Project : KG Convention Hall @ Channarayapatna

Client : Kariyappa Gowda


Date : 05.04.2021
Version : R2
GENERAL NOTES
Note 1 Unless specified all works are for supply, installation, loading, unloading, testing, commissioning and balancing to be considered.
Note 2 All bill of quantities items are to be read in conjunction with drawings and technical specifications whether specified or not.
Note 3 Vendors shall submit the technical data sheet duly filled.
Note 4
Note 5

FIRST FLOOR MAIN HALL - Ducting & Accessories


Sl. RATE AMOUNT
DESCRIPTION UNIT QUANTITY
No: SUPPLY INSTALLATION SUPPLY INSTALLATION
1 G.S.S DUCTING as per SMACNA Standards.
All ducting shall be of factory fabricated completely finished and transported
to site in a 'L' form. GS sheet shall be Class VIII – with zinc coating of 120
gm / sqmt surface area. TDF type flanges with neoprene rubber gaskets of
thickness to match the dimensions of the ducts shall be used for connecting
two ducts. The cost of the duct shall include the threaded rod supports,
wired supports, angle flanges, anchor fastners, hot dipped galvanized bolts
and nuts etc.,
The Duct to be manufactured and assembled as per SMACNA standard for
Class-500pascals.
24G. Ducting Sqmt. 50 650 220 32,500 11,000
22G. Ducting Sqmt. 70 750 220 52,500 15,400
20G. Ducting Sqmt. 300 850 220 2,55,000 66,000
18G. Ducting Sqmt. 5 950 220 4,750 1,100
2 Site fabricated G.S.S DUCTING
SITC of site fabricated ducts as per site condition. The cost of the duct shall
include the threaded rod supports, angle flanges, anchor fasteners, hot
dipped galvanized bolts and nuts etc.,
24G. Ducting Sqmt. 10 720 220 7,200 2,200
22G. Ducting Sqmt. 10 820 220 8,200 2,200
20G. Ducting Sqmt. 20 920 220 18,400 4,400
18G. Ducting Sqmt. RO 1120 220
3 Round Duct
Round duct with single skin construction shall be of factory fabricated
completely finished and transported to site. GS sheet shall be Class VIII –
with zinc coating of 120 gm / sqmt surface area. The cost of the duct shall
include the threaded rod supports, angle flanges, anchor fastners, hot
dipped galvanized bolts and nuts etc.,
The Duct to be manufactured and assembled as per SMACNA standard for
Class-500pascals.
Note : Insulation shall be provided from inside.Same is quntified under
separete line item
24G. Ducting Sqmt. 50 845 250 42,250 12,500
22G. Ducting Sqmt. RO
4 DOUBLE SKIN PLENUM
Double skin powder coated plenum should be of factory fabricated,
constructed with outer skin with not less than 0.63mm thick GI sheet and
the inner sheet shall be of not less than 0.63mm GI plain sheet., with 25mm
thick sandwiched RPUF (CFC free) insulation of density not less than
40kg/m³. And with necessary High grade Extruded Aluminum cross supports Sqmt. RO
for rigidity and cutouts for duct & AHU connections. The plenum shall be
provided with an access door of size not less than 800mm x 600mm. The
price quoted shall include supporting arrangement with MS channels for
suspending the plenum from the ceiling slab.
5 ROUND FLEXIBLE DUCTS WITH INSULATION.
The round flexible duct inner core should be made of double lamination of
Aluminum Foil, Polyester & Metalized polyester film permanently bonded to a
coated spring steel wire helix. Fiberglass insulation shall be of 25mm thick
with minimum density of 16 kg/m³. The outer insulation jacket vapour barrier
shall be made of fiber glass reinforced metalized polyester film laminated
with aluminum foil as per the technical specifications.
250mm Dia. Rmts RO
350mm Dia. Rmts 150 280 100 42,000 15,000
6 ACOUSTIC INSULATION OF DUCTS
Class "1" type, Open cell elastomeric Acoustic insulation with density not
less than 140 kg / m3. Insulation material to be fire retardant. Moisture
resistant-joining tapes of 2 inches width with self adhesive to be supplied
