz 131.36 45100.41
114.28 131.37
114.68 132.16
MAX 50KTL3-XL2 652.19 73.55 47966.87 114.46 60Hz 131.37 45102.95
114.32 131.38
127.21 132.14
MAX 50KTL3-XL2 652.08 81.18 52937.91 127.02 50Hz 131.35 50068.82
126.88 131.37

TRF No. IEC62109_1B


Page 49 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

127.29 132.21
MAX 50KTL3-XL2 652.09 81.20 52948.89 127.07 60Hz 131.41 50092.88
126.93 131.43
120.12 120.12
MAX 50KTL3-XL2 652.04 80.79 52679.02 119.40 50Hz 119.40 50036.62
119.41 119.41
139.98 120.11
MAX 50KTL3-XL2 652.07 80.85 52717.80 139.79 60Hz 119.37 50075.74
139.63 119.39
114.45 197.45
MAX 75KTL3-XL2 201.25 359.27 72302.92 115.03 50Hz 196.36 67675.09
115.17 196.14
114.46 197.68
MAX 75KTL3-XL2 201.19 359.93 72414.36 115.06 60Hz 196.61 67755.47
115.26 196.37
126.79 179.62
MAX 75KTL3-XL2 201.27 359.27 72310.96 127.29 50Hz 178.61 68167.39
127.53 178.40
126.80 179.76
MAX 75KTL3-XL2 201.21 359.82 72399.73 127.34 60Hz 178.77 68219.42
127.63 178.53
139.13 164.37
MAX 75KTL3-XL2 201.22 359.57 72353.98 139.59 50Hz 164.46 68432.29
139.93 163.23
139.15 164.52
MAX 75KTL3-XL2 201.19 360.07 72440.75 139.63 60Hz 163.61 68488.05
140.02 163.38
114.59 198.00
MAX 75KTL3-XL2 360.75 197.61 71286.89 114.29 50Hz 196.83 67547.37
114.14 196.90
114.71 198.05
MAX 75KTL3-XL2 360.59 197.85 71342.18 114.38 60Hz 196.86 67590.81
114.23 196.92
127.26 198.04
MAX 75KTL3-XL2 360.57 218.53 78795.57 126.97 50Hz 196.88 75076.17
126.82 196.96
127.40 198.04
MAX 75KTL3-XL2 360.41 218.74 78835.55 127.08 60Hz 196.85 75105.77
126.92 196.92
139.84 179.91
MAX 75KTL3-XL2 360.44 217.19 78283.58 139.58 50Hz 178.83 74968.01
139.41 178.88
139.95 179.99
MAX 75KTL3-XL2 360.39 217.41 78352.62 139.66 60Hz 178.90 75019.18
139.49 178.95
114.66 198.16
MAX 75KTL3-XL2 651.79 109.53 71392.90 114.37 50Hz 196.97 67631.45
114.22 197.00

TRF No. IEC62109_1B


Page 50 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

114.69 197.77
MAX 75KTL3-XL2 651.78 109.20 71170.86 114.35 60Hz 196.58 67457.84
114.20 196.59
127.36 198.24
MAX 75KTL3-XL2 651.65 121.14 78940.41 127.07 50Hz 197.05 75170.05
126.90 197.08
127.42 197.81
MAX 75KTL3-XL2 651.59 120.87 78753.92 127.09 60Hz 196.62 74992.16
126.93 196.63
139.86 180.34
MAX 75KTL3-XL2 651.66 120.35 78427.99 139.60 50Hz 179.25 75120.71
139.43 179.27
139.97 180.29
MAX 75KTL3-XL2 651.59 120.37 78432.12 139.65 60Hz 179.20 75097.21
139.49 179.19

TRF No. IEC62109_1B


Page 51 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

4.3 TABLE: Thermal testing P


Model : MAX 75KTL3-XL2 -
temperature t of part/at: t (C) permitted t
(C)
test Condition : PV input: PV input: PV input: PV input:
650Vdc 650Vdc 360Vdc 360Vdc
AC output: AC output: AC output: AC output: -
3~ 140Vac, f ull 3~ 110Vac, f ull 3~ 140Vac, f ull 3~ 110Vac, f ull
loading loading loading loading
Ambient 45.6 45.5 45.5 44.7 --
DC switch, outside 74.6 72.9 71.3 68.8 85
DC switch, inside 69.7 68.0 66.4 63.9 85
PV connector 68.0 67.6 64.7 63.4 90
Output terminal 76.7 76.0 73.4 71.9 90
Handle 64.6 64.9 61.3 60.8 70
Heatsink 69.0 67.3 65.7 63.2 100*
Mounting surf ace 70.6 68.9 67.3 64.7 90
Enclosure, top 70.7 69.0 67.4 64.9 100*
LCD panel 62.4 60.7 59.1 56.6 95
Internal wires: AC f ilter
76.4 74.5 73.1 70.4 105
board to output terminal
Internal wires: power 105
73.1 71.2 69.8 67.0
board to Cap board
Internal wires: INV 105
71.2 69.3 67.9 65.2
inductance to I/O board
Internal wires: I/O 105
71.9 70.0 68.6 65.9
board to AC f ilter board
Internal wires: switch to 105
68.4 66.5 65.1 62.4
input board
Internal wires: switch to 105
65.7 63.8 62.4 59.8
terminal
Boost inductance 112.0 109.3 108.7 105.3 130
Lead wires of boost
72.6 70.5 69.3 66.4 105
inductance
CT HCT1 on input
71.7 70.5 68.4 66.4 85
board
CT HCT1 of PV strings 69.9 68.7 66.6 64.6 85
PV varistor 71.9 70.6 68.6 66.4 85
Optocoupler U27 80.8 79.5 77.5 75.4 100
AC transf ormer TX2 108.3 103.3 104.9 102.7 110
DC transf ormer TX1 105.8 101.1 102.5 100.4 110
PCB near to IGBT 80.8 75.9 78.1 75.8 130
MCU TMS320F28075 79.8 74.8 77.1 74.6 For

TRF No. IEC62109_1B


Page 52 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

ref erence
For
MCU TMS320F28067 75.1 70.2 72.5 70.0
ref erence
For
CPLD chip 75.4 70.5 72.8 70.3
ref erence
PCB close to boost
86.9 82.5 83.6 80.0 130
IGBT
PCB close to INV IGBT 88.9 84.9 85.9 82.8 130
INV inductance 116.6 114.6 113.3 110.4 130
Common chock 116.8 114.8 113.5 110.6 130
LCL f ilter inductance 107.2 105.2 103.9 101.1 110
Output relay RY3 78.7 75.8 75.5 72.5 85
ISO relay 76.2 73.4 73.0 70.1 85
SPS input f ilter Cap 71.9 69.6 68.6 66.4 100
Input f ilter Cap on input 100
74.1 72.8 70.8 68.7
board
Bus thin capacitor 76.1 74.8 72.8 70.7 110
Bus cap 73.7 72.4 70.4 68.3 105
Output f ilter cap 73.1 71.8 69.8 67.7 100
Y Cap on input board 71.6 70.3 68.3 66.2 110
Y cap on PV string
73.7 72.4 70.4 68.3 110
sensor board
Y cap on I/O board 71.1 69.8 67.8 65.7 110
Output X cap 68.6 67.3 65.3 63.2 100
AC varistor 71.3 70.0 68.1 66.0 85
Fan FAN6 71.6 70.3 68.3 66.3 85
Fan FAN7 68.5 66.7 65.1 62.8 85
For
Internal temperature 68.1 67.0 65.0 62.9
ref erence
*Symbol 14 of annex C used.

TRF No. IEC62109_1B


Page 53 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

4.3 TABLE: Thermal testing P


Model : MAX 75KTL3-XL2 -
temperature t of part/at: t (C) permitted t
(C)
test Condition : PV input: PV input: PV input: PV input:
650Vdc 650Vdc 360Vdc 360Vdc
AC output: AC output: AC output: AC output: -
3~ 140Vac, 3~ 110Vac, 3~ 140Vac, 3~ 110Vac,
derating derating derating derating
Ambient 59.9 59.9 59.1 59.8 --
DC switch, outside 78.3 75.6 74.2 72.5 85
DC switch, inside 74.3 71.6 70.3 68.5 85
PV connector 70.1 67.4 66.0 64.3 90
Output terminal 79.1 76.4 75.0 73.3 90
Handle 67.7 65.0 63.7 61.9 70
Heatsink 72.3 69.6 68.2 66.5 100*
Mounting surf ace 76.2 73.5 72.1 70.4 90
Enclosure, top 76.9 74.2 72.8 71.1 100*
LCD panel 68.0 65.3 63.9 62.2 95
Internal wires: AC f ilter
79.8 78.1 76.8 75.0 105
board to output terminal
Internal wires: power
76.6 74.9 73.5 71.8 105
board to Cap board
Internal wires: INV
75.0 73.3 71.9 70.2 105
inductance to I/O board
Internal wires: I/O
75.2 73.5 72.1 70.4 105
board to AC f ilter board
Internal wires: switch to
72.3 70.6 69.2 67.5 105
input board
Internal wires: switch to
70.1 68.5 67.1 65.4 105
terminal
Boost inductance 95.1 92.5 91.1 89.4 130
Lead wires of boost
75.9 73.3 71.9 70.2 105
inductance
CT HCT1 on input
74.3 71.6 70.2 68.5 85
board
CT HCT1 of PV strings 72.3 69.6 68.2 66.5 85
PV varistor 73.9 71.2 69.8 68.1 85
Optocoupler U27 82.1 79.4 78.1 76.3 100
AC transf ormer TX2 110.7 108.0 106.6 104.9 110
DC transf ormer TX1 106.8 104.1 102.7 101.0 110
PCB near to IGBT 82.9 80.2 78.8 77.1 130
MCU TMS320F28075 86.1 83.4 82.1 80.3 For

TRF No. IEC62109_1B


Page 54 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

ref erence
For
MCU TMS320F28067 83.6 80.9 79.5 77.8
ref erence
For
CPLD chip 84.4 81.7 80.4 78.6
ref erence
PCB close to boost
84.3 81.6 80.2 78.5 130
IGBT
PCB close to INV IGBT 90.3 87.6 86.2 84.5 130
INV inductance 98.3 95.7 94.3 92.6 130
Common chock 90.1 87.4 86.0 84.3 130
LCL f ilter inductance 95.1 92.4 91.0 89.3 110
Output relay RY3 80.8 78.1 76.7 75.0 85
ISO relay 76.4 73.8 72.4 70.7 85
SPS input f ilter Cap 76.3 73.6 72.2 70.5 100
Input f ilter Cap on input
board 78.1 75.4 74.1 72.3 100

Bus thin capacitor 81.6 78.9 77.5 75.8 110


Bus cap 77.4 74.7 73.4 71.6 105
Output f ilter cap 77.6 74.9 73.5 71.8 100
Y Cap on input board 74.4 71.7 70.3 68.6 110
Y cap on PV string
77.4 74.7 73.3 71.6 110
sensor board
Y cap on I/O board 74.7 72.1 70.7 69.0 110
Output X cap 72.7 70.0 68.6 66.9 100
AC varistor 74.8 72.1 70.7 69.0 85
Fan FAN6 79.1 76.4 75.0 73.3 85
Fan FAN7 74.9 72.2 70.8 69.1 85
For
Internal temperature 76.0 73.7 70.6 68.9
ref erence
*Symbol 14 of annex C used.

TRF No. IEC62109_1B


Page 55 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

4.4 TABLE: fault condition tests P


ambient temperature (C) ................................. : 25 ⎯
test f use
component test f use
No. f ault voltage current result
No. time No.
(V) (A)
PCE
1. reverse Error message: “Error 204”.
PV input bef ore 850 5min -- -- EUT can't start.
start up No damaged, no hazard.
2. No Error message.
DC
PV input 850 5min -- -- EUT is operating normally.
overload
No damaged, no hazard.
3. Error message: “Error 600”.
EUT disconnected f rom grid
AC Output s-c 850 5min -- --
immediately.
No damage, no hazard.
4. Error message: “Error 416”.
AC EUT disconnected f rom grid
AC Output 850 5min -- --
overload immediately.
No damage, no hazard.
5. Error message: “Error 300”.
lack of EUT disconnected f rom grid
AC Output 850 3min -- --
phase immediately.
No damage, no hazard.
6. Phase
sequence Error message: “Error 300”.
AC exchange 850 EUT can't start.
3min
Output(R-N)
bef ore No damage, no hazard.
start up
7. Error message: “Warning400”.
Cooling block EUT is alarmed but can operate
850 10min -- --
f ailure vents normally.
No damage, no hazard.
8. No Error message.
Cooling Block EUT is operating normally(
850 2h -- -- Enter over temperature and load
f ailure Wind reduction mode).
No damaged, no hazard.
9. No Error message.
Cooling wrap EUT is operating normally(
850 2h -- -- Enter over temperature and load
f ailure quilt reduction mode).
No damaged, no hazard.

TRF No. IEC62109_1B


Page 56 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

10. Error message: “Warning400”.


Cooling
EUT is alarmed but can operate
Failure(FAN stalled 850 10min -- --
normally.
1)
No damage, no hazard.
11. Error message: “Warning400”.
Cooling
EUT is alarmed but can operate
f ailure(FAN2 stalled 850 10min -- --
normally.
)
No damage, no hazard.
12. Error message: “Warning400”.
Cooling
EUT is alarmed but can operate
f ailure(FAN3 stalled 850 10min -- --
normally.
)
No damage, no hazard.
13. Error message: “Warning400”.
Cooling
EUT is alarmed but can operate
f ailure(FAN4 stalled 850 10min -- --
normally.
)
No damage, no hazard.
14. Error message: “Warning400”.
Cooling
EUT is alarmed but can operate
f ailure(FAN5 stalled 850 10min -- --
normally.
)
No damage, no hazard.
15. Error message: “Warning400”.
Cooling
EUT is alarmed but can operate
f ailure(FAN6 stalled 850 10min -- --
normally.
)
No damage, no hazard.
PV INPUT Board
16. Error message: “Error 426”.
PV current
detection EUT disconnected f rom grid
o-c 850 5min -- --
immediately.
f ailure (R10)
No damage, no hazard.
17. Error message: “Error202”.
PV voltage
detection EUT disconnected f rom grid
s-c 850 5min -- --
immediately.
f ailure (R23)
No damage, no hazard.
18. Error message: “Error 202”.
PV voltage
detection EUT disconnected f rom grid
s-c 850 5min -- --
immediately.
f ailure (R31)
No damage, no hazard.
Power Board
19. Error message: “Error 416”.
Inverter
EUT disconnected f rom grid
IGBT M1 (2- s-c 850 5min -- --
3PIN) immediately.
M1 damage, no hazard.

TRF No. IEC62109_1B


Page 57 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

20. Error message: “Error 416”.


Inverter EUT disconnected f rom grid
IGBT M1 (4- s-c 850 5min -- --
immediately.
5PIN)
M1 damage, no hazard.
21. Error message: “Error 416”.
Inverter EUT disconnected f rom grid
IGBT M1 (2- s-c 850 5min -- --
immediately.
9PIN)
M1 damage, no hazard.
22. Inverter Error message: “Error 416”.
IGBT M1 EUT disconnected f rom grid
s-c 850 5min -- --
Drive f ailure immediately.
(R325) M1 damage, no hazard.
23. Inverter Error message: “Error 416”.
IGBT M1 EUT disconnected f rom grid
s-c 850 5min -- --
Drive f ailure immediately.
(R327) M1 damage, no hazard.
24. Inverter NTC No Error message.
detection
s-c 850 5min -- -- EUT is operating normally.
f ailure(R368
) No damaged, no hazard.

25. Inverter NTC No Error message.


detection
s-c 850 5min -- -- EUT is operating normally.
f ailure(C268
) No damaged, no hazard.

26. Boost NTC No Error message.


detection
o-c 850 5min -- -- EUT is operating normally.
f ailure
(R371) No damaged, no hazard.

27. Boost NTC No Error message.


detection
s-c 850 5min -- -- EUT is operating normally.
f ailure
(C273) No damaged, no hazard.

28. Error message: “Error 416”.


Boost IGBT EUT disconnected f rom grid
Q1 Drive s-c 850 5min
immediately.
f ailure (R75)
Q1 damage, no hazard.
29. Error message: “Error 416”.
Boost IGBT EUT disconnected f rom grid
Q1 Drive s-c 850 5min
immediately.
f ailure (R81)
Q1 damage, no hazard.
30. Error message: “Error 416”.
Boost IGBT EUT disconnected f rom grid
s-c 850 5min -- --
Q1 (2-3PIN) immediately.
Q1 damage, no hazard.

TRF No. IEC62109_1B


Page 58 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

31. Error message: “Error 416”.


Boost IGBT EUT disconnected f rom grid
s-c 850 5min -- --
Q1 (1-2PIN) immediately.
Q1 damage, no hazard.
IO Board
32. BOOST1
current No Error message.
detection o-c 850 5min -- -- EUT is operating normally.
f ailure No damaged, no hazard.
(R423)
33. BOOST1
current No Error message.
detection s-c 850 5min -- -- EUT is operating normally.
f ailure No damaged, no hazard.
(C140)
34. Error message: “Error 300”.
AC voltage EUT disconnected f rom grid
detection s-c 850 5min -- --
immediately.
f ailure(R67)
No damage, no hazard.
35. AC voltage Error message: “Error 300”.
detection EUT disconnected f rom grid
s-c 850 5min -- --
f ailure(C113 immediately.
) No damage, no hazard.
36. AC voltage Error message: “Error 300”.
detection EUT disconnected f rom grid
o-c 850 5min -- --
f ailure(R206 immediately.
) No damage, no hazard.
37. INV voltage No Error message.
detection
s-c 850 5min -- -- EUT is operating normally.
f ailure(R122
) No damaged, no hazard.

38. INV voltage No Error message.


detection s-c 850 5min -- -- EUT is operating normally.
f ailure(C89) No damaged, no hazard.
39. INV voltage No Error message.
detection
o-c 850 5min -- -- EUT is operating normally.
f ailure(R351
) No damaged, no hazard.

40. ISO
insulation No Error message.
detection EUT is operating normally.
s-c 850 5min -- --
detects
f ailure(R293 No damaged, no hazard.
)

TRF No. IEC62109_1B


Page 59 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

41. ISO
insulation No Error message.
detection
s-c 850 5min -- -- EUT is operating normally.
detects
f ailure(C344 No damaged, no hazard.
)
42. ISO
insulation No Error message.
detection
o-c 850 5min -- -- EUT is operating normally.
detects
f ailure(R762 No damaged, no hazard.
)
43. ISO
insulation No Error message.
detection
o-c 850 5min -- -- EUT is operating normally.
detects
f ailure(R110 No damaged, no hazard.
6)
44. BUS voltage Error message: “Error 508”.
detection EUT disconnected f rom grid
o-c 850 5min -- --
f ailure immediately.
(R261) No damage, no hazard.
45. BUS voltage Error message: “Error 508”.
detection EUT disconnected f rom grid
s-c 850 5min -- --
f ailure immediately.
(C340) No damage, no hazard.
46. BUS voltage Error message: “Error 508”.
detection EUT disconnected f rom grid
o-c 850 5min -- --
f ailure immediately.
(R758) No damage, no hazard.
47. BOOST
Overcurrent Error message: “Error 416”.
protection EUT disconnected f rom grid
detection s-c 850 5min -- --
immediately.
f ailure No damage, no hazard.
(R1124)
48. BOOST
Overcurrent
No Error message.
protection
detection o-c 850 5min -- -- EUT is operating normally.
f ailure No damaged, no hazard.
(R1126)
49. DC auxiliary No Error message.
source
s-c 850 5min -- -- EUT is shut down
f ailure
Q42(2-3PIN) No damaged, no hazard.

TRF No. IEC62109_1B


Page 60 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

50. DC auxiliary No Error message.


source
s-c 850 5min -- -- EUT is shut down
f ailure
Q42(1-3PIN) No damaged, no hazard.

