MHOG Sewer and Water Standard Details
MHOG Sewer and Water Standard Details
2'-0"
PIPE RESTRAINT SCHEDULE
GROUND BURIED PRESSURE PIPE - POLYETHYLENE ENCASED DUCTILE IRON PIPE
K
REDUCERS REDUCERS PLACE LAYER OF
PIPE TEES, 90° 22-1/2° 11-1/4° DEAD
45° BENDS (ONE SIZE (TWO SIZE BOND BREAKER
DIAMETER BENDS BENDS BENDS ENDS
REDUCTION)* REDUCTIION)* BETWEEN VALVE 3"
BOX AND CONCRETE
2'-0"
4 13 5 3 1 40 -- -- EXISTING OR PROPOSED SEWER
6 19 8 4 2 58 31 --
EXISTING OR PROPOSED 5"
3.
12"
8 24 10 5 2 75 30 70 WATER MAIN TW PLACE LAYER OF
90° BEND VALVE BOX
OR TEE BOND BREAKER
MIN
CONCRETE
12 34 14 7 3 107 57 116
4"
4" THICK,
BETWEEN VALVE
4000 PSI
45° BEND
16 43 18 9 4 139 59 137 2'x2'x4" BOX AND CONCRETE
4" CONC PAD TRACER WIRE
J 20 52 22 10 5 169 59 134 MIN DIRECT BURY PIPE: COPPER HEAD 10CCS HS TRACER W
CAST IRON TRACER WIRE BOX MAY
24 61 25 12 6 199 60 132 DIRECTIONAL DRILL PIPE: COPPER HEAD SOLOSHEET 1
CUT EXISTING PIPE BE PLACED ANYWHERE WITHIN THE
HS TRACER WIRE
30 73 30 15 7 242 85 168 AS REQUIRED CONCRETE AT LEAST 4" FROM EDGE
MIN.
18"
RESTRAINED JOINTS SEE OF PAD
36 84 35 17 8 281 84 168 NOTE:
SPECIFICATIONS (TYPICAL) 1. TRACER WIRE BOXES LOCATED WITHOUT A VALVE
NOTE: ALL BOXES & ADJOINING TW
1. LENGTHS OF PIPE RESTRAINT ARE GIVEN IN FEET. BOX ONLY REQUIRE AN 18" X 18" CONCRETE PAD.
BOXES SHALL BE ENCASED IN A
2. IF REQUIRED PIPE DIAMETER IS NOT LISTED IN THIS TABLE, THE NEXT LARGEST PIPE DIAMETER SHALL BE USED. 2. TRACER WIRE BOX SHALL HAVE A LOCKING LID
CONC. PAD UNLESS OTHERWISE
3. THIS TABLE IS BASED ON A TEST PRESSURE OF 180 PSI (OPERATING PRESSURE PLUS WATER HAMMER. FOR W/STANDARD AWWA PENTAGON KEY.
45° BEND 45° BEND DETERMINED BY MHOG.
OTHER TEST PRESSURES, ALL VALUES TO BE INCREASED OR DECREASED PROPORTIONALLY.
4. THE VALUES PROVIDED OF RESTRAINT LENGTH ARE IN EACH DIRECTION FROM THE POINT OF DEFLECTION OR
I TERMINATION EXCEPT FOR TEES, AT WHICH ONLY THE BRANCH IN THE DIRECTION OF THE STEM.
5. IF TIE RODS ARE USED, USE FOUR RODS MINIMUM AND ADD 1/8-INCH TO BAR DIAMETER AS CORROSION PLAN SECTION
ALLOWANCE.
* SIZE REDUCTION IS BASED UPON THE PIPE DIAMETER SHOWN IN THIS TABLE.
