You are on page 1of 1

KITCHEN VENTILATION FOR FOOD COURT

SERIAL

FLOOR NAME

TOTALAREA

HEIGHT

M2

ZONE NAME

KITHEN AREA

EXTRA HEAVY DUTY

NORMAL DUTY

TOTAL EXHAUST

TOTAL SUPPLY MAKE UP

EXH.FAN

0.8 AREA

0.3 KITCHEN AREA

0.7 KITCHEN AREA

(112 X EXTRA) + (75 X NORMAL)

0.8 CFM

1.10%

FC-01

65.5

5.6

216

52

16

37

4512

3609

FC-02

65.5

5.6

216

52

16

37

4512

3609

FC-03

71

5.6

234

57

17

40

4890

3912

FC-04

34

5.6

112

27

19

2342

1874

FC-05

34

5.6

112

27

19

2342

1874

FC-06

34

5.6

112

27

19

2342

1874

FC-07

34.5

5.6

114

28

19

2376

1901

FC-08

105

5.6

346

84

25

59

7232

5786

FIRST

1
2

SUPPLY FAN

ONE A/C

FC-09

67

5.6

221

54

16

38

4615

3692

10

FC-10

69

5.6

227

55

17

39

4753

3802

11

FC-11

34.5

5.6

114

28

19

2376

1901

12

FC-12

34.5

5.6

114

28

19

2376

1901

13

FC-13

34.5

5.6

114

28

19

2376

1901

14

FC-14

34.5

5.6

114

28

19

2376

1901

15

FC-15

68.5

5.6

226

55

16

38

4718

3775

16

FC-16

65.5

5.6

216

52

16

37

4512

3609

17

FC-17

65.5

5.6

216

52

16

37

4512

3609

EXH-FAN 15300 CFM

SF-11000

EXH-FAN 7800 CFM

SF-5700

EXH-FAN 10500 CFM

SF-7700

EXH-FAN 13000 CFM

SF-9400

EXH-FAN 7800 CFM

SF-5700

EXH-FAN 15300 CFM

SF-11000