0 ratings0% found this document useful (0 votes) 4K views24 pagesPEC Tables
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
APPENDIX A
‘Appendix A. Electrical Symbols
Ne DESCRIPTION SYMBOL, No DESCRIPTION
TH) GENERAL ELECTRICALSY MBOLS 120 [aes Geation
11 | tighaing Arester i 2. Vapor Dicharge Lamp
12 | Su ‘
age Arester t
“Est Lamp
13 | Growad art) 4
14 | crooner)
hy 6 Lamp Outle! with Pull Switch
-
15 | savise Ennace Po
sass aww 7, Outlet with Blank Cover
1.65 | Serie Ensunce (Telephone) + Fan
17 | Kitpuwt.tioer Meee 9. Clock
p-@
1 fore o-0
10, Single Convenience
1. Duplex Convenience
1d lamas sone h 12, Weatherproof Convenience
ae uy
(ecm el
oleate 5 Teche
(ACU, WH, D,R, ete)
16. Flooe PTD
oF i
Tome
113 | Pe Cut
13. Microphone
1.14 | Main Distribution Panelboard ‘MOP 19. Telephone.
2. tnewon
= TH [Satis
T Sage POP
ip eee earns ES 2 Duplex (2 single pole witcher on
[| contanion ype tas omeates] Sy —] ee
pnnan Type Watae Cave
uas||art Surer Pho Pusat Docume] ESP Eee See ie seta
Switch
‘Combination Type Mawr, Coat [4 Double Pate
ombinaion Type Meter, Canoe,
ATL Stare Plas Cnet Breaker Ea 5 These Pole
720 | Oxtews Celing [Wa 6 Thee Way
7. Four-Way
1 ecm tae alaAPPENDIX A
Ne. DESCRIPTION SYMBOL, No. DESCRIPTION
1.21 | Swinches (continuation)
10, Master Selector 5, {continstion)
137 | Wing Spb (erost-lies indicate numberof wires)
1, Remote Coal Se
Tnieeam
Junction Box
Pull Box
=o
10, Closed Circit Television
Riser Up
wn
Riser Down,
139)
16 | CRU Homerin
(Number indicates Cieuit No.) La)
Las.
Pash Bution
a] sJe/olk]
Lal
Buzzer (Indicate Voliage)
1.42 | Thermocouple
‘ell indicate Voltage)
1.43 | Converter, Tranemiter
130
1st
12
Hom
Amplifier
‘Anmuncistor
1.44 | Single Phase Bridge Reotfer
Plug aad Socket Device
Lovdspeaker
1.46 | Filaseas Lamp
Teleptwoae Exchange
Q
1a | Disha Lamp ae
Ti 2:0 ROTATING MACHINES
Telephone Terminal Cebinet
21 | AC Generator
Fire Alarm System
1, Maral
2. Control Pant
22. | DE Generane
By \a/BlAldlyaiGie
@|©
3. Hea Detter
4, Flame Detector
5. Smoke Detector
6 Ionization Detector
@|®
@©®|oF§
;
i
Wiring Symbols (erot-lines
it
Ble
ag | Tse Phe
with Squirel-C
Three Phase Indision Matar
—FA—FA_ with Squirel-Cage Rotor, Both
= Ends of the Winding Broaght out
O|@
947ARTICLE 4.30 — MOTORS, MOTOR CIRCUITS AND CONTROLLERS
4.30.14 Tables
‘Table 4.30.14.1 Full-Load Current in Amperes, Direct-Current Motors
The following values of full-tond eurrents’ are for motors running at base speed,
Horsepower 90 Volts 115 Volts 180 Volts 230 Volts 500 Volts
14 we 3 20 15 -
6 52 a 26 20 -
” 68 sa a 2
oy 96 v6 “a 38
1 22 on a7
na 83 ey
2 . 7 we 8s
3 Po 6 a
5 ” a 2
m2 - ss - » 136
0 - Te 3 1
1s - ne . ss 2
» - we : n x
2s . ry 8 ”
»” . ne . 106 4
“a - pe M40 o
ra - aor ° 3 =
o - . 20 3
% - : - 255 im
Wo - - : at et
ns . . . 435 x
130 - . . ‘se6 2
200 - : os a0
Tae wea OCG
“Based of UL 308
‘Table 4.30.14.2 Full-Load Currents in Amperes, Single-Phase Alternating-Current Motors
‘The following values of full-load currents are for motors running at usual speeds and motors with normal t
characteristics. The voltages listed are rated motor voltages. The currents listed shall be permitted far system vol
ranges of 110 to 120 and 220 to 240 volts,
Horsepower 115 Volts 200 Volts 208 Volts 230 Volts | Horsepower 115 Volts 200 Volts 208 Volts _230 Volts
370ARTICLE 4.30 — MOTORS, MOTOR CIRCUITS AND CONTROLLERS .
Table 4.30,14.3 Full-Load Current, Two-Phase Alternating-Current Motors (4-Wire)
‘The following values of full-load current arc for motors running at speeds usual for belted motors and motors with
normal torque characteristics. Current in the common conductor of 2-phaso, 3-wire system will be 1.41 times the value
given. The voltages listed arc rated motor voltages. The currents listed shall be permitted for system voltage ranges of
110 to 120, 220 to 240, 440 to 480, and $50 to 600 volts.
‘and Wound Rotor
460 Volts 575 Volts 2300 Volts
10 08
2 Lo
16 3
23 1s
30 24
42 33
66 33
oo 80—_—
"ARTICLE 2.20 — BRANCH-CIRCUIT, FEEDER AND SERVICE CALCULATIONS
“uble 2.20.1.3 Specific Purpose Calculation
“Exception No. 2: Where a building is designed and
References ‘constructed to comply with an enengy code adopied by
—_] Section | the local authority and specifying an overall lighting
Calculation Article | (or Part) density of less than 13.5 volt-amperes/13.5 nr, the unit
Fir Condivoning wd Refigeraane tighting loads in Table 2 20.2.3 far office and bank areas
Eauipmen. BranchCireutCordacter | 44) a40d within the building shall he permitted to be reduced ty
Sing U1 vole-amperes!}1 mt .
Ficed Fccuic Heateg Equipe or |
Pipctioes i ee epcncrat | 427 | 27.4 2.20.25 Other Loads — All Oscupancies, In all
suing occupancies, the minimum load for cach outlet for
Taian See a : Zi igeneral-use receptacles and outlets not used far general
eat Bench Cueut Song a basal” Mia illumination shall not be less than that calculated in
‘Mow, ios aso 220.2.5(A) through (L), the loads shown being based
sad = on nominal branch-circuit voltages.
barra ai oramowrts) | 439 | 430.24 Exception: The loads af outlets serving switchboards
land switching feames in relephone exchanges shall be
ecco Nal Been Caled) 219 | 21022 natived from the calculations
‘Over 6D6 Woh Feeder Colelasons
[Phase Converters, Conductors ‘Table 2.20.2.3 General Lighting Loads by
422. ‘Occupancy
2.20.2 Branch-Circuit Load Caleulations
‘Type af Occuppancy
2,202.1 General, Branch-circuit loads shall be
‘calculated as shown in 2.20.2.3, 2.20.25, and 2.20.2.7,
2.20.2.3 Lighting Load for Specified Occupancies. A.
‘unit load of not less than that specified in Table 2.20.2.3
for occupancies specified shall constitute the minimum
lighting load. The floor area for each floor shall be
calculated from the outside dimensions of the building,
dwelling unit, or other area involved. For dwelling
units, the calculated floor area shall not include open
porches, garages, or unused oF unfinished spaces not
‘adaptable for future use.
