You are on page 1of 17

Project : NCSCM

GENERAL NOTES COVERING BILL OF QUANTITIES

Contractors should factor in prices for DG power / water / storage etc. None will be
a
provided for at site.
The minimum quality benchmark will be decided by the Owner / Project management
b
consultant / Architect based on mock up samples before commencing work.
Unless otherwise specified the rates quoted shall be inclusive of the following ~ Cost of
c
material, taxes, transport, labour, overheads and profit, etc.,

d No wastages shall be paid separately. The same shall be factored in the quoted rate.

Contractor to be responsible for hiring / operating of all machines / equipment. Approval to


e
be obtained from Project Management Consultant before operating.

f Quoted rates to exclude taxes and added separately in grand summary sheet.

Architect : Flying Elephant Studio McD BERL Pvt.Ltd


Project : NCSCM HVAC BOQ

SUMMARY - HVAC WORKS BOQ


AMOUNT EXCLUDING
SL.NO. ITEM DESCRIPTION TAXES
TAXES
ED VAT
1 Chiller BOQ

2 Pumps BOQ

3 Cooling Tower BOQ

4 AHU's & Fan's BOQ

5 Low side HVAC works BOQ

6 Electrical related HVAC works BOQ

TOTAL 0

GRAND TOTAL EXCLUDING TAXES


TAXES
GRAND TOTAL INCLUDING TAXES
Project : NCSCM HVAC BOQ

UMMARY - HVAC WORKS BOQ


TAXES

SERVICE TAX
Bill of Quantites
Project: NCSCM

SL
DESCRIPTION OF WORK UNIT QTY RATE (Rs.) AMOUNT (Rs.)
NO
Design, Supply, Installation, Testing & Commissioning of Air-Conditioning system
for NCSCM, Chennai as follows:

Water cooled chiller package suitable for HFC 134a having Multiple compressor of
equal capacity of screw type ( semi/hermetic type) complete with suction and
discharge shut off valves and with Variable speed drive, HP/LP cutouts, oil pressure
failure switch, gague panel, cranckcase heater, automatic capacity
control,microprocessor based control for chiller control,watercooled condenser,
1
DX/Flooded chiller,with multiple circuits, controls such as thermostatic expansion
valve, cooling thermostat antifreeze thermostat, water pressure/flow switch
refrigerant pipes and fittings, strainer, sight glass isolating valves, rubber bellows,
suction line and chiller insulation, first charge of gas and oil, base frames, GI casing,
vibration isolators as per specifications.

a 125 TR Water cooled screw chiller with HFC 134a Refrigerant Nos 2

b Installation, clearance, freight upto site, insurance and commissioning charges Nos 2

Single stage centrifugal coupled horizontal type pumpset with axial suction port and
radial discharge port,with EFF1 drive motor, bronze impeller mechnical seal, three
phase TEFC squirrel cage motor with IP55 protection, class F insulation having a
2
speed of 1440 rpm with inertia base, vibration isolation springs, rubber isolation
bellows, flexible coupling for chilled water circulation having the following duty
conditions as per specifications

Primary Chilled Water pump,

a 1136 LPM against a head of 10 m with EFF1 motors - Pumps supply only Nos 3

Installation, clearance, freight upto site, insurance pump insulation and


b Nos 3
commissioning charges

Single stage centrifugal coupled horizontal type pumpset with axial suction port and
radial discharge port,with EFF1 drive motor, bronze impeller mechnical seal, three
phase TEFC squirrel cage motor with IP55 protection, class F insulation having a
3
speed of 1440 rpm with inertia base, vibration isolation springs, rubber isolation
bellows, flexible coupling for chilled water circulation having the following duty
conditions as per specifications

Secondary Chilled Water pump,

a 1136 lpm against a head of 20 m with EFF1 motors - Pumps supply only Nos 3

Installation, clearance, freight upto site, insurance pump insulation and


b Nos 3
commissioning charges

Architects: Flying Elephant Studio McD BERL Pvt. Ltd


Page 4 of 17
last modified on: 18 May 2013 715446899.xls
Bill of Quantites
Project: NCSCM

Single stage centrifugal coupled horizontal type pumpset with axial suction port and
radial discharge port,with EFF1 drive motor, bronze impeller mechnical seal, three
phase TEFC squirrel cage motor with IP55 protection, class F insulation having a
4
speed of 1440 rpm with inertia base, vibration isolation springs, rubber isolation
bellows, flexible coupling for chilled water circulation having the following duty
conditions as per specifications

