Irps
Topics covered
Irps
Topics covered
369302e 1 03.15.21
Description
The GRX-IRPS Partition Sensor uses an infrared
transmitter/receiver pair to detect partition movement
and, in conjunction with other Lutron products,
coordinates lighting preset functions in areas such as
partitioned meeting rooms or ballrooms. The
GRX-IRPS may be used with Athena, Quantum,
Energi Savr Node, GRAFIK Eye QS, GRAFIK 3000,
and GRAFIK 4000 systems.
Features
• Automatically combines lighting preset functions
when partition is open creating one large space.
• Lighting preset functions become independent as
partition is closed creating several smaller spaces.
• For operation with Quantum and Athena systems,
the GRX-IRPS requires either an interface (QSE-IO)
or wallstation with contact closure input (QSWS2-,
QSWA-, or similar) and a power supply (GRX-12VDC
or PP-DV).
• For operation with GRAFIK Eye QS or Energi Savr
Node systems, the GRX-IRPS requires an interface
(QSE-IO) and a power supply (GRX-12VDC
or PP-DV).
• For operation with GRAFIK Eye 3000 / 4000 system,
the GRX-IRPS requires an interface (GRX-IO) and a
power supply (GRX-12VDC or PP-DV).
Job Number:
GRAFIK Systems GRX-IRPS-WH Accessories
369302e 2 03.15.21
Specifications
Power Connection
• Operating voltage: Low-voltage PELV (Class 2: USA) • Wire leads provided.
12 – 24 V-, 135 mA.
Finish
– Lutron recommends using a GRX-12VDC plug-
in power supply or a PP-DV power supply (both • White painted plastic.
ordered separately). Environment
∙ One GRX-12VDC can supply power to eleven
• 32 °F – 104 °F (0 °C – 40 °C). Relative humidity less
sensor transmitter / receiver pairs.
than 90% non condensing.
∙ One PP-DV can supply power to one sensor
transmitter / receiver pair. Mounting
• Transmitter and receiver have reverse polarity and • Surface mount indoors only.
short-circuit protection.
Sensor Status Indicator
• Receiver and transmitter includes an LED indicator
that assists in sensor alignment during installation and
provides sensor operating status.
– Transmitter LED will be green when properly
powered and transmitting
– Receiver LED will be orange when receiving beam
and not illuminate when blocked.
System Capacity
• Each GRX-IO or QSE-IO Interface (prefix QSWS2-,
QSWA-, or similar; ordered separately) can accommodate
up to five GRX-IRPS partition sensors for five different
moveable walls.
• Each seeTouch wallstation (ordered separately) can
accommodate one GRX-IRPS partition sensors for one
moveable wall.
• Contact closure output from GRX-IRPS is configurable
to normally open or normally closed from receiver unit.
Job Number:
GRAFIK Systems GRX-IRPS-WH Accessories
369302e 3 03.15.21
• Receiver and transmitter surface mount in 1-gang U.S. wallboxes 3.5 in (89 mm) deep, mounted facedown from
the ceiling. Indoor use only.
• The sensors must be mounted in a position where the partition separates the transmitter and receiver when the
partition is closed.
• Transmitter and receiver may be located no more than 8 ft (2.43 m) apart.
• Adjustable mounting brackets allow easy alignment during installation.
• Wires feed through the back of the transmitter / receiver.
Side View
Standard single-gang U.S. wallbox mounted facedown and
flush with ceiling surface (typical of two).
