Standby Generator Maintenance Checklist

Checklist for standby Generator

Uploaded by

arunputhussery
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
179 views3 pages

Standby Generator Maintenance Checklist

Checklist for standby Generator

Uploaded by

arunputhussery
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd

Table 1. Standby generator maintenance checklist.

Maintenance Frequency
Component Action Bi-
Weekly Monthly Annually
Annually
Run generator with no load for several
minutes until operating temperature is
X
achieved; verify control function and look
for alarms, warnings, or indicator lights.
Inspect engine, radiator, and generator for
debris, as well as for loose or broken X
fittings, hoses, wires, and guards.
Electric Generator
Run the system for 1 hour under a full
building load initiated by ATS. Record
the system operating parameters (e.g.,
X
coolant temperature, oil pressure, battery
voltage, and generator alternating current
voltage).
Perform load bank test. X
Fuel System Check fuel tank to assure levels are
adequate and, if present, drain water from X
filter bowl.
Assure there are no fuel or other fluid
X
leaks.
Inspect accessible areas of fuel tank for
damage and corrosion. Verify that
X
emergency vent components move freely
and are not obstructed (all tanks) .
Replace fuel filter(s). X
Inspect fuel hose, replace if necessary. X
Check oil level and inspect system
X
components for leakage.
Sample oil. X
Grease generator bearing (if applicable). X
Lubrication System
Replace oil and oil filter (based on oil
sample results) and inspect system X
components.
Replace engine oil hoses if necessary. X
Inspect hoses and belts, replacing if
needed, and verify that the engine block X
heater is operating properly.
Check engine coolant level. X
Check coolant lines and connections. X
Check coolant condition with kit/test
Cooling System X
strip, replace if needed.
Inspect and adjust belts, verify engine
block heater is operating, check radiator
cap (replace cap if gasket is cracked or
X
damaged), clean exterior of radiator,
inspect fan shroud, and inspect system
components.
Starting System Assure that the generator is in “Auto”
X
mode for automatic start-up.
Clean battery connections and apply
corrosion inhibitor. Check starter motor
X
and charger connections and inspect
system components.
Check battery electrolyte level and
X
specific gravity.
Inspect and clean engine speed timing X
sensor.
Perform visible emissions observation. X
Clean crankcase breather and inspect
X
Exhaust System system components.
Inspect exhaust system, muffler, and
X
exhaust pipe.
Check that the generator’s circuit breaker
X
is closed.
Clean out electrical boxes, panels, and
Electrical System X
alarm boxes. Inspect wiring.
Inspect and clean ATS contacts and
X
wiring.
Inspect air intake system. Replace filter if
Air Intake System X
needed.
Record all run hours. Upon activity completion
System Document all maintenance activities in
Documentation log book or electronic computerized Upon activity completion
maintenance management system.