You are on page 1of 1

CHILL WATER PIPING

S.no

Header
Section

Water
Qty.

Pipe
Size

Length
between

GPM

(in)

take off (ft)

Fittings

Fitting
Equivalent

Total
Equivalent

Frictional Loss

Length (ft)

Length (ft)

(ft of water per


100 equiv ft)

Friction
Head
(ft of
water)

Riser
1

0-1

457

2+13 = 15

2 -el

2 x 13 = 26

41

3.28

1 to 2

325

14

14

1.12

2 to 3

188

14

14

1.12

3 to 4

97

2 1/2

14

14

1.12

A-B

457

10

1-p +1-gv

8+6 = 14

24

1.92

C-D

132

12+2 = 14

1-tee+1-gv+1-el

15+3.2+7.5 = 25.7

39.7

3.17

E-F

137

12+2 = 14

1-tee+1-gv+1-el

15+3.2+7.5 = 25.8

39.7

3.17

G-H

89

2 1/2

12+2 = 14

1-tee+1-gv+1-el

12+2.8+6 = 20.8

34.8

2.78

I-J

97

2 1/2

12+2 = 14

1-tee+1-gv+1-el

12+2.8+6 = 20.9

34.8

2.98

Header

77 | P a g e