Condenser Water pump,

a 1420 lpm against a head of 20 m with EFF1 motors - Pumps supply only Nos 3

Installation, clearance, freight upto site, insurance pump insulation and


b Nos 3
commissioning charges

Non combustible fibreglass towers having cross flow design, basin, PVC louver, drift
eliminator, low noise fan, ladder, vibration isolators, nozzles TEFC squirrel cage type
5 with variable speed induction motor with IP 55 protection and class F insulation
suitable for chiller capacity of following TR and an approach of 5 deg F as per
specifications

a Cooling tower suitable for 125 TR Chiller Nos 2

b Installation, clearance, freight upto site, insurance and commissioning charges Nos 2

Microprocessor based pump logic controller with adjustable frequency drive for
motor, complete by pass starter with IP 55 Enclosure, Required quantity of
6 differential pressure / temperature transmitter, incoming MCCB / ACB with control
wirng for software integration, built in Software integrator suitable for BAS as per
specifications

a For Secondary pumpset( 2 +1 ) with differential pressure transmitter and wiring Set 1

b Installation, clearance, freight upto site, insurance and commissioning charges Set 1

Floor mounted airhandling unit with double skin consturction complete with filter
section with pre filters and fine filters ( MERV13),Variable speed drives with suitable
7 bypass starters, multi row chilled water coils, fan section with backward curved
plugtype/ direct driven drive motor, canvas, supports,commissioning filters,
vibration isolators and outlet damper, fire damper as per specifications

Air Handling unit having a capacity of 17 TR and 7000 cfm against a static pressure
a Nos 1
of 65 mm WG and suitable drive motor - Supply only

Clearance, Freight upto site Transportation, insurance installation and


b Nos 1
commissioning

Air Handling unit having a capacity of 12 TR and 5000 cfm against a static pressure
c Nos 1
of 65 mm WG and suitable drive motor - Supply only

Clearance, Freight upto site Transportation, insurance installation and


d Nos 1
commissioning

Architects: Flying Elephant Studio McD BERL Pvt. Ltd


Page 5 of 17
last modified on: 18 May 2013 715446899.xls
Bill of Quantites
Project: NCSCM

Ceiling suspended airhandling unit with double skin construction complete with filter
section with filters, multi row chilled water coils, fan section with forward curved
8
centrifugal fan, drive motor, canvas, supports, vibration isolators, commissioning
filters, outlet dampers, drain pan with pump as per specifications

Air Handling unit having a capacity of 15 TR and 5000 cfm against a static pressure
a Nos 1
of 50 mm WG and suitable drive motor - Supply only

Clearance, Freight upto site Transportation, insurance installation and


b Nos 1
commissioning

Air Handling unit having a capacity of 10 TR and 4000 cfm against a static pressure
c Nos 10
of 40 mm WG and suitable drive motor - Supply only

Clearance, Freight upto site Transportation, insurance installation and


d Nos 10
commissioning

Air Handling unit having a capacity of 7.5 TR and 3000 cfm against a static pressure
e Nos 7
of 40 mm WG and suitable drive motor - Supply only

Clearance, Freight upto site Transportation, insurance installation and


f Nos 7
commissioning

Air Handling unit having a capacity of 5 TR and 2000 cfm against a static pressure
g Nos 5
of 40 mm WG and suitable drive motor - Supply only

Clearance, Freight upto site Transportation, insurance installation and


h Nos 5
commissioning

Air Handling unit having a capacity of 3 TR and 1200 cfm against a static pressure
i Nos 4
of 40 mm WG and suitable drive motor - Supply only

Clearance, Freight upto site Transportation, insurance installation and


j Nos 4
commissioning

Air Handling unit having a capacity of 2.5 TR and 1000 cfm against a static pressure
k Nos 1
of 40 mm WG and suitable drive motor - Supply only

Clearance, Freight upto site Transportation, insurance installation and


l Nos 1
commissioning

High Precision Units floor mounted type with chilled water coil, fine filter, heater and
humidifier section, EC fan, drive motor, for evaporator fan, return air louvers, MS /
10
GI powder coated casing, microprocessor control, hardware and software for BAS
hookup, controls as per specifications.

a 10 TR , 5200 cfm Nos 1

Architects: Flying Elephant Studio McD BERL Pvt. Ltd


Page 6 of 17
last modified on: 18 May 2013 715446899.xls
Bill of Quantites
Project: NCSCM

