Unit QTY RATE AMOUNT
SECTION 1 : EQUIPMENTS
SECTION 1.2 : Primary & Secondary Chilled Water Pumps with VFD,Air seperator,Chemical Dozing,Expansion tank
Head : The Head is calculated based on initial design details how ever contractor to
select pump to match with chiller flow rate and pressure drop,actual system head is
based on the finalized equipment / pipe lengths. Head calaculation and selection to
be submitted to consultant for review / approval. The procurement shall be processed
only after head calculations & selections duly verified from the consultants.
SITC of Primary Chilled Water Pumps verical / Horizontal split casing chilled water
circulating pump set complete with TEFC motor,steel fabricated base plate,vibration
isolation pads,stuffing box with mechanical seal,Flexible pipe connectors etc. The
pumps shall be suitable for operation on 415 volts +/-10 Volts,3 phase,50 HZ AC
power supply,Pump motor should be EFF1 rated. Pump material and operating
conditions are given here under.(2Working+1 Standby) Note:FRP Hood should be
provided.
Nos 5
Type - End Suction Back pull out
Body - CI
Impeller - Bronze
Flow rate - 420 GPM / 26.5 LPS
Head - 15 mts
Minimum efficiency - 75%
SITC of Secondary Chilled Water Pumps verical / Horizontal split casing chilled water
circulating pump set complete with TEFC motor WITH Class F insulation,steel
fabricated base plate,vibration isolation pads,stuffing box with mechanical
seal,Flexible pipe connectors etc. The pumps shall be suitable for operation on 415
+/- 10 volts,3 phase,50 HZ AC power supply,Pump motor should be EFF1
rated.The motor shall be also be suitable for operation on adjustable frequency
drive.Pumpmaterial and operating conditions are given hereunder (2
Working + 1 standby).Note:FRP Hood should be provided. Nos 5
Type - End Suction Back pull out
Body - CI
Impeller - Bronze
Flow rate - 420 USGPM / 26.5 LPS
Head - 20 mts
Minimum efficiency - 75%
1
BOQ - HVAC
Supply, installation, testing & commissioning of Closed loop expansion tank as per
standards & requirements.The tank shall be made of mild steel and has a synthetic
rubber membrane. Nitrogen gas or compressed air is filled in space between the
membrane and the wall of the tank. The tank should be supplied complete with
booster pumps(1W+1S),isolating valve, check valve, drain valve & pressure gauge. Set 1
Before connecting the tank to water system, the gas pressure should be checked
through the charging valve and adjusted according to the requirements, the control
panel should also be included. The quoted price shall be inclusive of structural
support for the tank. Capacity of tank is 1000 lts+ Pumps with N+1 confirgration
Supply, installation, testing & commissioning of Air Seperator made out of MS Sheet
as per Specification and Schematic diagram - 500 Ltrs.for Chilled water system. Set 1
Pressure Rating shall be PN 16.
Chilled Water Chemical Treatment system- (Automatic Chemical dosing pot system
Set 1
+dosing Pump+Dosing pots + Cleaning Chemicals)
Capacity- 6.2 KW, Supply Air volume - 620 L/sec, ESP-250 Pa Nos 1
Capacity- 7.1 KW, Supply Air volume - 823 L/sec, ESP-250 Pa Nos 1
Capacity- 8.2 KW, Supply Air volume - 912 L/sec, ESP-250 Pa Nos 1
Capacity- 9 KW, Supply Air volume - 824 L/sec, ESP-250 Pa Nos 2
Capacity- 9.1 KW, Supply Air volume - 822 L/sec, ESP-250 Pa Nos 1
Capacity- 9.1 KW, Supply Air volume - 1043 L/sec, ESP-250 Pa Nos 1
Capacity- 9.8 KW, Supply Air volume - 886 L/sec, ESP-250 Pa Nos 1
Capacity- 10.1 KW, Supply Air volume - 914 L/sec, ESP-250 Pa Nos 1
Capacity- 11.1 KW, Supply Air volume - 1311 L/sec, ESP-250 Pa Nos 1
Capacity- 12 KW, Supply Air volume - 1134 L/sec, ESP-250 Pa Nos 1
Capacity- 12.3 KW, Supply Air volume - 1333 L/sec, ESP-250 Pa Nos 1
Capacity- 12.4 KW, Supply Air volume - 1481 L/sec, ESP-250 Pa Nos 1