FPN: The unit values are based on minimum load conditions and
100 peroent power factor and may not prove suficientexpecty
forthe installation contemplated
Exception: Where the building is designed and
constructed to comply with an energy cade adopted by
the local authority the lighting load shail be permitted
to be caleulaied at the values specified in the energy
code where she following conditions are met.
{1) A power monitoring system is installed that will
provide continuous information regarding the
total general lighting load of the building,
(2) The power monitoring system will be set with
‘olarm values to aleri the building owner or
manager if the lighting load exceeds the values
set by the energy code.
(8) The demand factors specified in 2.20.3.3 are not
‘epplied to the general lighting tood.
‘rmores and andioriants
Banks com
Rarber shops and beauty parors a
Chareses 8
Clubs 6
Cour rooms 6
Doveling unite 4
Garages — commercial (storage! 4
Hospitals 16
Hlofels and motels, including apartnent houses
‘wiihout provision for epoking by tenant?
Industral commercial (lof) buibfings 6
Lodge rooms 2
offoe buildings ae
Restaurmats 6
Schools ™
Stores 4
\Werthounes (storage) 2
tn any of the preceding oscupencies exc=pt 006-
family dwelings and ivividual dwelling vis of
iy and cifamaly dwellings:
‘Assembly halls and audizociams 4
alls, coridors, closes, stxiways ‘ARTICLE 220
(A) MotorOperated and Combination Loads,
Where a circuit supplies only motor-operated loads,
“Article 4.30 shall apply. Where a circuit supplies only
air-conditioning equipment, refrigerating equipment,
‘or both, Article 4.40 shall apply. For circuits supplying,
loads consisting of motor-operated utilization equipment
thet is fastened in place and fuss a motor larger than 18
inp in combination with other loads, the total ealeulated
load shall be based on 125 percent of the largest motor
load plus the sum of the other loads.
(B) Inductive and LED Lighting Loads. For circuits,
supplying lighting units that have ballasts, transformers,
‘autotransformers, or LED drivers, the calculated load
shall be based on the total ampere ratings of such units
and not on the total watis of the lamps
(©) Range Loads. It shall be permissible 10 apply
demand factors for range loads in accordance with
Table 2.20.3.16, including Note 4,
2.20.3 Feeder and Service Load Calculations
2.203.1 General. The calculated load of a feeder or
servive shall not be less than the sum of the loads on the
branch circuits supplicd, as determined by Part 2.20.2,
after any applicable demand factors permitted by Part
2.203 or 2.204 or required by Part 2.20.5 have been
applied.
FPN: See Examples D1 10 10 in Appendix D. Sec 2.202:B)
for the muaxignum load in amperes permited for lighting wis
sporting af less than 100 percent power fot.
2.2033 General Lighting. The demand factors
specified in Table 2.20.3.3 shall epply to thet portion
‘of the total branch-circuit load calculated for general
illumination. They shall not be applied in determining
the number of branch circuits for general illumination.
2.20.3.4 Show-Window and Track Lighting.
(A) Show Windows For show-window lighting, a load
of not less than 660 volt-amperestinear meter shall be
included for a show window, measured horizontally
along its base.
FEN: See 220:25(G) for bach ciccuits applying, show
windows
(B) Track Lighting. For track lighting in other than
dwelling units or guest rooms or guest suites of hotelsor
motels, an additional lead of 150 volt-amperes shall be
included for every 600 mm of lighting track or fraction
thereof. Where multicircuit track is installed, the load
shall be considered to be divided equally between the
track circuits,
BRANCH-CIRCUIT, FEEDER AND SERVICE CALCULATIONS
‘Table 2.20.33 Lighting Load Demand Factors
Portion of
Lighting Load to | Demand
Type of Occupancy | Which Demand | Factor
(Percent)
Dwelling units
Remainder ove
Tanpoo a
Tiars0 Oars] ©
Hospitals Remainder over
50,000 at x
Fane PEenpeatesal
weet | ame | ao
ocean prveoe
——o [ a
Fra as00wiare|
Wirdusestaoneey | Rarer over] 29
1250001
Fea Facies oF sable shal not soph
foau of feeders or sereices supplying areas in hospital, hotels an
‘otek where the eatire lighting is likely to be used oo tr, a
Inoperating roonssballoors, or dining rooms,
Exception: If tne tack lighting is supplied through
device that limits the current to the teack, the load shall
be permitted 10 be calculated Based on the rating of the
device used to limit the current
2.20.3.5 Receptacle Loads — Other Than Dwelling
Units. Receptacle loads calculated in accordance with
2.20.2.54H)) and (1) shall be permitted to be made subject
to the demand factors given in Table 2.20,3.3 or Table
2.20.35, A
2.20.3.11 Motors. Motor loads shall be calculated in
‘accordance with 4,302.4, 4.0.2.5, and with 4.40.16
for hermetic refrigerant motor compressors.
2.20342 Fixed Electric Space Heating. Fixed electric
space-heating loads shall be calculated at 100 pereent
of the total connected load. However, in no case shall
a feeder or service Joad current rating be less than the
roting of the largest branch circuit supplied.
‘Table 2.20.3.5 Demand Factors for Non-Dwelling
Receptacle Loads
Portion of Receptacle Lond
to Which Demand Factor
“Applies (Volt-Amperes)
First 10 KVA or less a
Remainder over 10KVA at
Demand Factor (%)ARTICLE 2.20 — BRANCH-CIRCUIT, FEEDER AND SERVICE CALCULATIONS
“Table 2.20.3.15 Demand Factors for Household,
Electric Clothes Dryers
Exception: Where reduced loading of the conductors
results from units operating on duty-eycle, intermittently,
‘or from all units not operating at the same time can be
supported by load computations, the feeder and service
‘conductors are permitted to heave an ampacity tess than
100 percent, provided the conductors have an ampacity
for the load so determined.
2.203.13 Small-Appliance and Laundry Loads —
Dwelling Unit.
(A) Small-Appliance Circuit Load. In cach dwelling
‘unit, the load shall be calculated at |$00volt-amperes for
cach 2-wiresmall-appliancebranch circuitas covered by
2.10.1.11(C)(1). Where the load is subdivided through
‘two of more feeders, the calculated load for each shall
fnelude not less than 1500 volt-amperes for each 2.wire
small-epplianee branch circuit. These loads shall be
ppeflnitted to be included with che general lighting load
and subjected to the demand faetors provided in Table
2203.3.
Exception: The individual branch circuit permitted by
2.10.3.3(B)(1). Exception No. 2. shat! be permitted ta
be excluded from the caiculation required by 2.20.3.13.
(B) Laundry Circuit Load. A load of not les than 1500
‘yoll-amperes shall be included for each 2-wire laundry
branch circuit installed as covered by 2.10.1.1(C)
(Q). This load shall be permitted to be included with
the general lighting load and subjected to the demand
{factors provided in Table 2.2033.
2.20.3.14 Appliance Load — Dwelting Unit(s). It shall
‘be permissible to apply a demand factor of 75 percent
to the nameplate rating load of four or more appliances
‘fastened in place, other than electric ranges, clothes
dryers, space-heating equipment, or sir-conditioning
‘equipment, that are served by the same feeder or service
in a one-family, two-family, or makifamily dwelling.