51. DC auxiliary No Error message.


source +15V s-c 850 5min -- -- EUT is shut down
f ailure No damaged, no hazard.
52. DC auxiliary No Error message.
source -15V s-c 850 5min -- -- EUT is shut down
f ailure No damaged, no hazard.
53. DC auxiliary No Error message.
source +8V s-c 850 5min -- -- EUT is shut down
f ailure No damaged, no hazard.
54. AC auxiliary No Error message.
source
s-c 850 5min -- -- EUT is shut down
f ailure
Q48(2-3PIN) No damaged, no hazard.

55. AC auxiliary No Error message.


source
s-c 850 5min -- -- EUT is shut down
f ailure
Q48(1-3PIN) No damaged, no hazard.

56. AC auxiliary No Error message.


source
s-c 850 5min -- -- EUT is shut down
+24V.S
f ailure No damaged, no hazard.

57. Error message: “Error 201”.


GFCI EUT disconnected f rom grid
s-c 850 5min -- --
f ailure(C7) immediately.
No damage, no hazard.
58. Error message: “Error 201”.
GFCI EUT disconnected f rom grid
o-c 850 5min -- --
f ailure(R19) immediately.
No damage, no hazard.
59. AC current Error message: “Error 416”.
detection EUT disconnected f rom grid
s-c 850 5min -- --
f ailure(C365 immediately.
) No damage, no hazard.
60. AC current Error message: “Error 416”.
detection EUT disconnected f rom grid
o-c 850 5min -- --
f ailure(R814 immediately.
) No damage, no hazard.
61. DC Error message: “Error 402”.
component s-c EUT disconnected f rom grid
detection 850 5min -- --
immediately.
f ailure(R814
) No damage, no hazard.

TRF No. IEC62109_1B


Page 61 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

62. Error message: “Error 405”.


s-c bef ore
RY3 850 5min -- -- EUT can't start.
start up
No damage, no hazard.
63. AC current Error message: “Error 406”.
overcurrent EUT disconnected f rom grid
protection s-c 850 5min -- --
immediately.
f ailure(C419
) No damage, no hazard.

64. Error message: “Error 411”.


Optocoupler EUT disconnected f rom grid
f ailure(C276 s-c 850 5min -- --
immediately.
)
No damage, no hazard.
65. Internal
environment No Error message.
NTC
s-c 850 5min -- -- EUT is operating normally.
detection
f ailure(C215 No damaged, no hazard.
)
66. Internal
environment No Error message.
NTC
o-c 850 5min -- -- EUT is operating normally.
detection
f ailure(C520 No damaged, no hazard.
)
67. Internal
environment No Error message.
NTC
o-c 850 5min -- -- EUT is operating normally.
detection
f ailure(C525 No damaged, no hazard.
)
68. Transf ormer No Error message.
output
f ailure(TX1 s-c 850 5min -- -- EUT is shut down.
、TX2) No damaged, no hazard.

BUS-CAP-1 Board
69. Electrolytic Error message: “Error 404”.
capacitor EUT disconnected f rom grid
s-c 850 5min -- --
board 1 immediately.
f ailure(C1) No damage, no hazard.
BUS-CAP-2 Board
70. Electrolytic Error message: “Error 404”.
capacitor EUT disconnected f rom grid
s-c 850 5min -- --
board 1 immediately.
f ailure(C19) No damage, no hazard.
Control board

TRF No. IEC62109_1B


Page 62 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

71. No Error message.


Main chip EUT disconnected f rom grid
s-c 850 5min -- --
+3.3V f ailure immediately.
No damage, no hazard.
72. No Error message.
Main chip EUT disconnected f rom grid
s-c 850 5min -- --
XL2 f ailure immediately.
No damage, no hazard.
73. No Error message.
Main chip EUT disconnected f rom grid
o-c 850 5min -- --
XL2 f ailure immediately.
No damage, no hazard.
74. Main and Error message: “Error 411”.
sub CPU EUT disconnected f rom grid
o-c 850 5min -- --
communicati immediately.
on f ailure No damage, no hazard.
75. No Error message.
Sub chip EUT disconnected f rom grid
s-c 850 5min -- --
+3.3V f ailure immediately.
No damage, no hazard.
76. No Error message.
Sub chip XL EUT disconnected f rom grid
s-c 850 5min -- --
f ailure immediately.
No damage, no hazard.
77. No Error message.
Sub chip EUT disconnected f rom grid
o-c 850 5min -- --
XL1 f ailure immediately.
No damage, no hazard.
M3 board
78. Main chip No Error message.
+3.3V.S s-c 850 5min -- -- EUT is operating normally.
f ailure No damage, no hazard.
79. Main chip No Error message.
COXL1 s-c 850 5min -- -- EUT is operating normally.
f ailure No damage, no hazard.
80. Main chip No Error message.
COXL1 o-c 850 5min -- -- EUT is operating normally.
f ailure No damage, no hazard.

TRF No. IEC62109_1B


Page 63 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

supplementary inf ormation:


s-c: short-circuited, o-c: open-circuited, o-l: overload.
During the test:
Fire do not propagate beyond the PCE.
Equipment do not emit molten metal.
Enclosures do not def orm to cause non-compliance with the standard.
Pass the dielectric test.

TRF No. IEC62109_1B


Page 64 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

7.3.6.3.3 TABLE: protective equipotential bonding; N/A


Measured between: Test current Voltage drop Resistance result
(A) (V) (mΩ)

supplementary inf ormation


The alternative of 7.3.6.3.5 was considered.

7.3.6.3.7 TABLE: touch current measurement P


Measured between: Measured Limit Comments/conditions
(mA) (mA)
Live parts and plastic enclosure 1.152 3.5 N/A
Live parts and communication 0.415 3.5 N/A
ports
supplementary inf ormation

7.3.7 TABLE: clearance and creepage distance measurements P


clearance cl and creepage distance Up U r.m.s. required cl required dcr
dcr at / of : (V) (V) cl (mm) (mm) dcr (mm) (mm)
IO board: Y2 Cap C1, C2, C3, C21, 1100Vdc 1100Vdc 5.16 7.26 5.52 7.26
C492, C493, C494 and earthed (BI)
HCT1 board: Y2 Cap C1, C2, C3, C5, 1100Vdc 1100Vdc 5.16 7.55 5.52 7.55
C6, C7 and earthed (BI)
HCT2 board: Y2 Cap C1, C2, C3, C5, 1100Vdc 1100Vdc 5.16 6.65 5.52 6.65
C6, C7, C8 and earthed (BI)
IO board: Optocoupler U21, U22, 1100Vdc 1100Vdc 8.38 9.00 11.04 13.70
U27, U28, U31, U32 (RI)
Power board: Primary winding and
1100Vdc 1100Vdc 8.38 11.56 11.04 11.56
Sec winding of transf ormer TX1 (RI)
Power board: Primary winding and
1100Vdc 1100Vdc 8.38 11.38 11.04 11.38
Sec winding of transf ormer TX2 (RI)
AC f ilter board: L2 and earther (BI) 1100Vdc 1100Vdc 5.16 6.18 5.52 6.18
PCB and metal enclosure (BI) 1100Vdc 1100Vdc 5.16 12.65 11.0 15.33

Remarks:
1) FI: f unction insulation BI: Basic insulation SI: Supplementary insulation RI: Reinf orced insulation
2) A f orce of 10 N applied to the internal comp onents and 250 N applied to the enclosure f or measure
3) For PV circuit, system voltage is 1100V and overvoltage Category is OVCII, impulse voltage
corresponding to PV circuit is 4772V.
4)For AC main circuit, nominal voltage is 300V and overvoltage category is OVC III, impulse voltage is
corresponding to main circuit is 4000V.
5)For relay across main output. RMS voltage used f or creepage is rationalized to 600V and overvoltage
category is OVCII. For other insulation between live parts, which PV circuit and main circuit is not isolated
PV system voltage 1100V is considered f or the maximum working voltage.
6)The PCE enclosure is rated IP66 and the pollution degree inside enclosure is reduced f rom PD3 to PD2.

TRF No. IEC62109_1B


Page 65 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

7.3.7 TABLE: clearance and creepage distance measurements P


7)The disconnection devices are two relay in series at line. Clearance between contacts of each relay
rated min. 1.5mm. each relay with two contact gaps together to withstand the PV impulse voltage
according to IEC 62109-2 Clause 4.4.4.15.2.2. Thus the clearance requirement f or each contact is half of
the requirement.
8) Have been corrected accord to altitude up to 4000m
9)Triple Insulated Wire is used on transf ormer TX1 as secondary output.

7.3.7 TABLE: distance through insulation measurement P


U r.m.s. test voltage required di di
distance through insulation di at/of :
(V) (V) (mm) (mm)
Optocoupler 300Vac 4240Vdc -- certif ied
1100Vdc

7.5 TABLE: electric strength measurements, impulse voltage test and partial P
discharge test
partial
impulse
test voltage discharge
test voltage applied between: withstand result
(V) extinction
voltage (V)
voltage (V)
PV supply circuits to enclosure 2120 6000 N/A No breakdown
AC mains circuits to enclosure 2120 6000 N/A No breakdown
PV supply circuits to LCD Panel 4240 8000 N/A No breakdown
AC mains circuits to LCD Panel 4240 8000 N/A No breakdown
PV supply circuits to COM port 4240 8000 N/A No breakdown
AC mains circuits to COM port 4240 8000 N/A No breakdown

TRF No. IEC62109_1B


Page 66 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

9.2 TABLE: Limited power sources N/A

Circuit output tested:


Note: Measured Uoc (V) with all load circuits disco nnected:
Components Sample No. Uoc (V) Isc (A) VA

Meas. Limit Meas. Limit

supplementary inf ormation:


Sc=Short circuit, Oc=Open circuit

TRF No. IEC62109_1B


Page 67 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
The whole unit
Shenzhen
Metal IEC 62109-1 Tested with
Growatt New AL-5052 Min. thickness 1.0mm
Enclosure Energy Co., Ltd. IEC 62109-2 appliance

Interchangeabl IEC 62109-1 Tested with


(Alternative) Interchangeable Min. thickness 1.0mm
e IEC 62109-2 appliance
Shenzhen
yaxinda
PCB YXD-ML V-0,130℃,CTI≥175 UL796 UL*
Technology
CO..LTD
Interchangeabl
(Alternative) Interchangeable V-0,130℃,CTI≥175 UL796 UL*
e
Metal,overall measured:
L:500mm, IEC 62109-1 Tested with
Heat sink Fei Rong Da AL-1060
W:290mm, IEC 62109-2 appliance
H:90mm
Metal,overall measured:
L:500mm, IEC 62109-1 Tested with
(Alternative) Interchangeable AL-1060
W:290mm, IEC 62109-2 appliance
H:90mm
Metal,overall measured:
L:500mm, IEC 62109-1 Tested with
(Alternative) Interchangeable AL-1060 W:290mm,
IEC 62109-2 appliance
H:60mm
Thermal
WOER RSFR 600V 125℃ UL 224 UL*
casing
(Alternative) TYCO VERSAFIT V2 600V 125℃ UL 224 UL*
(Alternative) KAIHENG K-2 600V 125℃ UL 224 UL*
DONGGUA N SALIP T S-
(Alternative) 600V 125℃ UL 224 UL*
SALIPT CO LTD 901-600

Insulation WTM-0 MIN 0.13mm


HENKEL K-10# UL746A UL*
gasket 150℃
V-0 ,
(Alternative) SABIC FR700 UL746A UL*
Min.0.23mm ,130℃

V-0 ,
(Alternative) SABIC FR65 UL746A UL*
Min.0.23mm ,130℃
LCD screen
SABIC FR60(f 1) Min.0.23mm,V-0, UL1649 UL*
cover

TRF No. IEC62109_1B


Page 68 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
130℃,F1

Autotex XE
(Alternative) SABIC Min.0.2mm,105℃,F1 UL1649 UL*
(f 2)
DONGGUA N VP-D4 B-P
VACONN
PV Input HSMO 30A/1100V , IP68 , - IEC/EN6285 TUV
terminal POWER
VP-D4 B-P 40~+85℃ 2 R50396796
ELECTRONIC
HSFO
CO.,LTD
DONGGUA N
VACONN YF-H4-P-F 30A/1000V, IP67, - IEC/EN6285 TUV
(Alternative) POWER
YF-H4-P-M 40~+85℃ 2 R50344236
ELECTRONIC
CO.,LTD
Helios H4
35A/1100V, IP68, - IEC/EN6285 TUV
(Alternative) Amphenol 4mm2
40~+85℃ 2 R50388083
Bulkhead
PV-ADBP4-
Staubli Electrical S2/6 39A/1250V,IP 68 , - IEC/EN6285 TUV
(Alternative)
Connectors AG PV-ADSP4- 40~+85℃ 2 R60127181
S2/6
Shenzhen Hengxi TUV
HX-H4-P-SMN 30A/1100V , IP68 , - IEC/EN6285
(Alternative) Technology SUD64.290.19
HX-H4-P-SFN 40~+85℃ 2
Co.Ltd .00585.02
Jiangxi Jinko PV PV-JK03M2-F IEC/EN TUV
(Alternative) 50A /1500Vdc,IP68,
Material Co., Ltd. PV-JK02M1-M 62852 R50318165
Huizhou
Xinchuangchen HX-H4-P-SMN IEC/EN TUV
(Alternative) Technology 30A/1100Vdc,IP68
HX-H4-P-SFN 62852 R50521133
Co., Ltd
Shenzhen
Output connection DSTB300-04-
Technology Co., R 400A/1000V UL508 UL*
terminal
Ltd
PV input BEIJING
1100V,20A
EPEOPLE’S GHX5-32P- TUV
switch 750V,50A EN 60947
ELECTRIC 6P-1000-32 R50439884
(switch1,2) IP66
PLANT CO., LTD
BEIJING
EPEOPLE’S GHX5-32P- 1100V,50A TUV
(Alternative) ELECTRIC 6P-1100-50 IP66 EN 60947
R50439884
PLANT CO., LTD

TRF No. IEC62109_1B


Page 69 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
BEIJING
1100V,32A
EPEOPLE’S GHX5-32P- TUV
(Alternative) 800V,50A EN 60947
ELECTRIC 6P-1100-32 R50439884
IP66
PLANT CO., LTD
BEIJING
1500V,16A
EPEOPLE’S GHX5-32P- 700V, 55A
TUV
(Alternative) ELECTRIC 6P-1500-16 EN 60947
IP66 R50439884
PLANT CO., LTD
Shanghai TUV SUDN8A
NDG3V- 1250V/32A
Liangxin 800V/50A
(Alternative) 50/6/1/02/M/1 EN 60947 0835740315R
ELECTRIC
PLANT CO., LTD 5 ev.02
Zhejiang Benyi 1200Vdc,25A
TUVR5042530
(Alternative) ELECTRIC BYST.1-50-6 800Vdc,40A EN 60947
PLANT Co.LTD IP66 1

ProJoy Electric PEDS150R- 1200V,10A


TUV
(Alternative) 600V, 40A EN 60947
Co., Ltd. HM40-6 R50494197
IP66
ProJoy Electric PEDS150R- 1200V,15A
TUV
(Alternative) 700V, 55A EN 60947
Co., Ltd. HM55-6 R50494197
IP66
ProJoy Electric PEDS150- 1200V,15A
TUV
(Alternative) 700V, 55A EN 60947
Co., Ltd. HM55-6 R50494197
IP66
1200V,10A
ProJoy Electric PEDS150- TUV
(Alternative) 600V, 40A EN 60947
Co., Ltd. HM40-6 R50494197
IP66
1100V,10A
TUVR5043632
(Alternative) Santon XBHP3610/2 500V, 45A EN 60947
IP66 4
Shanghai
NDG3V- 1250V/32A
Liangxin TUV SUDN8A
(Alternative) 50/H/8/6/02/M/ 1000V/50A EN 60947
ELECTRIC 0835740315
15 6Pole
PLANT CO., LTD
BEIJING
GHX6-
EPEOPLE’S 1500V/55A TUV
(Alternative) 55P/6/P/1500/ EN 60947
ELECTRIC 6Pole R50514449
55
PLANT CO., LTD
BEIJING
GHX6-
EPEOPLE’S 1500V/50A TUV
(Alternative) 55P/6/P/1500/ EN 60947
ELECTRIC 6Pole R50514449
50
PLANT CO., LTD
BEIJING 1100V,20A
PV input GHX5-32P- TUV
EPEOPLE’S 750V, 50A EN 60947
switch 3(MAX- ELECTRIC 8P1000-32 R50439884
8Pole,IP66

TRF No. IEC62109_1B


Page 70 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
XL1 series) PLANT CO., LTD
BEIJING
EPEOPLE’S GHX5-32P- 1100V,50A TUV
(Alternative) ELECTRIC 8P-1100-50 6Pole,IP66 EN 60947
R50439884
PLANT CO., LTD
BEIJING
1100V,32A
EPEOPLE’S GHX5-32P- TUV
(Alternative) 800V,50A EN 60947
ELECTRIC 8P-1100-32 R50439884
6Pole,IP66
PLANT CO., LTD
ProJoy Electric PEDS150R- 1200V/10A
TUV
(Alternative) 600V/40A EN 60947
Co., Ltd. HM40-8 R50389807
8Pole,IP66
Shanghai
NDG3V- 1250V/36A TUV SUDN8A
Liangxin
(Alternative) 50/8/1/02/M/1 800V/63A EN 60947 0835740315R
ELECTRIC
4 8Pole,IP66 ev.02
PLANT CO., LTD
1200V/20A
TUVR5043632
(Alternative) Santon XBHP+3810/2 600V/50A EN 60947 4
6Pole,IP66
Zhejiang Benyi 1250V,25A
ELECTRIC TUVR5042530
(Alternative) BYST.1-50-8 800V, 40A, EN 60947 1
PLANT Co.LTD 8Pole,IP66
PV input BEIJING
switch EPEOPLE’S GHX5-32P- 1100V,50A TUV
3(MAX-XL2 ELECTRIC 4P-1100-50 4Pole,IP66 EN 60947 R50439884
series) PLANT CO., LTD
Shanghai
NDG3V- 1250V/32A
Liangxin TUV SUDN8A
(Alternative) 50/H/4/6/02/M 1000V/50A EN 60947
ELECTRIC 0835740315
/15 4Pole
PLANT CO., LTD
BEIJING
GHX6-
EPEOPLE’S 1500V/55A TUV
(Alternative) 55P/4/P/1500/ EN 60947
ELECTRIC 4Pole R50514449
55
PLANT CO., LTD
BEIJING
GHX6-
EPEOPLE’S 1500V/50A TUV
(Alternative) 55P/4/P/1500/ EN 60947
ELECTRIC 4Pole R50514449
50
PLANT CO., LTD
SHENZHEN 1000Vac,
WOER HEAT-
PV input 1250Vdc,105C,
SHRINKABLE 10269 UL 758 UL*
internal wire AWG12#
MATERIAL CO
LTD AWG10#

(Alternative) SHENZHEN 10183 1000Vac, 1200Vdc UL 758 UL*

TRF No. IEC62109_1B


Page 71 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
WOER HEAT- 105C, AWG12#
SHRINKABLE AWG10#
MATERIAL CO
LTD
SHENZHEN
WOER HEAT- 60000Vdc,200C,
(Alternative) SHRINKABLE 3239 AWG12# UL 758 UL*
MATERIAL CO AWG10#
LTD
1000Vac,1250Vdc,105
(Alternative) WENCHANG 10269 C, AWG12# UL 758 UL*
AWG10#
3000Vac,105C,
(Alternative) WENCHANG 3239 AWG12# UL 758 UL*
AWG10#
3Q WIRE & 1000Vac,1200Vdc,105
(Alternative) CABLE CO LTD 10183 C, AWG12# UL 758 UL*
AWG10#
3Q WIRE & 2000Vac,2000Vdc,105
(Alternative) CABLE CO LTD 11627 C, AWG12# UL 758 UL*
AWG10#
SHENZHEN
WOER HEAT- 600Vac, 105C,
AC output
SHRINKABLE 1015 AWG2# UL 758 UL*
internal wire
MATERIAL CO AWG1#
LTD
600Vac, 105C,
(Alternative) Interchangeable 1015 AWG2# UL 758 UL*
AWG1#
1000Vac,105℃,
(Alternative) Interchangeable 10269 AWG2# UL 758 UL*
AWG1#
HUIZHOU
Input Boost INDUCTANCE NPH5935200
959V1- 320uH, Class H IEC 62109-1 Tested with
inductor (MAX ELECTRONIC
75/320uH IEC 62109-2 appliance
-XL1 series) TECHNOLOGY
CO.,LTD
Shenzhen
NPH5935200
Growatt New IEC 62109-1 Tested with
(Alternative) 959V1- 320uH, Class H
Energy 75/320uH IEC 62109-2 appliance
Technology Co.,

