BILL OF QUANTITY

Construction of Office Block at IIT Kanpur Outreach Centre NOIDA (SH: Air-conditioning Works).
Section -A
Name of Firm
ITEM DESCRIPTION UNIT QTY. RATE AMOUNT
1.0 EQUIPMENT

1.1 VRF OUTDOOR UNITS

Supply, Installation, Testing and Commissioning of air cooled variable


refrigerant flow modular type condensing units,each comprising of multiple
scroll compressors all inverter driven, full charge of refrigerant gas (R-410a),
lubricating oil and all accessories as per the specifications. The condensing units
shall be suitable to work on heating/ cooling mode. The minimum Energy
Efficiency Ratio shall be as per ASHRAE STANDARDS 90.1 -2001 table 6.2.1B . The
COP of the system shall be greater than 4 under ARI conditions for 100% load .
The condensing units shall be suitable for operation on 415 ± 10% volts, 50Hz, 3
phase AC power supply and the condensing units shall be of following
capacities:

16 HP (12.8 TR) nominal higher capacity No 1 0.00


18 HP (14.4 TR) nominal higher capacity No 3 0.00
26 HP (20.8 TR) nominal higher capacity No 1 0.00
54 HP (43.2 TR) nominal higher capacity No 1 0.00

NOTES:
The above mentioned outdoor units shall be provided with anti corrosion
treatment ( from factory). The quoted price shall be inclusive of same.

1.2 VRF INDOOR UNITS

Supply,Installation,Testing and Commissioning of variable refrigerant flow


modular type indoor units wired/wireless remote suitable for R410a refrigerant
comprising of all accessories as per the specifications. The indoor units shall be
suitable to work on cooling as well as heating mode.The minimum Energy
Efficiency Ratio shall be as per ASHRAE STANDARDS 90.1 -2001 table 6.2.1B.
The indoor units shall be suitable for operation on 220 ±6% volts, 50Hz, 1
phase AC power supply. Ductable indoor units shall be suitable to handle
extent of ductwork as shown in the design drawings and dehumidified air
quantity as mentioned in the heat load summary sheet under "Special
Conditions". The indoor unit shall be complete with pre filter & remote as per
requirement The indoor units shall be of following capacities:

a. Cassette Type Indoor Units


(with wired/ cordless control)

i. 3.2 TR nominal capacity No 9 0.00


ii. 2.6 TR nominal capacity No 8 0.00
iii. 2 TR nominal capacity No 6 0.00
iv. 1.6 TR nominal capacity No 8 0.00
v. 1 TR nominal capacity No 12 0.00

Page 1 of 10
ITEM DESCRIPTION UNIT QTY. RATE AMOUNT
1.3 CUSTOMISED VRF INDOOR UNITS
VERTICAL FLOOR MOUNTED AHU (FOR GROUND FLOOR)

Supply, Installation, Testing & Commissioning of sheet metal sectionalised


construction double skin air handling units with 46 mm thick injected PUF of
density not less than 40 Kg/CuM with thermal break profile. The air handling
units shall be complete with pre-filter section with synthetic fibre filters, coil
section with multirows deep DX heating/ cooling coil of copper tube & aluminium
fin construction, fan section complete with DIDW centrifugal fan with Factory
fitted VFD and MCB/ MCCB of appropriate rating with cable termination box,
suitable for total static pressure as detailed below, IE-02 squirrel cage induction
motor, belt drive package, insulated stainless steel drain pan and vibration
isolation arrangement all complete as per specifications. AHUs shall be selected
for a maximum face velocity of 500 FPM. The units shall be compatible with VRF
outdoor units.

