Chilled Water System Flow Calculations

The document outlines calculations for flow rates in a chilled water system, using formulas to determine GPM based on temperature differences and tonnage. It specifies conditions for pipe sizes, including velocity and head loss considerations. Additionally, it provides capacity values for various pipe sizes and their corresponding GPM rates.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
26 views1 page

Chilled Water System Flow Calculations

The document outlines calculations for flow rates in a chilled water system, using formulas to determine GPM based on temperature differences and tonnage. It specifies conditions for pipe sizes, including velocity and head loss considerations. Additionally, it provides capacity values for various pipe sizes and their corresponding GPM rates.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Flow M = lb/hr

Q = M Cp dT

Tr x 12000 = GPM x 500 x 1 x dT

Tr x 24 = GPM x dT

GPM = Tr x 24 / dT

dT = CWR - CWS

dT = 55 - 45 = 10F

GPM = Tr x 24 / 10

GPM = TR x 2.4

If Pipe Size < 2" = 4 FPS Vel

If Pipe Size > 2" = 4ft/100' Head Loss

Closed Piping = Chilled Water System GPM = Tr x 2.4

1 1/2" 1" 3/4" 2 1/2" Capacity 25 TR


10TR 5TR 3TR 25TR
24GPM 12 GPM 7.2 GPM 60 GPM GPM = 60

103.2 GPM 79.2 GPM 67.2 GPM 60 GPM


3" 2 1/2" 2 1/2" 2 1/2"

Draw Line on Vel - 4ps - Chk Pipe Size if less then 2" then OK

OR if >2" then draw another line of Friction - 4ft/100'