Ceiling
1.5 in (38 mm)
GRX-IRPS-WH GRX-IRPS-WH
Transmitter Receiver
Partition
8 ft (2.43 m) maximum
Top View
Single gang wallbox
(typical of two)
Wallbox mounting
line of center
Job Number:
GRAFIK Systems GRX-IRPS-WH Accessories
369302e 4 03.15.21
System Diagrams
Ceiling
GRX-IRPS GRX-IRPS
Transmitter (TX) Receiver (RX)
(GRX-12VDC
Room A Room B or PP-DV)
Partition
1 21 2
3 43 4
CCI 1
P/N 500-10728
COM
CCI 45
CCI 34
CCI 23
CCI 12
P/N 500-10728
COM
5
CCI
CCI
CCI
CCI
CCI
V+
MUX
COM
MUX
V+
MUX
COM
MUX
5 COM
NO
NO
1-2 COM
3-4 COM
CCO 5 NO
4 NC
CCO 1 NO
CCO 3 NC
NC
CCO 5 NC
CCO 4 NO
CCO 1 NC
5 COM
3 NO
CCO 2 NO
COM
3-4 COM
5 NO
NC
CCO 1 NO
3 NC
2 NC
NC
CCO 4 NO
CCO 1 NC
CCO 3
CCO 2
1-2 2
CCO
CCO
CCO
CCO
CCO
CCO
CCO
CCO
Wallstations R
R
V V
V V
0-240-24
V V 1A 1A
0-240-24
V V ½A½A
R
R
GRX-IO
GRX-IO
24 V 200 mA
24 V 200 mA
Wallstations
800.523.9466
800.523.9466
+1.610.282.3800
+1.610.282.3800
www.lutron.com
www.lutron.com
CCO 1
1 2
2 3
3 4
4 5
STAT
CCO
CCO
CCO
CCO
CCO 5
1 2 34 56 78
STAT
CCO
CCO
CCO
CCO
1 2 34 56 78
N
PGM O
N
PGM
4.022" x 5.017"
Lutron
11-21 -07
GRX-IO
BLACK
Ceiling
GRX-IRPS GRX-IRPS
Transmitter Receiver
(GRX-12VDC
or PP-DV)
Room B
Room A
Partition
To CCI1-5
Quantum hub or
Energi Savr Node Athena hub2
QSE-IO
CCO 5
CCO 4
CCO 3
CCO 2
CCO 1
STAT
O
N
8 7 6 5 4 3 2 1
QSE-IO-
24 V 200 mA
Wallstation Wallstation
800.523.9466
R V R
V 0-24 V 1A
0-24 V ½A
CCO 4 NO
CCO 1 NO
CCO 5 NO
CCO 1 NC
CCO 2 NC
CCO 3 NC
CCO 5 NC
CCO 2 NO
CCO 3 NO
CCO 4 NC
3-4 COM
1-2 COM
QS
COM
MUX
MUX
COM
CCI 1
CCI 2
CCI 3
CCI 4
CCI 5
V+
LUTRON
Job Number:
GRAFIK Systems GRX-IRPS-WH Accessories
369302e 5 03.15.21
CCO 5
CCO 4
CCO 3
CCO 2
CCO 1
STAT
O
N
8 7 6 5 4 3 2 1
A
Wiring Diagrams ®
QSE-IO-
GRAFIK Eye 3000 and 4000 Systems 24 V
800.523.9466
+1.610.282.3800
200 mA
www.lutron.com/qs
243C IND. CONT. EQ.
GRX-IO
R V R
V 0-24 V 1A
0-24 V ½A
CCO 4 NO
CCO 1 NO
CCO 5 NO
CCO 1 NC
CCO 5 NC
CCO 2 NC
CCO 3 NC
CCO 2 NO
CCO 3 NO
CCO 4 NC
3-4 COM
1-2 COM
5 COM
COM
CO
MUX
MU
MU
MUX
COM
C 1
CCI
CCI
C 2
C
CCI 3
C
CCI 4
C
CCI 5
V+
V
4 3 2 1
Ceiling
GRX-IRPS GRX-IRPS
Transmitter (TX) Receiver (RX)
Room A Room B
Partition
Note: Diagram represents a single partition. A GRX-IO will accomodate up to five GRX-IRPS partition sensors (five partitions). A single GRX-12VDC will
power up to eleven GRX-IRPS partition sensors.
Note: The GRX-IO is programmed for partition mode. Set input closures for maintained inputs (refer to the GRX-IO installation instructions).
CCO 5
CCO 4
CCO 3
CCO 2
CCO 1
STAT
O
N
8 7 6 5 4 3 2 1
A
QSE-IO-
Athena, Quantum, Energi Savr Node, and GRAFIK Eye QS Systems 24 V 200 mA
800.523.9466
+1.610.282.3800 243C IND. CONT. EQ.
www.lutron.com/qs
V
V
0-24 V
R
1A
QSE-IO
0-24 V ½A
CCO 4 NO
CCO 1 NO
CCO 5 NO
CCO 1 NC
CCO 5 NC
CCO 2 NC
CCO 3 NC
CCO 2 NO
CCO 3 NO
CCO 4 NC
3-4 COM
1-2 COM
5 COM
QS
CO
COM
MUX
MU
MU
MUX
COM
C 1
CCI
CCI
C 2
C
CCI 3
C
CCI 4
C
CCI 5
V
V+
4 3 2 1
Black
PP-DV
Black (Line/Hot)
Blue Black (Common) White (Neutral)
Brown Red (24 V-)
Red
Blue (Control)
Red
Blue Brown
Ceiling
GRX-IRPS GRX-IRPS
Transmitter (TX) Receiver (RX)
Room A Room B
Partition
Note: Diagram represents a single partition. A QSE-IO will accomodate up to five GRX-IRPS partition sensors (five partitions). A single PP-DV will power
one GRX-IRPS partition sensor.
Note: The QSE-IO is programmed for partition mode. Set input closures for maintained inputs (refer to the QSE-IO installation instructions).
The Lutron logo, Lutron, Athena, GRAFIK Eye, Energi Savr Node, GRAFIK Systems, Quantum, and seeTouch are trademarks or registered trademarks of Lutron Electronics Co.,
Inc. in the US and/or other countries.
Job Number: