You are on page 1of 22

BOQ - HVAC

TENDER
Unit QTY RATE AMOUNT

SECTION 1 : EQUIPMENTS

SECTION 1.1 : Air Cooled Chiller as per the specifications.


ARI Standard 550-92 / Eurovent certified Air cooled screw chiller package
-IMPORTED
SITC of Air cooled Screw Chiller Package consisting of multiple nos. hermitically
sealed screw compressors (of equal capacity in independent refrigerant circuits in the
case of multiple compressors) suitable with R-134a complete with suction valve,
discharge valves, relief valve, crank case heaters, relays, purge & pressure relief
valves & Flooded chiller complete with Antifreeze cooling thermostat, electronic
expansion valve,victaulic coupling,flow switchs, chiller insulation & Aircooled
condenser interconnecting piping, suction line insulation,Aircooled chillers shall be
with condensor guard to protect from weather conditions,noise level of the chiller
without the acoustic jacket has to be submitted along with the offer,
Microprocessor control panel suitable for automatic operation incorporating all safety
function as per equipment specifications & other points as listed below: The quoted
price should also include the BMS card (open protocol) to transfer the data to
the plant manager.
The unit mouted starter panel shall be complete with IP-55 protection for air cooled
chiller consisting of power disconnecting switches with fuses, star-delta starters for
compressor motors, Starters for the condenser fans, under/over voltage trip, single
phase preventers, communication card which can accept 4-20 mA or 2-10 Vdc analog
signal.
All components shall be mounted on welded steel base frame, structural steel
profiles/panels made out of galvanized sheet steel, protected with primary coat &
finished with acrylic paint. The chiller shall be mouted on 1" deflection spring isolators.
Chiller Plant Manager is expected to carry out sequencing, scheduling, load sharing
between chillers and fetching necessary data for BMS integration as specified in the
technical specifications. Necessary hard ware / software for transfer of entire signal
to the third party BMS System. Please refer Technical Specs & requirements for
further details.
Ensure necessary Computer selection with Model / Catalogue is attached with
quote. Without Documantion as listed above will not be considered evaluation.
175 TR Aircooled Screw chillers ( 4W + 1S ) Nos 5
Ambient dry bulb temperature : 29 Deg.c
Site Elevation =7725ft above sea level
Chilled water Inlet temerature : 12 Deg.c
Chilled water outlet temerature : 7 Deg.c
Fouling factor : 0.0001 hr•ft2°F/Btu’
Refrigerant to comply with Montreal Protocol
Compressors to have VFD
Chiller to be capable of achieveing minimum 40% flow downturn

SECTION 1.2 : Primary & Secondary Chilled Water Pumps with VFD,Air seperator,Chemical Dozing,Expansion tank
Head : The Head is calculated based on initial design details how ever contractor to
select pump to match with chiller flow rate and pressure drop,actual system head is
based on the finalized equipment / pipe lengths. Head calaculation and selection to
be submitted to consultant for review / approval. The procurement shall be processed
only after head calculations & selections duly verified from the consultants.
SITC of Primary Chilled Water Pumps verical / Horizontal split casing chilled water
circulating pump set complete with TEFC motor,steel fabricated base plate,vibration
isolation pads,stuffing box with mechanical seal,Flexible pipe connectors etc. The
pumps shall be suitable for operation on 415 volts +/-10 Volts,3 phase,50 HZ AC
power supply,Pump motor should be EFF1 rated. Pump material and operating
conditions are given here under.(2Working+1 Standby) Note:FRP Hood should be
provided.
Nos 5
Type - End Suction Back pull out
Body - CI
Impeller - Bronze
Flow rate - 420 GPM / 26.5 LPS
Head - 15 mts
Minimum efficiency - 75%

SITC of Secondary Chilled Water Pumps verical / Horizontal split casing chilled water
circulating pump set complete with TEFC motor WITH Class F insulation,steel
fabricated base plate,vibration isolation pads,stuffing box with mechanical
seal,Flexible pipe connectors etc. The pumps shall be suitable for operation on 415
+/- 10 volts,3 phase,50 HZ AC power supply,Pump motor should be EFF1
rated.The motor shall be also be suitable for operation on adjustable frequency
drive.Pumpmaterial and operating conditions are given hereunder (2
Working + 1 standby).Note:FRP Hood should be provided. Nos 5
Type - End Suction Back pull out
Body - CI
Impeller - Bronze
Flow rate - 420 USGPM / 26.5 LPS
Head - 20 mts
Minimum efficiency - 75%

1
BOQ - HVAC

VARIABLE FREQUENCY DRIVES & LOGIC CONTROL PANEL


Supply, Installation, Testing & Commissioning fo variable speed pumping system
comprising of following accessories. The system shall be complete in all respects
including electrical components for motor of secondary chilled water pumps. Each
pump shall have an independent adjustable frequency drive. Common Panel with
suitable controller to control 5 Nos (4w+1s). Pumps separately. Including Auto-
Manual Star Delta Starter with suitable Amp contactors and interlocking for below
mentioned capacity motor ratings as per specs and drawing. Including sensor,
transmiter, control wiring etc complete in all respect. It shall be also BMS compatible.
Panel should be IP 55 Rated.
For Secondary chilled water pumps
Variable frequency drive (VFD) : 5 Nos
Micro processor based pump controller : 1 No
Differential pressure sensors/Transmitters : 5 Nos
Software down loaded in pump controller : Job
Auto-Manual Star-Delta starter : 5 Sets
Control wiring :As quantified below.
Variable speed pumping system described above Set 1