Clearance, Freight upto site Transportation, insurance installation and


c Nos 1
commissioning

High Precision Units floor mounted type with DX coil, fine filter, heater and
humidifier section, EC fan, drive motor, Variable speed drive for evaporator fan,
11
return air louvers, MS / GI powder coated casing, microprocessor control, hardware
and software for BAS hookup, controls, ref. Piping as per specifications.

a 10 TR , 5200 cfm Nos 1

Copper refrigerant piping, insulation, drain piping, frame work for indoor and
outdoor and other accessories including Electrical cable/wiring and Clearance,
c Lot 1
Freight upto site Transportation, insurance installation and commissioning(Indoor
and out door units location to be reffered In the drawing)

Chilled water Fan coil unit of double skin construction with compact cooling coil,
multispeed fan motor, the blower shall be dynamicaly balanced and designed for
silent operation, the filters shall be washable synthetic media type arranged for
convenient cleaning and replacement, drain pan with pump .The units as specified in
Schedule of Quantities shall be factory fitted with valve package comprising of 2 way
12
pressure independent valve suitable for variable CHW flow with modulating actuator,
ball with Y strainer valve at inlet & Ball valve at outlet and necessary piping
connections. The actuator of modulating valve shall be provided with interface cards
to receive 0-10V or 4-20 mA signal from Minxon Digital Thermostat.The unit is
supplied with corded remote controller of approved as per specifications

Fan Coil Unit having a capacity of 1 TR and 400 cfm against a static pressure of 15
a Nos 18
mm WG and suitable drive motor - Supply only

Clearance, Freight upto site Transportation, insurance installation and


b Nos 18
commissioning

Chilled water Cassette type indoor units with compact cooling coil, multispeed fan
motor, the blower shall be dynamicaly balanced and designed for silent operation, the
filters shall be washable synthetic media type arranged for convenient cleaning and
replacement and inbuilt drain pump.The units as specified in Schedule of Quantities
shall be factory fitted with valve package comprising of 2 way pressure independent
13
valve suitable for variable CHW flow with modulating actuator, ball with Y strainer
valve at inlet & Ball valve at outlet and necessary piping connections. The actuator of
modulating valve shall be provided with interface cards to receive 0-10V or 4-20 mA
signal from Minxon Digital Thermostat.The unit is supplied with corded remote
controller of approved as per specifications

Cassette Unit having a capacity of 3.0 TR and 1200 cfm against a static pressure of
a Nos 1
15 mm WG and suitable drive motor - Supply only

Clearance, Freight upto site Transportation, insurance installation and


b Nos 1
commissioning

Architects: Flying Elephant Studio McD BERL Pvt. Ltd


Page 7 of 17
last modified on: 18 May 2013 715446899.xls
Bill of Quantites
Project: NCSCM

Cassette Unit having a capacity of 2.5 TR and 1000 cfm against a static pressure of
c Nos 3
15 mm WG and suitable drive motor - Supply only

Clearance, Freight upto site Transportation, insurance installation and


d Nos 3
commissioning

Cassette Unit having a capacity of 2.0 TR and 800 cfm against a static pressure of 15
e Nos 5
mm WG and suitable drive motor - Supply only

Clearance, Freight upto site Transportation, insurance installation and


f Nos 5
commissioning

Chilled water High wall mounted indoor units with compact cooling coil, multispeed
fan motor, the blower shall be dynamicaly balanced and designed for silent operation,
the filters shall be washable synthetic media type arranged for convenient cleaning
and replacement and drain pan.The units as specified in Schedule of Quantities shall
be factory fitted with valve package comprising of 2 way pressure independent valve
13
suitable for variable CHW flow with modulating actuator, ball with Y strainer valve
at inlet & Ball valve at outlet and necessary piping connections. The actuator of
modulating valve shall be provided with interface cards to receive 0-10V or 4-20 mA
signal from Minxon Digital Thermostat.The unit is supplied with corded remote
controller of approved as per specifications

Hiwall Unit having a capacity of 1.0 TR and 400 cfm against a static pressure of 15
a Nos 5
mm WG and suitable drive motor - Supply only

Clearance, Freight upto site Transportation, insurance installation and


b Nos 5
commissioning

Supply, installation testing & commissioning of Hi wall Split air conditioner of 1.0
TR /400 cfm capacity with Scroll compressors with matching condensers MS Frame
14 Nos 1
for mouting the units to be provided with rubber pads, the frame should be painted
with two coats for ATM ground floor.

