You are on page 1of 17

Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

PROJECT: OZONE GALLERIA MALL @ RANCHI


BILL OF QUANTITIES FOR HVAC LOW SIDE WORKS
DATE : 06.09.2013 Revision-R0
Sl No Description Unit Qty Rate Amount

Note: The contractor should read the specifications thoroughly and quote the price for
each item. The BOQ should read in conjuction with specification, drawing & equipment
schedule.
NOTE : Quoted price shall be inclusive of Supply, sea freight, insurance, packing and
forwarding charges etc., as applicable

COOLING TOWER
1.00
Supply, Installation, testing and commissioning of CTI approved MULTI CELL INDUCED
DRAFT CROSS FLOW COOLING TOWERS for airconditioning system. Each tower shall be
complete with basin, casing, distribution system, filling, louvers, ladder, fan, Motor and
other complete accessories as described in the technical specifications. Motor shall be
suitable for 415±10% volts, 50 cycles and 3 phase power supply. Tower shall be designed
with high efficiency drift eliminators to meet current environmental standards and
guidelines for microbial control. Each tower cell must be installed with individual cold
water basins and water discharge sumps to facilitate maintenance without causing
disruption to the other cells in operation. Tower for airconditioning system shall be
selected on the basis of following parameters Refer Equipment schedule & Technical
Specification for details

Make : Marley /BAC / Advance


a Cooling Tower – 825 USGPM Nos 2
Ambient WB Temperature : 82°F
Cooling capacity : 275TR
Leaving water leaving temperature : 87 °F
Entering water entering temperature : 97 °F

I TOTAL VALUE FOR COOLING TOWER

II CENTRIFUGAL PUMPS

PRIMARY CHILLED WATER PUMPS


1.00 Supply, installation, testing & commissioning of Centrifugal monobloc type pumpset motor
shall be suitable for 415 + 10% volts, 50 cycles/second, 3-phase power supply. The quoted
price shall include cost of thermal insulation and cladding . The unit complete should be
suitable for outdoor installation at the roof of the building. Refer Equipment schedule &
Technical Specification for details

Make : ITT BELL & GOSSETT, GRUNDFOS, Armstrong


1.10 Primary Chilled Water pumps Nos 4
660 USGPM
Head in Ft - 40

SECONDARY CHILLED WATER PUMPS


2.00 Supply, installation, testing & commissioning of End Suction Back pull out Centrifugal
chilled water pumpsets suitable for VFD. Factory mounted on a common base with electric
motor for recirculation of water for the central air conditioning system. All pumps shall be
aligned properly as required and complete with mechanical seal. The pump motor shall be
suitable for 415 + 10% volts, 50 cycles/second, 3-phase power supply. The quoted price
shall include cost of thermal insulation and cladding . The unit complete should be suitable
for outdoor installation at the roof of the building. Refer Equipment schedule & Technical
Specification for details

Make : ITT BELL & GOSSETT, GRUNDFOS, Armstrong


2.10 Secondary Chilled Water pumps Nos 4

Consultants :- Entask Consultancy


Architects: BENTEL ASSOCIATES Page 1 of 16 services Pvt Ltd.
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

Sl No Description Unit Qty Rate Amount


660 USGPM - 17 KW
Head in Ft - 90

2.11 Supply, installation, testing & commissioning of VFD, VFD controller, microprocessor panel
necessary cabling, two sets of sensors, required enclosure, with By Pass control, including lot 1
cabling and cable Termination etc.

CONDENSER CHILLED WATER PUMPS


3.00 Supply, installation, testing & commissioning of End Suction Back pull out type pumpset
motor shall be suitable for 415 + 10% volts, 50 cycles/second, 3-phase power supply. The
quoted price shall include cost of thermal insulation and cladding . The unit complete
should be suitable for outdoor installation at the roof of the building. Refer Equipment
schedule & Technical Specification for details

