Professional Documents
Culture Documents
Project : Altus 23
Location : Balewadi
Total 868195
Note: -
Taxes At Actual
BILL OF QUANTITIES FOR BASEMENT VENTILATION
Supply of Ductless Ventilation Jet fans of dual speed for Normal ventilation and Smoke
Extraction application for car parking. The complete fan assembly with its Casing, impeller
& motor (not only the motor or one of the item) shall be sourced from one manufacturer and
certified as tested for 300 Φ and suitable for 3000C for 2 hours operation. Adequate
number of CO2 sensors,electrical starter panels with fire rated power / control cabling for 3
phase fans and logic controller with necessary control cabling will form a part of the same.
The Rating with 6000 /3000 CFM for Fire and Normal Mode . System shall be designed for
2 Jet Fan 6 ACPH in normal condition and 12 ACPH in emergency condition. Nos. 4 37500 150000
Supply of MCC Electrical Panel made out of 2/1.6 mm CRCA sheet finished with Siemens
Grey powder coated painting and degree of protection - IP-54. Panel complete with Built in
PLC, MCB/MPCB Feeders and Starters for Jet Impulse fans with dual speed, Exhaust air
Axial fans. All Jet Impulse Fans, Fresh air and Exhaust air Fans are controlled through CO2
level feedback by individual MCC Panel's PLC. All panels shall be floor mounted and top
cable entry, suitable incomer MCCB, aluminum bus bar and custom built microprocessor
logic controller with necessary control wiring etc. Each feeder shall have TPN MCB, two
ELECTRICAL starters and indication lamps, toggle switch for two speed operations and PLC logic
3 CONTROL PANEL controller with necessary internal control wiring etc.This panel auto operated based on Fire
WITH PLC: alarm Panel I/O ports ,consider the I/O port connections from FAS panel.
Basement
Ventilation Control
Supply of Electrical panel including incomer mccb ryb indicating lamp load manager with
Panel for all
RJ-48 24 v /10A power supply, outgoing starters with mcb , contactor and overload relay &
equipment's
Programmable Controller with HDMI and ethernet /modbus port to communicate for
3.1 ( Nos. 1 65000 65000
basement panels with all electrical protections.The control panel consist of main Incomer
EXHAUST/FRESH
swithchgear and control equipment for auto operation for all Ventillation equipment based
FANS/JET
on Co2 sensor inputs refer drawings for Modes of Operation.
FANS/CO2
SENSOR)
CARBON DIOXIDE Supply of CO2 Smoke Detector ( CO2 SENSORS ) & 24VDC Power Supply for CO2
4 Nos. 2 12450 24900
-CO2 SENSOR sensor
BILL OF QUANTITIES FOR BASEMENT VENTILATION
Supply of Fire and smoke damper electric actuators are operation in Start the Axial Fan
combination for fire and smoke dampers in ventilation systems with maximum safety in all
situations, the fire and smoke actuators all codes operating for commercial buildings in
6 Motorised Damper tested for 30,000 open-closed cycles with approved dampers. Fire damper blades shall be Sqmt 4 13700 54800
one piece folded high strength galvanised steel construction. In normal position, these
blades shall be gathered and stacked at the frame head providing maximum air passage and
preventing passing air current from creating noise chatter.
Supplying of alluminium powder coated louvers for fresh air and exhaust air for ground
7 LOUVERS Sqmt 12 4500 54000
floor
8 MS(Mild Steel) Supplying of MS fabrication frame work to install the Axail Fan in the cut out provided . Kg 60 140 8400
Supplying, erecting & terminating PVC armoured cable 6 core 4sq mm copper
conductor and (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/
Cable for Exhaust
9 trusses/pole or laid in provided trench/ pipe as per specification for Fire mode Axial Fan Mtr. 84 360 30240
Air Axial Fan
Supply of Power & control Armoured Copper cabling between panel & equipment with 1.5
11 Jet Fans Mtr. 50 130 6500
Sqmm with 6 core for Jet Fans .
Supply of Power & control Flexible Copper cabling between panel & equipment with 1
12 Co2 Mtr. 25 110 2750
Sqmm with 3 core for Co2 .
Supplying of UTP networking Cat-6 cable suitable for LAN / WAN Computer net-working
Panel Cable for as per specification No. WG-COC/NC
13 Mtr. 100 280 28000
lopping to controller
Supplying of EARTHING for Axial Fan 8 SWG Single GI Wire/ 6 Sq mm Single core
14 GI Erthing Mtr. 20 140 2800
copper Umarmoured FRLS Wire
CFD Certification CFD Anaylsis to be Presented by Supply or Manufauture to the consultants befor
15 Lot. 1 34000 34000
from Manufacturer instalation at site for Basement Ventilation System.
Total 730830
Note: - Smoke Test should be conducted After complition of site for proformance of the system
BILL OF QUANTITIES FOR BASEMENT VENTILATION
Sr.