Capacity- 12.5 KW, Supply Air volume - 1414 L/sec, ESP-250 Pa Nos 4
Capacity- 13.8 KW, Supply Air volume - 1607 L/sec, ESP-250 Pa Nos 1
Capacity- 14.1 KW, Supply Air volume - 1640 L/sec, ESP-250 Pa Nos 1
Capacity- 15 KW, Supply Air volume - 1714 L/sec, ESP-250 Pa Nos 1
Capacity- 15.3 KW, Supply Air volume - 1762 L/sec, ESP-250 Pa Nos 2
Capacity- 15.9 KW, Supply Air volume - 1877 L/sec, ESP-250 Pa Nos 1
Capacity- 17.5 KW, Supply Air volume - 1951 L/sec, ESP-250 Pa Nos 1
Capacity- 20.4 KW, Supply Air volume - 2371 L/sec, ESP-250 Pa Nos 1
Capacity- 20.6 KW, Supply Air volume - 1896 L/sec, ESP-250 Pa Nos 1
Capacity- 20.8 KW, Supply Air volume - 1193 L/sec, ESP-250 Pa Nos 1
Capacity- 26 KW, Supply Air volume - 2927 L/sec, ESP-250 Pa Nos 1
Capacity- 27.1 KW, Supply Air volume - 2306 L/sec, ESP-250 Pa Nos 1
Capacity- 32 KW, Supply Air volume - 2700 L/sec, ESP-250 Pa Nos 1
Capacity- 40.8 KW, Supply Air volume - 1110 L/sec, ESP-250 Pa Nos 1
Capacity- 76.8 KW, Supply Air volume - 2253 L/sec, ESP-250 Pa Nos 1
Capacity- 99.1 KW, Supply Air volume - 2027 L/sec, ESP-250 Pa Nos 1
2
BOQ - HVAC
Supply, installation, testing & commissioning of Electric duct Heater for guest rooms Nos 273
3
BOQ - HVAC
SECTION 1.6 : Precision Air conditioning Unit with DX coil (Data centre, B1)
Supply, Installation, Testing and commisioning of Double skin, Floor mounted bottom
discharge precision air conditioning unit , motor suitable for operation on 415 +/- 10%
volts, 50 Hz, 3 phase, A.C. power supply, DX cooling coil (No of rows shall be as per
coil selection), filter section, outlet volume control dampers with suitable actuator with
a provision for CO2 signal sensing,CO2 sensors with wiring to be included for each
unit and all the necessary accessories, necessary vibration isolators and complete as
per specifications. The duties of equipments listed below and accessories shall be as
per equipment schedule. Unit shall be with VFD and with suitable bypass starter and
BMS compatible
Supply, installing, testing, commissioning & handing over of Atrium Smoke exhaust
air unit, Floor mounted double skin horizontal unit. Each unit complete with squirrel
cage induction motor, centrifugal fan belt drive and vibration isolators. Motor shall be
suitable for 415 +/- 10% volts with 2 Hours Fire rated, 50 cycles AC supply with
imported make fans complete with Fan section with forward curved fan. Heavy duct
flexible double layer canvas connection shall be provided at the outlet of unit Fan.
19042 L/ S ,500 Pa ESP Nos 6
4
BOQ - HVAC
DG VENTILATION UNIT
Supply, installing, testing & commissioning of Axial fans with Fan & motor connecting
terminals.
Fresh air fans
20000 L/s Nos 3
Exhaust air fans
20000 L/s Nos 3
ECOLOGY UNIT :
Kitchen ECOLOGY Unit in Double Skin Construction, comprising of electrostatic filters
and exhaust fans as mentioned below. Panel
thickness - 25 mm (PUF insulation), Outer skin - 24G pre-coated, Inner Skin - 24G
Plain GI, Frame-Extruded aluminium profile with thermal break, Unit base-GI, Fan-
DIDW Backward curved AMCA certified, Motor-TEFC induction, suitable for air 24
hrs operation, efficiency EEF2 Scrubber :
Casing 18G GI, powder coated, pre-filters aluminium washable, Cell - Aluminium, with
ionizing/ collection section in single casing, Ioniser - Tungsten wire, Control Panel-
with panel cooling fan, ON-OFF-Wash indications, Special features such as BMS dry
contacts, short circuit-arc protection and auto restore power pack, Scrubber must be
selected for 95% or more efficiency as per ASHRAE 52.1 test.
14698 L/s, 800 Pa ESP - Main Kitchen - GL Nos 1
3334 L/s, 600 Pa ESP - Show Kitchen - GL Nos 1
5
BOQ - HVAC
Supply, installation, testing & commissioning of the following equipment & materials,
scaffoldings, all leads and lifts etc. complete as per specifications and drawings.