DPT Cabling in 19 mm MS conduit Lot 1

Supply, installation, testing & commissioning of Closed loop expansion tank as per
standards & requirements.The tank shall be made of mild steel and has a synthetic
rubber membrane. Nitrogen gas or compressed air is filled in space between the
membrane and the wall of the tank. The tank should be supplied complete with
booster pumps(1W+1S),isolating valve, check valve, drain valve & pressure gauge. Set 1
Before connecting the tank to water system, the gas pressure should be checked
through the charging valve and adjusted according to the requirements, the control
panel should also be included. The quoted price shall be inclusive of structural
support for the tank. Capacity of tank is 1000 lts+ Pumps with N+1 confirgration

Supply, installation, testing & commissioning of Air Seperator made out of MS Sheet
as per Specification and Schematic diagram - 500 Ltrs.for Chilled water system. Set 1
Pressure Rating shall be PN 16.

Chilled Water Chemical Treatment system- (Automatic Chemical dosing pot system
Set 1
+dosing Pump+Dosing pots + Cleaning Chemicals)

SECTION 1.3 : Ceiling Mounted Air Handling Units as per specifications


Supply, installation, testing and commissioning of sectional ceiling suspended Unit
double skin type complete with 25mm thick coated, fibrous-glass duct liner ,forward
curve fan section, cooling coil no of rows shall be as per coil selection, section with
coil,filter section with standard filters, fan motor, drive belt, fresh air damper and the
fan outlet velocity shall be 10.0 m/s maximum etc. as per specifications and
drawings.

Capacity- 6.2 KW, Supply Air volume - 620 L/sec, ESP-250 Pa Nos 1
Capacity- 7.1 KW, Supply Air volume - 823 L/sec, ESP-250 Pa Nos 1
Capacity- 8.2 KW, Supply Air volume - 912 L/sec, ESP-250 Pa Nos 1
Capacity- 9 KW, Supply Air volume - 824 L/sec, ESP-250 Pa Nos 2
Capacity- 9.1 KW, Supply Air volume - 822 L/sec, ESP-250 Pa Nos 1
Capacity- 9.1 KW, Supply Air volume - 1043 L/sec, ESP-250 Pa Nos 1
Capacity- 9.8 KW, Supply Air volume - 886 L/sec, ESP-250 Pa Nos 1
Capacity- 10.1 KW, Supply Air volume - 914 L/sec, ESP-250 Pa Nos 1
Capacity- 11.1 KW, Supply Air volume - 1311 L/sec, ESP-250 Pa Nos 1
Capacity- 12 KW, Supply Air volume - 1134 L/sec, ESP-250 Pa Nos 1
Capacity- 12.3 KW, Supply Air volume - 1333 L/sec, ESP-250 Pa Nos 1
Capacity- 12.4 KW, Supply Air volume - 1481 L/sec, ESP-250 Pa Nos 1
Capacity- 12.5 KW, Supply Air volume - 1414 L/sec, ESP-250 Pa Nos 4
Capacity- 13.8 KW, Supply Air volume - 1607 L/sec, ESP-250 Pa Nos 1
Capacity- 14.1 KW, Supply Air volume - 1640 L/sec, ESP-250 Pa Nos 1
Capacity- 15 KW, Supply Air volume - 1714 L/sec, ESP-250 Pa Nos 1
Capacity- 15.3 KW, Supply Air volume - 1762 L/sec, ESP-250 Pa Nos 2
Capacity- 15.9 KW, Supply Air volume - 1877 L/sec, ESP-250 Pa Nos 1
Capacity- 17.5 KW, Supply Air volume - 1951 L/sec, ESP-250 Pa Nos 1
Capacity- 20.4 KW, Supply Air volume - 2371 L/sec, ESP-250 Pa Nos 1
Capacity- 20.6 KW, Supply Air volume - 1896 L/sec, ESP-250 Pa Nos 1
Capacity- 20.8 KW, Supply Air volume - 1193 L/sec, ESP-250 Pa Nos 1
Capacity- 26 KW, Supply Air volume - 2927 L/sec, ESP-250 Pa Nos 1
Capacity- 27.1 KW, Supply Air volume - 2306 L/sec, ESP-250 Pa Nos 1
Capacity- 32 KW, Supply Air volume - 2700 L/sec, ESP-250 Pa Nos 1
Capacity- 40.8 KW, Supply Air volume - 1110 L/sec, ESP-250 Pa Nos 1
Capacity- 76.8 KW, Supply Air volume - 2253 L/sec, ESP-250 Pa Nos 1
Capacity- 99.1 KW, Supply Air volume - 2027 L/sec, ESP-250 Pa Nos 1

2
BOQ - HVAC

SECTION 1.4 : Fan Coil Units as per the specifications.


Supply, installation, testing & commissioning of blow through Fan Coil Units (FCU)
with Fan, Motor with three speed control, cooling Coil, Filter & additional insulated
drip tray with motor connecting terminals.