TRF No. IEC62109_1B


Page 72 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
Ltd
NPH5935200
Eagle Electric IEC 62109-1 Tested with
(Alternative) 959V1- 320uH, Class H
Co., Ltd. 75/320uH IEC 62109-2 appliance

SHENZHEN
NPH5935200
JINGQUANHUA IEC 62109-1 Tested with
(Alternative) 959V1- 320uH, Class H
ELECTRONICS 75/320uH IEC 62109-2 appliance
CO.,LTD
Shenzhen Click NPH5935200
IEC 62109-1 Tested with
(Alternative) Technology Co., 959V1- 320uH, Class H
75/320uH IEC 62109-2 appliance
Ltd.
Qingdao Yunlu
NPH5935200
New Energy IEC 62109-1 Tested with
(Alternative) 959V1- 320uH, Class H
Technology Co., 75/320uH IEC 62109-2 appliance
Ltd.
Shenzhen
NPH5935200
Haiguang IEC 62109-1 Tested with
(Alternative) 959V1- 320uH, Class H
Electronics Co., 75/320uH IEC 62109-2 appliance
Ltd
Shenzhen YaMa NPH5935200
IEC 62109-1 Tested with
(Alternative) Xi Eletctoronics C 959V1- 320uH, Class H
75/320uH IEC 62109-2 appliance
o.,Ltd.
HEFEI ECRIEE-
NPH5935200
TAMURA IEC 62109-1 Tested with
(Alternative) 959V1- 320uH, Class H
ELECTRIC 75/320uH IEC 62109-2 appliance
CO. ,LTD.
SHENZHEN HOR NPH5935200
IEC 62109-1 Tested with
(Alternative) ANS ELECTRON 959V1- 320uH, Class H
75/320uH IEC 62109-2 appliance
ICS CO.,LTD
Huizhou
NPH5935200
Sansheng IEC 62109-1 Tested with
(Alternative) 959V1- 320uH, Class H
Electronic Co., 75/320uH IEC 62109-2 appliance
Ltd.
NPH5935200
(Alternative) SHENZHEN 320uH, Class H IEC 62109-1 Tested with
959V1-

TRF No. IEC62109_1B


Page 73 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
TRANSFORMER 75/320uH IEC 62109-2 appliance
ELECTRONICS
CO.,LTD.
HUIZHOUSHI CH NPH5935200
IEC 62109-1 Tested with
(Alternative) UANGHUA INDU 959V1- 320uH, Class H
75/320uH IEC 62109-2 appliance
STRIAL CO.,LTD.
HUIZHOU
BOOST INDUCTANCE NPC6550211
IEC 62109-1 Tested with
inductor ELECTRONIC 228V2-60 465uH, Class H
GV/465uH IEC 62109-2 appliance
(MAX-XL2) TECHNOLOGY
CO.,LTD
Shenzhen
Growatt New NPC6550211
IEC 62109-1 Tested with
(Alternative) Energy 228V2-60 465uH, Class H
GV/465uH IEC 62109-2 appliance
Technology Co.,
Ltd
NPC6550211
Eagle Electric IEC 62109-1 Tested with
(Alternative) 228V2-60 465uH, Class H
Co., Ltd. GV/465uH IEC 62109-2 appliance
SHENZHEN
NPC6550211
JINGQUANHUA IEC 62109-1 Tested with
(Alternative) 228V2-60 465uH, Class H
ELECTRONICS GV/465uH IEC 62109-2 appliance
CO.,LTD
Shenzhen Click NPC6550211
IEC 62109-1 Tested with
(Alternative) Technology Co., 228V2-60 465uH, Class H
GV/465uH IEC 62109-2 appliance
Ltd.
Qingdao Yunlu
NPC6550211
New Energy IEC 62109-1 Tested with
(Alternative) 228V2-60 465uH, Class H
Technology Co., GV/465uH IEC 62109-2 appliance
Ltd.
Shenzhen
NPC6550211
Haiguang IEC 62109-1 Tested with
(Alternative) 228V2-60 465uH, Class H
Electronics Co., GV/465uH IEC 62109-2 appliance
Ltd

TRF No. IEC62109_1B


Page 74 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
Shenzhen YaMa NPC6550211
IEC 62109-1 Tested with
(Alternative) Xi Eletctoronics C 228V2-60 465uH, Class H
GV/465uH IEC 62109-2 appliance
o.,Ltd.
HEFEI ECRIEE-
NPC6550211
TAMURA IEC 62109-1 Tested with
(Alternative) 228V2-60 465uH, Class H
ELECTRIC GV/465uH IEC 62109-2 appliance
CO. ,LTD.
SHENZHEN HOR NPC6550211
IEC 62109-1 Tested with
(Alternative) ANS ELECTRON 228V2-60 465uH, Class H
GV/465uH IEC 62109-2 appliance
ICS CO.,LTD
Huizhou
NPC6550211
Sansheng IEC 62109-1 Tested with
(Alternative) 228V2-60 465uH, Class H
Electronic Co., GV/465uH IEC 62109-2 appliance
Ltd.
SHENZHEN
NPC6550211
TRANSFORMER IEC 62109-1 Tested with
(Alternative) 228V2-60 465uH, Class H
ELECTRONICS GV/465uH IEC 62109-2 appliance
CO.,LTD.
HUIZHOUSHI CH NPC6550211
IEC 62109-1 Tested with
(Alternative) UANGHUA INDU 228V2-60 465uH, Class H
GV/465uH IEC 62109-2 appliance
STRIAL CO.,LTD.
WUXI YOUFAUN
EIW/MW 35- 200℃
-WIRE ELECTRIC CO UL1446 UL*
CS
LTD
DUPONT
-MARGIN SPECIALTY
PRODUCTS Nomex 410 220℃ UL94 UL*
TAPE
USA, LLC
WU JIANG
TAIHU
-VARNISH INSULATING ET-90 180℃ UL1446 UL*
MATERIAL CO
LTD
SHENZHEN
WOER HEAT-
- TUBE SHRINKABLE RSFR-H 200℃ UL224 UL*
MATERIAL

TRF No. IEC62109_1B


Page 75 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
CO.,LTD
SHEN ZHEN
SISUN SILICON
-EPOXY TECHNOLOGY XS-1199-A/B -60~200℃ UL94 UL*
CO.,LTD
HUIZHOU
INDUCTANCE PHD6581200
IEC 62109-1 Tested with
INV inductor ELECTRONIC 670V1- 115uH, Class H
TECHNOLOGY 26/115uH IEC 62109-2 appliance
CO.,LTD
Shenzhen
Growatt New PHD6581200
IEC 62109-1 Tested with
(Alternative) Energy 670V1- 115uH, Class H
26/115uH IEC 62109-2 appliance
Technology Co.,
Ltd
PHD6581200
Eagle Electric IEC 62109-1 Tested with
(Alternative) 670V1- 115uH, Class H
Co., Ltd. IEC 62109-2 appliance
26/115uH
SHENZHEN
PHD6581200
JINGQUANHUA IEC 62109-1 Tested with
(Alternative) 670V1- 115uH, Class H
ELECTRONICS 26/115uH IEC 62109-2 appliance
CO.,LTD
Shenzhen Click PHD6581200
IEC 62109-1 Tested with
(Alternative) Technology Co., 670V1- 115uH, Class H
26/115uH IEC 62109-2 appliance
Ltd.
Qingdao Yunlu
PHD6581200
New Energy IEC 62109-1 Tested with
(Alternative) 670V1- 115uH, Class H
Technology Co., 26/115uH IEC 62109-2 appliance
Ltd.
Shenzhen
PHD6581200
Haiguang IEC 62109-1 Tested with
(Alternative) 670V1- 115uH, Class H
Electronics Co., 26/115uH IEC 62109-2 appliance
Ltd
Shenzhen YaMa PHD6581200
IEC 62109-1 Tested with
(Alternative) Xi Eletctoronics C 670V1- 115uH, Class H
26/115uH IEC 62109-2 appliance
o.,Ltd.

TRF No. IEC62109_1B


Page 76 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
HEFEI ECRIEE-
PHD6581200
TAMURA IEC 62109-1 Tested with
(Alternative) 670V1- 115uH, Class H
ELECTRIC 26/115uH IEC 62109-2 appliance
CO. ,LTD.
SHENZHEN HOR PHD6581200
IEC 62109-1 Tested with
(Alternative) ANS ELECTRON 670V1- 115uH, Class H
26/115uH IEC 62109-2 appliance
ICS CO.,LTD
Huizhou
Sansheng PHD6581200
IEC 62109-1 Tested with
(Alternative) Electronic Co., 670V1- 115uH, Class H
26/115uH IEC 62109-2 appliance
Ltd. (Southeast
Gate 1)
SHENZHEN
PHD6581200
TRANSFORMER IEC 62109-1 Tested with
(Alternative) 670V1- 115uH, Class H
ELECTRONICS 26/115uH IEC 62109-2 appliance
CO.,LTD.
HUIZHOUSHI CH PHD6581200
IEC 62109-1 Tested with
(Alternative) UANGHUA INDU 670V1- 115uH, Class H
26/115uH IEC 62109-2 appliance
STRIAL CO.,LTD.
WUX I YOUFA UN
ELECTRIC CO
LTD
-WIRE SHANGHA I EIW 200℃ UL1446 UL*
YOUTUO
MAGNE T WIRE
CO
DUPONT
-MARGIN SPECIALTY
Nomex 410 220℃ UL94 UL*
TAPE PRODUCTS
USA, LLC
WU JIA NG
TA IHU
-VARNISH INS ULA TING ET-90 180℃ UL1446 UL*
MATE RIA L CO
LTD
SHENZHEN
- TUBE RSFR-H 200℃ UL224 UL*
WOER HEAT-

TRF No. IEC62109_1B


Page 77 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
SHRINKABLE
MATERIAL
CO.,LTD
SHEN ZHEN
SISUN SILICON
-EPOXY XS-1199-A/B 200℃ UL94 UL*
TECHNOLOGY
CO.,LTD
12038VA24Q
Internal f an NMB 24Vdc/1.4A/5700RPM IEC 60950 VDE*
FUE1
NMB DBTA1225B4 24Vdc/0.62A/ EN60950 TUV SUD*
(Alternative) S-051
Delta Electronics THB1224B 24Vdc/0.6A/4500RPM
(Alternative) Industry Co., Ltd. IEC 60950 TUV*
Dong Guan Anci MGT12024ZB 24Vdc/2.25A/7000RPM
Electronic -W38
(Alternative) Technology Co., UL 507 UL E187236
Ltd
Delta Electronics THB1224CE- 24Vdc/1.62A/5700RPM
(Alternative) Industry Co., Ltd. 00D1X IEC 60950 TUV*
09238DE24P
External f an NMB 24Vdc/1.1A IEC 60950 VDE*
CUE1
09238RE24M IEC 62368-1 VDE116206
(Alternative) NMB 24Vdc/1.1A
CTD1
Delta Electronics THD0924HEG 24Vdc/1.15A/10700RP TUV*
(Alternative) Industry Co., Ltd. DA M IEC 60950
Delta Electronics PFB0924DHE TUV*
(Alternative) 24Vdc/1.1A/7200RPM IEC 60950
Industry Co., Ltd. GT7
Dongguan
MGT9224YB-
(Alternative) Protechnic 24Vdc/1.5A/10700RPM EN 62368-1 TUV SUD*
W38
Electric Co.,Ltd
BOOST IGBT
(Q1、Q2、
Q3、Q4、
Q5、Q6、
Q7、Q8、
ON NGTB40N120 IEC 62109-1 Tested with
Q9、Q10、 1200V/40A/175℃
Semiconductor FL3WG IEC 62109-2 appliance
Q11、Q12、
Q13、Q14、
Q15、 Q16、
Q17、Q18、
Q19、Q20)

TRF No. IEC62109_1B


Page 78 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
ON FGY40T120S IEC 62109-1 Tested with
Atl. 1200V/40A/175℃
Semiconductor MD IEC 62109-2 appliance
ON FGH40T120S IEC 62109-1 Tested with
(Alternative) Semiconductor 1200V/40A/175℃
MD IEC 62109-2 appliance
ON FGH75T120S IEC 62109-1 Tested with
(Alternative) 1200V/75A/175℃
Semiconductor QDN IEC 62109-2 appliance
IKW40N120H IEC 62109-1 Tested with
(Alternative) Inf ineon 1200V/40A/175℃
3 IEC 62109-2 appliance
IKW40N120C IEC 62109-1 Tested with
(Alternative) Inf ineon 1200V/40A/175℃
S6 IEC 62109-2 appliance
IKW40N120C IEC 62109-1 Tested with
(Alternative) Inf ineon 1200V/40A/175℃
H3 IEC 62109-2 appliance
IKW40N120E IEC 62109-1 Tested with
(Alternative) Inf ineon 1200V/40A/175℃
S5 IEC 62109-2 appliance
FGW40N120 IEC 62109-1 Tested with
(Alternative) FUJI 1200V/40A/175℃
WE IEC 62109-2 appliance
RBN40H125S IEC 62109-1 Tested with
(Alternative) Renesas 1250V/40A/175℃
1FPQ-A0 IEC 62109-2 appliance
RBN75H125S IEC 62109-1 Tested with
(Alternative) Renesas 1200V/75A/175℃
1FP4-A0 IEC 62109-2 appliance
STGWA40H1 IEC 62109-1 Tested with
(Alternative) ST 1200V/40A/175℃
20DF2 IEC 62109-2 appliance
MacMic Science
MM40G3U120 IEC 62109-1 Tested with
(Alternative) & Technology 1200V/40A/175℃
BX IEC 62109-2 appliance
Co., Ltd.
MacMic Science IEC 62109-1 Tested with
MM50G3U120
(Alternative) & Technology 1200V/50A/175℃
BMX IEC 62109-2 appliance
Co., Ltd.
MagnaChip MBQ40T120Q
IEC 62109-1 Tested with
(Alternative) Semiconductor ESTH 1200V/40A/175℃
Ltd. IEC 62109-2 appliance

China Resources
CRG40T120B IEC 62109-1 Tested with
(Alternative) Microelectronics 1200V/40A/175℃
K3SD IEC 62109-2 appliance
Limited
(Alternative) STARPOWER DG50Q12T2 1200V/50A/175℃ IEC 62109-1 Tested with

TRF No. IEC62109_1B


Page 79 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
Semiconductor IEC 62109-2 appliance
Ltd.
KGF40N120K IEC 62109-1 Tested with
(Alternative) KEC 1200V/40A/175℃
DA IEC 62109-2 appliance
IEC 62109-1 Tested with
(Alternative) MCC MIWP75N120 1200V/75A/175℃
IEC 62109-2 appliance
INV IGBT
ON NXH450N65L
(M1、M2、 650V/450A/175℃ UL1557 UL*
Semiconductor 4Q2F2SG
M3)
NXH600N65L
ON
(Alternative) 4Q2F2PG 650V/600A/175℃ UL1557 UL*
Semiconductor
NXH600N65L
ON
(Alternative) 4Q2F2SG 650V/600A/175℃ UL1557 UL*
Semiconductor
Vincotech 30-
Electronic PT07NIB300S
(Alternative) 700V/300A/175℃ UL1557 UL*
Modules(Shenzh 503-
en)Co.Ltd LH36F58Y
Vincotech
30-
Electronic
(Alternative) FT07NIB300S 700V/300A/175℃ UL1557 UL*
Modules(Shenzh
502-LE06F58
en)Co.Ltd
F3L400R10W
(Alternative) Inf ineon 950V/400A/175℃ UL1557 UL*
3S7F
F3L400R07W
(Alternative) Inf ineon 650V/400A/175℃ UL1557 UL*
3S5
Power Board
BUS f ilm cap
(C184, C185,
C186, C187, PAN600A75J IEC 62109-1 Tested with
FARAD 600V,75uF, 105℃
C188, C190, 4 IEC 62109-2 appliance
C191, C192,
C193, C194)
Hubei Aihua FDA2KJ756M IEC 62109-1 Tested with
(Alternative) 600V,75uF, 105℃
Group Co., Ltd. 204MD5 IEC 62109-2 appliance
Guangdong
Fengming 1GLBH675D6 IEC 62109-1 Tested with
(Alternative) 600V,75uF, 105℃
Electronic 00-02 IEC 62109-2 appliance
Technology Co.,

TRF No. IEC62109_1B


Page 80 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
Ltd.
C3D1U756JM IEC 62109-1 Tested with
(Alternative) Faratronic 600V,75uF, 105℃
0AC00 IEC 62109-2 appliance
Huarong EPB-
Electronics Co., 756J0575DB1 575V,75uF, 105℃ IEC 62109-1 Tested with
(Alternative)
Ltd. 52B-FF IEC 62109-2 appliance
B32778S5756 IEC 62109-1 Tested with
(Alternative) EPCOS 600V,75uF, 105℃
K514 IEC 62109-2 appliance
MKP1848C67 IEC 62109-1 Tested with
(Alternative) Visa 600V,75uF, 105℃
560JY* IEC 62109-2 appliance
C4AEHBW57 IEC 62109-1 Tested with
(Alternative) TEMET 600V,75uF, 105℃
50A3NJ IEC 62109-2 appliance
Y2 (C203,
C43Q1472K4
C204, C210, Faratronic Y2/4.7nF/1500Vdc EN60384-14 ENEC*
0C000
C217A)
R413F1470M
(Alternative) TEMET Y2/4.7nF/1000Vdc EN60384-14 ENEC*
1
Huarong
KY2X1472K0 Y2/4.7nF/1000Vdc/110
(Alternative) Electronics Co., IEC60384 ENEC*
300AB1101 ℃
Ltd.
413F1470(1) Y2/4.7nF/300Vac/110
(Alternative) TEMET IEC60384 ENEC*
M1(2) ℃
Optocoupler
(U1, U2, U3, DIN VDE V
-0.3V to 33 V ,-40℃ to VDE*
U4, U5, U6, TI UCC23313 0884-
150℃, 3750 Vrms
11:2017-01
U7, U8, U9,
U10)
-40℃-125℃,5V, - EN 60747-5- TUV*
(Alternative) AVAGO ACPL-W61L
3750V 2:2001+A1
2.7 to 5.5 V, -40 to IEC 60747-
(Alternative) TOSHIBA TLP2761 VDE*
125℃,5000 Vrms, 5-5:2007
IO Board
AC f ilm
Capacitor
(C9, C10, C6AR8805KF IEC 62109-1 Tested with
Faratronic 380VAC,8uF, 105℃
C11, C12, 10382 IEC 62109-2 appliance
C13, C14,
C15, C16,