DESCRIPTION Unit Qty Rate Total Amount
No.
Installing, testing and commissioning of Dual Speed smoke spill fans as per specifications.Fan
shall be direct driven tube/vane axial fan.Fan and casing shall be suitable for smoke exhaust
application.Motor and belt drive shall be mounted outside ,so that it is not exposed to smoke stream
Exhaust Air Axial
& thermally rated for 3000C for 2 hours as per [BS EN 12101-3:2002] Class-B. Motors shall be
1 Fan ( Normal/ Fire
suitable for 415+10% volts, 50 cycles , 3 phase AC supply an static pressure shall be as indicated .
Mode )
Fans shall be activated from fire signal from fire alarm system/Co sensor .Fan shall be with flexible
fire proof flexible connection at inlet and outlet along with mounting clits, grouting frame, spring
hanger etc.
Installing, testing and commissioning of of Ductless Ventilation Jet fans of dual speed for Normal
ventilation and Smoke Extraction application for car parking. The complete fan assembly with its
Casing, impeller & motor (not only the motor or one of the item) shall be sourced from one
manufacturer and certified as tested for 300 Φ and suitable for 3000C for 2 hours operation.
2 Jet Fan Nos. 4 6500 26000
Adequate number of CO sensors,electrical starter panels with fire rated power / control cabling for
3 phase fans and logic controller with necessary control cabling will form a part of the same. The
Rating with 6000 /3000 CFM for Fire and Normal Mode . System shall be designed for 6 ACPH in
normal condition and 12 ACPH in emergency condition.
Installing, testing and commissioning of of MCC Electrical Panel made out of 2/1.6 mm CRCA
sheet finished with Siemens Grey powder coated painting and degree of protection - IP-54. Panel
complete with Built in PLC, MCB/MPCB Feeders and Starters for Jet Impulse fans with dual speed,
Exhaust air Axial fans with VFD. All Jet Impulse Fans, Fresh air and Exhaust air Fans are
ELECTRICAL
controlled through CO2 level feedback by individual MCC Panel's PLC. All panels shall be floor
3 CONTROL PANEL 0
mounted and top cable entry, suitable incomer MCCB, aluminum bus bar and custom built
WITH PLC:
microprocessor logic controller with necessary control wiring etc. Each feeder shall have TPN
MCB, two starters and indication lamps, toggle switch for two speed operations and PLC logic
controller with necessary internal control wiring etc. This panel auto operated based on Fire alarm
Panel I/O ports ,consider the I/O port connections from FAS panel.
CARBON DIOXIDE Installing, testing and commissioning of of CO2 Smoke Detector ( CO2 SENSORS ) & 24VDC
4 Nos. 2 1250 2500
-CO2 SENSOR Power Supply for CO2 sensor
BILL OF QUANTITIES FOR BASEMENT VENTILATION
Sr.
DESCRIPTION Unit Qty Rate Total Amount
No.
Installing, testing and commissioning of of Fire and smoke damper electric actuators are operation
in Start the Axial Fan combination for fire and smoke dampers in ventilation systems with
maximum safety in all situations, the fire and smoke actuators all codes operating for commercial
6 Motorised Damper buildings in tested for 30,000 open-closed cycles with approved dampers. Fire damper blades shall Sqmt 4 1500 6000
be one piece folded high strength galvanised steel construction. In normal position, these blades
shall be gathered and stacked at the frame head providing maximum air passage and preventing
passing air current from creating noise chatter.
Installing, testing and commissioning of alluminium powder coated louvers for fresh air and exhaust
7 LOUVERS/GRILL Sqmt 12 1000 12000
air for ground floor
Installing, testing and commissioning of MS fabrication frame work to install the Axail Fan in the
8 MS(Mild Steel) Kg. 60 40 2400
cut out provided .
Installing, testing and commissioning of Power & control Armoured Copper cabling between panel
11 Jet Fans Mtr. 50 35 1750
& equipment with 1.5 Sqmm with 6 core for Jet Fans .
Installing, testing and commissioning of Power & control Flexible Copper cabling between panel &
12 Co2 Mtr. 25 35 875
equipment with 1 Sqmm with 3 core for Co2 .
Panel Cable for Installing, testing and commissioning of UTP networking Cat-6 cable suitable for LAN / WAN
13 Mtr. 100 60 6000
lopping to controller Computer net-working as per specification No. WG-COC/NC
Installing, testing and commissioning of Earthing for Axial Fan . 8 SWG Single GI
14 GI Erthing Mtr. 20 100 2000
Wire / 6 Sq mm Single core copper Umarmoured FRLS Wire
Total 137365
Note: -
Smoke Test should be conducted After complition of site for proformance of the system
Barnd's Of Material
8 LT Switchgear Schneider/ABB/Siemens/Eaton