FCU- 0.5KW, Supply Air volume - 53 L/sec Nos 5


FCU- 0.6KW, Supply Air volume - 74 L/sec Nos 1
FCU- 0.7KW, Supply Air volume - 83 L/sec Nos 3
FCU- 0.8KW, Supply Air volume - 91 L/sec Nos 6
FCU- 0.9KW, Supply Air volume - 86 L/sec Nos 1
FCU- 1.1KW, Supply Air volume - 125 L/sec Nos 1
FCU- 1.4KW, Supply Air volume - 98 L/sec Nos 1
FCU- 1.4KW, Supply Air volume - 160 L/sec Nos 2
FCU- 1.5KW, Supply Air volume - 170 L/sec Nos 5
FCU- 1.6KW, Supply Air volume - 185 L/sec Nos 5
FCU- 1.8KW, Supply Air volume - 192 L/sec Nos 2
FCU- 2KW, Supply Air volume - 232 L/sec Nos 2
FCU- 2.1KW, Supply Air volume - 249 L/sec Nos 6
FCU- 2.2KW, Supply Air volume - 252 L/sec Nos 5
FCU- 2.3KW, Supply Air volume - 275 L/sec Nos 17
FCU- 2.4KW, Supply Air volume - 285 L/sec Nos 20
FCU- 2.5KW, Supply Air volume - 297 L/sec Nos 46
FCU- 2.6KW, Supply Air volume - 309 L/sec Nos 38
FCU- 2.7KW, Supply Air volume - 259 L/sec Nos 1
FCU- 2.7KW, Supply Air volume - 321 L/sec Nos 40
FCU- 2.8KW, Supply Air volume - 287 L/sec Nos 1
FCU- 2.8KW, Supply Air volume - 332 L/sec Nos 13
FCU- 2.9KW, Supply Air volume - 309 L/sec Nos 1
FCU- 2.9KW, Supply Air volume - 342 L/sec Nos 38
FCU- 3KW, Supply Air volume - 299 L/sec Nos 1
FCU- 3KW, Supply Air volume - 354 L/sec Nos 7
FCU- 3.1KW, Supply Air volume - 365 L/sec Nos 6
FCU- 3.2KW, Supply Air volume - 378 L/sec Nos 1
FCU- 3.3KW, Supply Air volume - 390 L/sec Nos 7
FCU- 3.5KW, Supply Air volume - 347 L/sec Nos 1
FCU- 3.5KW, Supply Air volume - 402 L/sec Nos 3
FCU- 3.6KW, Supply Air volume - 351 L/sec Nos 1
FCU- 3.7KW, Supply Air volume - 435 L/sec Nos 4
FCU- 3.8KW, Supply Air volume - 449 L/sec Nos 6
FCU- 3.9KW, Supply Air volume - 391 L/sec Nos 1
FCU- 4KW, Supply Air volume - 471 L/sec Nos 2
FCU- 4.1KW, Supply Air volume - 480 L/sec Nos 4
FCU- 4.2KW, Supply Air volume - 484 L/sec Nos 1
FCU- 4.3KW, Supply Air volume - 504 L/sec Nos 4
FCU- 4.7KW, Supply Air volume - 456 L/sec Nos 1
FCU- 4.8KW, Supply Air volume - 560 L/sec Nos 1
FCU- 5KW, Supply Air volume - 584 L/sec Nos 1
FCU- 5.3KW, Supply Air volume - 561 L/sec Nos 1
FCU- 5.3KW, Supply Air volume - 621 L/sec Nos 1
FCU- 5.4KW, Supply Air volume - 618 L/sec Nos 5
FCU- 5.8KW, Supply Air volume - 682 L/sec Nos 1
FCU- 5.9KW, Supply Air volume - 593 L/sec Nos 1
FCU- 5.9KW, Supply Air volume - 683 L/sec Nos 1
FCU- 6KW, Supply Air volume - 589 L/sec Nos 1
FCU- 6.3KW, Supply Air volume - 639 L/sec Nos 1
FCU- 8.1KW, Supply Air volume - 895 L/sec Nos 1
FCU- 11.3KW, Supply Air volume - 1131 L/sec Nos 1
FCU- 14.7KW, Supply Air volume - 1505 L/sec Nos 1
FCU- 15.9KW, Supply Air volume - 853 L/sec Nos 2

Supply, installation, testing & commissioning of Electric duct Heater for guest rooms Nos 273

SECTION 1.5 : Floor Mounted Air Handling Units


Supply, installation, testing & commissioning of double skin floor mounted AHU's as
per specification including all accessories as specified in detailed tender
specification;Pre-Plasticised Sheet/ powder coated GI sheet , Extruded Aluminium
penta post frame work, Screwless cabinet,Draw-through Fan section, coil section,
filter section, with SS Insulated drain pan; ARI certified Cooling coil of copper tubes
and aluminium fins (min. 10fins per inch) and required number of rows deep, TEFC
sq.cage induction motor of required rating; DIDW fan and washable 20micorn pre-
filter

58.4 KW , 5737 L/sec capacity with min 500 Pa ESP Nos 1


65.1 KW , 5171 L/sec capacity with min 500 Pa ESP Nos 1
75 KW , 5916 L/sec capacity with min 500 Pa ESP Nos 1

3
BOQ - HVAC

206.9 KW , 17770 L/sec capacity with min 500 Pa ESP Nos 1


239.4 KW , 9243 L/sec capacity with min 500 Pa ESP Nos 1

SECTION 1.6 : Precision Air conditioning Unit with DX coil (Data centre, B1)

Supply, Installation, Testing and commisioning of Double skin, Floor mounted bottom
discharge precision air conditioning unit , motor suitable for operation on 415 +/- 10%
volts, 50 Hz, 3 phase, A.C. power supply, DX cooling coil (No of rows shall be as per
coil selection), filter section, outlet volume control dampers with suitable actuator with
a provision for CO2 signal sensing,CO2 sensors with wiring to be included for each
unit and all the necessary accessories, necessary vibration isolators and complete as
per specifications. The duties of equipments listed below and accessories shall be as
per equipment schedule. Unit shall be with VFD and with suitable bypass starter and
BMS compatible