TRF No. IEC62109_1B


Page 81 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
C17, C18,
C19, C20)
Hubei Aihua FAG38K805K IEC 62109-1 Tested with
(Alternative) 380VAC,8uF, 105℃
Group Co., Ltd. 762KL5 IEC 62109-2 appliance
Guangdong
Fengming
1GFBH580A3 IEC 62109-1 Tested with
(Alternative) Electronic 380VAC,8uF, 105℃
80-303 IEC 62109-2 appliance
Technology Co.,
Ltd.
B32756S8805 IEC 62109-1 Tested with
(Alternative) EPCOS 380VAC,8uF, 105℃
K500 IEC 62109-2 appliance
Y2 (C32) EPCOS R413D110000 Y2 1nF/1000Vdc EN60384-14 ENCN*
Atl. Faratronic MKP63 Y2 0.001uF/300VAC EN60384-14 ENEC*
Huarong
Y2X1102K030
Atl. Electronics Co., Y2 0.001uF/300VAC IEC60384 ENEC*
0AB1101
Ltd.
C43Q1472K4
Y2 (C473) Faratronic Y2/4.7nF/1500Vdc EN60384-14 ENEC*
0C000
R413F1470M
Atl. TEMET Y2/4.7nF/1000Vdc EN60384-14 ENCN*
1
Huarong
KY2X1472K0 Y2/4.7nF/1000Vdc/110
Atl. Electronics Co., IEC60384 ENEC*
300AB1101 ℃
Ltd.
413F1470(1)
Atl. TEMET Y2/4.7nF/300Vac/110℃ IEC60384 ENEC*
M1(2)
Y2 capacitor
(C1, C2, C3,
Faratronic MKP63 Y2/10nF/300V EN60384-14 ENEC*
C21, C492,
C493, C494)
R413I210000
(Alternative) ARCOTRONICS Y2/10nF/1000Vdc IEC60384 ENEC*
00K
CS14-
(Alternative) TDK F2GA103MY Y2/10nF/300Vac IEC60384 VDE*
GKA
413F2100(1)
(Alternative) KEMET Y2/10nF/300Vac IEC60384 ENEC*
M1(3)
Y2-250VAC-
(Alternative) Matsuda Industry Y2/10nF/250Vac IEC60384 VDE*
Y5V-103m
Y2 (C1, C2, CS14-
C3, C21, TDK F2GA103MY Y2/10nF/300Vac IEC60384 VDE*
GKA
C492, C493,

TRF No. IEC62109_1B


Page 82 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
C494
413F2100(1)
(Alternative) KEMET Y2/10nF/300Vac IEC60384 ENEC*
M1(3)
Y2-250VAC-
(Alternative) Songtian Industry Y2/10nF/250Vac IEC60384 VDE*
Y5V-103m
EN
ISO Relay Xiamen Hongf a
RYHF140FF 10A,250Vac,12V 61810-1 TUV*
(RY7, RY8) Acoustic Co., Ltd.
EN 60730-2-
31A/250Vac,12V 9
Xiamen Hongf a
(Alternative) RYHF140FF /2.25mm/-40- EN 60730- TUV*
Acoustic Co., Ltd.
85℃ 1

894H-2AH2- EN/IEC
(Alternative) Song chuan EN/IEC 61810 TUV*
FC 61810
10A,
CHI03-V- EN 61810-
(Alternative) Churod 250Vac,12V/1.5 TUV*
112DC2 1
mm/-40-85℃
GFCI CTSR 3-
LEM -5A~5A/ -40℃~105℃ UL 508 UL*
(GFCI1) TP/SP19

(Alternative) SINOMAGS SFG-3.0P/P1 -5A~5A/ -40℃~105℃ EN 61010 TUV*


TUV
(Alternative) SINOMAGS SFG-3.0P/P1 -5A~5A,-40~+105℃ EN 61010
R50428205
TUV
(Alternative) SINOMAGS SFG-P-P3 -5A~5A,-40~+105℃ EN 61010
R50428205
AC Relay
(RY1, RY2, Xiamen Hongf a HF167F- 800Vac/200A/-
EN61810 TUV*
RY3, RY4, Acoustic Co., Ltd. 200/12-H3F 40℃~85℃
RY5, RY6)
Songchuan 511ZP-1AD-F- 800Vac/200A/-
(Alternative) EN61810 TUV*
Precision C12 40℃~85℃
CHAR- 830Vac/200A/-
(Alternative) Churod EN 61810 TUV*
112A200 40℃~85℃
Xiamen Hongf a 1000Vac/250A/-
(Alternative) HF167F EN61810 TUV*
Acoustic Co., Ltd. 40℃~85℃
Songchuan 1000Vac/250A/-
(Alternative) 511ZP EN61810 TUV*
Precision 40℃~85℃
AC current
LZSR 200- -450A~+450A/ - IEC 62109-1 Tested with
sensor (HCT1, LEM
TP/SP1 40℃~85℃ IEC 62109-2 appliance
HCT2, HCT3)

TRF No. IEC62109_1B


Page 83 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
LZSR 200- -450A~+450A/- IEC 62109-1 Tested with
(Alternative) LEM
P/SP1 40℃~85℃ IEC 62109-2 appliance
-
SINOMAGS STB-200LA/Z 450A~+450A/(3.125mV/ IEC 62109-1 Tested with
(Alternative)
A)/-40℃~85℃ IEC 62109-2 appliance
STB- -450A~+450A/ - IEC 62109-1 Tested with
(Alternative) SINOMAGS
200LA/ZN 40℃~85℃ IEC 62109-2 appliance
T60404- -400A~+400A/ - IEC 62109-1 Tested with
(Alternative) VAC
N4644-X052 40℃~85℃ IEC 62109-2 appliance
Ningbo CRRC
Times
NACL.200P- IEC 62109-1 Tested with
(Alternative) Transducer -600A~+600A,85℃
S6-SP3VN IEC 62109-2 appliance
Technology Co.,
Ltd.
-600A~+600A/ - IEC 62109-1 Tested with
(Alternative) SINOMAGS STB-300LA/M
40℃~85℃ IEC 62109-2 appliance
Communicatio
n EN 60747-
optocoupler(U 40℃-125℃,5V, - 5-2
AVAGO ACPL-W61L TUV*
21, U22, U27, 3750V, IEC 60747-
5-2
U28, U31,
U32)
EN 60747-
5V, -40 ~105℃,5000 5-2 VDE*
(Alternative) TOSHIBA TLP2761
Vrms,

SPS SHENZHEN
TRANSFORMER IEC 62109-1 Tested with
Transf ormer EER42 Class F
ELECTRONICS IEC 62109-2 appliance
(TX1) CO.,LTD.
SHENZHEN
CLICK IEC 62109-1 Tested with
(Alternative) EER42 Class F
Technology Co., IEC 62109-2 appliance
Ltd.
Huizhou Baohui
Electronic IEC 62109-1 Tested with
(Alternative) EER42 Class F
Technology Co., IEC 62109-2 appliance
Ltd.
Shenzhen
Haiguang IEC 62109-1 Tested with
(Alternative) EER42 Class F
Electronics Co., IEC 62109-2 appliance
Ltd.

TRF No. IEC62109_1B


Page 84 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
Daxin Electronics IEC 62109-1 Tested with
(Alternative) EER42 Class F
Co., Ltd. IEC 62109-2 appliance
Shenzhen
IEC 62109-1 Tested with
(Alternative) Hongyuansheng EER42 Class F
Electron Co.,ltd. IEC 62109-2 appliance
Sunshine
IEC 62109-1 Tested with
(Alternative) Electrinics Co., EER42 Class F
Ltd. IEC 62109-2 appliance
Shenzhen
Yamaxi IEC 62109-1 Tested with
(Alternative) EER42 Class F
Electronics Co., IEC 62109-2 appliance
Ltd.
SHENZHEN
JINGQUANHUA IEC 62109-1 Tested with
(Alternative) EER42 Class F
ELECTRONICS IEC 62109-2 appliance
CO.,LTD
HuiZhou
ChuanHua IEC 62109-1 Tested with
(Alternative) EER42 Class F
Magnetoelectric IEC 62109-2 appliance
Co., Ltd.
SUMITOMO
-Bobbin BAKELITE CO PM-9823 150℃ UL94 UL*
LTD
Chang Chun T375HF/T200
(Alternative) 150℃ UL94 UL*
Plastics Co., Ltd HF
Changyuan
Electronics(shenz
-Tube CB-TT-L 155℃ UL224 UL*
hen) Co., Ltd Or
Equal
Shenzhen xUEW@, QA
-Magnet wire Dayang Industry TYPE:MW 79- 155℃ UL1446 UL*
Co Ltd or Eqyal C
xUEW/155,Q
Dong Guan Yida
A-x/155
(Alternative) Industrial Co., Ltd 155℃ UL1446 UL*
Type:MW 79-
Or Equal
C
Jingjiang Yahua
Pressure
-Tape PF* 180℃ UL510 UL*
Sensitive Glue
Co., Ltd Or Equal
Elantans Zhuhai
-Varnish B-277-@ 155℃ UL1446 UL*
Co. Ltd
SPS SHENZHEN
TRANSFORMER EER42 Class F IEC 62109-1 Tested with
Transf ormer ELECTRONICS IEC 62109-2 appliance

TRF No. IEC62109_1B


Page 85 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
(TX2) CO.,LTD.
SHENZHEN
CLICK IEC 62109-1 Tested with
(Alternative) EER42 Class F
Technology Co., IEC 62109-2 appliance
Ltd.
Huizhou Baohui
Electronic IEC 62109-1 Tested with
(Alternative) EER42 Class F
Technology Co., IEC 62109-2 appliance
Ltd.
Shenzhen
Haiguang IEC 62109-1 Tested with
(Alternative) EER42 Class F
Electronics Co., IEC 62109-2 appliance
Ltd.
Daxin Electronics IEC 62109-1 Tested with
(Alternative) EER42 Class F
Co., Ltd. IEC 62109-2 appliance
Shenzhen
IEC 62109-1 Tested with
(Alternative) Hongyuansheng EER42 Class F
Electron Co.,ltd. IEC 62109-2 appliance
Sunshine
IEC 62109-1 Tested with
(Alternative) Electrinics Co., EER42 Class F
Ltd. IEC 62109-2 appliance
Shenzhen
Yamaxi IEC 62109-1 Tested with
(Alternative) EER42 Class F
Electronics Co., IEC 62109-2 appliance
Ltd.
SHENZHEN
JINGQUANHUA IEC 62109-1 Tested with
(Alternative) EER42 Class F
ELECTRONICS IEC 62109-2 appliance
CO.,LTD
HuiZhou
ChuanHua IEC 62109-1 Tested with
(Alternative) EER42 Class F
Magnetoelectric IEC 62109-2 appliance
Co., Ltd.
SUMITOMO
-Bobbin BAKELITE CO PM-9823 150℃ UL94 UL*
LTD
Chang Chun T375HF/T200
(Alternative) 150℃ UL94 UL*
Plastics Co., Ltd HF
Changyuan
Electronics(shenz
-Tube CB-TT-L 155℃ UL224 UL*
hen) Co., Ltd Or
Equal
Shenzhen xUEW@, QA
-Magnet wire Dayang Industry TYPE:MW 79- 155℃ UL1446 UL*
Co Ltd or Eqyal C

TRF No. IEC62109_1B


Page 86 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
xUEW/155,Q
Dong Guan Yida
A-x/155
(Alternative) Industrial Co., Ltd 155℃ UL1446 UL*
Type:MW 79-
Or Equal
C
Jingjiang Yahua
Pressure
-Tape PF* 180℃ UL510 UL*
Sensitive Glue
Co., Ltd Or Equal
Elantans Zhuhai
-Varnish B-277-@ 155℃ UL1446 UL*
Co. Ltd
PV INPUT Board
PV SPD
(MOV1,
MOV2, MOV3,
MOV4, MOV5, SHENZHEN 510Vac/610Vdc,
MOV6, MOV7, HAIPENGXIN TUV
PV20K-670 10KA(8/20us),- EN 50539
MOV8, MOV9, ELECTRONICS R50456594
CO Ltd 40~85℃
MOV10,
MOV11,
MOV12,
MOV13)
Anhui Golden 670Vdc,
Power Electrical GTSP- 0B180413.AG
(Alternative) 10KA(8/20us),- EN 61000
Technology MDV670/20/A PUU44
Co.,Ltd 40~85℃
510Vac/670Vdc,
PV 670-20M2- SUD
(Alternative) PTG Corporation 10KA(8/20us),- EN 50539
10 B088817 0022
40~85℃
510Vac/670Vdc,
PV 670-25M2- B
(Alternative) PTG Corporation 10KA(8/20us),- EN 61643
10R 170188817016
40~85℃
Shenzhen
Junyao 420Vac/560Vdc,
(Alternative) Electronic 681KN20 10KA(8/20us), - UL1449 E327997
Technology Co., 40~85℃
Ltd.
Thinking 510Vac/670Vdc,
TVR20821KS TUV
(Alternative) Electronic 6.5KA(8/20us),- EN61051
Y J50411784
Industrial Co.,Ltd 40~85℃
Boost Sensor SINOMAGS STK-32PL 32A/5V/-40℃~105℃ EN60950 TUV*

TRF No. IEC62109_1B


Page 87 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
(HCT1,
HCT2, HCT3,
HCT4, HCT5,
HCT6, HCT7,
HCT8, HCT9,
HCT10)f or
MAX-XL1
series.

LEM HLSR-32-P 32A/-40-105℃ IEC 62109-1 Tested with


(Alternative)
IEC 62109-2 appliance
(Alternative) SINOMAGS STK-20PL 20A/5V/-40℃~105℃ EN60950 TUV*
Tamura
(Alternative) LA17P030S05 32A,+105℃ UL 508 E243511
Corporation
Boost Sensor
(HCT1,
HCT2, HCT3,
HCT4, HCT5,
TUV
HCT6, HCT7, SINOMAGS STK-50PL 50A,+105℃ EN60950
R50428205
HCT8, HCT9,
HCT10)f or
MAX-
XL12series.
(Alternative) LEM HLSR 50-P 50A,+105℃ UL 508 E189713
Tamura
(Alternative) LA17P050S05 50A,+105℃ UL 508 E243511
Corporation
BUS-CAP Board
BUS capacitor
(C1, C2, C3,
C4, C5, C6,
C7, C8, C9, Nantong Jianghai
ECS2YBB471 IEC 62109-1 Tested with
C10, C11, Capacitor Co., 470uF/550Vdc/105℃
MLA350070E IEC 62109-2 appliance
Ltd.
C12, C13,
C14, C15,
C16, C17,
C18, C19,

TRF No. IEC62109_1B


Page 88 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
C20, C21,
C22, C23,
C24, C25,
C26, C27,
C28)
LGN2L471ME IEC 62109-1 Tested with
(Alternative) Nichicon 470uF/550Vdc/105℃
LENW IEC 62109-2 appliance
LGN2L471ME IEC 62109-1 Tested with
(Alternative) Nichicon 470uF/550Vdc/105℃
LANH IEC 62109-2 appliance
LGX2H471ME IEC 62109-1 Tested with
(Alternative) Nichicon 470uF/550Vdc/105℃
LC58 IEC 62109-2 appliance
EKMS551VS IEC 62109-1 Tested with
(Alternative) NCC 470uF/550Vdc/105℃
N471MA60S IEC 62109-2 appliance
Samyoung
TLS550VS47 IEC 62109-1 Tested with
(Alternative) Electronics 470uF/550Vdc/105℃
0M IEC 62109-2 appliance
Co.,LTD.
CAPXON
ELECTRONIC UK471M550P IEC 62109-1 Tested with
(Alternative) 470uF/550Vdc/105℃
(SHENZHEN) 600A IEC 62109-2 appliance
CO., LTD.
CAPXON
ELECTRONIC UL471M550P IEC 62109-1 Tested with
(Alternative) 470uF/550Vdc/105℃
(SHENZHEN) 700AP4RPV IEC 62109-2 appliance
CO., LTD.
CAPXON
ELECTRONIC UL471M550P IEC 62109-1 Tested with
(Alternative) 470uF/550Vdc/105℃
(SHENZHEN) 700A00APRV IEC 62109-2 appliance
CO., LTD.
Aihua Inf inity
Capacitors ELT2HM471R IEC 62109-1 Tested with
(Alternative) 470uF/550Vdc/105℃
(Suzhou) Co., 60KTL IEC 62109-2 appliance
Ltd.
Aihua Inf inity
Capacitors ELT2JM471R IEC 62109-1 Tested with
(Alternative) 470uF/550Vdc/105℃
(Suzhou) Co., 60KT IEC 62109-2 appliance
Ltd.
B43544S7477 IEC 62109-1 Tested with
(Alternative) TDK 470uF/550Vdc/105℃
M002 IEC 62109-2 appliance
AC Filter Board
Y2 (C1, C2, C43Q1223K6
Faratronic Y2/22nF/300Vac/110℃ EN60384-14 ENEC*
C3) 0C000

TRF No. IEC62109_1B


Page 89 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
413I2220(1)M
(Alternative) KEMET Y2/22nF/300Vac /110℃ IEC60384 ENEC*
1(2)
B32022B3223
(Alternative) TDK Y2/22nF/300Vac/110℃ IEC60384 VDE*
M289
AC SPD
385Vac,
(MOV1,
Haipengxin PV20K-500 10KA(8/20us), EN 50539 TUV*
MOV2, MOV3, 1350Vpk,-40~85℃
MOV4)
Anhui Golden
Power Electrical GTSP- 385Vac, 10KA(8/20us),
(Alternative) EN 50539 TUV*
Technology MAV385/20/A -40~85℃
Co.,Ltd
PV 500-20M2- 385Vac, 20KA(8/20us),
(Alternative) PTG EN 50539 TUV SUD*
10 -40~85℃
230Vac, 10KA(8/20us)
(Alternative) Haipengxin PV20K-670 EN 50539 TUV*
510Vac, 20KA(8/20us)
PV 670-20M2-
(Alternative) PTG 510V, 20KA(8/20us) EN 50539 TUV SUD*
10
Thinking
TVR20821KS
(Alternative) Electronic 670Vdc/10KA EN61051 TUV*
Y
Industrial Co.,Ltd
HUIZHOU
INDUCTANCE
LCL LCL/5uH±12 5uH±12%/4Ts/6*7*1P, IEC 62109-1 Tested with
ELECTRONIC
inductance(L2) TECHNOLOGY %/ Class F IEC 62109-2 appliance
CO.,LTD
Eagle Electric LCL/5uH±12 IEC 62109-1 Tested with
(Alternative) 5uH±12%/4Ts/6*7*1P
Co., Ltd. %/ IEC 62109-2 appliance
Jingquanhua
LCL/5uH±12 IEC 62109-1 Tested with
(Alternative) Technology Co., 5uH±12%/4Ts/6*7*1P
%/ IEC 62109-2 appliance
Ltd.
Qingdao Yunlu
New Energy LCL/5uH±12 IEC 62109-1 Tested with
(Alternative) 5uH±12%/4Ts/6*7*1P
Technology Co., %/ IEC 62109-2 appliance
Ltd.
Shenzhen Click
LCL/5uH±12 IEC 62109-1 Tested with
(Alternative) Technology Co., 5uH±12%/4Ts/6*7*1P
%/ IEC 62109-2 appliance
Ltd.
Shenzhen Click
LCL/5uH±12 IEC 62109-1 Tested with
(Alternative) Technology Co., 5uH±12%/4Ts/6*7*1P
%/ IEC 62109-2 appliance
Ltd.
JUNG SHING
-WIRE EIW 6*7mm/200℃ UL1446 UL*
WIRE CO LTD