Copper refrigerant piping, insulation, drain piping, frame work for indoor and
outdoor and other accessories including Electrical cable/wiring and Clearance,
a Lot 1
Freight upto site Transportation, insurance installation and commissioning(Indoor
and out door units location to be reffered In the drawing)

Architects: Flying Elephant Studio McD BERL Pvt. Ltd


Page 8 of 17
last modified on: 18 May 2013 715446899.xls
Bill of Quantites
Project: NCSCM

Supply, Installation, Testing and commisioning of Double skin outdoor mounted type
Heat recovery unit made of 50mm thick panels consisting of GI casing of thickness
0.63mm outside layer and 0.63mm inside layer with factory injected PUF insulation,
Supply & Return air Centrifugal blower(Forward curved/backward curved)sections
with aerofoil constructions, Heat recovery wheel section, belt drive packages with
TEFC motor suitable for operation on 415 +/- 10% volts, 50 Hz, 3 phase, A.C. power
15 supply, Fresh air Pre-filter section, Heat recovery descicant wheel, Fresh air, return
air & exhaust air dampers with suitable actuator with a provision for CO2 signal
sensing,CO2 sensors with wiring to be included for each unit and all the necessary
accessories, necessary vibration isolators and complete as per specifications. The
duties of equipments listed below and accessories shall be as per equipment schedule.
Heat recovery wheel efficiency should not be less than 75%. Unit shall be with VFD
and with suitable bypass starter and BMS compatible and as per specifications

900 Cfm Fresh air and Exhaust against a static pressure of 50 mm WG having
a Nos 2
suitable drive motors

Cabinet type Exhaust air handling unit with double skin construction complete with
damper gravity louver, cengrifugal blower, 3 phase drive motor, anti vibration
18
mounts suitable for floor mounting with commissioning filters having capacities as
follows as per specifications:

a 4500 cfm against a static pressure of 40mm WG having suitable drive motor Nos 1

b 2800 cfm against a static pressure of 40mm WG having suitable drive motor Nos 2

b 2200 cfm against a static pressure of 40mm WG having suitable drive motor Nos 3

c 1650 cfm against a static pressure of 40mm WG having suitable drive motor Nos 1

Cabinet type Fresh air handling unit with double skin construction complete with
damper gravity louver, cengrifugal blower, 3 phase drive motor, anti vibration
18
mounts suitable for floor mounting with commissioning filters having capacities as
follows as per specifications:

a 2450 cfm against a static pressure of 40mm WG having suitable drive motor Nos 1

b 2250 cfm against a static pressure of 40mm WG having suitable drive motor Nos 1

c 1870 cfm against a static pressure of 40mm WG having suitable drive motor Nos 2

d 1400 cfm against a static pressure of 40mm WG having suitable drive motor Nos 1

e 1150 cfm against a static pressure of 40mm WG having suitable drive motor Nos 1

Inline type Fresh air fan with double skin construction complete with damper gravity
19 louver, centrifugal blower, 3 phase/1 Phase drive motor, anti vibration mounts
suitable for floor mounting having capacities as follows as per specifications

a 500 cfm against a static pressure of 20mm WG having suitable drive motor Nos 1

Architects: Flying Elephant Studio McD BERL Pvt. Ltd


Page 9 of 17
last modified on: 18 May 2013 715446899.xls
Bill of Quantites
Project: NCSCM

b 350 cfm against a static pressure of 20mm WG having suitable drive motor Nos 1

Cabinet type Exhaust air handling unit( Kitchen area ) with double skin construction
complete with damper gravity louver, cengrifugal blower, 3 phase drive motor, anti
20
vibration mounts suitable for floor mounting with commissioning filters having
capacities as follows as per specifications:

a 4600 cfm against a static pressure of 40mm WG having suitable drive motor Nos 1

Cabinet type Fresh air handling unit( Kitchen area ) with double skin construction
complete with damper gravity louver, cengrifugal blower, 3 phase drive motor, anti
21
vibration mounts suitable for floor mounting with commissioning filters having
capacities as follows as per specifications:

a 3700 cfm against a static pressure of 40mm WG having suitable drive motor Nos 1