33.8 KW , 4765 L/sec capacity Nos 1

SECTION 1.7 : Fans

STAIRCASE PRESSUIRZATION UNIT - Supply, installation, testing, commissioning


& handing over of 0.63mm thk GI sheet metal cabinet type,floor mounted doubleskin
pressurization unit equipped with 50 mm thick, 48 kg/cum fiberglass insulation
secured in place by weld pins complete with Fan section with DIDW centrifugal
forward curved fan of, Filter section with pre filter of 90% efficiency efficiency down to
10 microns . The filter section shall be so arranged that they can be easily removed
for cleaning. Heavy duct flexible double layer canvas connection shall be provided at
the outlet of Fresh air unit Fan. All Fresh air unit shall be suitable for outdoor
installation provided with Canopy
10150 L/ S ,500 Pa ESP Nos 1
10906 L/ S ,500 Pa ESP Nos 1
14669 L/ S ,500 Pa ESP Nos 1
17042 L/ S ,500 Pa ESP Nos 1

Supply, installing, testing, commissioning & handing over of Corridor Smoke


exhaust air unit of cabinet type, Floor mounted double skin horizontal unit. Each
unit complete with squirrel cage induction motor, centrifugal fan belt drive and
vibration isolators. Motor shall be suitable for 415 +/- 10% volts with 2 Hours Fire
rated, 50 cycles AC supply with imported make fans complete with Fan section with
forward curved fan. Heavy duct flexible double layer canvas connection shall be
provided at the outlet of unit Fan.
2225 L/ S ,500 Pa ESP Nos 2

Supply, installing, testing, commissioning & handing over of Atrium Smoke exhaust
air unit, Floor mounted double skin horizontal unit. Each unit complete with squirrel
cage induction motor, centrifugal fan belt drive and vibration isolators. Motor shall be
suitable for 415 +/- 10% volts with 2 Hours Fire rated, 50 cycles AC supply with
imported make fans complete with Fan section with forward curved fan. Heavy duct
flexible double layer canvas connection shall be provided at the outlet of unit Fan.
19042 L/ S ,500 Pa ESP Nos 6

CORRIDOR MAKEUP AIR UNITS - Supply, installation, testing, commissioning &


handing over of 0.63mm thk GI sheet metal cabinet type,floor mounted doubleskin
equipped with 50 mm thick, 48 kg/cum fiberglass insulation secured in place by weld
pins complete with Fan section with DIDW centrifugal forward curved fan of, Filter
section with pre filter of 90% efficiency efficiency down to 10 microns . The filter
section shall be so arranged that they can be easily removed for cleaning. Heavy duct
flexible double layer canvas connection shall be provided at the outlet of Fresh air unit
Fan. All Fresh air unit shall be suitable for outdoor installation provided with Canopy
4025 L/S, 500 Pa ESP Nos 2

LIFTWELL/ LIFT LOBBY PRESSUIRZATION UNIT - Supply, installation, testing,


commissioning & handing over of 0.63mm thk GI sheet metal cabinet type,floor
mounted doubleskin equipped with 50 mm thick, 48 kg/cum fiberglass insulation
secured in place by weld pins complete with Fan section with DIDW centrifugal
forward curved fan of, Filter section with pre filter of 90% efficiency efficiency down to
10 microns . The filter section shall be so arranged that they can be easily removed
for cleaning. Heavy duct flexible double layer canvas connection shall be provided at
the outlet of Fresh air unit Fan. All Fresh air unit shall be suitable for outdoor
installation provided with Canopy
3428 L/S, 500 Pa ESP Nos 1
4234 L/S, 500 Pa ESP Nos 1
4234 L/S, 500 Pa ESP Nos 1
5246 L/S, 500 Pa ESP Nos 1
5432 L/S, 500 Pa ESP Nos 1

KITCHEN EXHAUST UNIT

4
BOQ - HVAC

Supply,Installation,testing and commissioning of ELECTROSTATIC PRECIPITATION


BASED DRY TYPE SCRUBBER UNIT for Kitchen exhaust. The unit shall be made of
1.0/1.5 mm thick galvanized sheet, High bake epoxy powder coated, washable
aluminum mesh pre-filter, Stainless steel spiked ionizers to create high voltage DC
field. Unit shall have aluminum collector plates with an average efficiency of 90-95%
in single pass, collector cell should be removable for cleaning..The unit shall be
integrated & connected with Kitchen Exhaust fan including all necessary accessories
to complete the installation. Air moving capacities shall be as follows
SITC of axial fan to suit below configurations
800 L/S,400 Pa ESP Nos 1
900 L/S,250 Pa ESP Nos 1
279 L/S,250 Pa ESP Nos 1

LAUNDRY EXHAUST UNIT


Supply, installing, testing, commissioning & handing over of Laundry exhaust air unit
of cabinet type, Floor mounted double skin horizontal unit. Each unit complete with
squirrel cage induction motor, centrifugal fan belt drive and vibration isolators. Motor
shall be suitable for 415 +/- 10% volts, 50 cycles AC supply, complete with Fan
section with forward curved fan with Lint filters, Heavy duct flexible double layer
canvas connection shall be provided at the outlet of unit Fan. provision to fix active
carbonated filter to be made in exhaust fan unit.
1959 L/S, 500Pa ESP Nos 1