WATER MAIN UTILITY OFFSET VALVE/TRACER WIRE BOX IN CONCRETE DETAIL
BASED UPON: INTERNAL PRESSURE: 180
PIPE DEPTH: 5 NO SCALE
BEDDING CLASS: TYPE 4
SOIL TYPE: GOOD SAND
SAFETY FACTOR: 2
HYDRANT FLAG
PER SPECIFICATIONS HYDRANT
H RHINO FIBER CURVE
COMMERCIAL BUILDING CAST IRON
UTILITY MARKER "BLUE
SHUT OFF VALVE COLOR" - WATER MAIN, CURB BOX
BEYOND (REQUIRED IN
PUBLIC WATERMAIN REMOTE AREAS AS
66"
DETERMINED BY MHOG)
SURFACE
PRIVATE WATERMAIN
RESTORATION
UTILITY EASEMENT
WATER MAIN PAVEMENT
BASE
HYDRANT PER
HEAVY DUTY
R.O.W. LINE
SPECIFICATIONS
STORZ FITTING CAST IRON
G
2" MIN. 25' MAX. FOR EASEMENT PLAN VALVE BOX
6" MAX. 2'-6" MIN. 6" DIA PIPE
4"
FIRE SUPPRESSION FIN. GRADE
ABOVE FINAL GRADE LINE (TYP. 4"-8") 2'x2'x4" CONCRETE PAD
DOMESTIC SERVICE CORP. CURB SERVICE
15"
(TYP. 2") 1" 1" 1" 2 1/2"
DETAIL)
1 1/4" 1 1/4" 1 1/4" 3" 6" MIN INSIDE
PRIVATELY OWNED CAST IRON
6' DEPTH OF BURY (MIN.)
5'-6" MIN.
6" GATE VALVE SEE NOTE WATERMAIN CURB BOX
MIN.
RESTRAIN JOINTS 2" 1 1/2"X 2" 2" 3"
BACK TO BRANCH AND BOX SEE EXTENSION
SPECIFICATIONS MDOT CLASS II
TEE SAND COMPACTED
TO 95% VARIES
3"
WATER MAIN MDOT CLASS II
F (TYPICALLY 12')
MIN.
SAND COMPACTED
6"
VARIABLE
TO 95%
(ONE PIECE OF PIPE)
CONTRACTOR
TO PLUG
DRAIN ROAD R.O.W. OR EASEMENT
CURB STOP
IN PAVEMENT
SERVICE PIPE
CORPORATION STOP
PUBLICLY OWNED WATERMAIN
(8"MINIMUM) CURB STOP PER SPECIFICATIONS
NOTES:
* THE LENGTH OF 6" PIPE FROM THE MAIN TO THE LOCATED AT R.O.W.
1. VALVE BOX SHALL NOT REST ON VALVE OR MAIN LINE PIPE. EXTEND SERVICE TO EDGE
HYDRANT ASSEMBLY CANNOT EXCEED 25'. ANY PIPE
E 2. A VALVE STEM EXTENSION WITH CENTERING RING IS OF EASEMENT AND CAP
OVER 25 FEET SHALL BE 8" DIAMETER MINIMUM AND NOTE: PUBLICLY OWNED SHUT OFF VALVE TO BE LOCATED IN EASEMENT. REQUIRED FOR VALVES BURIED DEEPER THAN 6'.
DESIGNED PER MHOG SPECIFICATIONS.
SECTION
FIRE HYDRANT ASSEMBLY COMMERCIAL BUILDING WATER SERVICE LAYOUT GATE VALVE AND BOX WATER SERVICE LATERAL
HOUSE PLUMBING
IRRIGATION
SYSTEM
ISOLATION BALL VALVE
INSTALL A PRESSURE
VACUUM BREAKER
D
(PVB) ON IRRIGATION
STANDARD DETAILS
E
IRRIGATION WATER
C METER HORN
66"
B ISOLATION BALL
VALVE
REQUIRED
ISOLATION BALL VALVE
TO
SERVICE LEAD
HOUSE
METER
PRESSURE REDUCING VALVE
ISOLATION BALL VALVE NOTES:
1. ALL METERS ARE TO BE INSTALLED HORIZONTALLY IN A DRY, CLEAN, SANITARY
LOCATION THAT IS READILY ACCESSIBLE. THIS DRAWING IS NOT TO SCALE & IS
ONLY A REPRESENTATION OF HOW THE METERS SHOULD BE INSTALLED. THE
A SECOND METER IS OPTIONAL FOR IRRIGATION USAGE. METERS SHOULD NOT BE
UPDATED: MAY 2015
INSTALLED IN LINE (ONE RIGHT AFTER THE OTHER).