2203.15 Electric Clothes Dryers — Dwelling
Unit(s). The load for household electric clothes dryers
in a dwelling unit(s) shall be either $000 warts (volt-
amperes) or the nameplate rating, whichever is larger,
for each dryer served. The use of the demand factors in
Table 2.20315 shall be permitted. Where two of more
‘single-phase dryers are supplied by a 3-phase, 4-wire
feeder or service, the total load shall be calculated on
the basis of twice the maximum number connected
between any two phases. Kilovolt-amperes (kVA) shall
be considered equivalent 10 kilowatts (kW) for loads
calculated in tis section.
2,203.16 Electric Cooking Appliances in Dwelling
Units and Household Cooking Appliances Used
in Instruetional Programs. The load for household
electric ranges, wall-mounted ovens, counter-mounted
cooking units, and other household cooking appliances
individually rated in excess of 124 kW shall be
permitted io be calculated in accordance with Table
2203.16, Kilovol-amperes (KVA) shall be considered
equivalent to kilowatts (kW) for loads calculated under
this section.
Where two or more single-phase ranges are supplied
by a S-phase, 4-wire feeder or service, the total load
shall be calculated on the basis of twice the maximum
number connected between any two phases.
FPN No.1: See the examples in Appendia D.
FPN No, 2: See Table 2203.17 for conmeccial cooking
equipment
2,203.17 Kitchen Equipment — Other Than
Dwelling Unit(s). It shall be permissible to calculate
the load for commercial electric cooking equipment,
dishwasher booster heaters, water heaters, and other
kitchen equipment in accordance with Table 2.20.3.17.
‘These demand factors shall be applied to all equipment
that has either thermostatic control or intermittent use
as kitchen equipment. These demand factors shall not
apply to space-heating, venuilating, oF air-conditioning
equipment.
However, in no case shall the feeder or service
‘calealated load be less than the sum of the largest two
kitchen equipment loads.
2,203.21 Noneoincident Loads. Where it is unlikely
that two or more noneoincident loads will be in use
simultaneously, it shall be permissible wo use only
the largest load{s) that will be used at one time for
ccaleulating the total load of a feeder or service.
37ARTICLE 2.20 — BRANCH-CIRCUIT, FEEDER AND SERVICE CALCULATIONS
Table 2.20.3.16 Demand Factors and Loads for Household Electric Ranges, Wall Mounted Ovens, Counter Mounted
‘Cooking Units, and Other Household Cooking Appliances over 1°54 KW Rating (Column C to be used in all cases exeept
+
Demand Factor (%) (See Notes) ‘Column C Maximum Demand (kW)
‘Number of Appliances | Colymn A (Less than 3 Column B (3 1/2 kW (See Notes)
‘| Sinasoa | seappeaaay | Se
: a ei
6 7° =f Py 3
s fe : |
Sa
Over 12 EW Bough 27 LW rages al of sume rin. For snges iva red more tan (2 KW tape taa 27 Whe macs denand
inGeluna Cable inresse spre or exh aicoal iowa of Mn Orr ALON ee fy shh ey of al ge eee
ONEEBM kW troup 27 rnp of nea satings For anges indvidhaly raid more han 834 Wa of fecal ings, bucoone excel
Z2ILW. mn serge vale of ry thal be alee hy addg together he os oa rnge wo aoa ie al comers Wed cae 12 Ee ey
fang ated es Ea 12 LW) and dvd bythe tl nambe orange, Ten he tamu demand Cahn shall ences SFr rach
Sova Sk hugh EAE Irene eke Sunt eal print ald fe amelie ng oom eoting
Ove A trngh ESA ee el sia tciume cto os ngs of alt hoc
appliances td mrs Bn 14 A but noc mere tan 54 HW an iol he rs yt era toes spain is Catan Aer Cabaret ae
restate efsrplaies Whee the reting of cooking aplene aks andr bot Cohn And Coline Bie demand ter a exch lose
pled othe places fr hc columy adie fee ae tee,
3{BfeetCiret ad shal be perso calle theron load fer oe sng in secordace wih abe 2203.16 Th baoticit
lua or ne walled sven o ore cousterwarsed coking uni sl fe muncpine ing of plane Tas tenets ead ie
tmouad eockng wnt and net costa wo wul-mounes reer al spi Mom sale anc cuca end iced mike see oes al
‘tld yee manne ring fb hl apn ang esy Inn a eqeslet one nee
Stee hh meme rtd den popu
58“Table 2.20.3.17 Demand Factors for Kitchen
Equipment - Other than Dwelling Units
Namber of Unitcaf Equipment Demand Factor (74)
1 100
2 100
3 cy
4 so
3 10
Gand over 6s
2.20.3.22 Feeder or Service Neutral Loa
(A) Basic Calculation. The feeder or servicenentral load
shall be the maximum unbalance ofthe load determined
by this article. The maximum unbalanced load shall be
the maximum net calculated load between the neutral
ge conductor and any one ungrounded conductor.
Exeption: For 3-wire, 2-phase or J-wire, 2-phase
‘stems, the maximum unbalanced load shall be the
maximum net calculated toad beeen the neutral
ceonductor and any one ungrounded conductor
multiplied by 140 percent.
(B) Permitted Reductions. A service or feeder
supplying the following loads shall be permitted to have
an additional demand factor of 70 percent applied 10
the amount in 2.20.3.22(B)(1) or partion of the amount
in 2.203.22(B)(2) determined hy the following basic
caleulations:
(1) A feeder or service supplying household electric
ranges, wall-mounted ovens, counter-mounted
cooking units, and electric dryers, where the
maximum unbalanced load has been determined
in accordance with Table 2.20.3, 16 for ranges and
Table 2.20.3.15 for dryers
(2) That portion of the unbalanced load in excess
of 200 amperes where the feeder or service is
supplied from a 3-wire de or single-phase ac
system; or a 4-wire, 3-phase system; or a 3-wire,
2ephase system, or a S-Wwite, 2-phase system
FPN: See Enamples Dito D8 in Apponsix D,
Prohibited Reductions. There shall be no reduction
“of the neutral or grounded conductor capacity applied to
“the amount in 2.20.3.22(C)(1), or portion of the amount
Sin (C2), from that determined by the basic calculation:
(Q) Any portion of a 3-wire circuit consisting of 2
‘ungrounded conductors and the neutral conductor
» of a4-wire, 3-phase, wye-connected system
(2) That portion consisting of nonlinear loads
supplied from a 4-wire, wye-connected, 3-phase
system
ARTICLE 220 — BRANCH-CIRCUIT. FEEDER AND SERVICE CALCULATIONS
FPN: A Sphase, 4wite, wye-connecied power system used io
supply power 0 nonlinear loads may necessitate thatthe power
system design allow fr the possibuity of high harmonic nexaral
cenducir curen's.
2.20.3.23 Dwelling Unit—More than 150 Square
‘Metres Floor Aren, For a dwelling unit having & floor
‘area more than 150 square metres, the feeder and service
loads shall be computed with 100 percent demand
factor on the airconditioning load and the lighting load.
The cooking load shall be computed in accordance with
Section 2.20.3.16, Other loud shall be permitted to be
computed with 40 percent demand factor.
2.20.4 Optional Feeder and Serviee Load
Calculations
2204.1 General. Optional feeder and service load
calculations shall be permitted in accordance with Part
2204.
2.20.43 Dwelling Unit.
(A) Feeder and Service Load. This section applies to
a dwelling unit having the totel connected load served
by a single 230-volt set of 2-wire service, or 115/230-
volt or 208Y/120-volt set of 3-wite service or feeder
conductors with an ampacity of 100 or greater. It shall
tbe permissible to calculate the feeder and Service loads
in accordance with this section instead of the method
specified in Part III of this article. The calculated load
shall be the result of adding the loads from 2.20.4.3(B)
and (C). Feeder and service-entrance conductors
whose calculated load is determined by this optional
calculation shall be permitted to have the neutral. load
determined by 2,20.3,22.