DG VENTILATION UNIT
Supply, installing, testing & commissioning of Axial fans with Fan & motor connecting
terminals.
Fresh air fans
20000 L/s Nos 3
Exhaust air fans
20000 L/s Nos 3

DIRECT CONNECTION IN LINE CENTRIFUGAL DUCT FANS: The casing shall be


made of mild steel suitable treated for rust prevention or galvanized iron sheet of
adequate thickness. The unit shall be supplied complete with flexible connector and
flanges to connect to duct work. The package to include damper, filter, wire mesh bird
screen and cowl.
Fresh Air fans
150 L/s, 250 Pa ESP - Pump room 2 - B2 Nos 1
1200 L/s,250 Pa ESP - Pump room 1 - B2 Nos 1
6400 L/s,300 Pa ESP - STP Plant room - B2 Nos 1
2200 L/s,300 Pa ESP - Substation - B1 Nos 1

Exhaust Air Fans


50 L/s - Shop Toilet - G Nos 1
117 L/s,200 Pa ESP - Gents & Ladies Toilet - G Nos 1
136 L/s,200 Pa ESP - Pool Machine Room - GM Nos 1
165 L/s,250 Pa ESP - Pump room 2 - B2 Nos 1
194 L/s,250 Pa ESP - Garbage Room - B1 Nos 1
235 L/s,200 Pa ESP - Gents & Ladies Toilet - G Nos 1
238 L/s,250 Pa ESP - Workshop & Maintanance - B1 Nos 1
794 L/s,250 Pa ESP - Chinese Cuisine - GL Nos 1
1300 L/s,250 Pa ESP - Pump room 1 - B2 Nos 1
2633 L/s,250 Pa ESP - All Day Dinning - GM Nos 1
7100 L/s,300 Pa ESP - STP Plant room - B2 Nos 1
2200 L/s,300 Pa ESP - Substation - B1 Nos 1

SITC of Wall Mounted Propellar fan Nos RO

ECOLOGY UNIT :
Kitchen ECOLOGY Unit in Double Skin Construction, comprising of electrostatic filters
and exhaust fans as mentioned below. Panel
thickness - 25 mm (PUF insulation), Outer skin - 24G pre-coated, Inner Skin - 24G
Plain GI, Frame-Extruded aluminium profile with thermal break, Unit base-GI, Fan-
DIDW Backward curved AMCA certified, Motor-TEFC induction, suitable for air 24
hrs operation, efficiency EEF2 Scrubber :
Casing 18G GI, powder coated, pre-filters aluminium washable, Cell - Aluminium, with
ionizing/ collection section in single casing, Ioniser - Tungsten wire, Control Panel-
with panel cooling fan, ON-OFF-Wash indications, Special features such as BMS dry
contacts, short circuit-arc protection and auto restore power pack, Scrubber must be
selected for 95% or more efficiency as per ASHRAE 52.1 test.
14698 L/s, 800 Pa ESP - Main Kitchen - GL Nos 1
3334 L/s, 600 Pa ESP - Show Kitchen - GL Nos 1

CAR PARK VENTILATION FANS

5
BOQ - HVAC

Supply, installation, testing & commissioning of the following equipment & materials,
scaffoldings, all leads and lifts etc. complete as per specifications and drawings.

Exhaust Air Fan

Supply , Installation, testing and commissioning of AMCA certified Vane Axial


Exhaust air Fans suitable for 415±10% volts, 50 cycles, 3 phase AC power supply,
IP55, S1 duty, IS325, class F insulation. Single speed motor, properly supported with
MS frame, spring vibration isolators, flexible fire proof canvas, leak proof ducting
connection with civil plenum with properly grouted M.S angles. MS structure should
be painted with hot deep galvanised of minimum 80 micron DFT. The fan shall be
direct driven and with flexible connector. The noise level in the basement car parking
shall not exceed 60dBA measured 3.0m from equipment casing. Provide sound
attenuators shall to achieve required noise level if required. The fan shall be
minimum 65% efficient. Fans specified for use in carpark ventilation applications shall
be rated for 300oC, 2 hours and for normal applications shall be rated for
temperature of 55oC.
Basement 1 (Normal & fire mode)
Compartment 1 : 9500 L/s, 350 Pa ESP - Normal Mode Nos 1
Compartment 2 : 12400 L/s, 350 Pa ESP - Fire Mode Nos 1

Fresh Air Fan

Supply , Installation, testing and commissioning of AMCA certified Vane Axial fresh
air Fans suitable for 415±10% volts, 50 cycles, 3 phase AC power supply, IP55, S1
duty, IS325, class F insulation. Single speed motor, properly supported with MS
frame, spring vibration isolators, flexible fire proof canvas, leak proof ducting
connection with civil plenum with properly grouted M.S angles. MS structure should
be painted with hot deep galvanised of minimum 80 micron DFT. The fan shall be
direct driven and with flexible connector. The noise level in the basement car parking
shall not exceed 60dBA measured 3.0m from equipment casing.Provide sound
attenuators to achieve required noise level if required. The fan shall be minimum
65% efficient. Fans specified for use in carpark ventilation applications shall be rated
for 300oC, 2 hours and for normal applications shall be rated for temperature of 55oC.