The unit shall be supplied with electronic expansion valve/s (Dx), thermostat/s,
control wiring & all accessories as required for completing the installation. The
price shall be inclusive of these items. Fan outlet velocity shall not exceed 2000
FPM (10.2 MPS). AHUs shall be of following design parameters:

AHU Ref. Load Capacity SP No. of Motor


No. Nom. (Cfm) (mm WG) Rows Rating
(TR) (HP)
AHU-2 6.6 2500 35 4 1.5 No 2 0.00

1.4 VRF FRESH AIR TREATMENT UNIT - FLOOR MOUNTED (TFAU)

Supply, Installation, Testing & Commissioning of sheet metal sectionalised


construction double skin treated fresh air unit with 46 mm thick injected PUF of
density not less than 40 Kg/CuM with thermal break profile. The treated fresh air
units shall be complete withpre-filter (MERV-8), fine filter (MERV-13) coil section
with six rows deep DX cooling/heating coil of copper tube & aluminium fin
construction , fan section complete with floor standing backward curved DIDW
centrifugal fan with Factory fitted VFD and MCB/ MCCB of appropriate rating
with cable termination box, IE-02 squirrel cage induction motor, belt drive
package, insulated stainless steel drain pan and vibration isolation pads all
complete as per specifications. AHUs shall be selected for a maximum face
velocity of 500 FPM. The units shall be compatible with VRF outdoor units. The
unit shall be supplied with electronic expansion valve/s (Dx), thermostats, control
wiring & all accessories as required for completing installation. Fan outlet
velocity shall not exceed 2000 FPM (10.1 MPS).

AHU Capacity SP No. of Motor Ref.


No. (Cfm) (mm WG) Rows Rating(HP) Load Nom.
TFA -1 2100 50 6 2 16.5 TR No 3 0.00

1.5 Supply, Fabrication and Installation of MS frame using channels/angle iron


sections as required for mounting of air cooled remote condensers and air
cooled condensing units for VRF outdoor units. The frame work shall be applied
with red oxide primer and thereafter, two coats of enamel paint of
approved colour. The general arrangement drawing for frame work shall be got
approved from the Architects/Structural Engineers prior to commencement of
fabrication. KG 280 0.00

Page 2 of 10
ITEM DESCRIPTION UNIT QTY. RATE AMOUNT
1.6 COPPER PIPING (REFRIGERANT PIPING)

Supply, Installation, Testing & Commissioning of high pressure copper


refrigerant piping suitable for R 410a refrigerant of suitable size as required
and duly insulated with 19mm/13mm thick closed cell elastomeric insulation in
tubing form inclusive of glass cloth and UV treatment. External Refrigerant
piping shall be laid on GI covered cable trays. Piping inside occupied spaces
shall be supported using GI ladder type cable trays. The cost of GI covered cable
tray and supports to be included in the quoted price. Entire refrigerant piping
work be carried out in accordance with the specifications. Piping shall be of
following sizes:

Pipe Size Min. Wall Insulation


Size (O.D.) Thickness Thickness
a. 41.3 mm 1.43 mm 19 mm RM 50 0.00
b. 34.9 mm 1.21 mm 19 mm RM 40 0.00
c. 28.6 mm 1.00 mm 19 mm RM 250 0.00
d. 22.9 mm 1.00 mm 13 mm RM 180 0.00
e. 19.1 mm 1.00 mm 13 mm RM 100 0.00
f. 15.9 mm 1.00 mm 13 mm RM 240 0.00
g. 12.7 mm 0.80 mm 13 mm RM 260 0.00
h. 9.5 mm 0.80 mm 13 mm RM 330 0.00
i. 6.4 mm 0.80 mm 13 mm RM 70 0.00

1.7 FITTINGS

Supply, Installation , Testing and Commissioning of following imported fittings


to be provided in refrigerant pipe line. Material of construction for fittings shall
be similar to refrigerant piping.

a. Y- joints for refrigerant piping (pair). No 49 0.00

Drain Piping (CPVC)


1.8 Supply & installation, testing and commissioning of Rigid heavy class CPVC piping
complete with fittings, supports as per specifications and duly insulated with
6 mm thick closed cell crosslinked polyethylene (XLPE) tubular insulation.