{B) General Loads, The general calculated load shall
be not less than 100 percent of the first 10 kVA plus 40.
percent of the remainder of the following loads:
(1) 24 voltamperesim? for general lighting and
general-use receptacles. The floor area for
each floor shall be calculated from the outside
dimensions of the dwelling unit. The calculated
floor area shall not include open parches, garages,
‘or unused or unfinished spaces not adaptable for
future use,
(2) 1500 volt-umperes for each 2-wire, 20-ampere
small-appliance branch circuit and each laundry
branch circuit eovered in 2.10.1.11¢C)(1) and (C)
@.
(3) The nameplate rating of the following:
All appliances that are fastened in place,
permanently connected, or located to be on a
specific circuit
30ARTICLE 2.20 — BRANCH.CIRCUIT, FEEDER AND SERVICE CALCULATIONS:
Ranges, wall-mounted ovens, counter: mounted
cooking units
¢. Clothes dryers that are not connected to the
laundry branch circuit specified in item (2)
dd. Water heaters
(4) The nameplate ampere or KVA rating of all
permanently connected motors not included in
item (3).
(C) Heating and Air-Conditioning Load. The largest
of the following six selections (load in kVA) shall be
included:
(1) 100 percent of the aameplate reting(s) of the air
conditioning and cooling
(2) 100 percent of the nameplate rating(s) of the heat
pump when the heat pump is used without any
supplemental electric beating,
(3) 100. percent of the nameplate rating(s) of
the heat pump compressor and 65 percent of
the supplemental electric heating for central
eleciric space-heating systems. If the heat pump
compressor is prevented fom operating at the
same time as the supplementary heat, it does not
need to be added to the supplementary heat for
the toval central space heating load.
(4) 65 percent of the nameplate rating(s) of electric
space heating if less than four separately
controlled units.
(5) 40 percent of the nameplate rating(s) of electric
space heating if four ar more separately controlled
units
(6) 100 percent of the nameplate ratings of electric
thermal storage and other heating systems where
the usual load is expected to be continuous a the
fall nameplate value. Systems qualifying under
‘this selection shall not be ealewlated under any
cother selection in 2.20.4.3(C).
2.20.4.4 Existing Dwelling Unit. This section shall be
permitted 10 be used to determine if the existing service
cr feeder is of sufficient capacity to serve additional
Joads, Where the dwelling unit is served by a 230-volt,
2.wire service, or 115/230-voltor 208¥/120-volt, 3-wire
service, it shall be permissible to calculate the toval load
in accordance with 2.20.44) or (B),
(A) Where Additional Air-Conditioning Equipment
or Electric Space-Heating Equipment Is Not to Be
Installed. The following percentages shall he used for
‘existing and additional new loads,
Percent of Load
Load (kVA)
First 8 KVA of load at 100
Remainder of load at 40
‘oad calculations shall include the following:
oo
(1) General lighting and general-use receptacles at
24 voltamperes/m? as determined by 220.23 ~
{2} 1500 volt-amperes for each 2-wire, 20-ampere
small-appliance branch circuit and each laundry
branch circuit eavered in 2.10.1.L1(CML) and (C)
@
(3) The nameplate rating of the following:
a All appliances that are fasteaed in place,
permanently connected, or located to be on a
specific circuit
b. Ranges, wall-mounted ovens, counter-mounted
‘cooking units
«Clothes dryers that are not connected to the
laundry branch circuit specified in itern (2)
4. Water heaters
(B) Where Additional Air-Conditioning Equipment
or Electric Space-Heating Equipment Is to Be
Installed. The following percentages shall be used for
‘existing ond additional new loads, The larger connected
load of air-conditioning or space-heating, but not both,
shall be used.
Load ot Load
Airconditioning equipment 100
Central electric space heating 100
‘Less than four separately controlled 60
space-heating units
First 8 KVA ofall other loads 100
‘Remainder of all other loads 40
(Other Toads shall include the following:
(1) General lighting and general-use receptacles at
24 voltamperes/m” as determined by 2.202.344
(2) 1500 voliamperes for each 2owire, 20-ampere
small-appliance branch circuit and cach laundry
branch circuit covered in 2.10,1.11(CX1) and (C)
Q
(3) The nameplate rating of the following:
4, All appliances that are fastened in place,
permanently connected, or located to be on a
specific circuit
>. Ranges, wall-mounted ovens, counter-mounted
cooking units
. Clothes dryers that are not connected to the
laundry branch circuit specified in iter (2)
4. Water heatersARTICLE 2.20 — BRANCH-CIRCUIT, FEEDER AND SERVICE CALCULATIONS
2.20.45 Multifamily Dwelling.
(A) Feeder or Serviee Load. [t shall be permissible to
calculate the load of a feeder or service that supplics
three or more dwelling units of a multifamily dwelling,
in accordance with Table 2.20.4.5 instead of Part 2.20.3
ifall the following conditions are met:
(1) No dwelling unit is supplied by more than one
feeder.
(2) Each dwelling unit is equipped with electric
cooking equipment.
Exception: When the ealeulated load for multifamily
dwellings without electric cooking in Part 2.20.3
exceeds that calculated under Part 2.204 for the
identical load pius eiectric cooking (based un & kW per
um), the lesser of the vo loads shall be permitted 10
ge de used.
(3) Each dwelling unit is equipped with either electric
space heating or air conditioning, or both. Feeders
and service conductors whose calculated load is
determined by this optional calculation shall he
permitted to have the neutral load determined by
2203.22.
(B) House Loads. House loads shall be calculated in
accordance with Part 2.20.3 of this article and shall
bbe in addition ta the dwelling unit loads calculated in
accordance with Table 2.20.4.5.
(€) Calculated Loads. The calculated load to which
the demand factors of Table 2.20.4.5 apply shall include
the following:
(1) 24 volt-amperes'm? for general lighting and
general-use receptacles
(2) 1500 volt-amperes for each 2-wire, 20-ampere
small-appliance branch circuit and each laundry
branch circuit covered in 2.10.1.11(CX1) and (C)
Q
G) The nameplate rating of the following:
All appliances that are fastened in place,
permanently connected, or located 10 be on a
specific cieuit
b. Ranges, wall-mounted ovens, counter-mounted
‘cooking units
¢. Clothes dryers that are not connected to the
Iaundry branch circuit specified in item (2)
Water heaters
(4) The nameplate ampere or KVA rating of all
permanently connected motors not included in
item (3)
(5) The larger of the air-conditioning load or the
fixed electric space-heating load.
2.20.4.6 Two Dwelling Units. Where two dwelling
units are supplied by a single feeder and the calculated
load under Part Til of this article exceeds that for three
identical units calculated under 2.20.4.5, the lesser of
te two loads shall be penmitted to be used.
2.204.7 Schools. The calculation of a feeder or service
cad for schools shall be permitted in accordance with
Table 2.20,4.7 in lieu of Part 2.203 where equipped
with electric space heating, air conditioning, or both.