Machine made GSS Ducting with flanges, neoprene gaskets, factory made supports,
22
with black painting as per specifications (factory made with ductmate flanges)

a 24 G Sqm 2150
b 22 G Sqm 650
c 20 G Sqm 5

Alluminium Fresh/Exhaust air louver of aerofoil construction wiyh nylon mosquito


23
net,dampers as per specifications as follows:

a Rate per sq.mt of louver face area Sqm 2

Aluminium volume control dampers with PVC gear and opposed blades with handle
24
as per specs.(Shall be suitable for motorised actuation)

a Rate per sq.mt of face area Sqm 14

GSS Fire Dampers with 90 min fire rating with temperature sensor, alarm panel with
25 motorised actuator, provision for receipt of external fire signal, wiring as per
specifications.

a 500 x 150 Nos 8


b 300 x 150 Nos 12

c Rate per sq.mt of face area Sqm 2


d Actuator No's 20

26 Aluminium powder coated diffusers having regular design

a 600 x 600 supply air diffuser with VCD Nos 20

c 600 x 600 return air diffuser w/o VCD Nos 20

29 Aluminium powder coated Jet Nozzle Diffusers as per specs

a 650 cfm Nos 1

Floor grilles with extruded aluminium louvres, 4 quadrant with independent volume
30 Nos 6
control dampers and frame work having a size of 600 x 600 mm as per specifications

Architects: Flying Elephant Studio McD BERL Pvt. Ltd


Page 10 of 17
last modified on: 18 May 2013 715446899.xls
Bill of Quantites
Project: NCSCM

Aluminium flexible duct with 25 mm thick insulation , worm clips, supports as


31
follows

a 250 mm dia Rmt 60

32 Aluminium powder coated continous grilles with 0/15 deg. Deflection as follows

a 100 mm wide Rmt 950

Aluminium powder coated Spot grille/Stoke discreate grille with 0/15 deg.Deflection
33
as follows

a 1000x100 Nos 9

34 Aluminium powder coated Supply/exhaust air Disc valve with opposed blade

a 150 mm dia for toilets Nos 150

PVC flexible duct with worm drive clamps having the following sizes as per
35 specifications as follows:(alternatively single skin aluminium flexible shall be
offered)

a 150 mm dia Rmt 90

Acoustic lining of ducting with 15mm thick open cell nitrile rubber insulation with
36 Sqm 500
aluminium tape as per specifications

Duct insulation with 15 mm thick close cell nitrile rubber insulation factory
37 Sqm 1300
laminated aluminium foil and aluminium tape as per specs

Chilled water piping with black steel pipes, fittings, RCC Sleepers, factory made
supports, sand cushioning including digging and refilling of earth for buried pipes
38
along with Thermal insulation of buried chilled water pipes with TF Quality EPS
insulation, finished with sand cement plaster and tarfelt as per specifications:

MS 'C' Class pipe with insulation as per specifications,(BURREED PIPES)

a 200 mm dia Rmt 100


b 150 mm dia Rmt 20
b 125 mm dia Rmt 25
c 100 mm dia Rmt 100
d 80 mm dia Rmt 120
e 65 mm dia Rmt 45

MS pipes for chilled water applications above ground with 19 mm thick nitrile
39 rubber which bonds to the pipe, the outer casing material shall be galvanized,
stainless steel or high density polyethylene tubes with vapour barrier, comply to class
O fire rating standards with comprehensive strength upto 275 kPa, the PU Foam shall
be CFC Free agent finished with supports/hangers as per specifications
ABOVE GROUND
MS 'C' Class pipe with insulation as per specifications,

a 150 mm dia Rmt 25


b 125 mm dia Rmt 25

Architects: Flying Elephant Studio McD BERL Pvt. Ltd


Page 11 of 17
last modified on: 18 May 2013 715446899.xls
Bill of Quantites
Project: NCSCM

MS B Class

c 100 mm dia Rmt 25


d 80 mm dia Rmt 150
e 65 mm dia Rmt 50
f 50 mm dia Rmt 300
g 40 mm dia Rmt 100
h 32 mm dia Rmt 120
i 25 mm dia Rmt 200

All valves are to be considered with nitrile rubber insulation finished with polyshied
as per specifications

40 Butterfly valves with insulation as per specifications,

a 200 mm dia Nos 2


b 150 mm dia Nos 16
c 80 mm dia Nos 8
d 65 mm dia Nos 4
e 50 mm dia Nos 153
f 40 mm dia Nos 17
g 32 mm dia Nos 78