Supply , Installation, testing and commissioning of AMCA certified Vane Axial fresh
air Fans suitable for 415±10% volts, 50 cycles, 3 phase AC power supply, IP55, S1
duty, IS325, class F insulation. Single speed motor, properly supported with MS
frame, spring vibration isolators, flexible fire proof canvas, leak proof ducting
connection with civil plenum with properly grouted M.S angles. MS structure should
be painted with hot deep galvanised of minimum 80 micron DFT. The fan shall be
direct driven and with flexible connector. The noise level in the basement car parking
shall not exceed 60dBA measured 3.0m from equipment casing.Provide sound
attenuators to achieve required noise level if required. The fan shall be minimum
65% efficient. Fans specified for use in carpark ventilation applications shall be rated
for 300oC, 2 hours and for normal applications shall be rated for temperature of 55oC.
6
BOQ - HVAC
SECTION 1.8 : Controls - 2 Way Valve (Pressure Independent Modulating Type) package, thermostat and necessary wiring
Black steel ERW medium duty to BS 1387/API 5L Grade B Standard schedule pipes
and fittings including all supports
20 mm RMT 1700
25 mm RMT 330
32 mm RMT 450
40 mm RMT 450
50 mm RMT 550
65 mm RMT 860
80 mm RMT 900
100 mm RMT 500
125 mm RMT RO
7
BOQ - HVAC
8
BOQ - HVAC
Chilled Water Piping Insulation for Piping in ean-A/C area with closed cell Elastomeric
Rubber (Density 55-70 Kg/m3) without canvas covering . Foster coating for all piping
for all bulding.
(32 mm thick upto including pipe size 80 mm dia 50 mm thick for pipesize 100 mm dia
and above)
Chilled Water Piping Insulation for Piping in Non-A/C area with closed cell
Elastomeric Rubber (Density 55-70 Kg/m3) without canvas covering . Foster coating Item 1
for all piping for all bulding.
(32 mm thick upto including pipe size 80 mm dia 50 mm thick for pipesize 100 mm dia
Item 1
and above)
Aluminium Cladding as weather -proffing and mecahnical protection for Chilled Water
Item 1
Piping Insulation in External Areas / Exposed Areas
Leak Detection System complete with all wiring, accessories, sensors & control panel
Item 1
interfaced with BMS for chilled water line only.
GI Ducting
26G Sq.m RO
24G Sq.m 1930
22G Sq.m 970
20G Sq.m 970
18G Sq.m 50
9
BOQ - HVAC
Thermal Insulation - 13mm thick closed cell Elastomeric Nitrle rubber insulation Sq.m 2745
Flexible Ducting
250 mm dia RMT RO
200 mm dia RMT 100
150 mm dia RMT 600
100 mm dia RMT 250
Butterfly dampers
250 mm dia Nos RO
200 mm dia Nos 65
150 mm dia Nos 400
100 mm dia Nos 165
Fresh air duct termination with VCD, Wiremesh & Bell mouth Item 1
Allow for corrosion treatment on all HVAC equipment, accessories for saline
Item 1
environment
Allow for all protective painting and cleaning pipes ,Fittings and Equipment Item 1
Allow for setting out the works ,marking positions of holes ,mortices,chases or the like Item
Allow for testing of chilled water pipework during construction Item 1
Allow for all identification labels, plates,charts and identification of plant ,equipment Item 1
Allow for the provision of operating /maitenance manuals Item 1
Allow for Fire Stop material between sleeve and service ONLY. Item 1
Allow for testing and Commisoning including production of test certificates Item 1
Thermometer /Pressure Gauges Item 1
Allow for acoustic treatment as specified for all mechanical services equipment. Item 1
Any other items that is required for the satisfactory performance of the system but eat
Item 1
detailed in the BOQ, shall be included
Allow for Co-ordination with Local Authorities, Infrastructure Consultants, Structural,
Item 1
Architectural Consultants and incorporating the requirements as provided.
Allow for the preparation of shop drawings, O & M manuals and approvals. Item 1
10
BOQ - HVAC
Bill 04 - HVAC
Summary Page
SECTION 1 : EQUIPMENTS
SECTION 2 : CHILLED WATER PIPING - ( Valves, Insulation and Accessories)
SECTION 3 : DUCTING AND ITS ACCESSORIES
SECTION 4 : SUNDRIES / GENERAL ITEMS
SECTION 5 : PROVISIONAL SUM ITEMS & BUDGETARY ALLOWANCES
11
BOQ - HVAC
12
BOQ - HVAC
13
BOQ - HVAC
14
BOQ - HVAC
15
BOQ - HVAC
16
BOQ - HVAC
17
BOQ - HVAC
18
BOQ - HVAC
19
BOQ - HVAC
20
BOQ - HVAC
21
BOQ - HVAC
22