a. 50mm dia RM 100 0.00


b. 40mm dia RM 110 0.00
c. 32mm dia RM 180 0.00
d. 25mm dia RM 110 0.00

1.9
CENTRALIZED REMOTE CONTROLLER (TOUCH SCREEN TYPE)
Central remote Controller (Touch Screen Type) : Supply, installation,
testing & commissioning of the Graphic central remote Controller. It must
act as an advanced air conditioning management system to
facilitate complete control of VRF air conditioning equipment, It should be
user friendly through its touch screen, icon display and color LCD display.
Integratable upto 64 remote controller groups (including AHUs & TFAs)
and BMS compatible with ethernet/Wi-Fi communication protocol for
remote monitoring. In addition to basic controls such as settings for No 1 0.00
on/stop,the operation mode & temperature,the air quantity and auto louver
can be set.If a problem occurs, an alarm code immediately shows the
details of the problem.An external input terminal is provided as
standard.External signals enable the following function: central
operation/stop,demand control,emergency stop,central operation output,&
central alarm output.

TOTAL CARRIED TO SUMMARY (EQUIPMENT) Rs. 0.00

Page 3 of 10
ITEM DESCRIPTION UNIT QTY. RATE AMOUNT

2.0 AIR DISTRIBUTION

2.1 Ductwork

a. Factory Fabricated Ductwork

Supply, Installation, Testing of factory fabricated ductwork complete with fire


retardant gaskets, slip on flanges, wire rope suspension arrangement, GI
perforated 'C' channel supports etc. in accordance with the approved shop
drawings and specifications.

a. 1mm-550mm (26 gauge) GSS ( C&SS) SqM 310 0.00


b. 551mm-750mm (26 gauge) GSS (TDC/TDF/SLIPON) SqM 120 0.00
c. 751mm-1000mm (24 gauge) GSS (TDC/TDF/SLIPON) SqM 120 0.00

b. Conventional site fabricated ducts using Lock Forming Machines / closing


machine

Supply, Installation, Testing of factory fabricated ductwork complete with fire


retardant gaskets, slip on flanges, wire rope suspension arrangement, GI
perforated 'C' channel supports etc. in accordance with the approved shop
drawings and specifications.

a. 0.47 mm (26 gauge) GSS SqM 100 0.00


b. 0.63mm (24 gauge) GSS SqM 90 0.00

2.2 Supply, Installation and Testing of 125mm deep Antivibration Flexible Joints
made out of imported fire retardant fabric with extruded aluminium frame/
flange on both sides of approved make. RM 10 0

2.3 Supply, Installation and Testing of multi blade type key operated louver
dampers of galvanised steel sheet for collars to be provided with suitable
links, levers and quadrants for manual control of volume of air flow and for
proper balancing of the air distribution system as per the approved shop
drawings and specifications. SqM 5 0

2.4 Supply, Installation and Testing of multiblade box type galvanised steel
sheet dampers for ducts to be provided with suitable links, levers and
quadrants for manual control of volume of air flow and for proper
balancing of the air distribution system as per the approved shop drawings
and specifications. SqM 2 0

2.5 Supply, Installation, Testing & Commissioning of smoke cum fire dampers of at
least 90-120 minutes fire rating as per the approved shop drawings &
specifications. Interlocking of fire dampers using copper control wiring and
requisite relays with existing AHU starter panel shall be affected as required.

a. Bare fire dampers SqM 1 0

b. Actuator with control panel, temperature sensor and spring return action
and suitable for 10-12 NM Torque. No 5 0

Page 4 of 10
ITEM DESCRIPTION UNIT QTY. RATE AMOUNT

2.6 Supply, Installation, Testing & Balancing of square supply air diffusers as per the

approved shop drawings and specifications with fixed air distribution grid,

removable key-operated volume control damper. The diffusers shall be anti-


smudge ring/flush type.