The connected load to which the demand factors of
Table 220.86 apply shall include all of the imterior and
exterior lighting, power, water heating, cooking, other
loads, and the larger of the air-conditioning load or
space-heating load within the building or structure,
Feeders and service conductors whuse calculated
load is determined by this optional calculation shall
be permitted to have the neutral load determined
by 2.20.3.22. Where the building or structure load is
calculated by this optional method, feeders within the
“Table 2.20.4.5 Optional Calculations — Demand
Factors for Three or More Multifamily Dwelling
Units
‘Namber of Dwelling Units | Demand Factor (°4)
35 5
0-7 “
-10 3
1 2
2-3 a
14-15 0
16-17 2a
18-20 38
2 ”
Be 36
was 38
26.0 4
28-30 3
at 3
32-33 3
34-36 30
37-38 2»
33-2 2a
45-48 2
45-20 6
51.88. 6
56-61 u
5 and over 2
6g jumper(s) from grounding electrode(s)
;permitted to be connected 10 an aluminum
busbar not fess than 6 mim thick x SO
‘and of sufficient length to accommodate
ion. The busbar shall be securely fastened
shall be installed in an accessible location.
ections shall be made by a listed connector
ox by the exothermic welding provess, The
ing electrode conductor shall be permitted
tobe run othe busbar, Where aluminum busbars
sed, the installation shall comply with
50,3.15(A).
17 Size of Alternating-Current Grounding
Conductor, The size of the grounding
conductor at the serviee, at cach building
‘where supplied by a feeder(s) or branch
oF at a separately derived system of a
‘or ungrounded ac system shall not be less
n in Table 2.50.3.17, except as permitted in
17(A) through (C).
ons toa Rod, Pipe, or Plate Electrode(s).
ling electrode conductor or bonding jumper
to 2 single or multiple rod, pipe, or plate
e(8).'or any combination thereof, as described
‘of electrodes that require a larger size of
the grounding electrode conductor shall not
quired to be larger than 14 mm? copper wire or 2:
P aluninum wire, om
ons to Concrete-Encased Electrodes. If
electrode conductor or bonding jumper
to a single or multiple concrete-encased
(8) a permitted in 2.50.3.3(A}3), does not
‘on fo other types of electrodes that require
er size of conductor, the grounding electrode
or shall not be required to be larger than 22 mi?
wire.
nections to Ground Rings. If the grounding
conductor or bonding, jumper connected
3.3(AN4), does
‘on to other types of electrodes that require
size of conductor, the grounding electrode
shall not be required to be larger than the
Used for the ground ring.
19 Grounding Elcetrode Conductor ai
Jumper Connection to Grounding
ss. The connection’of a grounding electrode
or ab the service, at each building or structure
supplied by a feeder(s) or branch cirouit(s), o¢
parately derived system and associated bonding
er(s) shall be made as specified 250.3.19(A)
nic).
ARTICLE 2.50 — GROUNDING AND BONDING:
(A) Accessibility. All mechanical lements used to
terminate a grounding electrode conductor or bonding
Jumper to a grounding electrode shall be accessible.
Exception No I: An encased or buried connection
10 a concrete-encased, driven, or buried grounding
electrode shall not be required to be accessible.
ExceptionNo, 2: Exothermic or irreversible compression
connections sed at terminations, together with the
mechanical means used to attach such terminations
to fireproofed structural metal whether or not the
mechanical means is reversible, shal! not be required
10 be accessible,
(B) Effective Grounding Path. The connection of a
grounding electrode conductor or bonding jumper to a
‘grounding electrode shall be made in # manner that will
ensure an effective grounding path, Where necessary
to ensure the grounding path for a metal piping system
used asa grounding electrode, bonding shall be provided
‘around insulated joints and around any equipment likely
to be disconnected for repairs or replacement. Bonding
Jumpers shall be of sufficient length to permit removal
of such equipment while retaining the integrity of the
‘grounding path,
{C) Grounding Electrode Conductor Connections
Grounding electrode conductors and bonding jumpers
sball be permitted to be connected at the following
locations and used 1 extend the connection to an
electrode(s):
Table 2,50.3.17 Grounding Electrode Conductor for
Alternating-Current Systems
Size of Largest
Ungrounded Service
Entrance Conductor
or Equivalent Ares for | sing of Grounding
Parallel Conductors! | itt ode Conductor
mn mm
‘Aluminum or ‘Aluminum or
Copper-Ciad Copper-Clad
Copper Aluminum | Copper | Aluminum
20or smal |S0orsmaller | 806.2) 8
Storso | 60.ara Tm 2
e080 | 100 or 125 2 30)
Over) [Over 15, w 0
through 175_| tough 250
Over 175 [Over 250 30
through 325 | dough 400
Over325 | Over 400 w 100
hewn 300_| through 850
Over 500 [Over 850 wo 1s
43ARTICLE 2.50 —- GROUNDING AND BONDING
2505.9 Bonding Loosely Jointed Metal Raceways.
Expansion fittings and telescoping sections of metal
Yaceways shall be made electrically continuous by
equipment bonding jumpers or other means
2505.11 Bonding in Hazardous (Classified)
Locations. Regardless of the voltage of the electrical
system, the clectrical continuity of non—current-
carrying metal parts of equipment, raceways, and other
‘enclosures in any hazardous (classificd) location, as
defined in 5.0.1.5, 5.5.1.5, and 5.6.1.5, shall be ensured
by any of the bonding methods specified in 2.50.5.3(B)
@) through (BX4). One or more of these bonding
‘methods shall be used whether or not equipment
‘grounding conductors of the wire type are installed
SO PPN: See 5:1.221, $2221, 53.221, 55.125, oF 5.41.25 for
505.13 Grounded Conductor,
luctors, and Jumpers.
‘Material, Bonding jumpers shall be of copper,
inum, copper-clad aluminum, or other corrosion-
material. A bonding jumper shall be a wire,
serew, or similar suitable conductor.
“Attachment, Bonding jumpers shall be attached
‘manner specified by the applicable provisions of
8 for circuits and equipment and by 2.50.3.21 for
Bonding
— Supply-Side Bonding Jumper,
Size for Supply Conductors in w Single
‘Raceway or Cable. The supply-side bonding
jumper shall not be smaller than specified in
Table 2.50.5.13(CX1).
‘Size for Parallel Conductor Installations in
“Two or More Raceways or Cables, Where the
‘ungrounded supply conductors are paralleled
‘in two oF mare raceways or cables, and an
‘individual supply-side bonding jumper is used
“for bonding these raceways or cables, the size of
-Supply-side bonding jumper for each raceway
‘cable shall be selected trom Table 2.50.5. 13(C)
(based on the size of the ungrounded supply
. ‘in each raceway or cable. A single
’ ‘bonding jumper installed for bonding
fro or more raceways or cables shall be sized in
with 2.50.5.13(C)(1).
12 The tern supp coaduearsincades urgroundes
hat do aot hae evercurcet pocstion eu thsi wey
Femina at aervce equipment the fre dixconnecting
watoly derived sysicm.
(75 man (1.0 mm eka) through 100 mu?
‘Table 2.50,5.13(C)(1) Grounded Conductor, Main
Bonding Jumper, System Bonding Jumper, and
‘Supply-Side Bonding Jumper for Alternating
Current Systems
Size of Largest
Ungrounded Conductor a
erEquivalitArea for | S2¢0f Grounding
Parallel Conductors* Bonding Jumper*
mo mm
Aluminem or Atumionn
Conperciag
conmer_|“Siuinum| Copper | ‘Aluaionn™
fare [walks —ansy-[—— te
sa fore [ie Te
60 or 30 100 oF 125, [ 2 30
Onert0—]Oretas | 30] $0
gh 3 up 9
orertts fovea) ao]
through 325, | through 400
Gres Yew to]
tah tg 0
Cr 500 [Ove 0 iNest
Lie ungrauedesaplycondces ae tart tan 300 ma compe
Sc alurinm, the rounded conor or boning jer eal ee
sare pot low thn (2 12 prea of tx rc ef he lange road
Sapp candor or eguvaet aes for palit spl eenducr. The
{rd cede orbonding jure tal nt be cequted wt age hn
the lages ungrounded cvedscor or of wagrounded ondecto.