TRF No. IEC62109_1B


Page 90 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
WU JIANG
TAIHU
-VARNISH INSULATING ET-90 180℃ UL1446 UL*
MATERIAL CO
LTD
DONGGUAN
SHIPAI
-EPOXY HUACHUANG 808AB-H 155℃ UL94 UL*
MATERIAL
FACTORY
-Insulation Voltaf lex
ISOVOLTA 180℃ UL1446 UL*
paper DMD3 0180
HUIZHOU
AC common INDUCTANCE
T85.7*55.6*25 IEC 62109-1 Tested with
mode ELECTRONIC Class H
.4C/382uH IEC 62109-2 appliance
TECHNOLOGY
inductance(L1)
CO.,LTD
Shenzhen
Growatt New
T85.7*55.6*25 IEC 62109-1 Tested with
(Alternative) Energy Class H
.4C/382uH IEC 62109-2 appliance
Technology Co.,
Ltd
Eagle Electric T85.7*55.6*25 IEC 62109-1 Tested with
(Alternative) Class H
Co., Ltd. .4C/382uH IEC 62109-2 appliance
SHENZHEN
JINGQUANHUA T85.7*55.6*25 IEC 62109-1 Tested with
(Alternative) Class H
ELECTRONICS .4C/382uH IEC 62109-2 appliance
CO.,LTD
Shenzhen Click
T85.7*55.6*25 IEC 62109-1 Tested with
(Alternative) Technology Co., Class H
.4C/382uH IEC 62109-2 appliance
Ltd.
Qingdao Yunlu
New Energy T85.7*55.6*25 IEC 62109-1 Tested with
(Alternative) Class H
Technology Co., .4C/382uH IEC 62109-2 appliance
Ltd.
Shenzhen
Haiguang T85.7*55.6*25 IEC 62109-1 Tested with
(Alternative) Class H
Electronics Co., .4C/382uH IEC 62109-2 appliance
Ltd.
Shenzhen
Yamaxi T85.7*55.6*25 IEC 62109-1 Tested with
(Alternative) Class H
Electronics Co., .4C/382uH IEC 62109-2 appliance
Ltd.
Hef ei Ecriee- T85.7*55.6*25
(Alternative) Class H IEC 62109-1 Tested with
Tamura Electric .4C/382uH

TRF No. IEC62109_1B


Page 91 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
Co.,Ltd. IEC 62109-2 appliance
Shenzhen
T85.7*55.6*25 IEC 62109-1 Tested with
(Alternative) Hongyuansheng Class H
.4C/382uH IEC 62109-2 appliance
Electron Co.,ltd.
Sunshine
T85.7*55.6*25 IEC 62109-1 Tested with
(Alternative) Electrinics Co., Class H
.4C/382uH IEC 62109-2 appliance
Ltd.
Shenzhen
Transf ormer T85.7*55.6*25 IEC 62109-1 Tested with
(Alternative) Class H
Electronics Co., .4C/382uH IEC 62109-2 appliance
Ltd.
HuiZhou
ChuanHua T85.7*55.6*25 IEC 62109-1 Tested with
(Alternative) Class H
Magnetoelectric .4C/382uH IEC 62109-2 appliance
Co., Ltd.
JUNG SHING
-WIRE EIW-H 200℃ UL1446 UL*
WIRE CO LTD
DONGGUAN
EATTO
-EPOXY ELECTRONIC E500(XX) 130℃ UL94 UL*
MATERIAL
CO.LTD
SHENZHEN
WAHCHANGWEI
-TUBE SRS-4.0 200℃ UL1441 UL*
INDUSTRIAL CO
LTD
PV HCT1 Board
Y2 capacitor
C43Q1103-40
(C1, C2, C3, Faratronic Y2/10nF/300V EN60384-14 ENEC*
A301+++
C5, C6, C7)
R413I210000
(Alternative) ARCOTRONICS Y2/10nF/1000Vdc IEC60384 ENEC*
00K
CS14-
(Alternative) TDK F2GA103MY Y2/10nF/300Vac IEC60384 VDE*
GKA
413F2100(1)
(Alternative) KEMET Y2/10nF/300Vac IEC60384 ENEC*
M1(3)
Y2-250VAC-
(Alternative) Matsuda Industry Y2/10nF/250Vac IEC60384 VDE*
Y5V-103m
String sensor SINOMAGS
STK- IEC 62109-1 Tested with
(HCT1, 25A/5V/ -40℃~105℃
25CTS/P1 IEC 62109-2 appliance
HCT2, HCT3)

TRF No. IEC62109_1B


Page 92 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
(Alternative) AVADI K03-25P 25A/5V/ -40℃~105℃ EN60950 TUV SUD*
LEM HMSR 20-P 20A/5V/-40℃~105℃ IEC 62109-1 Tested with
(Alternative)
IEC 62109-2 appliance
LEM HMSR 30-P 30A/5V/-40℃~105℃ IEC 62109-1 Tested with
(Alternative)
IEC 62109-2 appliance
ACS724KMA -50A~+50A/- IEC 62109-1 Tested with
(Alternative) ALLEGRO
TR-50AB-T 40℃~150℃ IEC 62109-2 appliance
ACS724LMCT -65A~+65A/- IEC 62109-1 Tested with
(Alternative) ALLEGRO
R-65AB-T 40℃~150℃ IEC 62109-2 appliance
PV HCT2 Board
Y2 capacitor
C43Q1103-40
(C1, C2, C3, Faratronic Y2/10nF/300V EN60384-14 ENEC*
A301+++
C5, C6, C7)
R413I210000
(Alternative) ARCOTRONICS Y2/10nF/1000Vdc IEC60384 ENEC*
00K
CS14-
(Alternative) TDK F2GA103MY Y2/10nF/300Vac IEC60384 VDE*
GKA
413F2100(1)
(Alternative) KEMET Y2/10nF/300Vac IEC60384 ENEC*
M1(3)
Y2-250VAC-
(Alternative) Matsuda Industry Y2/10nF/250Vac IEC60384 VDE*
Y5V-103m
String sensor SINOMAGS
STK-
(HCT1, 25A/5V/ -40℃~105℃ EN 50178 VIC*
25CTS/P1
HCT2, HCT3)
(Alternative) AVADI K03-25P 25A/5V/ -40℃~105℃ EN60950 TUV SUD*
LEM HMSR 20-P 20A/5V/-40℃~105℃ IEC 62109-1 Tested with
(Alternative)
IEC 62109-2 appliance
LEM HMSR 30-P 30A/5V/-40℃~105℃ IEC 62109-1 Tested with
(Alternative)
IEC 62109-2 appliance
ACS724KMA -50A~+50A/- IEC 62109-1 Tested with
(Alternative) ALLEGRO
TR-50AB-T 40℃~150℃ IEC 62109-2 appliance
ACS724LMCT -65A~+65A/- IEC 62109-1 Tested with
(Alternative) ALLEGRO
R-65AB-T 40℃~150℃ IEC 62109-2 appliance
PV HCT3 Board
Y2 capacitor
C43Q1103-40
(C1, C2, C3, Faratronic Y2/10nF/300V EN60384-14 ENEC*
A301+++
C5, C6, C7,

TRF No. IEC62109_1B


Page 93 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
C8)
R413I210000
(Alternative) ARCOTRONICS Y2/10nF/1000Vdc IEC60384 ENEC*
00K
CS14-
(Alternative) TDK F2GA103MY Y2/10nF/300Vac IEC60384 VDE*
GKA
413F2100(1)
(Alternative) KEMET Y2/10nF/300Vac IEC60384 ENEC*
M1(3)
Y2-250VAC-
(Alternative) Matsuda Industry Y2/10nF/250Vac IEC60384 VDE*
Y5V-103m
String sensor SINOMAGS

(HCT1, STK-
25A/5V/ -40℃~105℃ EN 50178 VIC*
HCT2, HCT3, 25CTS/P1

HCT4)
(Alternative) AVADI K03-25P 25A/5V/ -40℃~105℃ EN60950 TUV SUD*
LEM HMSR 20-P 20A/5V/-40℃~105℃ IEC 62109-1 Tested with
(Alternative)
IEC 62109-2 appliance
LEM HMSR 30-P 30A/5V/-40℃~105℃ IEC 62109-1 Tested with
(Alternative)
IEC 62109-2 appliance
ACS724KMA -50A~+50A/- IEC 62109-1 Tested with
(Alternative) ALLEGRO
TR-50AB-T 40℃~150℃ IEC 62109-2 appliance
ACS724LMCT -65A~+65A/- IEC 62109-1 Tested with
(Alternative) ALLEGRO
R-65AB-T 40℃~150℃ IEC 62109-2 appliance
Control Board
X02-
Lattice 1200UHC- 256PIN /100℃ IEC 62109-1 Tested with
CPU(U4)
4FTG256I IEC 62109-2 appliance
X02-
Lattice 1200UHC- 256PIN /100℃ IEC 62109-1 Tested with
(Alternative)
5FTG256I IEC 62109-2 appliance
TMS320F280 IEC 62109-1 Tested with
CPU(U5) TI 75 176PIN/105℃
IEC 62109-2 appliance
TMS320F283 IEC 62109-1 Tested with
(Alternative) TI 74S 176PIN/105℃
IEC 62109-2 appliance
TMS320F283 IEC 62109-1 Tested with
(Alternative) TI 75S 176PIN/105℃
IEC 62109-2 appliance
TMS320F283 IEC 62109-1 Tested with
(Alternative) TI 76S 176PIN/105℃
IEC 62109-2 appliance
(Alternative) TI TMS320F283 176PIN/105℃ IEC 62109-1 Tested with

TRF No. IEC62109_1B


Page 94 of 110 Report No. 220308046GZU-003
IEC 62109-1
Clause Requirement – Test Result – Remark Verdict

14 TABLE: list of critical components P


manuf acturer/ mark(s) of
object/part No. type/model technical data standard
trademark conf ormity 1)
77S IEC 62109-2 appliance
TMS320F283 IEC 62109-1 Tested with
(Alternative) TI 78S 176PIN/105℃
IEC 62109-2 appliance
TMS320F280 IEC 62109-1 Tested with
(Alternative) TI 7N 176PIN/105℃
IEC 62109-2 appliance
TMS320F280 IEC 62109-1 Tested with
CPU(U11) TI 100PIN/105℃
67PZT IEC 62109-2 appliance
M3 Board
Y2 capacitor
(C3, C73, C43Q1472K4
Faratronic Y2/4.7nF/1500Vdc EN60384-14 ENEC*
C84, C88, 0C000

C292, C338)
R413F1470M
(Alternative) KEMET Y2/4.7nF/1000Vdc EN60384-14 ENCN*
1
Huarong Co., KY2X1472K0 Y2/4.7nF/1000Vdc/110
(Alternative) IEC60384 ENCN*
Ltd. 300AB1101 ℃
413F1470(1)
(Alternative) KEMET Y2/4.7nF/300Vac/110℃ IEC60384 ENCN*
M1(2)

ST 3.3V/-40℃~105℃ IEC 62109-1 Tested with


CPU(U9) STM32F107V
CT 7 IEC 62109-2 appliance
STM32F107V IEC 62109-1 Tested with
(Alternative) ST C T6 3.3V/105℃
IEC 62109-2 appliance
STM32F205V IEC 62109-1 Tested with
(Alternative) ST CT6 3.3V/-40℃~85℃
IEC 62109-2 appliance
STM32F205V IEC 62109-1 Tested with
(Alternative) ST ET6 3.3V/-40℃~85℃
IEC 62109-2 appliance
STM32F205V IEC 62109-1 Tested with
(Alternative) ST GT6 3.3V/-40℃~105℃
IEC 62109-2 appliance
GD32F305VC IEC 62109-1 Tested with
(Alternative) GD T6 3.3V/-40℃~85℃
IEC 62109-2 appliance
R7FA6M1AD3 IEC 62109-1 Tested with
(Alternative) RENESAS CFP#AA0 3.3V/-40℃~85℃
IEC 62109-2 appliance
1) an asterisk indicates a mark which assures the agreed level of surveillance

TRF No. IEC62109_1B


Page 95 of 110 Report No. 220308046GZU-003

Appendix 1: Photos

Top view of the unit

Back view of the unit

TRF No. IEC62109_1B


Page 96 of 110 Report No. 220308046GZU-003

PV Input Terminal view

Side view

TRF No. IEC62109_1B


Page 97 of 110 Report No. 220308046GZU-003

Side view

AC Output Terminal view

TRF No. IEC62109_1B


Page 98 of 110 Report No. 220308046GZU-003

Internal view

Internal view

TRF No. IEC62109_1B


Page 99 of 110 Report No. 220308046GZU-003

Internal view

Power board view (Components side)

TRF No. IEC62109_1B


Page 100 of 110 Report No. 220308046GZU-003

Power board view (Soldered side)

I/O board view (Components side)

TRF No. IEC62109_1B


Page 101 of 110 Report No. 220308046GZU-003

I/O board view (Soldered side)

Cap board view (Components side)

TRF No. IEC62109_1B


Page 102 of 110 Report No. 220308046GZU-003

Cap board view (Reverse)

Control board view

TRF No. IEC62109_1B


Page 103 of 110 Report No. 220308046GZU-003

Control board view (Reverse)

PV Input board view f or MAX-XL2 series

TRF No. IEC62109_1B


Page 104 of 110 Report No. 220308046GZU-003

PV Input board view f or MAX-XL1 series

PV Input board view (Reverse) f or MAX-XL2 series

TRF No. IEC62109_1B


Page 105 of 110 Report No. 220308046GZU-003

AC Filter board view

AC Filter board view (Reverse)

TRF No. IEC62109_1B


Page 106 of 110 Report No. 220308046GZU-003

M3 Board view

M3 Board view (Reverse)

TRF No. IEC62109_1B


Page 107 of 110 Report No. 220308046GZU-003

Transf er Board view

Transf er Board view (Reverse)

TRF No. IEC62109_1B


Page 108 of 110 Report No. 220308046GZU-003

HCT1 Board view

HCT1 Board view (Reverse)

TRF No. IEC62109_1B


Page 109 of 110 Report No. 220308046GZU-003

HCT2 Board view

HCT2 Board view (Reverse)

TRF No. IEC62109_1B


Page 110 of 110 Report No. 220308046GZU-003

HCT3 Board view

(End of Report)

TRF No. IEC62109_1B


Test Report issued under the responsibility of:

TEST REPORT
IEC 62109-2
Safety of Power Converter for use in Photovoltaic Power Systems
Part 2: Particular requirements for inverters
Report Number. ............................ : 220308046GZU-004
Date of issue ................................ : 22 Jun 2022
Total number of pages .................. 27 pages

Name of Testing Laboratory Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
preparing the Report……………….: Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of
Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD,
Guangzhou, Guangdong, China
Applicant’s name.......................... : Shenzhen Growatt New Energy Co., Ltd.
Address ........................................ : 4-13/F, Building A, Sino-German (Europe) Industrial Park,
Hangcheng Ave, Bao’an District, Shenzhen, China
Test specification:
Standard....................................... : IEC/EN 62109-2:2011
Test procedure ............................. : Type approval
Non-standard test method…………..: N/A
Test Report Form No. ................... : IEC62109_2B
Test Report Form (s) Originator .... : LCIE - Laboratoire Central des Industries Electriques
Master TRF ................................... : Dated 2016-11
Copyright © 2016 IEC System of Conformity Assessment Schemes for Electrotechnical
Equipment and Components (IECEE System). All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as
copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting
from the reader's interpretation of the reproduced material due to its placement and context.

If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the ref erence to the
CB Scheme procedure shall be removed.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory
and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.
General disclaimer:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in f ull, without the written approval of the Issuing CB Testing
Laboratory. The authenticity of this Test Report and its contents can be verif ied by contacting the NCB,
responsible f or this Test Report.
Page 2 of 27 Report No. 220308046GZU-004
PV Grid
Test item description ..................... : inverter

GROWATT
Trade Mark ..................................... :
Same :as applicant
Manufacturer..................................
MAX 50KTL3-XL2,
Model/Type reference .................... : MAX 60KTL3-XL2, MAX 70KTL3-XL2, MAX 73KTL3-
XL2, MAX 75KTL3-XL2, MAX 50KTL3-XL1, MAX 60KTL3-XL1, MAX
70KTL3-XL1, MAX 73KTL3-XL1, MAX 75KTL3-XL1
Model
Ratings .......................................... : MAX MAX MAX MAX MAX
50KTL3- 60KTL3- 70KTL3- 73KTL3- 75KTL3-
XL2 XL2 XL2 XL2 XL2
Max.PV
1100Vdc
voltage
MPPT
180-850Vdc
voltage

Max.input
8*45A
current
PV Isc 8*56.5A
Nominal
output 3W/N/PE, 127/220Vac
voltage

Nominal
output 50/60Hz
Frequency
Max.output
144.3A 173.2A 183.7A 191.6A 196.9A
current
Max. output
50KW 60KW 70KW 73KW 75KW
power
Max.
apparent 55KVA 66KVA 70KVA 73KVA 75KVA
power
Power factor
0.8Leading~0.8Lagging
range
Safety level Class I
Ingress
IP 66
Protection
Operation
Ambient -30℃ - +60℃
Temperature
Software
TN1.0
version

Model MAX MAX MAX MAX MAX


50KTL3- 60KTL3- 70KTL3- 73KTL3- 75KTL3-

TRF No. IEC62109_2B


Page 3 of 27 Report No. 220308046GZU-004
XL1 XL1 XL1 XL1 XL1
Max.PV
1100Vdc
voltage
MPPT
180-850Vdc
voltage
Max.input
10*32A
current
PV Isc 10*40A
Nominal
output 3W/N/PE, 127/220Vac
voltage

Nominal
output 50/60Hz
Frequency
Max.output
144.3A 173.2A 183.7A 191.6A 196.9A
current
Max. output
50KW 60KW 70KW 73KW 75KW
power
Max.
apparent 55KVA 66KVA 70KVA 73KVA 75KVA
power
Power factor
0.8Leading~0.8Lagging
range

Safety level Class I


Ingress
IP 66
Protection
Operation
Ambient -30℃ - +60℃
Temperature
Software
TN1.0
version

TRF No. IEC62109_2B


Page 4 of 27 Report No. 220308046GZU-004

Responsible Testing Laboratory (as applicable), testing procedure and testing location(s):

Testing Laboratory: Intertek Testing Services Shenzhen Ltd. Guangzhou


Branch
Testing location/ address........................... : Room 02, & 101/E201/E301/E401/E501/E601/E701/E801
of Room 01 1-8/F., No. 7-2. Caipin Road, Science City,
GETDD, Guangzhou, Guangdong, China
Tested by (name, function, signature)........ : Jason Fu
Supervisor
Approved by (name, function, signature) ... : Tommy Zhong
Technical Manager

Testing procedure: CTF Stage 1: N/A


Testing location/ address........................... : N/A

Tested by (name, function, signature)........ : N/A


Approved by (name, function, signature) ... : N/A

Testing procedure: CTF Stage 2: N/A


Testing location/ address........................... : N/A

Tested by (name + signature) ..................... : N/A

Witnessed by (name, function, signature) .. : N/A


Approved by (name, function, signature) ... : N/A

Testing procedure: CTF Stage 3: N/A


Testing procedure: CTF Stage 4: N/A
Testing location/ address........................... : N/A

Tested by (name, function, signature)........ : N/A


Witnessed by (name, function, signature) .. : N/A
Approved by (name, function, signature) ... : N/A
Supervised by (name, function, signature) : N/A

TRF No. IEC62109_2B


Page 5 of 27 Report No. 220308046GZU-004

List of Attachments (including a total number of pages in each attachment):


N/A

Summary of testing:

Tests performed (name of test and test Testing location:


clause):
Intertek Testing Services Shenzhen Ltd.
All applicable tests Guangzhou Branch
Room 02, &
101/E201/E301/E401/E501/E601/E701/E801 of
Room 01 1-8/F., No. 7-2. Caipin Road, Science
City, GETDD, Guangzhou, Guangdong, China

Summary of compliance with National Differences (List of countries addressed):


N/A

The product fulfils the requirements of IEC/EN 62109-2:2011

TRF No. IEC62109_2B


Page 6 of 27 Report No. 220308046GZU-004

Copy of marking plate:


The artwork below may be only a draft. The use of certification marks on a product must be
authorized by the respective NCBs that own these marks.

