AIR CONDITIONING SYSTEM

PAN HUMIDIFIER LOAD CALCULATION

BUILDING
S.No. DESCRIPTION UNIT
ROOM1

1 Design Room Condition

- Temperature [°C] 24

- Relative Humidity [%} 50


Anticipated condition for Pan
2
humidifier sizing
- Temperature [°C] 24

- Relative Humidity [%} 45


Absolute humidity of air at design
3 [Kg/m3] 0.0109
room condition
Absolute humidity of air at
4 [Kg/m3] 0.0098
anticipated condition
Moisture to be added to increase
5 the humidity to maintain the [Kg/m3] 0.0011
design condition.
[CFM] 30600
6 Air Flow rate in supply air header
[m3/hr] 51989.73

7 Humidification load [kg/hr] 57.19

8 Heater capacity calculated [KW] 4.36

9 Pan Humidifier capacity selected [KW] 6