Powder coated extruded aluminium diffusers of approved colour & shade of


following sizes:

a. 600 x 600 diffusers with volume control damper having neck size as mentioned
in the "Approved for Construction" shop drawings suitable for fixing in gypsum No. 15 0
ceiling.
b. 300 x 300 diffusers with volume control dampers having neck size as
mentioned in the "Approved for Construction" shop drawings suitable for fixing No. 5 0
in gypsum ceiling.

2.7 Supply, Installation, Testing & Balancing of square diffusers same as supply air
diffusers but without volume control dampers for return air as per the
approved shop drawings & specifications.

Powder coated extruded aluminium diffusers of approved colour & shade of


following sizes:

a. 600x 600 diffusers . No. 10 0


a. 300x 300 diffusers . No. 5 0

2.8 Supply, Installation, Testing and Commissioning of pre-insulated factory


fabricated semi-rigid flexible ducts of aluminium construction duly supported at
regular interval as per site requirement . Ducts shall be of following sizes:

a. 150mm dia RM 20 0
b. 100mm dia RM 140 0

2.9 Supply, Installation, Testing and Balancing of one way blow linear supply cum
return air grilles complete with removable inner core as per approved shop
drawing and specifications. The grilles shall be of approved colour & shade.

a. Powder coated aluminium grille of extruded sections with integral flanges on


both sides & ends as required.

i. 100/150/200 mm High SqM 10 0

2.10 Supply, Installation and Testing of extruded aluminium powder Coated air trasfer
grilles to be provided at the doors.
SqM 1.5 0

2.11 Supply, Installation and Testing of fresh air grilles of powder coated /anodised
extruded aluminium with filters, inlet louvers dampers and bird screen, as per
approved shop drawings and specifications.
SqM 1 0

2.12 Supply,Installation, Testing and Balancing of spigots factory fabricated out of

galvanised steel sheet of different sizes to facilitate flexible duct connection.

a. 150mm dia No 10 0
b. 100mm dia No 45 0

Page 5 of 10
ITEM DESCRIPTION UNIT QTY. RATE AMOUNT

TOTAL CARRIED TO SUMMARY (AIR DISTRIBUTION) Rs. 0

Page 6 of 10
ITEM DESCRIPTION UNIT QTY. RATE AMOUNT

3.0 INSULATION

3.1 Supply and Application of internal acoustic/ thermal insulation of ducting

using open cell elastomeric insulation with adhesive, longitudinal &

transverse joints sealed with adhesive in neat & clean manner.


a. 15 mm thick SqM 200 0
b. 10 mm thick SqM 50 0

3.2 Supply and installation of aluminium foil faced closed cell elastomeric nitrile
rubber thermal insulation exhibiting class"O" properties on supply and return air
ducts with sealing of longitugnal and transverse joints with SR-505 adhesive as
per the approved specifications. Quoted price shall be inclusive of adhesive,
tapes as per specification.

a. 16mm thick SqM 450 0


b. 9 mm thick SqM 90 0

3.3 Supply and Application of thermal/acoustic lining of walls & ceiling of AHU
enclosure or insode ducts using fibreglass board having density not less than 80
Kg/CuM, laminated with aluminium foil on one side and three layers of black
glass cloth on the other side.

a. 25 mm thick SqM 100 0

TOTAL CARRIED TO SUMMARY (INSULATION) Rs.


0

Page 7 of 10
ITEM DESCRIPTION UNIT QTY. RATE AMOUNT

4.0 ELECTRICAL INSTALLATION

4.1 POWER CABLING

Supply, laying, affecting connections and Testing of the following sizes of


1.1 KV armoured PVC insulated aluminium/ copper conductor cables. Cables
shall be inclusive of all clamps,saddles,screws,cable identification tags, cable
terminal joints including terminal lugs, insulating tapes, affecting terminal
connections to the equipment as per the specifications and as required.
Quoted price shall be inclusive of GI perforated cable tray, support.

a. 4C x 35 Sqmm cable (Copper) RM 20 0


b. 4C x 10 Sqmm cable (Copper) RM 80 0
c. 3C x 6 Sqmm cable (Copper) RM 10 0
d. 3C x 4 Sqmm cable (Copper) RM 50 0

4.2 CONTROL WIRING

Supply, laying, affecting connections and Testing of the following sizes of


control cum transmission wiring to be laid in MS conduits between indoor units
and outdoor units.