2. PROPERTIES DESIGNATED "HIGH HAZARD" PER THE MHOG CROSS CONNECTION
RULES MANUAL WILL REQUIRE THE INSTALLATION OF A REDUCED PRESSURE
PRIVATE RESIDENCE ZONE (RPZ) BACK FLOW PREVENTION DEVICE.
THREADED 45°
EJIW HEAVY DUTY 1574 SOLID 1-#5
CLEANOUT COVER OR APPROVED EQUAL
SANITARY CAP
SERVICE 3-#5 EXTRA
LEAD
K 24"X24"X6" CONCRETE
6"
3"
EASEMENT/ PAD W/#4 BAR EACH SIDE
8"
PROPERTY LINE CLEANOUT
EXISTING GROUND BENDS AS REQUIRED
#4 REBAR
12"
PAINTED SAFETY CONCRETE PAD
ORANGE ABOVE GRADE
MAX.
OR AS DIRECTED
8'
BY THE ENGINEER AROUND RISER
PLASTIC PIPE LOCATION
SYSTEM MARKER
J UNDISTURBED WYE
SOIL PLUG OR CAP
UNDISTURBED SOIL 22.5° BENDS AS REQUIRED #5 AT 10" E.W.*
TOP PLAN * USE #5 AT 6" FOR D=8'-0"
SEWER WYE PAY LIMITS FOR SEWER CLEANOUT
PLAN SANITARY
SERVICE SEWAGE AIR
NOTES: LEAD RELIEF VALVE
1. ALL CONNECTION SHALL BE BELL AND SPIGOT TYPE.
6" PVC SDR 23.5 LATERAL AT 1.0% 2. CLEANOUT IS TO BE SAME DIAMETER AS SERVICE LEAD.
NOTE:
1. RISER PIPE MAY NOT BE REQUIRED FOR SHALLOW SEWERS AS SHOWN. 3. CONCRETE PAD REQUIRED UNLESS OTHERWISE
I 2. WHEN CONNECTING TO AN EXISTING SEWER THE AUTHORITY MAY DETERMINED BY MHOG.
REQUIRE CORING OF THE EXISTING PIPE AND INSTALLATION OF A SEWER 4. THERE MUST BE A 3" GAP FROM THE BOTTOM OF THE MH C.L.
SADDLE. SADDLE SHALL BE ROMAC "CB" SEWER SADDLE OR APPROVED CLEAN OUT LID TO THE TOP OF THE THREADED CAP. ELEVATION
EQUAL.
SANITARY SEWER LATERAL SEWER CLEANOUT DETAIL
6"
INCOMING SEWER GROUT HOLES AS REQUIRED
6" MIN.
10" DIA. VCP
INCOMING NEOPRENE CASING PIPE OR CP SUMP
SEWER FLAT WASHER DROP CONNECTION
H WHEN REQUIRED
10"
THREADED SIN E
CA R PIP & COVER AS SPECIFIED FIN. GRADE
INSERTS 6" MIN. IE
(CAST-IN) RR SAND FILL
CA 3" TO 8" BRICK
OR GRADE RING
WATERTIGHT COVER "C"
ANCHORAGE STEEL
(CLEAR
MANHOLE OPENING)
"T"
OUTGOING SEWER STRAP VENT
G ACCESS "d" WOOD
MANHOLE SCHEDULE
BLOCKING 1/2" MORTAR
"d"
OUTGOING PIPE SIZE D PLAN "X"=24"OR LESS OVER BLOCKS
SEWER (" d") MH STEPS SEWAGE AIR RELIEF
STANDARD MANHOLE PRESSURE GROUT WITH CONCRETE PRECAST CONC. M.H. AT 16" CTRS VALVE. MANUFACTURER
8"-24" 48" SIZE OF SEWER = D CASING PIPE (ASTM C-478) OR 8" 48" DIA. "D" ARI, MODEL D-025 WITH
PLAN TO BE SURMOUNTED BY 27"-36" 60" TABLE CONC. BLOCK WALL 2" THREADED INLET
2" NIPPLE
(6'-6" MIN.)
