1. Non Central AC
2. Package AC
3. VRV System
HE b/w Room Air and Sec Ref (Water) is kwn as CHW System
Air Cooled System : Ref in Condensor is cooled by Air (Atm Air) with help of Fan
Water Cooled System: Ref in Condensor is cooled by Water and then water is cooled by CT
DX System
A/C & W/C
SA / RA / FA
Capcity > 5TR
Mixing Chamber
SA / RA
Capcity < 5Tr
RA
FAHU / FAFCU
FA
Types of Chiller
Condensor Side
Evap Side
Comp Side
Chiller Selection:
Inputs:
1. BLG Load : 95 TR
2. Ambient Temp: 106 F
3. LWT of Chiller : 44F
Output:
1. Model No RTA 110
2. KW 102.8
3. EER 10.4
4. Size 5.62 x 2.24 x 2.2 m
5. Wt of Chiller 924 kg
6. Losses in Chiller 14 ft of wg
Primary Ref - Change of Phase - R134a, R22
Evap Cond
Evap Cond
SEC REF
CWS - 45F (6.6c)
PR Ref
Chiller
r) with help of Fan
CHW System
A/C & W/C
SA
Filter
pes of Chiller
A/C & WC
3 ch 2ch 1ch
BLG Load is 375 TR 125 187.5 375
Selecting Chiller : 3 W + 1SB
DX Chiller
3-Way Valve
23.31002 HP
SP - BLG Load
23.31002
10.20
HP
CHW Pipe Sizing
Chiller
Q = M Cp dT
GPM = TR x 24 / dT
GPM = TR x 2.4
Chiller - CT
GPM = TR x 3
Volume of System
1. Chiller
2. Pipes (CHWS / CHWR)
3. AHU / FCU / FAHU
Pump Head Calculation Flow of BLG = 96 GPM
Pump Selection - Flow & Head In Case one working one Standby the each Pump F
Flow - Chiller - BLG = GPM = TR x 2.4 In Case two working then each Pump Flow is 96 G
Head Calculation -
DH = 3M…?
SH = 15M
A/C
W/C
Q = M Cp dT
15000 Btu/hr
Q = M Cp dT
30 x TR = GPM x dT
GPM = 30 x TR / dT
750 GPM
Q = M Cp x dT
GPM x 8.33 = Lb/min
M= Mass flow Rate (Lb/min)
M = 750 x 8.33
M= 6247.5 Lb/min
Cp = 1 BTU/Lb.F
dT = 96-86 = 10F
Q = M Cp x dT
dT =
hwr = 96 F = 35.5 C
hws = 86 F = 30 C
dT = 35.5-30 = 5.5C
0.11
Bleed Off = 0.22 / ( 3-1)
0.11 M3/Hr
6.6 M3
6600 Lits
Inputs:
TONS = 40 TONS
WB = 78 F
3gpm / ton
Model No:
CSA - 610
Tower
Condensor HWS
Coil
HWR
Basin
HWS= HWR + 8 TO 10 F
EXAMPLE =78f
HWR = 78 +8 = 86F
HWS = 86 + 10 = 96 F
30
TR x 3 = GPM
312.35
10F
0.227205