Note:
1. The above markings are the minimum requirements required by the safety standard. For the
final production samples, the additional markings which do not give rise to misunderstanding
may be added.
2. Label is attached on the side surface of enclosure and visible after instal lation.
3. Other labels are identical to above, except the model’s name and ratings

TRF No. IEC62109_2B


Page 7 of 27 Report No. 220308046GZU-004
Test item particulars ............................................ :
Equipment mobility ............................................. : movable hand-held stationary
fixed transportable for building-
in
Connection to the mains..................................... : pluggable equipment direct plug-in
permanent connection for building-in
Enviromental category........................................ : outdoor indoor indoor
unconditional conditional
Over voltage category Mains .............................. : OVC I OVC II OVC III OVC IV
Over voltage category PV ................................... : OVC I OVC II OVC III OVC IV
Mains suppl y tolerance (%)................................. : -90 / +110 %
Tested for power system s .................................. : TN systems
IT testing, phase-phase voltage (V)..................... : ---
Class of equipment ............................................. : Class I Class II Class III
Not classified
Mass of equipment (kg) ...................................... : Approx. 84Kg
Pollution degree ................................................. : Outside PD3; Inside PD2
IP protection class .............................................. : IP 66
............................................................................ :

Possible test case verdicts:


- test case does not apply to the test object .......... : N/A
- test object does meet the requirement................ : P (Pass)
- test object does not meet the requirement.......... : F (Fail)
Testing ................................................................. :
Date of receipt of test item .................................... : 06 April 2022
Date (s) of performance of tests ........................... : 06 April 2022 to 08 Jun 2022

TRF No. IEC62109_2B


Page 8 of 27 Report No. 220308046GZU-004
General remarks:
"(See Enclosure #)" ref ers to additional inf ormation appended to the report.
"(See appended table)" ref ers to a table appended to the report.

Throughout this report a comma / point is used as the decimal separator.


This report shall be used together with report No. 220308046GZU-003
Manufacturer’s Declaration per sub-clause 4.2.5 of IECEE 02:
The application f or obtaining a CB Test Certif icate Yes
includes more than one f actory location and a
declaration f rom the Manuf acturer stating that the Not applicable
sample(s) submitted f or evaluation is (are)
representative of the products f rom each f actory has
been provided ........................................................ :

When differences exist; they shall be identified in the General product information section.
Name and address of factory (ies) : Guangdong Growatt New Energy Co., Ltd.
Growatt Industrial Park,No.17 Pingheng Road Pingtan Town,Huiya
ng District,Huizhou,Guangdong,China

TRF No. IEC62109_2B


Page 9 of 27 Report No. 220308046GZU-004
General product information:
The unit is a three-phase PV Grid inverter, it can convert the high PV voltage to Grid voltage and f eed into
Grid network.
The unit is providing EMC f iltering at the PV side and AC side. It is transf ormerless between the PV circuit
and AC circuit.
The unit has three controllers. The master controller DSP A measure the PV voltage and current, AFCI, PV
ISO and also communicate with the slave controller B and slave controller ARM and etc; The slave
controller DSP B is used to INV control and PV ISO measurement and etc.
The slave controller ARM monitor AC voltage, GFCI and communicate with the master controller DSP
The relays are designed to redundant structure that controlled by separately.
The master controller A and slave controller B are used together to control relay open or close, if the single
f ault on one controller, the other controller can be capable to open the relay, so that still providing saf ety
means.
The topology diagram as f ollowing:

Model differences:
All models are identical, except the number of MPPT and the output power derating in software.
The product was tested on:
The Software version: TN1.0
The Hardware version: V1.0
Other than special notes, typical model MAX 75KTL3-XL2 is used as representative for testing in this
report.

TRF No. IEC62109_2B


Page 10 of 27 Report No. 220308046GZU-004
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict

4 GENERAL TESTING REQUIREMENTS P


4.4.4 Single fault conditions to be applied P
4.4.4.15 Fault-tolerance of protection for grid-interactive P
inverters
4.4.4.15.1 Fault-tolerance of residual current monitoring See appended table P
according to 4.8.3.5: the residual current monitoring 4.4.4.15.1
system operates properly
a) . - The inverter ceases to operate P
- Indicates a f ault in accordance with §13.9 P
- Disconnect f rom the mains P
- not re-connect af ter any sequence of removing and P
reconnecting PV power
- not re-connect af ter any sequence of removing and P
reconnecting AC power
- not re-connect af ter any sequence of removing and P
reconnecting both PV and AC power
b) . - The inverter continues to operate N/A
- the residual current monitoring system operates N/A
properly under single f ault condition
- Indicates a f ault in accordance with §13.9 N/A
c) . - The inverter continues to operate regardless of N/A
loss of residual current monitoring functionality
- not re-connect af ter any sequence of removing and N/A
reconnecting PV power
- not re-connect af ter any sequence of removing and N/A
reconnecting AC power
- not re-connect af ter any sequence of removing and N/A
reconnecting both PV and AC power
- Indicates a f ault in accordance with §13.9 N/A
4.4.4.15.2 Fault-tolerance of automatic disconnecting means Two series relays in each line P
and can independent
operation f or each relay.
4.4.4.15.2 The means provided for automatic disconnection of a P
.1 grid-interactive inverter from the mains shall:
- disconnect all grounded current-carrying conductors Disconnected all line P
f rom the mains conductors from the mains

- disconnect all ungrounded current-carrying conductors P


f rom the mains
- be such that with a single f ault applied to the See appended table P
disconnection means or to any other location in the 4.4.4.15.2 Fault-tolerance of
inverter, at least basic insulation or simple separation automatic disconnecting
is maintained between the PV array and the mains There are two relays in serial
when the disconnecting means is intended to be in the used as automatic
open state. disconnection means.
Contact gap is basic
insulation.
4.4.4.15.2 Design of insulation or separation complies with The automatic disconnection P
.2 requirements of 7.3.7 of Part 1: report here Part 1 means is automatically

TRF No. IEC62109_2B


Page 11 of 27 Report No. 220308046GZU-004
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict

comment and verdict. checked bef ore the inverter


start operation
4.4.4.15.2 For non-isolated inverter, automatic checking of the See appended test table P
.3 isolation provided by a disconnect means after single 4.4.4.15.2 Fault-tolerance
fault. of automatic
disconnecting.
If the check f ail: P
- any still-f unctional disconnection means shall be lef t in
the open position
- at least basic or simple separation shall be maintained P
between the PV input and the mains
- the inverter shall not start operation P
- the inverter shall indicate a f ault in accordance with The screen shown error P
13.9 inf ormation.
4.4.4.16 A stand-alone inverter with a transfer switch to No such transf er switch N/A
transfer AC loads from the mains or other AC bypass
source to the inverter output:
- shall continue to operate normally N/A
- shall not present a risk of f ire as the result of an out-of- N/A
phase transf er
- shall not present a risk of shock as the result of an out- N/A
of -phase transf er
- And having control preventing switching: components N/A
f or malf unctioning ………….…:
4.4.4.17 Cooling system failure – Blanketing test See appended test table P
No hazards according to the criteria of sub-clause Cooling system failure –
4.4.3 of Part 1 shall result from blanketing the inverter Blanketing test.
This test is not required for inverters restricted to use
only in closed electrical operating areas.
Test stop condition: time duration value or stabilized P
temperature ………………………….:
4.7 ELECTRICAL RATINGS TESTS P
4.7.4 Stand-alone Inverter AC output voltage and frequency N/A
4.7.4.1 General N/A
4.7.4.2 Steady state output voltage at nominal DC input N/A
The steady-state AC output voltage shall not be less
than 90 % or more than 110 % of the rated nominal
voltage with the inverter supplied with its nominal
value of DC input voltage.
4.7.4.3 Steady state output voltage across the DC input range N/A
The steady-state AC output voltage shall not be less
than 85 % or more than 110 % of the rated nominal
voltage with the inverter supplied with any value within
the rated range of DC input voltage.
4.7.4.4 Load step response of the output voltage at nominal N/A
DC input
The AC output voltage shall not be less than 85 % or
more than 110 % of the rated nominal voltage for more
than 1,5 s after application or removal of a resistive
load.

TRF No. IEC62109_2B


Page 12 of 27 Report No. 220308046GZU-004
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict

4.7.4.5 Steady state output frequency N/A


The steady-state AC output frequency shall not vary
from the nominal value by more than +4 % or –6 %.
4.7.5 Stand-alone inverter output voltage waveform N/A
4.7.5.1 General N/A
4.7.5.2 The AC output voltage waveform of a sinusoidal N/A
output stand-alone inverter shall have a total harmonic
distortion (THD) not exceeding of 10 % and no
individual harmonic at a level exceeding 6 %.
4.7.5.3 Non-sinusoidal output waveform requirements N/A
4.7.5.3.1 General N/A
4.7.5.3.2 The total harmonic distortion (THD) of the voltage N/A
waveform shall not exceed 40 %.
4.7.5.3.3 The slope of the rising and falling edges of the positive N/A
and negative half-cycles of the voltage waveform shall
not exceed 10 V/µs measured between the points at
which the waveform has a voltage of 10 % and 90 % of
the peak voltage for that half-cycle.
4.7.5.3.4 The absolute value of the peak voltage of the positive N/A
and negative half-cycles of the waveform shall not
exceed 1,414 times 110 % of the RMS value of the rated
nominal AC output voltage.
4.7.5.4 Information requirements for non-sinusoidal N/A
waveforms
The instructions provided with a stand-alone inverter
not complying with 4.7.5.2 shall include the
information in 5.3.2.6.
4.7.5.5 Output voltage waveform requirements for inverters for dedicated loads. N/A
For an inverter that is intended only for use with a known dedicated load, the
following requirements may be used as an alternative to the waveform requirements
in 4.7.5.2 to 4.7.5.3.
The combination of the inverter and dedicated load shall be N/A
evaluated to ensure that the output wavef orm does not
cause any hazards in the load equipment and inverter, or
cause the load equipment to f ail to comply with the
applicable product safety standards.
The inverter shall be marked with symbols 9 and 15 of N/A
Table C.1 of Part 1.
The installation instructions provided with the inverter shall N/A
include the inf ormation in 5.3.2.13.
4.8 ADDITIONAL TESTS FOR GRID-INTERACTIVE INVERTERS P
4.8.1 General requirements regarding inverter isolation and Non-isolation inverter N/A
array grounding
- Type of Array grounding supported ………: N/A
- Inverter isolation …………………………….: N/A
4.8.2 Array insulation resistance detection for inverters for (See attached table) P
ungrounded and functionally grounded arrays
4.8.2.1 Array insulation resistance detection for inverters for P
ungrounded arrays
Inverter shall have means to measure DC insulation P

TRF No. IEC62109_2B


Page 13 of 27 Report No. 220308046GZU-004
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict

resistance f rom PV input (array) to ground before starting


operation
Or Inverter shall be provided with instruction in accordance The inverter can measure DC N/A
with 5.3.2.11. insulation resistance f rom PV
input array to ground bef ore
starting operation
Measured DC insulation resistance: ……………: P
Inverter measurement circuit shall be capable of detecting P
insulation resistance below the limit value R= Vmax/30mA
under normal conditions
Inverter measurement circuit shall be capable of detecting P
insulation resistance below the limit value R= Vmax/30mA
with ground f ault in the PV array
Isolated inverters shall indicate a f ault if the insulation N/A
resistance is less than the limit value
Isolated inverter f ault indication maintained until insulation N/A
resistance has recovered to a value higher than the limit
value
Non-isolated inverters, or inverters with isolation not complying with the leakage current P
limits in the minimum inverter isolation requirements in Table 30:
- shall indicate a f ault in accordance with 13.9 P
- shall not connect to the mains P
4.8.2.2 Array insulation resistance detection for inverters for N/A
functionally grounded arrays
a-1)The value of the total resistance, including the N/A
intentional resistance f or array f unctional grounding, the
expected insulation resistance of the array to ground, and
the resistance of any other networks connected to ground
(f or example measurement networks) must not be lower
than R = (VMAX PV/30 mA) ohms.
a-2) The installation instructions shall include the N/A
inf ormation required in 5.3.2.12.
b-1) As an alternative to a), or if a resistor value lower than N/A
in a) is used, the inverter shall incorporate means to detect,
during operation, if the total current through the resistor
and any networks (f or example measurement networks) in
parallel with it, exceeds the residual current values and
times in Table 31
b-2) Inverter shall either disconnect the resistor or limit the N/A
current by other means ……………:
b-3) If the inverter is a non-isolated inverter, or has isolation N/A
not complying with the leakage current limits in the
minimum inverter isolation requirements in Table 30, it
shall also disconnect from the mains.
c) The inverter shall have means to measure the DC N/A
insulation resistance f rom the PV input to ground before
starting operation, in accordance with 4.8.2.1.
4.8.3 Array residual current detection P
4.8.3.1 General P
4.8.3.2 30 mA touch current type test for isolated inverters N/A

TRF No. IEC62109_2B


Page 14 of 27 Report No. 220308046GZU-004
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict

4.8.3.3 Fire hazard residual current type test for isolated N/A
inverters
4.8.3.4 Protection by application of RCD’s Integrated RCM inside PCE P
- The requirement f or additional protection in 4.8.3.1 can P
be met by provision of an RCD with a residual current
setting of 30 mA, located between the inverter and the
mains..
- The selection of the RCD type to ensure compatibility P
with the inverter must be made according to rules f or
RCD selection in Part 1.
- The RCD provided integral to the inverter, or P
- The RCD provided by the installer if details of the N/A
rating, type, and location for the RCD are given in the
installation instructions per 5.3.2.9.
4.8.3.5 Protection by residual current monitoring P
4.8.3.5.1 General P
Where required by Table 30, the inverter shall provide P
residual current monitoring that f unctions whenever the
inverter is connected to the mains with the automatic
disconnection means closed.
The residual current monitoring means shall measure the P
total (both a.c. and d.c. components) RMS current.
As indicated in Table 30 f or different inverter types, array P
types, and inverter isolation levels, detection may be
required f or excessive continuous residual current,
excessive sudden changes in residual current, or both,
according to the f ollowing limits:
a) Continuous residual current: The inverter shall disconnect within 0,3 s and indicate a f ault P
in accordance with 13.9 if the continuous residual current ex ceeds:
- maximum 300 mA f or inverters with continuous ouput P
power rating ≤30kVA;
- maximum 10 mA per kVA of rated continuous output N/A
power f or inverters with continuous output power
rating > 30 kVA.
The inverter may attempt to re-connect if the array P
insulation resistance meets the limit in 4.8.2.
b) Sudden changes in residual current: The inverter shall P
disconnect f rom the mains within the time specif ied in
Table 31
The inverter indicates a f ault in accordance with 13.9, if a P
sudden increase in the RMS residual current is detected
exceeding the value in the table.
The inverter may attempt to re-connect if the array P
insulation resistance meets the limit in 4.8.2.
4.8.3.5.2 Test for detection of excessive continuous residual See appended test table P
current: test repeated 5 times and time to disconnect 4.8.3.5.2 Test for detection
shall not exceed 0,3 s. of excessive continuous
residual current
4.8.3.5.3 Test for detection of sudden changes in residual P
current repeated 5 times and each of the 5 results shall
not exceed the time limit indicated in for each row

TRF No. IEC62109_2B


Page 15 of 27 Report No. 220308046GZU-004
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict

(30mA, 60mA and150mA) of Table 31.


4.8.3.6 Systems located in closed electrical operating areas N/A
The protection against shock hazard is not required if N/A
the installation information provided with the inverter
indicates the restriction for use in a closed electrical
operating area, and
Installation inf ormation indicates what f orms of shock N/A
hazard protection are and are not provided integral to the
inverter, in accordance with 5.3.2.7.
The inverter shall be marked as in 5.2.2.6. N/A

5 MARKING AND DOCUMENTATION P


5.1 Marking P
5.1.4 Equipment ratings P
PV input ratings: See markings P
- Vmax PV (absolute maximum) (d.c. V) P
- Isc PV (absolute maximum) (d.c. A) P
a.c. output ratings: P
- Voltage (nominal or range) (a.c. V) P
- Current (maximum continuous) (a.c. A) P
- Frequency (nominal or range) (Hz) P
- Power (maximum continuous) (W or VA) P
- Power f actor range P
a.c input ratings: N/A
- Voltage (nominal or range) (a.c. V) N/A
- Current (maximum continuous) (a.c. A) N/A
- Frequency (nominal or range) (Hz) N/A
d.c input (other than PV) ratings: N/A
- Voltage (nominal or range) (d.c. V) N/A
- Current (maximum continuous) (d.c. A) N/A
d.c. output ratings: N/A
- Voltage (nominal or range) (d.c. V) N/A
- Current (maximum continuous) (d.c. A) N/A
Protective class (I or II or III) P
Ingress protection (IP) rating per part 1 P
An inverter that is adjustable f or more than one nominal N/A
output voltage shall be marked to indicate the particular
voltage f or which it is set when shipped f rom the f actory.
5.2 Warning markings P
5.2.2 Content for warning markings P
5.2.2.6 Inverters for closed electrical operating areas N/A
Where required by 4.8.3.6, an inverter not provided with N/A
f ull protection against shock hazard on the PV array shall
be marked with a warning that the inverter is only f or use
in a closed electrical operating area, and ref erring to the
installation instructions.
5.3 Documentation P
5.3.2 Information related to installation P

TRF No. IEC62109_2B


Page 16 of 27 Report No. 220308046GZU-004
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict

5.3.2.1 Ratings. Subclause 5.3.2 of Part 1 requires the documentation to include ratings P
information for each input and output. For inverters this information shall be as in
Table 33 below. Only those ratings that are applicable based on the type of inverter
are required.
PV input quantities : P
- Vmax PV (absolute maximum) (d.c. V) P
- PV input operating voltage range (d.c. V) P
- Maximum operating PV input current (d.c. A) P
- Isc PV (absolute maximum) (d.c. A) P
- Isc PV (absolute maximum) (d.c. A) P
- Max. inverter backf eed current to the array (a.c. or P
d.c. A)
a.c. output quantities: P
- Voltage (nominal or range) (a.c. V) P
- Current (maximum continuous) (a.c. A) P
- Current (inrush) (a.c. A, peak and duration) P
- Frequency (nominal or range) (Hz) P
- Power (maximum continuous) (W or VA) P
- Power f actor range P
- Maximum output f ault current (a.c. A, peak and P
duration or RMS)
- Maximum output overcurrent protection (a.c. A) P
a.c. input quantities: N/A
- Voltage (nominal or range) (a.c. V) N/A
- Current (maximum continuous) (a.c. A) N/A
- Current (inrush) (a.c. A, peak and duration) N/A
- Frequency (nominal or range) (Hz) N/A
d.c input (other than PV) quantities: N/A
- Voltage (nominal or range) (d.c. V) N/A
- Nominal battery voltage (d.c. V) N/A
- Current (maximum continuous) (d.c. A) N/A
d.c. output quantities: N/A
- Voltage (nominal or range) (d.c. V) N/A
- Nominal battery voltage (d.c. V) N/A
- Current (maximum continuous) (d.c. A) N/A
Protective class (I or II or III) P
Ingress protection (IP) rating per part 1 P
5.3.2.2 Grid-interactive inverter setpoints N/A
For a grid-interactive unit with f ield adjustable trip points, No adjustable setting N/A
trip times, or reconnect times, the presence of such available. Only the f actory
controls, the means f or adjustment, the f actory def ault def ault values, however the
values, and the limits of the ranges of adjustability shall adjustment shall be perf orme
be provided in the documentation f or the PCE or in other d by distribution network
f ormat such as on a website. operator.
Provided solution: …………………………………….
The setting of f ield adjustable setpoints shall be N/A
accessible f rom the PCE
5.3.2.3 Transformers and isolation N/A