2 if the ungrounded supply conductors axe ier ta 90 tm copper
‘& X50 ma akiminun anti the wxproande teppy coodacars and ht
teeing jumper ar of ferent tral (coppeshinum.o mppead
lteter ie of the pounded coor x tons per
Stal be fated en the ume we of ungrounded meply come f the
{se materhl athe rounded condor r bending per aad wll have
Siac couieleoto hat ote inaid wend sappy condor.
3 maple seo of sevice-ertranee condacos ae Wed a permed
in 23081, Exception No. 2. or f muiiple sew of tapounded sary
ondicon rt Peale for a eputely derive syst, the egivalen ae
‘tthe lgest ungroaned sippy condita) sal be Geteraited Dy the
largest sum the res ofthe corenponrng coeds ofeach tet
4. ae ae severance rodacb, the supply concer ssc
Shall be determined by he equivalent sizeof the largest Serviceman
oho raped forthe lat be ere
“Forte purposes agping thd ae ad is woke, the ten boning
super ries o sis Bendy jumpers, system Bonding Sper, and
‘ptr ending fre.
(D) Size — Equipment Bonding Jumper on Load
Side of an Overcurrent Device. The equipment
bonding jumper on the load side of an overcurrent
evice(s) shall be sized in accordance with 2.50.6.13.
FPN; Seo Table 1.1.1.8 for the cross-sectional area of conductors
0.25 mm through 100 mm.
A single common continuous equipment: bonding
Jumper shall be permitted to connect two or more
raceways or cables if the bonding jumper is sized in
accordance with 2.50.6,13 for the largest overcurrent
device supplying circuits therein.
"7ARTICLE 2.50 — GROUNDING AND BONDING
(B) Increased in Size, Where ungrounded conductors
are increased in size from the minimum size that has
sufficient ampacity for the intended installation, wire-
type equipment grounding conductors, where installed,
shall be increased in size proportionetely according 10
the cross-sectional area of the ungrounded conductors.
(C) Multiple Circuits. Where a single equipment
grounding conductor is run with multiple eireuits in the
same raceway, cable, of cable tray. st shall be sized for
the largest overcurrent device protecting conductors in
the raceway, cable, or cable tray, Equipment grounding
conductors installed in cable trays shall meet the
minimum requirements of 3.92.2.1(B\1 Xe).
{D) Motor Circuits. Equipment grounding conductors
for motor circuits shall be sized in accordance with (D)
(or (DX2).
(Q) General. The equipment grounding conductor
size shall not be smaller than determined by
2.50,6.13(A) based on the rating of the brancl
circuit short-circuit and ground-fault protective
device.
(2) Instantancous-Trip Circuit Breaker and Motor
Short-Cirenit Protector. Where the overcurrent
device is an instantaneous-trip circuit bresker or
a motor short-circuit protector, the equipment
grounding conductor shall be sized not smaller
than that given by 2.50.6.13(A) using the
maximum permitted rating of a dual element
time-delay fuse selected for branch-circuit short-
circuit and ground-feult protection in accordance
with 4.30.4.2(C\(L), Exception No. 1.
(E) Flexible Cord and Fixture Wire. The equipment
‘grounding conductor in a flexible cord with the largest
eitenit conductor 5.5 mm* (2.6 mm dia.) or smaller, and
the equipment grounding conductor used with fixture
‘wires of any size in accordance with 2.40.15, shall not
be smaller than 0.75 mm? (1.0 mm dia} copper and
shall not be smaller than the eireuit conduetars. The
equipment grounding conductor in a flexible cord with
a cireuit conductor larger than 5.5 mm* (2.6 mm dia.)
shall be sized in accordance with Table 2.50.6.13.
(F) Conductors in Parallel. For circuits of parallel
conductors as permitted in 310.10(H), the equipment
grounding conductor shall be installed in accordance
swith (1) o¢ (2).
() Conductor Installations in Raceways,
Auxillary Gutters, or Cable Trays.
(a) Single Raceway or Cable Tray. If conductors
are instalicd in parallel in the same raceway
124
or cable tray, a single wire-type conductor
shall be permited as the equipment grounding
conductor, The wire-type cquipment grounding
conductor shall be sized in accordance with
2,50.6.13, based on the overcurrent protective
device for the feeder or branch circuit. Wire-
type equipment grounding conductors installed
in cable trays shall meet the minimum
requirements of 3.92.2.1(BX(I){c). Metal
raceways or auxiliary gutters im accordance
with 2.50.69 or cable trays complying
with 3.92.2.51B) shall be permitted as the
‘equipment grounding conductor,
Table 2.50,6.13 Minimum Size Equipment
Grounding Conductors for Grounding Raceway
and Equipment
Rating or Satting of
Automatic Overcurrent | sige mm? (mm dia.)
Device in Circuit Ahead Copper
of Equipment, Condutt, Seni
etc., Not Exceeding Copper-Clad
(Amperes) Copper_| Aluminum®
15 zoe | 3se0
0 ssz0 | sss
x» $512.6) 8.03.2)
0 3526 |
« sszo | x02)
100 80222) u
200 rn z
300 2 x0
400 30 ®
300 30 3
600 38 «
‘Note: Where necessary 1b comply with 2-501-(AWS) or (BVA).
tHe cguipmcot grounding conductor shall be sized large thas given
inthis whle
* Sex installaon restrictions in 2.0.6.1)ARTICLE 3.10 — CONDUCTORS FOR GENERAL WIRING
(3) The manufacturer's name, trademark, or other
distinctive marking by which the organization
responsible for the product can be readily
identified.
(4) The square millimeter size or area.
FIN: See Cuntuctor Popentes,Teble 101.18, for conductor
area expressed in SI units for conductor sizes specified in square
miler size a area.
(5) Cable assemblies where the neutral conductor is
‘smaller than the ungrounded conductors shall be
90 marked.
(B) Method of Marking.
() Surface Marking. The following conductors
and cables shall be durably marked on the
surface. The square millimeter size or area sball
be repeated at intervals not exceeding 600 mm,
All other markings shall be repeated at intervals
not exceeding 1000 mm. *
(1) Single-conductor and multicondustor rubber-
and thermoplastic-insulated wire and cable
2) Nonmetallie-sheathed cable
‘Table 3.10.2.6(B)(16) Allowable Ampacities of Insulated Conductors Rated Up to and Including 2000 Volts,
60°C Through 90°C, Not More Than Three Current-Carrying Conductors in Raceway, Cable, or Earth
(Directly Buried), Based on Ambient Temperature of 30°C*
Temperature Rating of Conductor [See Table 3.10.3.1(A)]
ere [1S 908 rc 90°C
‘Types
RAW, | Types TBS, SA,SIS,
THHW, | FER, FEPB, MI, REH, ‘Types TBS, SA, SIS, RHI,
THW, | RHW-2, THIN, THEW, REW-2, THHN, THEW,
THWN, | THW-2,THWN.2, THW.2, THWN.2, USE-1
‘Types | XHINW, | USE-2,XHH,XHHW, | Types | XHHW, | XHH, XHBW, XHHW-2,
Conductor | TW.UF | USE,zw] XHHW2,zw2 | TWUF | USE ZW
Size mm: ‘COPPER ‘ALUMINUM OR COPPFR-CLAD ALUMINUM
2016)" 15 20 3 = —
3.520)" 2 23 30 Is 20 25
5526)" 30 35 40 2 30 38
8003.2) 20 50 5st 30 40 43
4 5 oS 75 40 30 ro
2 7” as 95 55 6 80,
85 100 us 80 90,
100 us 130 0 105
30 T 140 150 90 ry 125 a
60 130 138 170 100 120 138
30 155 190 20s 120 14s 165
100 185 220 240 140 170 190
125 210 255 285 165 200 223
150 240 288 320 190 20 255
175 260 305 345 205 mas. 2s
200 275 325 x 20 265 300
250 313 315 425 255 305 345.