Make : ITT BELL & GOSSETT, GRUNDFOS, Armstrong


3.10 Condenser Chilled Water pumps Nos 3
825 USGPM -
Head in Ft - 40

II TOTAL VALUE FOR CENTRIFUGAL PUMPS

III AIR HANDLING UNITS

1.00 Supply, installation, testing & commissioning of Double skin construction draw thru type
Horizontal Floor mounted / CEILING SUSPENDED AIR HANDLING UNITS with 25 mm thick
Sandwitched PUF insulation as per specification & as indicated in the Equipment Schedule.
Each complete with DIDW FORWARD Curved Centrifugal Fan, Pre filter of 10 micron, 6
row deep water coil of copper tube & aluminium fins construction with blue Hydraufillic
coating for chilled water coil, coil size shall be selected for a maximum face velocity of 500
feet/minute. and squirrel cage induction motor, centrifugal fan belt drive and vibration
isolators, Limit switches,Emergency Light , Guard for inspection door. Motor shall be
suitable for 415±10% volts, 50 cycles/second, 3 phase AC supply and also suitable for VFD
operation. Note: AHU shall be supplied with one set of pre commissioning filters. Refer
Equipment schedule & Technicla Specification for details

Make : Caryaire / VTS / Zeco / Edgetech


1.01 LGF-AHU-01 - 35 TR/ Nos 1
1.02 LGF-AHU-02 - 30 TR Nos 1
1.03 LGF-CSU-01 - 30 TR Nos 1
1.04 LGF-CSU-02 - 30 TR Nos 1
1.05 LGF-CSU-03 - 30 TR Nos 1
1.06 LGF-CSU-04 - 30 TR Nos 1
1.07 LGF-CSU-05 - 30 TR Nos 1
1.08 LGF-CSU-06 - 30 TR Nos 1
1.09 LGF-CSU-07 - 10 TR Nos 1
1.10 LGF-CSU-08 - 30 TR Nos 1
1.11 GF-AHU-01 - 30 TR Nos 1
1.12 GF-AHU-02 - 28 TR Nos 1
1.13 GF-CSU-01 - 17 TR Nos 1
1.14 GF-CSU-02 - 4.0 TR Nos 1
1.15 GF-CSU-03 - 3.0 TR Nos 1
1.16 GF-CSU-04 - 5.0 TR Nos 1
1.17 GF-CSU-05 - 5.0 TR Nos 1
1.18 GF-CSU-06 - 5.0 TR Nos 1
1.19 GF-CSU-07 - 5.0 TR Nos 1
1.20 GF-CSU-08 - 25 TR Nos 1
1.21 GF-CSU-09 - 11 TR Nos 1
1.22 GF-CSU-10 - 5.0 TR Nos 1
1.23 GF-CSU-11 - 4.0 TR Nos 1
1.24 GF-CSU-12 - 4.0 TR Nos 1
1.25 GF-CSU-13 - 5.0 TR Nos 1
1.26 GF-CSU-14 - 4.0 TR Nos 1

Consultants :- Entask Consultancy


Architects: BENTEL ASSOCIATES Page 2 of 16 services Pvt Ltd.
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