1/2" THK. MORTAR BED, SAND FILL "X" "Y"(MIN)
VARIES
GROUND OR STREET AND STANDARD MH FRAME 42"-48" 72" 2" S.S. BALL VALVE
SURFACE AND COVER PER TABLE. 6"-8" 20" 2" NIPPLE
54" 84"
PVC STANDARD "T" BUTT FUSE SADDLE (HDPE)
10"-12" 24"
"d" DOUBLE STRAP SADDLE (DIP)
F TRACER WIRE
14"-15" 30"
3" TO 8" CONC. d= D/2 OR 8" MINIMUM
BRICK OR GRADE 18"-21" 36"
C.L. CASING
ECCENTRIC CONE
RINGS
STANDARD 24",
24" 42"
C.L. PIPE MORTAR
8" MAX.
MIN.
36" OR 48"
12"
COLLAR
TO SUMP
NOTE: "T"=8" FOR "D"=4'-0" ALL
AROUND
"T"
MDOT CLASS II SAND SEE SPECIFICATIONS & 5'-0" 10" FOR
12"
3" DIA. PIPE
12"
FOR ALTERNATE LARGER "D"
CONST. METHODS
MH STEPS ONE PIPE SUPPORT
6"
AT 16" CASING PIPE #5 AT 12" E.W. TOP HDPE OR DIP WM
CTRS. PRESSURE GROUT (NONE FOR "D"=48")
E SECTION WITH CONCRETE SECTION
"D" REQUIRED WHEN AN INLET PIPE IS 24" OR WOOD BLOCKING NOTE: ALL PLUMBING MATERIALS TO BE NON-CORROSIVE,
MORE ABOVE THE OUTLET PIPE IN A MANHOLE AT 10' CENTERS ALL FITTINGS SHALL BE STAINLESS STEEL.
RISER SECTIONS
AS REQ'D
DROP CONNECTION CASING PIPE AIR RELIEF STRUCTURE
SLOPE
1:6
STD. 48", 60", 72",84",96"
MAX.
FILL 5. UTILITY TRENCHES LOCATED WITHIN A MDOT ROW SHALL CONFORM EXISTING SURFACE BACK OF CURB OR
PIPE UNDER PIPE NOT UNDER EDGE OF SHOULDER
TO MDOT STANDARD DETAIL R-83.
DRIVEN SURFACE DRIVEN SURFACE
6. TRACER WIRE IS REQUIRED ON FORCE MAIN ONLY AND SHALL BE 6" PVC, SDR 26
S.S. RISER
2" MIN. LEVELING BED 6" PRECAST OR 8" POURED IN PLACE BROUGHT TO GRADE AT A MINIMUM EVERY 1000 FEET IN A APPROVED FINISHED SURFACE SUITABLE MATERIAL CLAMP, GRINNELL
STANDARD DETAILS
(SAND OR STONE) CONC. BASE WITH #5 BARS AT 12" CAST IRON TRACER WIRE BOX ENCASED IN CONCRETE OR WITH AN EXCAVATED FROM FIGURE 261, TYP.