with the insulation material by the supplier.
15 mm thick Sqmt. 130 750 150 97,500 19,500
7 THERMAL INSULATION
Thermal insulation of the sheet metal duct with closed cell elastomeric
insulation of Class 'O' material with density of 40 - 55 kg/cum as per the
thickness mentioned below, with fire retardant adhesive and joints sealed
with 3mm thick, 50mm wide nitrile rubber self adhesive tape.
9 mm thick Sqmt. 300 365 150 1,09,500 45,000
9 mm thick with Aluminium Foil Sqmt. RO
8 UNDERDECK INSULATION WITH ELASTOMERIC INSULATION
Underdeck Insulation for the roof with closed cell elastomeric insulation -
Class O type, material density of 40 - 60 kg/cum as per the thickness
mentioned below, with fire retardant adhesive and joints sealed with 3mm
thick nitrile rubber self adhesive tape. Adhesive used for the insulation shall
be with Low - VOC content. All joints sealed with 3mm thick, 75mm wide
nitrile rubber self adhesive tape. (Underdeck to be done above false ceiling
areas except beams).
19 mm thick insulation Sqmt. 150 460 150 69,000 22,500
9 JET NOZZLE - EYE BALL
The Diffuser shall be of removable core type and constructed with high
grade aluminum extruded alloy and with powder coated finish with flanges
and plenum fix with double flap damper. Double flap damper for round
diffusers are used wherever gypsum ceiling is provided. Where the diffusers
are accessible spill air box with butterfly damper shall be considered.
Butterfly dampers are quantified separately
Neck size: 315 dia Outer size: 400 Standard Nos. 60 2400 250 1,44,000 15,000
10 GRILLES - Al.
The supply & installation of higher grade Aluminum Extruded powder coated
Sqmt. 32 6200 500 1,98,400 16,000
grilles with blade deflection of 0 & 15 deg
11 LOUVERS - Al.
High grade aluminum extruded Louvers for Fresh air intake & Exhaust air
exit at outer wall. The louver shall be of powder coated finish. The louver
shall be with 45 deg deflection and shall prevent rain water entry through the Sqmt. 1 6500 1,000 3,250 500
louvers. Bird mesh shall be part of supply of louvers. Louvers shall be
powder coated finish.
12 VOLUME CONTROL OPPOSED BLADE DAMPER
The volume control damper shall be of low leakage type with the outer shell
constructed of 16G thick galvanized steel frame and the blade/Leaf with 16G
Sqmt. 3 5500 500 16,500 1,500
thick GSS. And with necessary flanges for connection etc., as per
specification.
13 COLLAR DAMPER - OPPOSE BLADE TYPE
The collar damper shall be constructed out of extruded aluminum alloy with
multiple blade of oppose blade type. Shall be used for the supply air diffuser Sqmt. RO
& grilles as per the drawings & specifications.
14 BACK DRAFT DAMPER
The Back draft damper with the outer shell constructed of 16G thick
galvanized steel frame and the blade/Leaf with 1mm thick aluminum. And
Sqmt. RO
with necessary flanges for connection and suitable for installing inside the
duct and as per specifications.
15 SPIGOTS WITH BUTTERFLY DAMPER - CIRCULAR - SINGLE FLAP-GI
The Spigots with butterfly damper should constructed with not less than 18G
thick galvanized steel sheet, with single flap, brass bush, necessary stopper,
operating handle, flanges for fastening on to the duct surface and with
grooves for clamping the flexible ducts securely.
300 mm Dia Nos. RO
350 mm Dia. Nos. 60 350 100 21,000 6,000
16 MS SUPPORTS
Supply, Installation of MS supporting arrangement for ducts installed at triple
floor height which are to be supported from beam to beam, using MS
Kgs 700 75 25 52,500 17,500
channels, angles, tees etc. All supports shall be painted with one coat of
epoxy primer and two coats of epoxy paint of approved colour.
SUB TOTAL FOR AIR HANDLING UNITS EXCLUSIVE OF ALL
11,74,450 2,73,300
DUTIES AND TAXES
GRAND TOTAL 14,47,750