TRF No. IEC62109_2B


Page 17 of 27 Report No. 220308046GZU-004
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict

whether an internal isolation transf ormer is provided, and N/A


if so, what level of insulation (f unctional, basic, reinf orced,
or double) is provided by that transf ormer. The
instructions shall also indicate what the resulting
installation requirements are regarding such things as
earthing or not earthing the array, providing external
residual current detection devices, etc.
An inverter shall be provided with inf ormation to the installer regarding: N/A
- providing of internal isolation transf ormer N/A
- the level of insulation (f unctional, basic, reinf orced, or N/A
double)
The instructions shall also indicate what the resulting installation requirements are N/A
regarding:
- earthing or not earthing the array N/A
- providing external residual current detection devices N/A
- requiring an external isolation transf ormer, N/A
5.3.2.4 Transformers required but not provided N/A
An inverter that requires an external isolation transf ormer not provided with the unit, shall
be provided with instructions that specif y, and f or the external isolation transf ormer with N/A
which it is intended to be used:
- the conf iguration type N/A
- electrical ratings N/A
- environmental ratings N/A
5.3.2.5 PV modules for non-isolated inverters P
Non-isolated inverters shall be provided with installation P
instructions that require PV modules that have an IEC
61730 Class A rating
If the maximum AC mains operating voltage is higher than N/A
the PV array maximum system voltage then the
instructions shall require PV modules that have a
maximum system voltage rating based upon the AC
mains voltage.
5.3.2.6 Non-sinusoidal output waveform information N/A
The instruction manual f or a stand-alone inverter not complying with 4.7.5.2 shall include N/A
a warning that:
- the wavef orm is not sinusoidal, N/A
- some loads may experience increased heating, N/A
- the user should consult the manuf acturers of the N/A
intended load equipment bef ore operating that load
with the inverter
The inverter manuf acturer shall provide inf ormation regarding: N/A
- what types of loads may experience increased N/A
heating
- recommendations f or maximum operating times with N/A
such loads
The inverter manuf acturer shall specif y f or the wavef orms as determined by the testing in N/A
4.7.5.3.2 through 4.7.5.3.4.:
- THD N/A
- slope N/A
- peak voltage N/A

TRF No. IEC62109_2B


Page 18 of 27 Report No. 220308046GZU-004
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict

5.3.2.7 Systems located in closed electrical operating areas N/A


Where required by 4.8.3.6, an inverter not provided with f ull protection against shock N/A
hazard on the PV array shall be provided with installation instructions:
- requiring that the inverter and the array must be N/A
installed in closed electrical operating areas
- indicating which f orms of shock hazard protection are N/A
and are not provided integral to the inverter (f or
example the RCD, isolation transf ormer complying
with the 30 mA touch current limit, or residual current
monitoring f or sudden changes)
5.3.2.8 Stand-alone inverter output circuit bonding N/A
Where required by 7.3.10, the documentation f or an inverter shall include the f ollowing: N/A
- if output circuit bonding is required but is not provided N/A
integral to the inverter, the required means shall be
described in the installation instructions, including
which conductor is to be bonded and the required
current carrying capability or cross-section of the
bonding means;
- if the output circuit is intended to be f loating, the N/A
documentation f or the inverter shall indicate that the
output is f loating.
5.3.2.9 Protection by application of RCD’s Integrated RCM used inside N/A
Where the requirement f or additional protection in 4.8.3.1 N/A
is met by requiring an RCD that is not provided integral to
the inverter, as allowed by 4.8.3.4, the installation
instructions shall state the need f or the RCD,.
and shall specif y its rating, type, and required circuit N/A
location
5.3.2.10 Remote indication of faults P
The installation instructions shall include an explanation The instructions are specif ied P
of how to properly make connections to (where insection “Warning List ”of th
applicable), and use, the electrical or electronic f ault e product manual.
indication required by 13.9.
5.3.2.11 External array insulation resistance measurement Integrated resistance N/A
and response measurement inside
The installation instructions f or an inverter f or use with ungrounded arrays that does not N/A
incorporate all the aspects of the insulation resistance measurement and res ponse
requirements in 4.8.2.1, must include:
- f or isolated inverters: an explanation of what aspects N/A
of array insulation resistance measurement and response
are not provided, and
- an instruction to consult local regulations to determine N/A
if any additional f unctions are required or not;
- f or non-isolated inverters: an explanation of what N/A
external equipment must be provided in the system,
and
- what the setpoints and response implemented by that N/A
equipment must be, and:
- how that equipment is to be interf aced with the rest of N/A
the system.

TRF No. IEC62109_2B


Page 19 of 27 Report No. 220308046GZU-004
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict

5.3.2.12 Array functional grounding information N/A


Where approach a) of 4.8.2.2 is used, the installation instructions f or the inverter shall N/A
include all of the f ollowing:
a) the value of the total resistance between the PV N/A
circuit and ground integral to the inverter ………
b) the minimum array insulation resistance to ground N/A
that system designer or installer must meet when
selecting the PV panel and system design, based on
the minimum value that the design of the PV
f unctional grounding in the inverter was based
on ……………………………;
c) the minimum value of the total resistance R = VMAX N/A
PV/30 mA that the system must meet, with an
explanation of how to calculate the
total …………………………………………………;
d) a warning that there is a risk of shock hazard if the N/A
total minimum resistance requirement is not met.
5.3.2.13 Stand-alone inverters for dedicated loads N/A
Where the approach of 4.7.5.5 is used, the installation N/A
instructions f or the inverter shall include a warning that
the inverter is only to be used with the dedicated load f or
which it was evaluated, and
shall specif y the dedicated load. N/A
5.3.2.14 Identification of firmware version(s) P
An inverter utilizing f irmware f or any protective f unctions P
shall provide means to identif y the f irmware version.
This can be a marking, but the inf ormation can also be The f irmware version is P
provided by a display panel, communications port or any displayed on LCD display
other type of user interf ace……………………. panel and disclosed by
communication interf ace.

7 PROTECTION AGAINST ELECTRIC SHOCK AND ENERGY HAZARDS P


7.3 Protection against electric shock P
7.3.10 Additional requirements for stand-alone inverters N/A
One circuit conductor bonded to earth to create a N/A
grounded conductor and an earthed system.
The means used to bond the grounded conductor to N/A
protective earth provided within the inverter or
as part of the installation N/A
If not provided integral to the inverter, the required means N/A
shall be described in the installation instructions as per
5.3.2.8.
The means used to bond the grounded conductor to N/A
protective earth shall comply with the requirements f or
protective bonding in Part 1,
If the bond can only ever carry f ault currents in stand- N/A
alone mode, the maximum current f or the bond is
determined by the inverter maximum output f ault current.

TRF No. IEC62109_2B


Page 20 of 27 Report No. 220308046GZU-004
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict

Output circuit bonding arrangements shall ensure that in N/A


any mode of operation, the system only has the grounded
circuit conductor bonded to earth in one place at a time..
Switching arrangements may be used, in which case the N/A
switching device used is to be subjected to the bond
impedance test along with the rest of the bonding p ath
Inverters intended to have a circuit conductor bonded to N/A
earth shall not impose any normal current on the bond
except f or leakage current.
Outputs that are intentionally f loating with no circuit N/A
conductor bonded to ground, must not have any voltages
with respect to ground that are a shock hazard in
accordance with Clause 7 of Parts 1 and 2.
The documentation f or the inverter shall indicate that the N/A
output is f loating as per 5.3.2.8.
7.3.11 Functionally grounded arrays N/A
All PV conductors in a f unctionally grounded array shall N/A
be treated as being live parts with respect to protection
against electric shock.

9 PROTECTION AGAINST FIRE HAZARDS P


9.3 Short-circuit and overcurrent protection P
9.3.4 Inverter backfeed current onto the array P
The backf eed current testing and documentation requirements in Part 1 apply, including P
but not limited to the f ollowing.
Inverter backf eed current onto the PV array maximum P
value…………………………………….….
This inverter backf eed current value shall be provided in No backf eed current that can P
the installation instructions regardless of the value of the f low out of the inverter PV
current, in accordance with Table 33. input terminals.

13 PHYSICAL REQUIREMENTS P
13.9 Fault indication P
Where this Part 2 requires the inverter to indicate a f ault, both of the f ollowing shall be P
provided:
a) a visible or audible indication, integral to the inverter, P
and detectable f rom outside the inverter, and
b) an electrical or electronic indication that can be P
remotely accessed and used.
The installation instructions shall include inf ormation P
regarding how to properly make connections (where
applicable) and use the electrical or electronic means in
b) above, in accordance with 5.3.2.10.

TRF No. IEC62109_2B


Page 21 of 27 Report No. 220308046GZU-004
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict

4.4.4 TABLE: Single f ault condition to be applied P


Ambient temperature (C) ................................. : 25 ⎯
Power source f or EUT: Manuf acturer, -- ⎯
model/type, output rating .................................. :
4.4.4.15.1 Fault-tolerance of residual current monitoring
Componen Fault Supply Test Fuse # Fuse Observation
t voltage time current
No. (V) (A)
Error message: “Error 201”.

GFCI EUT disconnected f rom grid


s-c 600 5min -- --
f ailure(C7) immediately.
No damage, no hazard.
Error message: “Error 201”.
GFCI EUT disconnected f rom grid
f ailure(R19 o-c 600 5min -- --
immediately.
)
No damage, no hazard.
Check that the residual current monitoring operates properly Yes
Supplementary inf ormation:

4.4.4 TABLE: Single f ault condition to be applied P


Ambient temperature (C) ................................25: ⎯
Power source f or EUT: Manuf acturer, -- ⎯
model/type, output rating .................................. :
4.4.4.15.2 Fault-tolerance of automatic disconnecting means
Component Fault Supply Test Fuse # Fuse Observation
No. voltage time current
(V) (A)
Error message: “Error 405”.
s-c bef ore
RY3 600 5min -- -- EUT can't start.
start up
No damage, no hazard.
Error message: “Error 405”.
s-c bef ore
RY4 600 5min -- -- EUT can't start.
start up
No damage, no hazard.
Error message: “Error 405”.
s-c bef ore
RY5 600 5min -- -- EUT can't start.
start up
No damage, no hazard.

TRF No. IEC62109_2B


Page 22 of 27 Report No. 220308046GZU-004
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict

Error message: “Error 405”.


s-c bef ore
RY6 600 5min -- -- EUT can't start.
start up
No damage, no hazard.
Error message: “Error 405”.
s-c bef ore
RY7 start up 600 5min -- -- EUT can't start.
No damage, no hazard.
Error message: “Error 405”.
s-c bef ore
RY8 600 5min -- -- EUT can't start.
start up
No damage, no hazard.
Check that the relays f ulf il the basic insulation or simple separation There are two relays in serial used as
based on the PV circuit working voltage. automatic disconnection means.
Each active phase can be switched. (L and N) Yes
Supplementary inf ormation:

4.4.4.17 Cooling system f ainlure – Blanketing test P


Test voltage (Vdc).......................... : 360 ⎯
Test current (Idc) 218.53 ⎯
Test voltage (Vac).......................... : 127/220 ⎯
Test current (Iac) 198.04 ⎯
tamb1 (C) ....................................... : 42.46 ⎯
tamb2 (C) ....................................... : 45.60 ⎯
maximum temperature T of part/at:: T (C) Tmax (C)

Ambient temp. 45.6 --

Enclosure, Mounting surf ace 78.9 90

Enclosure, top 77.9 90

Enclosure, lef t side 70.7 90

Enclosure, right side 71.0 90

LCD screen 71.6 90


Supplementary inf ormation:

TRF No. IEC62109_2B


Page 23 of 27 Report No. 220308046GZU-004
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict

4.7.4 TABLE: Steady state Inverter AC output voltage and f requency N/A
Nominal DC input (V)
Nominal output AC voltage (V) :

AC output Frequency (Hz) Condition/status Comments


U (V)

Supplementary inf ormation:

TRF No. IEC62109_2B


Page 24 of 27 Report No. 220308046GZU-004
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict

4.8.2 TABLE: Array insulation resistance detection f or inverters f or ungrounded and P


f unctionally grounded arrays
4.8.2.1 Array insulation resistance detection f or inverters f or ungrounded arrays P
DC Voltage below DC Voltage f or Resistance between Required Insulation Result
minimum operating inverter begin ground and PV resistance
voltage operation input terminal R = (V MAX PV / 30mA)
(V) (V) (Ω) (Ω)
DC+
The PV inverter cannot
150V 200V 34kohm 36.67kohm start-up. Error message:
“203”
The PV inverter cannot
150V 510V 34kohm 36.67kohm start-up. Error message:
“203”
The PV inverter cannot
150V 750V 34kohm 36.67kohm start-up. Error message:
“203”
The PV inverter cannot
150V 950V 34kohm 36.67kohm start-up. Error message:
“203”
DC-
The PV inverter cannot
150V 200V 34kohm 36.67kohm start-up. Error message:
“203”
The PV inverter cannot
150V 510V 34kohm 36.67kohm start-up. Error message:
“203”
The PV inverter cannot
150V 750V 34kohm 36.67kohm start-up. Error message:
“203”
The PV inverter cannot
150V 950V 34kohm 36.67kohm start-up. Error message:
“203”
The PV inverter cannot
150V 200V 34kohm 36.67kohm start-up. Error message:
“203”

TRF No. IEC62109_2B


Page 25 of 27 Report No. 220308046GZU-004
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict

Note:
For isolated inverters, shall indicate a f ault in accordance with 13.9 (operation is allowed); the f ault indication shall
be maintained until the array insulation resistance has recovered to a value higher than the limit above
For non-isolated inverters, or inverters with isolation not complying with the leakage current limits in the minimum
inverter isolation requirements in Table 30, shall indicate a f ault in accordance with 13.9, and shall not connect to
the mains; the inverter may continue to make the measurement, may stop indicating a f ault and may connect to the
mains if the array insulation resistance has recovered to a value higher than the limit ab ove.
It is not required to test all PV input terminals if analysis of the design indicates that one or more terminals can be
expected to have the same result, f or example where multiple PV string inputs are in parallel.
Supplementary inf ormation:

4.8.3.2 TABLE: 30mA touch current type test f or isolated inverters N/A
Condition Current (mA) Limit ( 30mA)
DC+ to PE
DC- to PE
Supplementary inf ormation:
The touch current measurement circuit of IEC 60990, Figure 4 is connected f rom each terminal of th e array to
ground, one at a time.

4.8.3.3 TABLE: Fire hazard residual current type test f or isolated inverters N/A
Condition Current (mA) Limit ( 300mA or 10mA per kVA)
DC+ to PE
DC- to PE
Supplementary inf ormation:

TRF No. IEC62109_2B


Page 26 of 27 Report No. 220308046GZU-004
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict

4.8.3.5 TABLE: Protection by residual current monitoring P


Output power (kVA) : 75
Input voltage (V DC ): 850
Test conditions:
Frequency (Hz):50
Output AC Voltage ( V AC ):127/220

4.8.3.5.2 Test f or detection of excessive continuous residual current P

Fault Current (mA) Disconnection time (ms)


Limit
Measured 300mA f or output power ≤ 30 kVA
Measured Disconnection time Limit
Fault Current 10mA per kVA f or output power >
30 kVA
+ PV to N:
738.69 750 215.0 300
737.35 750 226.5 300
738.36 750 229.0 300
737.21 750 225.0 300
737.70 750 223.0 300
- PV to N:
739.18 750 221.5 300
742.18 750 220.5 300
743.67 750 219.5 300
736.36 750 218.5 300
741.66 750 220.5 300
Note:
– maximum 300mA f or inverters with continuous output power rating ≤30 kVA;
– maximum 10mA per kVA of rated continuous output power f or inverters with continuous output power rating > 30
kVA.
This test shall be repeated 5 times, and f or all 5 tests the time to disconnect shall not exceed 0,3s.
The test is repeated f or each PV input terminal. It is not required to test all PV input terminals if anal ysis of the
design indicates that one or more terminals can be expected to have the same result, f or example where multiple
PV string inputs are in parallel.
Supplementary inf ormation:

4.8.3.5.3 TABLE: Test f or detection of sudden changes in residual current P


+PV to N
UN
Limit (mA) Limit (ms)
Disconnection time (ms)
30 217.5 300
30 215.5 300
30 219.5 300
30 218.5 300
30 214.0 300

TRF No. IEC62109_2B


Page 27 of 27 Report No. 220308046GZU-004
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict

60 64.5 150
60 71.8 150
60 61.3 150
60 66.3 150
60 60.3 150

150 25.5 40
150 23.2 40
150 28.2 40
150 15.1 40
150 26.9 40
-PV to N
UN
Limit (mA) Limit (ms)
Disconnection time (ms)
30 207.0 300
30 206.0 300
30 210.5 300
30 208.5 300
30 222.0 300

60 58.5 150
60 67.0 150
60 57.3 150
60 63.5 150
60 74.0 150

150 22.6 40
150 16.4 40
150 22.3 40
150 19.3 40
150 11.2 40
Note:
The capacitive current is raised until disconnection.
Test condition: Ic + 30/60/150mA <= Icmax . R1 is set that 30/60/150mA Flow and switch S is closed.
Supplementary inf ormation:

(End of report)

TRF No. IEC62109_2B


Test Report issued under the responsibility of:

TEST REPORT
IEC 62116
Test procedure of islanding prevention measures for utility-
interconnected photovoltaic inverters

Report Number. .............................. : 220308046GZU-002


Date of issue ................................... : 30 May 2022
Total number of pages .................... 18 Pages

Name of Testing Laboratory Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
preparing the Report ...................... : Room 02, & 101/E201/E301/E401/E501/E601/E701/E801 of
Room 01 1-8/F., No. 7-2. Caipin Road, Science City, GETDD,
Guangzhou, Guangdong, China
Applicant’s name ............................ : Shenzhen Growatt New Energy Co., Ltd.

Address ........................................... : 4-13/F, Building A, Sino-German (Europe) Industrial Park,


Hangcheng Ave, Bao’an District, Shenzhen, China
Test specification:
Standard .......................................... : IEC 62116:2014
Test procedure ............................... : Type approval
Non-standard test method............. : N/A
Test Report Form No. ..................... : IEC62116B
Test Report Form(s) Originator..... : TÜV SÜD Product Service GmbH
Master TRF ...................................... : Dated 2017-11-03
Copyright © 2017 IEC System of Conformity Assessment Schemes for Electrotechnical
Equipment and Components (IECEE System). All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as
copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting
from the reader's interpretation of the reproduced material due to its placement and context.
If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the
CB Scheme procedure shall be removed.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory
and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.
General disclaimer:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing CB Testing
Laboratory. The authenticity of this Test Report and its contents can be verified by contacting the NCB,
responsible for this Test Report.

Disclaimer: This document is controlled and has been released electronically.