O.C. E.W. DIA OF BASE TO BE 18" APPROVED GREEN MARKER POST. SEWER TRENCH 90% 1
DRIVEN SURFACE
UNLESS OTHERWISE ON EXISTING
GREATER THAN MANHOLE SUBBASE SUITABLE 1 MANHOLE
C SPECIFIED
SECTION A-A TRENCH SLOPES IN MATERIAL
ACCORDANCE WITH EXCAVATED FROM PVC PIPE (SDR 26)
GRANULAR S.S. ANGLE
NOTES: MIOSHA EXISTING SURFACE SEWER TRENCH
MATERIAL MDOT BRACKETT
1. ALL SANITARY MANHOLES TO BE PRECAST REINFORCED CONCRETE WITH 90% UNLESS
REQUIREMENTS CLASS III 95% GRANULAR MATERIAL
PREMIUM JOINTS. SEE SPECIFICATIONS FOR BASE SLAB AND PIPE OPENINGS OTHERWISE
COMPACTION MDOT CLASS III
AND CONNECTIONS. SPECIFIED
OVERFILL 95% COMPACTION
2. MANHOLE CONES SHALL BE THE ECCENTRIC TYPE.
3. PROVIDE 6" OF COMPACTED GRANULAR MATERIAL UNDER ALL PRECAST
GRANULAR MATERIAL
CONCRETE BASE SLPVC.
MDOT CLASS II GRANULAR MATERIAL GRANULAR MATERIAL
4. FORCE MAINS CONNECT DIRECTLY TO A MANHOLE SHALL BE INSTALLED SO
12"
12"
12"
95% COMPACTION MDOT CLASS II MDOT CLASS II
THAT THE ELEVATION OF THE PIPE CROWNS MATCH. THE FORCE MAIN SHALL
Do 95% COMPACTION 95% COMPACTION
BE DIRECTED DOWNWARD INTO THE FLOW CHANNEL. THREADED S.S.
B TRACER WIRE
5. FOR SANITARY SEWERS ALL PIPES SHALL ENTER MANHOLE THROUGH RUBBER ROD ANCHORED
HAUNCH - TRACER WIRE TRACER WIRE EXISTING PIPE
BOOTED CONNECTION. MIN. Do/6 INTO MANHOLE
95% 2 - 45°
WALL
COMPACTION BENDS
Di Di Di
FRAME & COVER FOR SANITARY SEWER MANHOLES LOWER SIDE -
0.2 FT
90% SW 95% ML CLASS C
MANUFACTURER OR EQUAL OR 100% CL CONCRETE
EAST FILLET
TYPE TYPE OF COVER JORDAN NEENAH
PIPE AS CALLED SEE PIPE BEDDING
SANITARY - SOLID BEDDING 4" MIN. (6" MIN. FOR ON PLANS DETAIL FOR MATERIAL
SEE PIPE BEDDING DETAIL FOR
A
MH SELF-SEALING 1040.0000 R-1642 IF ROCK IS FOUND) Do/3 LOOSELY PLACED,
AROUND PIPE
MATERIAL AROUND PIPE
SANITARY - SOLID COMPACT BEDDING UNCOMPACTED BEDDING UPDATED MAY 2015
EACH SIDE 95%
MH WATERTIGHT 1040-APT R-1916-F PIPE WITHIN INFLUENCE
CO SOLID 1574A R-1973-A PIPE BEDDING PIPE UNDER/NOT UNDER DRIVEN SURFACE OF DRIVEN SURFACE
STANDARD MANHOLE TRENCH EXCAVATION & PIPE BEDDING INTERIOR SEWER LATERAL DROP CONNECTION
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
INCOMING POWER
EXISTING ELECTRICAL
METER AT HOUSE
(MINIMUM 30 AMP/240V
K SERVICE)
PUMP STATION ALARM PANEL NEMA 3R COMPLETE WITH
CIRCUIT BREAKERS AND WIRING BY MFR. INSTALLED AND
CONNECTED BY CONTRACTOR. WIRING FROM LOAD SIDE OF M
DECO. WATT HOUR METER TO CONTROL PANEL SHOWN IN PUMP STATION ALARM LIGHT
ONE-LINE DIAGRAM ON THIS SHEET. *MOUNT ALARM BOX FURNISHED BY STATION
WITHIN CLEAR VIEW OF PUMP STATION. FASTEN WITH MANUFACTURER 10'
GALVANIZED SCREWS TO BUILDING WALL OR 4"X6"X7'
MAX.
