ELECTRCIAL ROOM VENTILATION SYSTEM CALCULATION

Room Length (m) = 5.32

Room Width (m) = 2.5

Room Height (m) = 3.5

Room Volume (m3) = 46.55

Heat Load (kW) = 2

Outside Design Dry Bulb


= 43
Temperature (°C)

Temperature Range (°C) = 5

Specify Heat of air (kJ/kg °C) = 1.005

Density of air (kg/m3) = 1.11

Required Air Change Per Hour


= 15
(ACPH)

Calculations :-
Airflow (m3/s) Heat load
=
Air density X Specific Heat X Temperature difference

2
=
1.11 X 1.005 X 5
= 0.3585675227
Airflow (m3/hr) 1291
Ventilation Airflow (m3/hr) = Room Volume X ACPH

= 46.55 X 15
= 698

Selected Ventilation Airflow 1395 CMH (821 CFM) considering 10% safety factor.

Note - The ventilation airflow is based on maximum room temperature rise of 5°C above ambient dry bulb temp
minimum 15 air changes per hour whichever is maximum.