Only the version on the IECEE Website is the current document version
Page 2 of 18 Report No. 220308046GZU-002

Test item description : PV Grid inverter


Trade Mark ................. : GROWATT
Manufacturer ............. : Same as applicant
Model/Type reference : MAX 50KTL3-XL2, MAX 60KTL3-XL2, MAX 70KTL3-XL2, MAX 73KTL3-XL2
MAX 75KTL3-XL2, MAX 50KTL3-XL1, MAX 60KTL3-XL1, MAX 70KTL3-XL1,
MAX 73KTL3-XL1, MAX 75KTL3-XL1
Ratings ....................... : Model MAX MAX MAX MAX MAX
50KTL3- 60KTL3- 70KTL3- 73KTL3- 75KTL3-
XL2 XL2 XL2 XL2 XL2
Max.PV
1100Vdc
voltage
MPPT
180-850Vdc
voltage
Max.input
8*45A
current
PV Isc 8*56.5A
Nominal
output 3W/N/PE, 127/220Vac
voltage

Nominal
output 50/60Hz
Frequency
Max.output
144.3A 173.2A 183.7A 191.6A 196.9A
current
Max. output
50KW 60KW 70KW 73KW 75KW
power
Max.
apparent 55KVA 66KVA 70KVA 73KVA 75KVA
power
Power factor
0.8Leading~0.8Lagging
range
Safety level Class I
Ingress
IP 66
Protection
Operation
Ambient -30℃ - +60℃
Temperature
Software
TN1.0
version

TRF No. IEC 62116B


Page 3 of 18 Report No. 220308046GZU-002

Model MAX MAX MAX MAX MAX


50KTL3- 60KTL3- 70KTL3- 73KTL3- 75KTL3-
XL1 XL1 XL1 XL1 XL1
Max.PV
1100Vdc
voltage
MPPT
180-850Vdc
voltage
Max.input
10*32A
current
PV Isc 10*40A
Nominal
output 3W/N/PE, 127/220Vac
voltage

Nominal
output 50/60Hz
Frequency
Max.output
144.3A 173.2A 183.7A 191.6A 196.9A
current
Max. output
50KW 60KW 70KW 73KW 75KW
power
Max.
apparent 55KVA 66KVA 70KVA 73KVA 75KVA
power
Power factor
0.8Leading~0.8Lagging
range
Safety level Class I
Ingress
IP 66
Protection
Operation
Ambient -30℃ - +60℃
Temperature
Software
TN1.0
version

TRF No. IEC 62116B


Page 4 of 18 Report No. 220308046GZU-002

Responsible Testing Laboratory (as applicable), testing procedure and testing location(s):

Testing Laboratory: Intertek Testing Services Shenzhen Ltd. Guangzhou


Branch
Testing location/ address ............................ : Room 02, & 101/E201/E301/E401/E501/E601/E701/E801
of Room 01 1-8/F., No. 7-2. Caipin Road, Science City,
GETDD, Guangzhou, Guangdong, China
Tested by (name, function, signature) ....... : Joss Huang
Engineer
Approved by (name, function, signature) .. : Jason Fu
Supervisor

Testing procedure: CTF Stage 1: N/A


Testing location/ address ............................ :
N/A
Tested by (name, function, signature) ....... : N/A
Approved by (name, function, signature) .. : N/A

Testing procedure: CTF Stage 2: N/A


Testing location/ address ............................ :
N/A
Tested by (name + signature) ...................... : N/A
Witnessed by (name, function, signature) . : N/A
Approved by (name, function, signature) .. : N/A

Testing procedure: CTF Stage 3: N/A


Testing procedure: CTF Stage 4: N/A
Testing location/ address ............................ :
N/A
Tested by (name, function, signature) ....... : N/A
Witnessed by (name, function, signature) . : N/A
Approved by (name, function, signature) .. : N/A
Supervised by (name, function, signature) : N/A

TRF No. IEC 62116B


Page 5 of 18 Report No. 220308046GZU-002

List of Attachments (including a total number of pages in each attachment):


N/A

Summary of testing:

Tests performed (name of test and test Testing location:


clause): Intertek Testing Services Shenzhen Ltd.
All applicable tests Guangzhou Branch
Room 02, &
101/E201/E301/E401/E501/E601/E701/E801 of
Room 01 1-8/F., No. 7-2. Caipin Road, Science
City, GETDD, Guangzhou, Guangdong, China

Summary of compliance with National Differences (List of countries addressed):


N/A

The product fulfils the requirements of IEC 62116:2014

TRF No. IEC 62116B


Page 6 of 18 Report No. 220308046GZU-002

Copy of marking plate:


The artwork below may be only a draft. The use of certification marks on a product must be
authorized by the respective NCBs that own these marks.

Note:
1. The above markings are the minimum requirements required by the safety standard. For the final
production samples, the additional markings which do not give rise to misunderstanding may be
added.
2. Label is attached on the side surface of enclosure and visible after installation.
3. Other labels are identical to above, except the model’s name and ratings

TRF No. IEC 62116B


Page 7 of 18 Report No. 220308046GZU-002

Test item particulars...................................................:


Classification of installation and use.......................: Fixed and outdoor use
Supply Connection .....................................................: Permanent connection
.......................................................................................:
Possible test case verdicts:
- test case does not apply to the test object ........... : N/A
- test object does meet the requirement.................. : P (Pass)
- test object does not meet the requirement ........... : F (Fail)
Testing.......................................................................... :
Date of receipt of test item ........................................ : 06 April 2022
Date (s) of performance of tests ............................... : 06 April 2022 to 10 May 2022

General remarks:
"(See Enclosure #)" refers to additional information appended to the report.
"(See appended table)" refers to a table appended to the report.
Throughout this report a comma / point is used as the decimal separator.
Determination of the test conclusion is based on IEC Guide 115 in consideration of measurement
uncertainty.
This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between
Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the
agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the
agreement, for any loss, expense or damage occasioned by the use of this report. Only the Client is
authorized to permit copying or distribution of this report and then only in its entirety. Any use of the
Intertek name or one of its marks for the sale or advertisement of the tested material, product or service
must first be approved in writing by Intertek. The observations and test results in this report are relevant
only to the sample tested. This report by itself does not imply that the material, product, or service is or
has ever been under an Intertek certification program.
The test report only allows to be revised only within the report defined retention period unless standard or
regulation was withdrawn or invalid.
This report shall be used together with the report 220308046GZU-001.
Manufacturer’s Declaration per sub-clause 4.2.5 of IECEE 02:
The application for obtaining a CB Test Certificate Yes
includes more than one factory location and a Not applicable
declaration from the Manufacturer stating that the
sample(s) submitted for evaluation is (are)
representative of the products from each factory has
been provided ............................................................... :

TRF No. IEC 62116B


Page 8 of 18 Report No. 220308046GZU-002

When differences exist; they shall be identified in the General product information section.
Name and address of factory (ies) .......................... : Guangdong Growatt New Energy Co., Ltd.
Growatt Industrial Park,No.17 Pingheng Road
Pingtan Town,Huiyang District,Huizhou,
Guangdong,China

TRF No. IEC 62116B


Page 9 of 18 Report No. 220308046GZU-002

General product information:


The unit is a three-phase PV Grid inverter, it can convert the high PV voltage to Grid voltage and feed into
Grid network.
The unit is providing EMC filtering at the PV side and AC side. It is transformerless between the PV circuit
and AC circuit.
The unit has three controllers. The master controller DSP A measure the PV voltage and current, AFCI,
PV ISO and also communicate with the slave controller B and slave controller ARM and etc; The slave
controller DSP B is used to INV control and PV ISO measurement and etc.
The slave controller ARM monitor AC voltage, GFCI and communicate with the master controller DSP
The relays are designed to redundant structure that controlled by separately.
The master controller A and slave controller B are used together to control relay open or close, if the
single fault on one controller, the other controller can be capable to open the relay, so that still providing
safety means.
The topology diagram as following:

Difference of models:
All models are identical, except the number of MPPT and the output power derating in software.

Other than special notice, the model MAX 75KTL3-XL2 is as the representative test model in this report.

TRF No. IEC 62116B


Page 10 of 18 Report No. 220308046GZU-002
IEC 62116
Clause Requirement + Test Result - Remark Verdict

4 Testing circuit
The testing circuit shown in Figure 1 is P
employed.
Similar circuits are used for three-phase output. P
Parameters to be measured are shown in Table 1 P
and Figure 1. Parameters to be recorded in the
test report are discussed in Clause 7.
5 Testing equipment
5.1 Measuring instruments P
The waveform measurement/capture device is Waveform caught from the P
able to record the waveform from the beginning switch open and the EUT
of the islanding test until the EUT ceases to cease to energize
energize the island.
For multi-phase EUT, all phases are monitored. P
A waveform monitor designed to detect and P
calculate the run-on time may be used.
For multi-phase EUT, the test and measurement P
equipment is recorded each phase current and
each phase-to-neutral or phase-to-phase voltage,
as appropriate, to determine fundamental
frequency active and reactive power flow over
the duration of the test.
A sampling rate of 10 kHz or higher is P
recommended. The minimum measurement
accuracy is 1 % or less of rated EUT nominal
output voltage and 1 % or less of rated EUT
output current
Current, active power, and reactive power P
measurements through switch S1 used to
determine the circuit balance conditions report
the fundamental (50 Hz or 60 Hz) component.
5.2 DC power source
5.2.1 General P
A PV array or PV array simulator (preferred) may Topcon PV simulator used P
be used. If the EUT can operate in utility-
interconnected mode from a storage battery, a
DC power source may be used in lieu of a
battery as long as the DC power source is not the
limiting device as far as the maximum EUT input
current is concerned.
The DC power source provides voltage and P
current necessary to meet the testing
requirements described in Clause 6.
5.2.2 PV array simulator P

TRF No. IEC 62116B


Page 11 of 18 Report No. 220308046GZU-002
IEC 62116
Clause Requirement + Test Result - Remark Verdict

The tests are conducted at the input voltage Topcon PV simulator used P
defined in Table 2 below, and the current is
limited to 1,5 times the rated photovoltaic input
current, except when specified otherwise by the
test requirements.
A PV array simulator is recommended, however, P
any type of power source may be used if it does
not influence the test results.
5.2.3 Current and voltage limited DC power supply N/A
with series resistance
A DC power source used as the EUT input source N/A
is capable of EUT maximum input power (so as
to achieve EUT maximum output power) at
minimum and maximum EUT input operating
voltage.
The power source provides adjustable current N/A
and voltage limit, set to provide the desired short
circuit current and open circuit voltage when
combined with the series and shunt resistance
described below.
A series resistance (and, optionally, a shunt N/A
resistance) is selected to provide a fill factor
within the range:
Output power: Sufficient to provide maximum
EUT output power and other levels specified by
test conditions of table 5.
Response speed: The response time of a
simulator to a step in output voltage, due to a 5%
load change, results in a settling of the output
current to within 10% of its final value in less
than 1ms.
Stability: Excluding the variations caused by the
EUT MPPT, simulator output power remains
stable within 2 % of specified power level over
the duration of the test: from the point where
load balance is achieved until the island
condition is cleared or the allowable run-on time
is exceeded.
Power factor: 0.25 to 0.8
5.2.4 PV array N/A
A PV array used as the EUT input source is N/A
capable of EUT maximum input power at
minimum and maximum EUT input operating
voltage.

TRF No. IEC 62116B


Page 12 of 18 Report No. 220308046GZU-002
IEC 62116
Clause Requirement + Test Result - Remark Verdict

Testing is limited to times when the irradiance N/A


varies by no more than 2 % over the duration of
the test as measured by a silicon-type
pyranometer or reference device. It may be
necessary to adjust the array configuration to
achieve the input voltage and power levels
prescribed in 6.1.
5.3 AC power source
The utility grid or other AC power source may be P
used as long as it meets the conditions specified
in Table 4.

5.4 AC loads
On the AC side of the EUT, variable resistance, P
capacitance, and inductance are connected in
parallel as loads between the EUT and the AC
power source. Other sources of load, such as
electronic loads, may be used if it can be shown
that the source does not cause results that are
different than would be obtained with passive
resistors, inductors, and capacitors.
All AC loads are rated for and adjustable to all P
test conditions. The equations for Qf are based
upon an ideal parallel RLC circuit. For this
reason, non-inductive resistors, low loss (high
Qf) inductors, and capacitors with low effective
series resistance and effective series inductance
are utilized in the test circuit. Iron core inductors,
if used, are not exceed a current THD of 2 %
when operated at nominal voltage. Load
components are conservatively rated for the
voltage and power levels expected. Resistor
power ratings are chosen so as to minimize
thermally-induced drift in esistance values
during the course of the test.
Active and reactive power is calculated (using P
the measurements provided in Table 1) in each
of the R, L and C legs of the load so that these
parasitic parameters (and parasitics introduced
by variacs or autotransformers) are properly
accounted for when calculating Qf.

TRF No. IEC 62116B


Page 13 of 18 Report No. 220308046GZU-002
IEC 62116
Clause Requirement + Test Result - Remark Verdict

6 Test for single or multi-phase inverter


6.1 Test procedure (see appended table) P
The test uses an RLC load, resonant at the EUT P
nominal frequency (50 Hz or 60 Hz) and matched
to
the EUT output power.
For multi-phase EUT, the load is balanced across P
all phases and the switch S1 as in Figure 1 opens
all phases
This test is performed with the EUT conditions as P
in Table 5, where power and voltage values are
given as a percent of EUT full output rating.
a)..Determine EUT test output power P
b) .Adjusting the DC input source P
c) .Turn off the EUT and open S1 P
d) .Adjust the RLC circuit to have Qf = 1.0 ±0.05 P
e)..Connect the RLC load configured in step d) to P
the EUT by closing S2
f) ..Open the utility-disconnect switch S1 to P
initiate the test, Run-on time is recorded.
g) .For test condition A, adjust the real load and P
only one of the reactive load components to
each of the load imbalance conditions shown
in the shaded portion of table 6. If any of the
recorded run-on times are longer than the
one recorded for the rated balance condition,
then the non-shaded parameter combinations
also require testing.
h) For test condition B and C, adjust the only one P
reactive load components by approximately
1,0% per test, within a total range of 95% to
105% of the operating point. If run-on times are
still increasing at the 95% or 105% points,
additional 1% increments have to be taken until
run-on times begin decreasing.
6.2 Pass/fail criteria
An EUT is considered to comply with the P
requirements for islanding protection when each
case of recorded run-on time is less than 2 s or
meets the requirements of local codes.
7 Documentation
At a minimum, the following information is P
recorded and maintained in the test report.
a) Specifications of EUT. Table 8 provides an P
example of the type of information that is
provided.

TRF No. IEC 62116B


Page 14 of 18 Report No. 220308046GZU-002
IEC 62116
Clause Requirement + Test Result - Remark Verdict

b) Measurement results. Table 9 provides an P


example of the type of information that is
provided. Actual measured values is to be
recorded.
c) Block diagram of test circuit. P
d) Specifications of the test and measurement P
equipment. Table 10 provides an example of the
type of information that is provided.
e) Any test configuration or procedure details P
such as methods of achieving specified load and
EUT output conditions.
f) Any additional information required by the P
testing laboratory's accreditation.
g) Specify the evaluation criterion from clause P
6.2 that was utilized to determine if the product
passed or failed the test.
Annex A Islanding as it applies to PV systems(Informative) --
A.1 General --
A.2 Impact of distortion on islanding --
Annex B Test for independent islanding detection device (relay)(Informative) --
B.1 Introduction --
B.2 Testing circuit --
B.3 Testing equipment --
B.4 Testing procedure --
B.5 Documentation --

TRF No. IEC 62116B


Page 15 of 18 Report No. 220308046GZU-002
IEC 62116
Clause Requirement + Test Result - Remark Verdict

6 TABLE: tested condition and run-on time P


Model: Tested on model MAX 75KTL3-XL2 with frequency 50Hz
No. PEUT (% Reactiv PAC QAC Run-on PEUT Actual VDC Which
of EUT e load time(ms) (KW) Qf (V) load is
rating) (% of (Var) selected
normal) to be
adjusted
(R or L)
Test condition A
1 100 100 0 0 459.5 75.11 1.00 800 /
2 100 100 -5 -5 332.5 75.11 0.98 800 /
3 100 100 -5 0 279.5 75.11 0.95 800 /
4 100 100 -5 +5 305.0 75.11 0.93 800 /
5 100 100 0 -5 401.0 75.11 1.03 800 /
6 100 100 0 +5 311.5 75.11 0.98 800 /
7 100 100 +5 -5 258.5 75.11 1.08 800 /
8 100 100 +5 0 279.5 75.11 1.06 800 /
9 100 100 +5 +5 157.5 75.11 1.03 800 /
Test condition B
10 66 66 0 0 299.5 49.68 1.00 520 /
11 66 66 0 -5 196.0 49.68 1.03 520 L
12 66 66 0 -4 292.0 49.68 1.02 520 L
13 66 66 0 -3 287.5 49.68 1.02 520 L
14 66 66 0 -2 243.5 49.68 1.01 520 L
15 66 66 0 -1 242.0 49.68 1.01 520 L
16 66 66 0 1 308.0 49.68 0.99 520 L
17 66 66 0 2 464.0 49.68 0.99 520 L
18 66 66 0 3 415.5 49.68 0.98 520 L
19 66 66 0 4 409.5 49.68 0.98 520 L
20 66 66 0 5 311.5 49.68 0.97 520 L
Test condition C
21 33 33 0 0 838.0 24.81 1.00 309 /
22 33 33 0 -5 529.0 24.81 1.03 309 L
23 33 33 0 -4 668.0 24.81 1.02 309 L
24 33 33 0 -3 832.0 24.81 1.02 309 L
25 33 33 0 -2 652.0 24.81 1.01 309 L
26 33 33 0 -1 770.0 24.81 1.01 309 L
27 33 33 0 1 716.0 24.81 0.99 309 L
28 33 33 0 2 600.0 24.81 0.99 309 L
29 33 33 0 3 858.0 24.81 0.98 309 L
30 33 33 0 4 612.0 24.81 0.98 309 L
31 33 33 0 5 460.0 24.81 0.97 309 L

TRF No. IEC 62116B


Page 16 of 18 Report No. 220308046GZU-002
IEC 62116
Clause Requirement + Test Result - Remark Verdict

Supplementary information:
For test condition A:
If any of the recorded run-on times are longer than the one recorded for the rated balance condition, then
the non-shaded parameter combinations also require testing.
For test condition B and C:
If run-on times are still increasing at the 95 % or 105 % points, additional 1 % increments is taken until
run-on times begin decreasing.

TRF No. IEC 62116B


Page 17 of 18 Report No. 220308046GZU-002
IEC 62116
Clause Requirement + Test Result - Remark Verdict

6 TABLE: tested condition and run-on time P


Model: Tested on model MAX 75KTL3-XL2 with frequency 60Hz
No. PEUT (% Reactiv PAC QAC Run-on PEUT Actual VDC Which
of EUT e load time(ms) (KW) Qf (V) load is
rating) (% of (Var) selected
normal) to be
adjusted
(R or L)
Test condition A
1 100 100 0 0 730.0 75.11 1.00 800 /
2 100 100 -5 -5 330.0 75.11 0.97 800 /
3 100 100 -5 0 484.0 75.11 0.95 800 /
4 100 100 -5 +5 414.0 75.11 0.93 800 /
5 100 100 0 -5 322.0 75.11 1.03 800 /
6 100 100 0 +5 256.0 75.11 0.98 800 /
7 100 100 +5 -5 260.0 75.11 1.08 800 /
8 100 100 +5 0 648.0 75.11 1.06 800 /
9 100 100 +5 +5 588.0 75.11 1.04 800 /
Test condition B
10 66 66 0 0 335.5 49.68 1.00 520 /
11 66 66 0 -5 259.0 49.68 1.03 520 L
12 66 66 0 -4 327.0 49.68 1.02 520 L
13 66 66 0 -3 373.5 49.68 1.02 520 L
14 66 66 0 -2 327.5 49.68 1.01 520 L
15 66 66 0 -1 285.5 49.68 1.01 520 L
16 66 66 0 1 313.0 49.68 0.99 520 L
17 66 66 0 2 629.0 49.68 0.99 520 L
18 66 66 0 3 327.0 49.68 0.98 520 L
19 66 66 0 4 411.0 49.68 0.98 520 L
20 66 66 0 5 299.0 49.68 0.97 520 L
Test condition C
21 33 33 0 0 530.0 24.81 1.00 309 /
22 33 33 0 -5 134.5 24.81 1.03 309 L
23 33 33 0 -4 192.5 24.81 1.02 309 L
24 33 33 0 -3 178.5 24.81 1.02 309 L
25 33 33 0 -2 226.5 24.81 1.01 309 L
26 33 33 0 -1 234.5 24.81 1.01 309 L
27 33 33 0 1 235.5 24.81 0.99 309 L
28 33 33 0 2 153.5 24.81 0.99 309 L
29 33 33 0 3 182.5 24.81 0.98 309 L
30 33 33 0 4 176.5 24.81 0.98 309 L
31 33 33 0 5 175.5 24.81 0.97 309 L

TRF No. IEC 62116B


Page 18 of 18 Report No. 220308046GZU-002
IEC 62116
Clause Requirement + Test Result - Remark Verdict

Supplementary information:
For test condition A:
If any of the recorded run-on times are longer than the one recorded for the rated balance condition, then
the non-shaded parameter combinations also require testing.
For test condition B and C:
If run-on times are still increasing at the 95 % or 105 % points, additional 1 % increments is taken until
run-on times begin decreasing.

--- End of test report---

TRF No. IEC 62116B