WOLMANIZED POST AND BURY 3'.
FUSED ELECTRICAL DISCONNECT
SWITCH, SERVICE ENTRANCE
RATED.
J
SCHEDULE 80 PVC ELECTRICAL
CONDUIT (TYP.) PROVIDE #6 GROUND WIRE,
5"±
WARNING TAPE GRADE
WARNING TAPE
24"
ELECTRICAL QUICK
COVER IN ROADWAY
DISCONNECT BY
18" LNG. EXT. ROD MANUFACTURER,
5'-6" MIN.
COVER
CAST IRON CURB BOX W/ARCH BASE WIRED BY
5'-6" MIN.
CONTRACTOR.
H CHECK VALVE
CONNECT TO CURB TRENCHING DETAIL
VALVE W/CLOSE NIPPLE
FLOW
ITEM DESCRIPTION
1 4" PVC INLET PIPE*
2 4"x4"x2" TEE WITH 2" PIPE TO BUILDING VENT*
2'-6" MIN.
8 HEAVY-DUTY CAST IRON FRAME AND COVER ***
12 8 11
1 6 2 9 CONCRETE ADJUSTMENT RINGS
12
15 ALTERNATE PIPE EXIT REINFORCE AS REQUIRED FOR SERVICE CONDITIONS
10
13 4" PVC 90° ELBOW*
STANDARD DETAILS
13 11
4'-6"
4'-3 1/2"
13 * 6" PIPE MAY BE SUBSTITUDED TO MATCH UPSTREAM PIPE DIAMETER.
** REFER TO CLEAN OUT DETAIL(S) ON STANDARD DETAIL SHEET.
6 *** CLAY & BAILEY 2008 BV OR EQUAL (FROST PROOF COVERS OPTIONAL)
NOTE: PIPE ENTRY/EXIT SHALL 14 ****FM STAINLESS FASTNERS #63 OR EQUAL. 1/2"x2-1/2" SS BRACKET W/ 1/2"x1-1/2" FULLY THREADED
1'-6"
1'-0"
1'-0"
MATCH JCW PERMITTED SITE PLAN. 7 SS HEX BOLT WITH 1/2" SS WASHER AND 1/2"X1-3/4" SS ANCHORS. CLAMP TO BE FACTORY
INSTALLED.
B 3
TO BLDG VENT 3" NOTES:
1. THREE COVERS AND RISERS SHOWN. TWO COVERS AND RISERS CENTERED OVER UPPER TWO
SAMPLING PORT BAFFLES ARE OPTIONAL.
2. INTERCEPTOR SIZE - 1000 GAL MINIMUM (REVISE THE SIZE DIMENSIONS, AS NEEDED, FOR LARGER
4 10 CAPACITY INTERCEPTORS)
3. ALL JOINTS AT THE FRAME & COVER*, CONCRETE ADJUSTMENT RINGS AND THE LID OF THE
8'-6" INTERCEPTOR SHALL BE SEALED WITH A MINIMUM OF TWO (2) ROWS OF 3/4 TO 1 INCH PREFORMED
BUTYL JOINT SEALER AND A 6" BUTYL JOINT WRAP AROUND SLEEVE (EZ WRAP). THE ENDS OF THE 6"
EZ WRAP SHALL OVERLAP BY 12".
4. PIPING ON THE INTERIOR OF THE INTERCEPTOR SHALL BE PVC WITH SOLVENT-CEMENTED JOINTS.
5. GREASE INTERCEPTOR INCLUDING ADJUSTMENT RINGS AND CASTINGS SHALL BE WATER TESTED
A FOR WATER TIGHTNESS AFTER THE BACKFILL OPERATIONS HAVE BEEN COMPLETED IN ACCORDANCE
WITH THE LIVINGSTON COUNTY BUILDING DEPARTMENT SPECIFICATIONS FOR SEPTIC TANKS.
6. ONLY KITCHEN WASTE SHALL BE DIVERTED TO THE GREASE TRAP.