Basement 1 (Normal & Fire mode)


Compartment 1 : 8600 L/s, 350 Pa ESP - Normal Mode Nos 1
Compartment 2 : 11200 L/s, 350 Pa ESP - Fire Mode Nos 1

Heat Recovery Unit with Cooling coil - 164 KW


Supply, Installation, Testing and commisioning of Double skin outdoor mounted type
Heat recovery unit made of 50mm thick panels consisting of GI casing of thickness
0.63mm outside layer and 0.63mm inside layer with 25mm thick foil faced glass fiber,
Supply & Return air Centrifugal blower(backward curved)sections with aerofoil
constructions, Heat recovery wheel section, belt drive
packages with TEFC motor suitable for operation on 415 +/- 10% volts, 50 Hz, 3
phase, A.C. power supply, cooling coil (No of rows shall be as per coil selection),
Fresh air Pre-filter section, Heat recovery descicant wheel, Fresh air, return air &
exhaust air dampers with suitable actuator with a provision for CO2 signal
sensing,CO2 sensors with wiring to be included for each unit and all the necessary Nos 1
accessories, necessary vibration isolators and complete as per specifications. The
duties of equipments listed below and accessories shall be as per equipment
schedule. Heat recovery wheel efficiency should not be less than 75%. Unit shall be
with VFD and with suitable bypass starter and BMS compatible and as per
specifications.
Fresh air and Exhaust against a static pressure of 600 ESP having suitable drive
motors
Ambient DB temperature of 29 deg.C and Wet bulb temperature of 23 Deg.C
Supply Air volume - 10475 L/sec
Return Air volume - 7388 L/sec - 24 deg C

Heat Recovery Unit with Cooling coil - 205 KW


Supply, Installation, Testing and commisioning of Double skin outdoor mounted type
Heat recovery unit made of 50mm thick panels consisting of GI casing of thickness
0.63mm outside layer and 0.63mm inside layer with 25mm thick foil faced glass fiber,
Supply & Return air Centrifugal blower(backward curved)sections with aerofoil
constructions, Heat recovery wheel section, belt drive
packages with TEFC motor suitable for operation on 415 +/- 10% volts, 50 Hz, 3
phase, A.C. power supply, cooling coil (No of rows shall be as per coil selection),
Fresh air Pre-filter section, Heat recovery descicant wheel, Fresh air, return air &
exhaust air dampers with suitable actuator with a provision for CO2 signal
sensing,CO2 sensors with wiring to be included for each unit and all the necessary Nos 1
accessories, necessary vibration isolators and complete as per specifications. The
duties of equipments listed below and accessories shall be as per equipment
schedule. Heat recovery wheel efficiency should not be less than 75%. Unit shall be
with VFD and with suitable bypass starter and BMS compatible and as per
specifications.
Fresh air and Exhaust against a static pressure of 600 ESP having suitable drive
motors
Ambient DB temperature of 29 deg.C and Wet bulb temperature of 23 Deg.C
Supply Air volume - 14045 L/sec

6
BOQ - HVAC

Return Air volume - 12352 L/sec - 24 deg C

Heat Recovery Unit with Cooling coil - 142.8 KW


Supply, Installation, Testing and commisioning of Double skin outdoor mounted type
Heat recovery unit made of 50mm thick panels consisting of GI casing of thickness
0.63mm outside layer and 0.63mm inside layer with 25mm thick foil faced glass fiber,
Supply & Return air Centrifugal blower(backward curved)sections with aerofoil
constructions, Heat recovery wheel section, belt drive
packages with TEFC motor suitable for operation on 415 +/- 10% volts, 50 Hz, 3
phase, A.C. power supply, cooling coil (No of rows shall be as per coil selection),
Fresh air Pre-filter section, Heat recovery descicant wheel, Fresh air, return air &
exhaust air dampers with suitable actuator with a provision for CO2 signal
sensing,CO2 sensors with wiring to be included for each unit and all the necessary Nos 1
accessories, necessary vibration isolators and complete as per specifications. The
duties of equipments listed below and accessories shall be as per equipment
schedule. Heat recovery wheel efficiency should not be less than 75%. Unit shall be
with VFD and with suitable bypass starter and BMS compatible and as per
specifications.
Fresh air and Exhaust against a static pressure of 500 ESP having suitable drive
motors
Ambient DB temperature of 29 deg.C and Wet bulb temperature of 23 Deg.C
Supply Air volume - 9022 L/sec
Return Air volume - 6195 L/sec - 24 deg C

Fresh air handling unit without Heat Recovery -Capacity- 38 KW


Ambient DB temperature of 29 deg.C and Wet bulb temperature of 23 Deg.C Nos 1
Supply Air volume - 3168 L/sec

Fresh air handling unit without Heat Recovery -Capacity- 175 KW


Ambient DB temperature of 29 deg.C and Wet bulb temperature of 23 Deg.C Nos 1
Supply Air volume - 14472 L/sec

Fresh air handling unit without Heat Recovery -Capacity- 27 KW


Ambient DB temperature of 29 deg.C and Wet bulb temperature of 23 Deg.C Nos 1
Supply Air volume - 2234 L/sec

Fresh air handling unit without Heat Recovery -Capacity- 11 KW


Ambient DB temperature of 29 deg.C and Wet bulb temperature of 23 Deg.C Nos 1
Supply Air volume - 900 L/sec

SECTION 1.8 : Controls - 2 Way Valve (Pressure Independent Modulating Type) package, thermostat and necessary wiring

