AIR CONDITIONING SYSTEM

PAN HUMIDIFIER LOAD CALCULATION


BUILDING
S.No.

DESCRIPTION

UNIT

ROOM1

Design Room Condition


- Temperature

[C]

24

- Relative Humidity

[%}

50

- Temperature

[C]

24

- Relative Humidity

[%}

45

Anticipated condition for Pan humidifier


sizing

Absolute humidity of air at design room


condition

[Kg/m3]

0.0109

Absolute humidity of air at anticipated


condition

[Kg/m3]

0.0098

Moisture to be added to increase the


humidity to maintain the design
condition.

[Kg/m3]

0.0011

[CFM]

30600

[m3/hr]

51989.73

[kg/hr]

57.19

Air Flow rate in supply air header

Humidification load

Heater capacity calculated

[KW]

4.36

Pan Humidifier capacity selected

[KW]