41 Y type strainers with insulation as per specifications,

a 150 mm dia Nos 6


b 65 mm dia Nos 2
c 50 mm dia Nos 8
d 40 mm dia Nos 3
e 32 mm dia Nos 37

42 Wafer type check valves with insulation as per specifications,

a 150 mm dia Nos 6

Two way motorised valve with actuator and transformer as per specifications having
43
the following water flow, clearance, installation and with insulation as follows,

a 227 lpm Nos 1


b 182 lpm Nos 1
c 136 lpm Nos 2
d 91 lpm Nos 6
e 68 lpm Nos 3
f 45 lpm Nos 29
g 27 lpm Nos 8

44 Balancing valves with insulation as per specifications

a 150 mm dia Nos 2


b 65 mm dia Nos 2
c 50 mm dia Nos 8
d 40 mm dia Nos 3
e 32 mm dia Nos 37

45 Motorised Butterfly valves with insulation as per specifications

a 150 mm dia Nos 2

46 100 mm dia Dial type pressure gauges with thermo port Nos 112

47 Industrial type thermometers with thermo port Nos 100

Architects: Flying Elephant Studio McD BERL Pvt. Ltd


Page 12 of 17
last modified on: 18 May 2013 715446899.xls
Bill of Quantites
Project: NCSCM

Drain piping using CPVC pipe SDR11 with CPVC fittngs and insulated with 6mm
48 thick nitrile rubber insulation finished with polyshield. The pipe goes below ground
should be rapped with polythene sheet as follows:

UNDER GROUND

a 65 mm dia Rmt 150

Above GROUND

b 50 mm dia Rmt 45
c 40 mm dia Rmt 30
d 32 mm dia Rmt 50
e 25 mm dia Rmt 350

Membrane type automatic expansion tank having a capacity of 1000 litres as per
49 Nos 1
specifications

50 Condenser water pipes with black steel fittings, factory made supports as follows:

ABOVE GROUND
MS 'C' Class pipe with insulation as per specifications,

a 200 mm dia Nos 30


b 150 mm dia Nos 20

51 Butterfly valves is as per specifications,

a 150 mm dia Nos 14


b 100 mm dia Nos 2
b 50 mm dia Nos 2

47 Y type strainers is as per specifications,

a 150 mm dia Nos 3

48 Wafer type check valves is as per specifications,

a 150 mm dia Nos 3

49 Balancing valves is as per specifications,

a 150 mm dia Nos 2

50 Motorised Butterfly valves is as per specifications,

a 150 mm dia Nos 4

52 100 mm dia Dial type pressure gauges with thermo port Nos 10

53 Industrial type thermometers with thermo port Nos 4

The air seperator with Dirt seperator fabricated with Steel finished with dirt chamber,
air chamber, vent units, automatic valve, drain valve, suitable for flushing even when
54
in operation, suitable for threaded or flanged connections as per specifications of the
following sizes

a 200 mm dia Nos 1

55 Chemical dosing unit Nos 1

Architects: Flying Elephant Studio McD BERL Pvt. Ltd


Page 13 of 17
last modified on: 18 May 2013 715446899.xls
Bill of Quantites
Project: NCSCM

Condesate water connections,(from Condensate tank to Makeup tank) pump with


56 Set 1
level controller,valves and codensate tank with insulation

TOTAL

BILL OF QUANTITIES FOR ELECTRICAL RELATED HVAC WORKS FOR NCSCM

1.0 16Amp/6Amp Universal switch socket outlet

Supply and fixing of modular 6/16A,5 pin single phase switch socket outlet fixied in
a suitable size metal sheet box suitable for switches and sockets,including supply of
fixing materials interconnections complete as required and approved by the
consultant/client.

Supply Point 150


Installation Point 150

Supply and wiring with FRLS 2Rx4.0sqmm+1Rx2.5sqmm of 1.1KV grade,ISI


2.0 marked,PVC insulated single core stranded copper conductor cable conforming to
IS:694(with latest amendments) in existing conduit / raceways from DB to the first
point as required and approved by the consultant/client.

Supply Mtrs. 1000


Installation Mtrs. 1000

Supply and wiring with FRLS 4Rx6.0sqmm+1Rx4.0sqmm of 1.1KV grade,ISI


2.1 marked,PVC insulated single core stranded copper conductor cable conforming to
IS:694(with latest amendments) in 25mm dia conduit from DB to the first point as
required and approved by the consultant/client.