325 370 435 490 300) 355 405;
38 395 470 530, 3S 380 480
400, 400 480 335 320 385 440
500, 445 530. 595, 365 25 485
“Refer to 3.10.2.4(B}(2)a) forthe ampacity correction fasters where the ambient temperature is other than 30°C, Refer tw 3.102 6(BX3Ka) for
more than three cxreat-carying condctors,
**Refer 10 2.40.1 4(D) for conductor overcurrent protection Himiatians
174APPENDIX C =
‘Appendix C Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size
This informative annex is not @ part of the For cross-referencing conduit diameter sizes, refer to
requirements of this NFPA document but is included the table below.
for informational purposes only. Raceay Sie [inches] Metre Designstr(n)*
For cross-referencing conductor sizes, refer to the = He
table below. We aS
vs 21
AWGikemil ‘mm? (mm dia.) ; A
18 a2s(t A
2 02) Me a
4 20.6) 3
12 3500) o
10 5512.0) : a
e ao a2 1
6 Ma
; a ‘ 1
3 % e
6
2 30 + size appena Cony
A = Tre Fase
vo a Ci — Hoi Mee Tang (ENT)
oe He TAP — Ble! Neal Tubing (ENE
62 Hevea Nommeulie Tag (ENT
ae i CaIAy— Bal Naas Tig (ENT)
0) 100 C3. Fens Meal Consun EMO)
(50) Bs CHAP — Feniie Wel Cond FE)
G00) 150 C4— Faerie Mel Cond MC)
G50) [e-¥Ay— ntrnsdine Maal Com IME)
(400) [E5— Ligh Flenle Nope Conduit Type
(300) CS Uysal ean
300" LNeay ae
350 Ci Lagadigh Fle Nraslis Cont pga P
pie cm
is a) Gqeaign Fee Nowra Conn
(200) 450 (C7 — Lag Fis Novclie Con pe LF
090) 500 SS ee
Sisto, = aA Cath ee Renae Com
(1500) 750 (CA Ligon Fie Meal Conse (LPM)
(1750) a CAVA) — igual Fleible Net Conduit (LEME)
(2000) 1000 (C2 — Rips Neal Coeduit RME)
2s for Append C oy ‘CIA — Righd Maal Come RMOD
‘C10 — Riga PVE Condit, See 8
(CIOAT — Riga PVC Cond, Schele NO
(C1) — Rigi PVC Cond, Scheie 3 and MDPE Conu
CINAP — Riga PVC Condut, Sehedale 40 and HDPE
Con
CR Type A Ra IVC Conta
CRIA Tipe A Rig PVC Conti
Cs Type FB NC Conde
socio stalled must te a the compet 96
966APPENDIX C
‘Table C.10 Maximum Number of Conductors or Fixture Wires in Rigid PVC Conduit, Schedule 80
(Based on Chapter 10: Table 10.1.1.1, Table 10,1.1.4, and Table 10.1.1.5)
= ar
oe | SS" Gea eS ee
aw Chen Ter ay a Gs) au (33), (a) 78) gary | nosy TT 039 J ssp
Soo
SS
Baars] als i/ 2]? :
eo fofatefays of 3{3 @
fadaledelele| eee u
etd te as Ls ps pe
ce DSC OC OS EB OOO
> yet lala life [epee] syeale
p fefididatspide papaya] eye
tet te de LL LS IS Sle
oo SS
zfsle(: |e ffi ye yaya Tay
r wo fofofa la s|a ef | [os
stele tele ii : mola
engage [Pe SS
Rerw2 300 o o t t 3 10 4
Ss lai ' : o/s
o fafa : : ae
om [5s j ; ele
= pos ; : os
co fof : : ;
mo fads ; a4
mw led : : a fa
m io [s : i a
m4 i ‘ a
elit: : ; Pls
m ff ; ; ef
mw lela 3 ; 5
ee a = pe]
wow | oe ft | $ za » [os
ey oe fa ft : a ae
ide ‘ a
oa = =
ah 2 =
TiS SEL ELEI EZ i
Sat =e
tlelelalslelelele 3 | i
ee es a een eae ee eile
mee | Pt tad fe] eye yay a
Be ep pe os 2 [a
ee fyele fifi fe gileyeys AB
1021APPENDIX C
Table C.10 Continued
eae Taira Gi aed
ween Tie ey | 2 Os) (any (53) 6) 8) on
wea [oe sep pe rt pe 2 P38
wre ete de fod atid ede
mer | % folefofefelrfafale
eaw.2s 990 o o 0 a o 1 1 1 2
ve [ope eff TP ya
ete foto te |e tot
Se ae
PPS fa fs |e | ode |
f]o falafel s |e patie
fit lalelalel>|«
stole tes le
: tf] del ede] »
mom | os [stati ft. tits ts S
750 0 a 1 y] 3 + &
ee PSPS [sf ee] | ae | os |
ay 2 2 a 1 2 | u 108, 38
TE ° 7 3 T° wo | = | a |
1022APPENDIX C
‘Table C.11 Maximum Number of Conductors or Fixture Wires in Rigid PVC Conduit, Schedule 40 and HDPE.
Conduit (Based on Chapter 10: Table 10.1.1.1, Table 10.1.1.4, and Table 1.