2C x1.5 Sqmm copper wiring RM 1800 0

4.3 EARTHING

Providing & fixing in position the following bare GI tape/ Cu wire including

providing all fixing accessories & effecting proper connections.

a. 25mm x 6mm tape RM 10 0


b. 25mm x 3mm tape RM 20 0
c. 8 SWG Cu Wire RM 40 0
d. 12 SWG Cu Wire RM 280 0
4.4
Supply & fixing, testing & commissioning of outdoor type IP-65 floor mounted
electrical distribution panel made of 2mm thick steel sheet duly power coated
complete with voltmeter ammeters, indicating lamps, selector switches, single
1 phase preventers, CTs, contractors, for remote control panel operation & 3 Phase
4 wire digital LCD type energy meter complete as per specification and drawing
etc as reqd. comprising of the following, the board shall be fabricated as per the
detailed specification enclosed. VRF AC Main Panel
A INCOMING
400A 4P MCCB 36 kA,415 volts , 50Hz, with door interlocking with all connected
accessories – .
1 no. 0-60 Amp. Ammeter with selector switch.
1 no. Volt meter with selector switch 0-500volts.
3 nos. RYB Led indication lamps.
1 nos. Energy meter.
B OUTGOING
100A FP MCCB 25kA - 2 Nos.
63A FP MCCB 25kA - 4 Nos.
32A FP MCCB 25kA - 8 Nos. No 1 0

TOTAL CARRIED TO SUMMARY (ELECTRICAL) Rs. 0

Page 8 of 10
ITEM DESCRIPTION UNIT QTY. RATE AMOUNT
SECTION : B - ANNUAL MAINTENANCE CONTRACT
ITEM DESCRIPTION UNIT QTY. RATE AMOUNT

5 ANNUAL COMPREHENSIVE MAINTENANCE OF THE


INSTALLED VRF SYSTEM FOR 5 YEARS

Annual Comprehensive Maintenance Contract for period of 5


years after completion of 1(one) year of DLP (Defect Liability
period). The contract shall include all spares ,cosumables &
replacement of defective/damaged parts as required to run the
completely installed VRF AC system including AHU's etc.
For 1st year (0-12 Months) per month 12 0.00
For 2nd year (13-24 Months) per month 12 0.00
For 3rd year(25-36 Months) per month 12 0.00
For 4th year(37-48 Months) per month 12 0.00
For 5th year(49-60 Months) per month 12 0.00
TOTAL COMPREHENSIVE MAINTENANCE FOR 5 YEARS Rs. 0.0

Page 9 of 10
IIT KANPUR EXT AT NOIDA SCHEDULE OF QUANTITIES

Construction of Office Block at IIT Kanpur Outreach Centre NOIDA


(SH: Air-conditioning Works).
SUMMARY OF COSTS
SECTION : A
ITEM DESCRIPTION AMOUNT (Rs.)

1. EQUIPMENT 0.00
2 AIR DISTRIBUTION 0.00
3 INSULATION 0.00
4 ELECTRICAL 0.00

TOTAL Rs. 0.00

SECTION : B - ANNUAL MAINTENANCE CONTRACT


ITEM DESCRIPTION AMOUNT (Rs.)

1 AMC cost FOR 5 years (After one year of DLP) 0.00

TOTAL Rs. 0.00

FINAL SUMMARY OF COSTS


ITEM DESCRIPTION AMOUNT (Rs.)

1. SECTION - A 0.00

2 SECTION - B 0.00

TOTAL RS. 0.00

GRAND TOTAL RS. 0.00