Supply Mtrs. 1000


Installation Mtrs. 1000

3 MCB Distribution boards:

Supply and installation of following TPN/SPN MCB DBs of CRCA sheet steel
enclosure,dust and vermin proof ,rated for 440V/230V. 3/1 phase,50 HZ AC supply,
operation(doubledoor type )inclusive of busbar of suitable capacity,neutral link with
required outgoings,DIN bar,and earthing terminals and with silicon based fire/ Heat
resistant coating appiled inside the DB and painted with approved shade of paint
suitable for incorporating SP/DP/TP MCB as specified below with all materials
required including supply and fixing of MCBs/ ELMCBs / Isolators/ SFUs and fixed
in flush with wall along with all materials required including all associated civil
works and earthing as per specifications and the SLD, The MCB & MCCB' S have
the Ka Rating-10kA

3.1 6 WAY VTPN DB


( For Internal Main AC distribution DBs for all the floors)
3 Phase 6 way.Incoming 63A 4P MCCB
Outgoings: 63A TP MCB - 6 Nos.
Supply Each 7
Installation Each 7
6WAY TPN DB (For AC Single phase)-With Sub meter
3.2 3 Phase 8 way.Incoming 32A TPN MCB
Sub incommer: 1No. 25A DP ELCB for each phase

Outgoings: 12 Nos.10/16A SP MCB ( 'C' curve) with timer controlled

Supply Each 9
Installation Each 9

Architects: Flying Elephant Studio McD BERL Pvt. Ltd


Page 14 of 17
last modified on: 18 May 2013 715446899.xls
Bill of Quantites
Project: NCSCM

4 LT XLPE Cables

Supply of 1.1 KV grade, 2C/3C/3.5C/4C, XLPE insulated, and PVC overall sheathed,
stranded aluminium/Copper conductor, flat steel strip/ wire armoured cables
conforming to IS:1554/ Part I (with latest amendments)and of following sizes.The
cable shall bear ISI certification mark. Laying of the cable in ground/existing cable
tray/duct/shaft including transportation of cable to site,excavation of earth, laying the
cable and covering with sand and placing the bricks on sides and top,refilling with
earth and providing cable route/ joint markers complete as required. (the laying of
cable in trench shall include removing the trench cover, reclosing it after laying cable
in good condition and fixing it to the cable suupports on wall with suitable clamps
including supply of clamps complete as required)

4.1 3.5C X 150 Sq.mm AR. AL Cable (for CHILLERS)


Supply Mtrs 75
Laying Mtrs 75

4.2 4C X 25 Sq.mm AR. AL Cable (for Primary pumps, secondary pumps and cooling
towers,DB )
Supply Mtrs 500
Laying Mtrs 500
4.3 4C X 6Sq.mm AR. AL Cable (AHU )
Supply Mtrs 200
Laying Mtrs 200
5 LT XLPE Cables End termination
(Tinned copper lugs, long barrel )
5.1 3.5C X 150 Sq.mm AR. AL Cable (for CHILLERS) Nos 4

5.2 4C X 25 Sq.mm AR. AL Cable (for Primary pumps, secondary pumps and cooling Nos 24
towers) )

5.3 4C X 6 Sq.mm AR. AL Cable Nos. 34

6.0 Ladder/ Perforated type Cable tray

Supply and instllation of 2mm thick GI perforated/ ladder type cable tray with side
rail using suitable revets, washers, bolts,supporting brackets of same make and all
other accessories required for fixing the cable tray complete as required and as
directed by the Engineer-in-charge.

6.1 300 X 100 X 2mm wide ladder type cable tray


Supply Mtrs 20
Laying Mtrs 20
6.2 CONDUITS

Supply and Laying and fixing of FRLS PVC conduits of 2mm thick of the following
sizes in slab or external with necessary fixing accessories for PA system, home
automation and bms integaration as required with necessary accessories such as
bends, collars, junction boxes and pull boxes and with covering covering plate as
required as per the site condition and as approved by the client/ consultants.