“Trade Sie (Metre Designation
7
s |»
© 2 fa fr fo fu | a das | | | oo fo
‘ ets ts ts tet wt] ws} ae} ws |i
4 rf?]*,e|,e*,;4,2,sf" |» |
3 rpads | s fs fe ]w fads |x | ow
2 bdo da ta for fw fw | 2 ]om ] ows | os
1 rtrd s atu tet s |» [os
1
1
T
1
ajeeeeulssss
a)
1027APPENDIX
‘Table C.11 Continued
Conlncur Tends See ver Desiptor
Type Sue we [4 pepe: (22>? Peete 5
wore ie en [en es Lon pe | [oo | op | oom | om
cy a
ofo}aofa dao fads fs fados
ofoftofsr fads }adsfefada
ofofofi fut ofad«e]a}adn
500 eo fofofs titi ts }s | sts lw
remy | a
700 ofofofofu ta 2 af
Teva 10 ofofofofufuda a |e
mi, soo ofofofafu fu da da s |e
aw | 500 oto fotos foftidi s fe
wo fe fo fo yo pe fo yo ss
wo | o@ fo fo fo falar fa fa 2] 4
wo | a fo fo fo fafr fa fa rf
wo | ao |ofofofa fof fa ifs
ww | o | o | o fo |» |o fs ta fe
fo} sf
1 TT
2 s {as Joos fo fo | oo foot | are | oss | aor | soe
» s | oo fas fo | | @ fos | ar | ae | ass | om
5 a |s fa fw fon fw fos | om | ws | ar | 26 | oe
‘ eta to fa fis | iw | x Lo | |» | iw | os
7 SS es ae
3 rfar fads fe fo fw | wo | ao foo | |
2 vfoar fa fos for fom fw fas | fos | os | oo
A ota ft ads ts |e |e] aw | s | |» |
To a
20 of afta lata foe fs ful ofa pa la
ras, x0 ofa fadada fs fafa} «fa |» fa
30 ofa fi ti dz | s foe fs fe fis |» | ss
70 a
0 ofofa fafa fs fae fo fa fu fw | a
340 a 0 ' 1 1 z 3 : , ofa fay
“0 ofafofifafla fs} s fs ts fo pow
$0 ofoflofitsr tite ts ts ts | fiw
on 7p)epet? te tot? te?) ys f?: fs
70 ofofofofa fafa fs fae js fafa
730 o}o}ofoefa fafa fa fs fafa pan
a0 o fo} ofofa fafa fe fs fa dr fw
so ofeolofofsefa fa feta fete fe
wo | io fo | o | o fo fs fs fa ts ts ts ts
" 7p ps poe os pe | pan |e | a2 [oe | ne
2 «| a [oo [96 | we | a2 | ae | ace | srr | ose
0 o | wo we fa fo foo | use | am | 2a | ae | oe
rere | sto |wl in|» |» | | |i | io | 7 | 6
E ° 2 7] ep fs pw |e | a [oo [ie |e
4 1 fos fs ]os | 2 fw | foo | se [ors | ue |r
3 1 {2 fa dor | w fw fs fos | | @ | oo |
2 rtitsfe}s tout} » |» | ofa | jm
(cnt
1028APPENDIX C
‘Table C.12 Maximum Number of Conductors or Fixture Wires in Type A, Rigid PVC Conduit
(Based on Chapter 10: Table 10.1.L.1, Table 10.1.1.4, and Table 10.1.1.5)
te
a
~ fa fia fos fom | os
a fs] fos] oo
a sfultu]ox fo» |
ate te} s+ tutatau|a |e
a
vfs fats | os fu fa ]a |
ofa fads fa fa fata fa
oti tats ft sts tel «|
a
vfaufadada]o fo da los
ofa fadada ds fe] wo
etiti tif status
sam. gaw, | 20 a
Baw 300, o 0 1 1 1 1 3 4 6
350 o fe toto fai da fafals
0 ofofofalda fa afal«
0 ofototiti fi »tals
wo a
70 ofofofofifufat: fades
10 o}ofofofifufadaudada
00 ofofofofi fal aduda ds
x0 ofet>otote}i}ititiz|s
7 a
i350 ofofofofefaftafaldada
1x0 ofotlofofe to fa] uta]
me |. fo fo fe fofelofarfurfa la
mo | - |e |o lo |ofls|ofs titi di
rr oa a
Tae 2 - 8 au“ 4 Ww a0 20 i 6 303
“i.
m2 » foe fw fw fw fom | w | oo | us | oe | os
' a {io | ow fw [a | s |» | |» |
m7 7 [oe po poe a |] toe [sear] 2
se e o fw |ow foe | | we fom | ae | ow | an
Be |e s fe fo fa] a | a fw | | |
‘ 2fa]> fel fx |» |» | on | «
¢ Tape Pa aa
‘ sta fafa fo du fafa la pw
i fafade a fu fala | «
. ' 1 a s a 6 “ 2 a
\ titi ts >[u fw la |»
10 on a oe
20 ofada da s fos fa |i | oo
10 ofa da fafa fe fa dw fe |e
6 oti ti tit: ts te to tutu
1033ma
a
oa
165
%0
w
n
2”
2
0
aa
3)
tet
m
a
us
[ae
>
6
0
a
1s
2
hia.
6
70
i
4
“Trade Se (Meare Desa)
5
a
w
in
APPENDIX C
or
ey
2
@
oer
om
7
307
Conductor
(awarkemy
300
1300
bs
200)
w
0
4a
300
350
Table C.12 Continued
ik
oy
2
E
=
20
3
19
ua
os
a
is
Te
70
a
w
a
u
5
Pa
6
a
00
700
130
w
2
0
PAH
Fe, Fee,
Pra,
1034APPENDIX C
Table C13 Maximum Number of Conductors or Fixture Wires in Type EB, PVC Conduit
(Based on Chapter 10: Table 10.1.1.1, Table 10.1.1.4, and Table 10.1.1.5)
‘Condetme “Trade See ete Desioater
tape ‘Sie [1a] 34 tayiefl2 few] s [ey«~ys]«
‘CONDUCTORS
i - S ~@ >= > [ss]
0 - |. da sw | um | ia | an | as
10 Z - | 3 x | ue | ase | 203 | ae
2 2 - a {oa | o | ae | os
‘ = | fo. s fo fs | |
; = epee pee
3 . w o | «|e |e
= ’ w» lo |o | 2
1 - =| s o]-foafrtats le
- 1 ~ - ~ - 7 =o fof |
2 - 2 s | - | w fa | we fs | x
a -|- a iPou fw a fu fu ]a fu
40 -|-J] + - [> [> | 2 | |x
raarane, [9 =f a a
uiW2 wo ot |: = [a s|o6fs felon
390 “ : 1 ats fafa dw
0 -|- 1 af}s |e |o fu
|__ so _|-|- iol ee: ican | sp able
oT =Tap= |: a
70 a |e fa >}a]ale]e
10 2 =|. rte feta fade foe
300 >to] -d-]->e]-]e2)2,4)e es
on Soh Ses [is tech [ot | ei: ie || ee
T080 = a a a
1250 -|-]f-]f- de vf ijel|bds
150 -|-]- - fa rfujtads a
198 - J. ]- - | 1 faupapa | a
200 = [oe] + | a vf pa fe ts
ry = = a |= se ot | ae [oe [or
rena, | on 2 fe fe fe fe fo fe [oe | an | oe | om | os
rave 0 |. e |e | oo | - fw | oie | am | oss | ste
- - | w | | 2 | oo | ws
~ | : 7m | |
pa -|- -|s «8
mess 0 : “ M8
: iL: >|. s
> ~y- 1 21 1
5 -|- w | - 19
a7, 3 < 2 |. | um
RHE Hi ‘ 8
ee ry ~ 7 *
2 ‘ “
a4 s 0
: 4 4
emi)APPENDIX C
‘Table C.13 Continued
Tain Reo Dap
te | OMe Tepes
awe en | es | an | 13)
en 7
w foto]: 3 s}aldn
on ee et . > s|o|o
w | >|: - a slo fa
[we | fe rte feds do
sur, [ae - 7 spe ys
awe | ow | . 1 a fads
niwe | XS Sf ofa fe jada ds
rive, | 9 . sa a fade
mn? | oe sloop} jets.
v9 1 7 psp
ite ~f ope d}a vfa do
‘0 a ee
he flys ja vo
200 . o{-{ifi
vr Topp |
8 of ~ | oe | oe
io 7 | > | | ms
" . ws | as
‘ . | ss
FT - ” 3
2 S| lp ofa ps pap»
1 - - - ww _| 2 2
va Td [> + ps
» 7 uw |»
aad v0 5 B 7
mee | [1 - |: ofl
wm |. |: ; 7 | 9
wo fo |. | - : af
500 - : : : i 5
mf [> 7 4
wo | : Df pada
wo || | - :|- [> ds
wp] pp ep a
o oy hf fam | ae
ee a fw | 2 |i |
: . 2) o | 6
2 o | fie | tw |
1040