Valve controls for AHU'S and FCU'S. (Considered below) ea 1


Room mounted thermostats(set point adjuster only) for Guest rooms, FOH areas (as
ea 1
specified by interior design)
Room mounted thermostats for BOH areas ea 1
Return Air Temperature sensors for all FCUs in FOH/BOH areas ea 1
Automatic controls for all Mechanical equipment listed under mechanical services
ea 1
specifications.
Window Pane open Micro Switch interlocked with FCU On/Off Control ea 1
FCU On/Off Control interface with facilities management system software. ea 1

TOTAL FOR SECTION 1:

SECTION 2 : CHILLED WATER PIPING - ( Valves, Insulation and Accessories)

Black steel ERW medium duty to BS 1387/API 5L Grade B Standard schedule pipes
and fittings including all supports
20 mm RMT 1700
25 mm RMT 330
32 mm RMT 450
40 mm RMT 450
50 mm RMT 550
65 mm RMT 860
80 mm RMT 900
100 mm RMT 500
125 mm RMT RO

Black steel ERW medium duty to BS 3601/API 5L Grade B Standard schedule


pipes(for pipes of dia 150 mm and above) and fittings including all supports

150 mm RMT 150


200 mm RMT 200
250 mm RMT 170

Section 2.1 : Valves

7
BOQ - HVAC

Section 2.1.1 : Butterfly valves, diameter


25 mm Nos RO
32 mm Nos RO
40 mm Nos 8
50 mm Nos 10
65 mm Nos 8
80 mm Nos 4
100 mm Nos 10
125 mm Nos RO
150 mm Nos 30
200 mm Nos RO
250 mm Nos RO

Section 2.1.2 : Ball valves with strainer, diameter


20 mm Nos 309
25 mm Nos 18
32 mm Nos 4

Section 2.1.3 : Ball valves without strainer, diameter


20 mm Nos 309
25 mm Nos 18
32 mm Nos 50

Section 2.1.5 : Strainers (Y-Strainers)


25 mm Nos 2
32 mm Nos 23
40 mm Nos 4
50 mm Nos RO
65 mm Nos RO
80 mm Nos RO
100 mm Nos RO
125 mm Nos RO
150 mm Nos 10

Section 2.1.6 : Flexible Connectors


20 mm Nos 618
25 mm Nos 36
32 mm Nos 54
40 mm Nos 8

Section 2.1.7 : Non Return Valve


150 mm Nos 10
50 mm Nos RO

Section 2.1.8 : Pressure Independent Modulating Control Valve


20 mm Nos 309
25 mm Nos 18
32 mm Nos 27
40 mm Nos 4
50 mm Nos 5
65 mm Nos 4
80 mm Nos 2
100 mm Nos 5
125 mm Nos RO

Section 2.1.9 : Air Purge Valve


Air Purge valves Nos 20
Auto Air Vent Nos 20

Section 2.1.10 : Rubber bellows


50 mm Nos 10
65 mm Nos 8
80 mm Nos 4
100 mm Nos 10
150 mm Nos 30
125 mm Nos
200 mm Nos RO

Section 2.1.11 : Flow switches


Flow switches Nos 5

Section 2.1.12 : Gauges


Temparature Gauges Nos 42
Pressure Gauges Nos 42

8
BOQ - HVAC

Section 2.1.8 : Drain valve


32 mm Nos 5
40 mm Nos 5
50 mm Nos 5

Section 2.1.9 : Balancing Valve


32 mm Nos
40 mm Nos
50 mm Nos
65 mm Nos
80 mm Nos
100 mm Nos
125 mm Nos
150 mm Nos 5
200 mm Nos

Section 2.1.10 : Motorized on-off valves, diameter


150 mm Nos 5

Section 2.1.11 : Test Points


Test Points Nos 716

Section 2.1.12 : Pot feeder for chilled water treatment


Pot feeder for chilled water treatment Nos 1

Section 2.2 : Chilled Water Piping Insulation and accessories


Chilled Water Piping Insulation Closed Cell Elastomeric Rubber (Density 55-70
Kg/m3 ) for Internal or Conditioned Area
(19 mm thick upto and including pipe size 100 mm dia 32 mm thick for all pipe sizes
above 100 mm dia)

20 mm dia with 19 mm thick insulation Sq.m


25 mm dia with 19 mm thick insulation Sq.m
32 mm dia with 19 mm thick insulation Sq.m
40 mm dia with 19 mm thick insulation Sq.m
50 mm dia with 19 mm thick insulation Sq.m
65 mm dia with 19 mm thick insulation Sq.m
80 mm dia with 19 mm thick insulation Sq.m
100 mm dia with 19 mm thick insulation Sq.m
125 mm dia with 19 mm thick insulation Sq.m

Chilled Water Piping Insulation for Piping in ean-A/C area with closed cell Elastomeric
Rubber (Density 55-70 Kg/m3) without canvas covering . Foster coating for all piping
for all bulding.
(32 mm thick upto including pipe size 80 mm dia 50 mm thick for pipesize 100 mm dia
and above)

150 mm dia with 50 mm thick insulation Sq.m


200 mm dia with 50 mm thick insulation Sq.m
250 mm dia with 50 mm thick insulation Sq.m

Chilled Water Piping Insulation for Piping in Non-A/C area with closed cell
Elastomeric Rubber (Density 55-70 Kg/m3) without canvas covering . Foster coating Item 1
for all piping for all bulding.
(32 mm thick upto including pipe size 80 mm dia 50 mm thick for pipesize 100 mm dia
Item 1
and above)
Aluminium Cladding as weather -proffing and mecahnical protection for Chilled Water
Item 1
Piping Insulation in External Areas / Exposed Areas
Leak Detection System complete with all wiring, accessories, sensors & control panel
Item 1
interfaced with BMS for chilled water line only.