6.3 25mm dia conduit


Supply Mtrs 1000
Laying Mtrs 1000

7.0 PART-4 LT PANELS


1.The rates shall include 100mm painted MS channel frame/ cement
foundation/suspening arrangement
2.Cost of all testing are deemed to be included in the rates
7.1 AC PANEL-1 (Loc: Chiller Room)

Architects: Flying Elephant Studio McD BERL Pvt. Ltd


Page 15 of 17
last modified on: 18 May 2013 715446899.xls
Bill of Quantites
Project: NCSCM

Design, manufacture, testing, installation, commissioning of Main L.T panel (MDB)


Incomer :-
One main incomer of 400 4P EDO 50KA MCCB.
400/5A, 10VA, C1 CTs (for Ammeter) - 1 No
CBCT ELR - 1 set
Three (3)- phase indicating lamps with MCBs. (LED type)-03 sets
Bus Bar:
400A TPN+E insulated Alu. Bus bar: 50kA
Out goings :
200 Amps TPN MCCB - 3
16 Amps TPN MCCB - 13 No

200A=1no 4P 50 KA MCCB WITH THERMAL MAGNETIC BASED O/L,S/C,

RELEASES WITH SP TERMINALS, FD KIT


CONTROL MCB 6A SP=1no.
TIMER 0-30 SEC=1no.
A/M SELECTOR SWITCH=1no.
INDICATING LAMPS ON/OFF/TRIP=1set
PUSH BUTTON ON/OFF=1set
POWER TERMINALS=1set
CONTROL TERMINALS=1set
OUTGOINGS:
1.200A=3 nos TPN MCCB

16 A =1no 4P 50 KA MCCB WITH THERMAL MAGNETIC BASED O/L,S/C,

RELEASES WITH SP TERMINALS, FD KIT


CONTROL MCB 6A SP=1no.
TIMER 0-30 SEC=1no.
A/M SELECTOR SWITCH=1no.
INDICATING LAMPS ON/OFF/TRIP=1set
PUSH BUTTON ON/OFF=1set
POWER TERMINALS=1set
CONTROL TERMINALS=1set
OUTGOINGS:
1.16A=13nos. TPN MCCB
Supply No. 1
Installation No. 1
7.2 AHU STARTER PANEL

'VFD provision' with bypass STAR/DELTA STARTER with Overload,Single


phasing, Under voltage and overvoltage, phase reverse protection with necessary
internal wiring. Starter should be compatible for BMS also with necessary inputs and nos 3
outputs provisions, power and control wiring should be carried out as per IS
standards suitable for current ranging from (0--16)Ampere.VFD cab have Single
phase input also

7.3 PUMP STATER PANELS

'VFD provision' with bypass STAR/DELTA STARTER with Overload,Single


phasing, Under voltage and overvoltage, phase reverse protection with necessary
internal wiring. Starter should be compatible for BMS also with necessary inputs and nos 3
outputs provisions, power and control wiring should be carried out as per IS
standards suitable for current ranging from (0--25)Ampere.

Architects: Flying Elephant Studio McD BERL Pvt. Ltd


Page 16 of 17
last modified on: 18 May 2013 715446899.xls
Bill of Quantites
Project: NCSCM

7.4 PUMP STATER PANELS-STAR/DELTA TYPE

Supply, installation, testing and commissioning of STAR/DELTA STARTER with,


Overload,Single phasing, Under voltage and overvoltage, phase reverse protection
with necessary internal wiring. Starter should be compatible for BMS also with no.s 10
suitable cabinet .Stareter panel should meet the requiremnst of following loads(85kw-
2,6.25kw-2,2.98kw-3,7.46kw-2,)

8 EARTHING STRIP
8.1 25x6mm GI strip (body earthing for Fencing, SUB- panels and DBs) Mtrs 200
8.2
8 Guage CU. strip (body earthing for Primary,Secondary,Cooling Towers,Chillers) Mtrs 50
8.3 DANGER BOARDS :

Supplying & fixing of 0.415KV danger boards with the word "DANGER" written in Nos. 5
English & Kannada as per EB/LOCAL EB AUTHORITIES requirement.

8.4 SAFETY ITEMS


8.4.1 Rubber mats, 1M wide and 10 mm thick, 1100V grade RM 10

8.4.2 Fire Extinguishers, ELECTRICAL DUTY 4.5Kg ABC Powder Nos. 4

8.4.3
Danger Boards on subpanels, In English, HINDI & LOCAL LANGUAGE. Nos. 20

8.4.4
Artificial Respiration Charts-In English, HINDI & LOCAL LANGUAGE Nos. 1

8.4.5 Cable route marker as required Nos. 25

TOTAL

GRAND TOTAL

Architects: Flying Elephant Studio McD BERL Pvt. Ltd


Page 17 of 17
last modified on: 18 May 2013 715446899.xls