TOTAL FOR SECTION 2:

SECTION 3 : DUCTING AND ITS ACCESSORIES


Ducting For AC & Ventilation ,including anti vibration mountings ,Coatings and paintings to prevent rusting and necessary accessories.

GI Ducting
26G Sq.m RO
24G Sq.m 1930
22G Sq.m 970
20G Sq.m 970
18G Sq.m 50

9
BOQ - HVAC

Kitchen Extract Ducting - 3 mm MS sheet of welded construction with Insulation, fire


Sq.m 470
rated.

Duct Acoustic Liner 25 mm thick,24 kg/m3 density Sq.m 1170

Thermal Insulation - 13mm thick closed cell Elastomeric Nitrle rubber insulation Sq.m 2745

Duct Insulation - Aluglass Insulation without canvas covering Sq.m RO

Aluminum Cladding of Duct Insulation in External Areas Sq.m 150

Flexible Ducting
250 mm dia RMT RO
200 mm dia RMT 100
150 mm dia RMT 600
100 mm dia RMT 250

Butterfly dampers
250 mm dia Nos RO
200 mm dia Nos 65
150 mm dia Nos 400
100 mm dia Nos 165

Fresh air duct termination with VCD, Wiremesh & Bell mouth Item 1

Grilles, Diffusers & Louvers

Supply air diffusers with plenum box Sq.m 70

Return air diffusers Sq.m 70

Supply air grilles Sq.m 60

Return air grilles Sq.m 60

Sand Trap Louvers Sq.m 22

Fresh Air Louvers Sq.m 30

Extract Air Louvers Sq.m 30

Volume Control Dampers (As per specifications and drawings) Sq.m 60

Fire Dampers (UL Listed) Item 1

Non Return Dampers Sq.m 10

Motorized Dampers - On General extract ductwork Item 1

Motorized Smoke Fire Dampers (UL Listed) Item 1

Sound Attenuators Sq.m 26

Pressure Relief Dampers Item 1

Access Doors For Fire Damper Item 1

TOTAL FOR SECTION 3:

SECTION 4 : SUNDRIES / GENERAL ITEMS

Allow for corrosion treatment on all HVAC equipment, accessories for saline
Item 1
environment
Allow for all protective painting and cleaning pipes ,Fittings and Equipment Item 1
Allow for setting out the works ,marking positions of holes ,mortices,chases or the like Item
Allow for testing of chilled water pipework during construction Item 1
Allow for all identification labels, plates,charts and identification of plant ,equipment Item 1
Allow for the provision of operating /maitenance manuals Item 1
Allow for Fire Stop material between sleeve and service ONLY. Item 1
Allow for testing and Commisoning including production of test certificates Item 1
Thermometer /Pressure Gauges Item 1
Allow for acoustic treatment as specified for all mechanical services equipment. Item 1
Any other items that is required for the satisfactory performance of the system but eat
Item 1
detailed in the BOQ, shall be included
Allow for Co-ordination with Local Authorities, Infrastructure Consultants, Structural,
Item 1
Architectural Consultants and incorporating the requirements as provided.
Allow for the preparation of shop drawings, O & M manuals and approvals. Item 1

10
BOQ - HVAC

Allow for the Interfacing with External networks Item 1


Allow for 3rd party testing and commissioning of entire HVAC system. Item 1
Allow for appointment of commissioning manager for intergrating all the
Item 1
commissioning agencies of entire MEP systems.
Allow for Swimming Pool Heating and Cooling as per the specialist requirement Item 1
Allow for sealants, paints and coatings for all MEP services, the VOC limit to fall
Item 1
under EHS guidelines.
Allow for enhanced commissioning for 10 months after building hand over. Item 1
Allow for outdoor air monitoring sensors in FA ductwork, on air inlet points and
Item 1
interfacing with FAHU.
Allow for CO2 monitoring sensors in restaurants, conference room and interfacing
Item 1
with FAHU- One Sensor for every 200 Sq m

TOTAL FOR SECTION 4:

SECTION 5 : PROVISIONAL SUM ITEMS & BUDGETARY ALLOWANCES


PC Sum Items for undetailed components of the project which are to be detailed at a later date. Tenderers are to include a % mark up
on
PCthis PC Sum
amount value
for the which
supply will
and be representative
installations of the mark
of unspecified HVACupunits
payable based on the final appointed value for this PC su
for this
SUM
development
- Add % of PC Sum item amount for Procuring, ordering, storing, markup, co-
%
ordination etc.
Budgetary Allowance for the supply and installation and commissioning of Kitchen
SUM
Hoods

TOTAL FOR SECTION 5:

Bill 04 - HVAC
Summary Page
SECTION 1 : EQUIPMENTS
SECTION 2 : CHILLED WATER PIPING - ( Valves, Insulation and Accessories)
SECTION 3 : DUCTING AND ITS ACCESSORIES
SECTION 4 : SUNDRIES / GENERAL ITEMS
SECTION 5 : PROVISIONAL SUM ITEMS & BUDGETARY ALLOWANCES

TOTAL FOR BILL NO.04:

11
BOQ - HVAC

12
BOQ - HVAC

13
BOQ - HVAC

14
BOQ - HVAC

15
BOQ - HVAC

16
BOQ - HVAC

17
BOQ - HVAC

18
BOQ - HVAC

19
BOQ - HVAC

20
BOQ - HVAC

21
BOQ - HVAC

22

You might also like