Sl No Description Unit Qty Rate Amount


1.27 GF-CSU-15 - 5.0 TR Nos 1
1.28 GF-CSU-16 - 25 TR Nos 1
1.29 1F-AHU-01 - 27 TR Nos 1
1.30 1F-AHU-02 - 27 TR Nos 1
1.31 1F-CSU-01 - 16 TR Nos 1
1.32 1F-CSU-02 - 2.0 TR Nos 1
1.33 1F-CSU-03 - 3.0 TR Nos 1
1.34 1F-CSU-04 - 3.0 TR Nos 1
1.35 1F-CSU-05 - 5.0 TR Nos 1
1.36 1F-CSU-06 - 4.0 TR Nos 1
1.37 1F-CSU-07 - 4.0 TR Nos 1
1.38 1F-CSU-08 - 5.0 TR Nos 1
1.39 1F-CSU-09 - 21 TR Nos 1
1.40 1F-CSU-10 - 4.0TR Nos 1
1.41 1F-CSU-11 - 4.0TR Nos 1
1.42 1F-CSU-12 - 4.0TR Nos 1
1.43 1F-CSU-13 - 4.0TR Nos 1
1.44 1F-CSU-14 - 12TR Nos 1
1.45 1F-CSU-15 - 4.0TR Nos 1
1.46 1F-CSU-16 - 4.0TR Nos 1
1.47 1F-CSU-17 - 5.0TR Nos 1
1.48 1F-CSU-18 - 3.0TR Nos 1
1.49 1F-CSU-19 - 3.0TR Nos 1
1.50 1F-CSU-20 - 3.0TR Nos 1
1.51 1F-CSU-21 - 3.0TR Nos 1
1.52 1F-CSU-22 - 21TR Nos 1
1.53 2F-AHU-01 - 28 TR Nos 1
1.54 2F-AHU-02 - 27 TR Nos 1
1.55 2F-CSU-01 - 16TR Nos 1
1.56 2F-CSU-02 - 2.0TR Nos 1
1.57 2F-CSU-03 - 2.0TR Nos 1
1.58 2F-CSU-04 - 3.0TR Nos 1
1.59 2F-CSU-05 - 3.0TR Nos 1
1.60 2F-CSU-06 - 4.0TR Nos 1
1.61 2F-CSU-07 - 4.0TR Nos 1
1.62 2F-CSU-08 - 4.0TR Nos 1
1.63 2F-CSU-09 - 4.0TR Nos 1
1.64 2F-CSU-10 - 22TR Nos 1
1.65 2F-CSU-11 - 4.0TR Nos 1
1.66 2F-CSU-12 - 2.0TR Nos 1
1.67 2F-CSU-13 - 3.0TR Nos 1
1.68 2F-CSU-14 - 12TR Nos 1
1.69 2F-CSU-15 - 4.0TR Nos 1
1.70 2F-CSU-16 - 4.0TR Nos 1
1.71 2F-CSU-17 - 5.0TR Nos 1
1.72 2F-CSU-18 - 3.0TR Nos 1
1.73 2F-CSU-19 - 3.0TR Nos 1
1.74 2F-CSU-20 - 3.0TR Nos 1
1.75 2F-CSU-21 - 3.0TR Nos 1
1.76 2F-CSU-22 - 22TR Nos 1
1.77 3F-AHU-01 - 26 TR Nos 1
1.78 3F-AHU-02 - 22 TR Nos 1
1.79 3F-CSU-01- 3.0TR Nos 1
1.80 3F-CSU-02- 3.0TR Nos 1
1.81 3F-CSU-03- 4.0TR Nos 1
1.82 3F-CSU-04- 2.0TR Nos 1
1.83 3F-CSU-05- 2.0TR Nos 1
1.84 3F-CSU-06- 2.0TR Nos 1
1.85 3F-CSU-07- 2.0TR Nos 1
1.86 3F-CSU-08- 2.0TR Nos 1
1.87 3F-CSU-09- 4.0TR Nos 1
1.88 3F-CSU-10- 5.0TR Nos 1
1.89 3F-CSU-11- 33TR Nos 1

Consultants :- Entask Consultancy


Architects: BENTEL ASSOCIATES Page 3 of 16 services Pvt Ltd.
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

Sl No Description Unit Qty Rate Amount


1.90 3F-CSU-12- 4.0TR Nos 1
1.91 3F-CSU-13- 4.0TR Nos 1
1.92 3F-CSU-14- 4.0TR Nos 1
1.93 3F-CSU-15- 4.0TR Nos 1
1.94 3F-CSU-16- 8.0TR Nos 1
1.95 3F-CSU-17- 17TR Nos 1
1.96 3F-CSU-18- 3.0TR Nos 1
1.97 4F-AHU-01 - 18 TR Nos 1
1.98 4F-AHU-02 - 18 TR Nos 1
1.99 4F-CSU-01- 22TR Nos 1
2.00 4F-CSU-02- 20TR Nos 1
2.01 4F-CSU-03- 9.0TR Nos 1
2.02 4F-CSU-04- 20TR Nos 1
2.03 5F-AHU-01 - 17 TR Nos 1
2.04 5F-AHU-02 - 24 TR Nos 1
2.05 5F-AHU-03 - 16 TR Nos 1
2.06 5F-AHU-04 - 20 TR Nos 1

III TOTAL VALUE FOR AIR HANDLING UNITS

IV CENTRIFUGAL FANS FOR VENTILATION

PRESSURIZATION FANS
Supply, Installation, Testing and Commissioning of cabinet type Double Skin construction
draw thru type , Floor Mounted type Fresh Air Handling Units with 50 mm thick , Intake
Plenum, suitable for Outdoor installation of below mentioned capacities( Fan & Filter
section only ) as per specification and as indicated in the drawing. Each complete TEFC
squirrel cage induction motor, Each complete with DIDW forward Curved aerofoil blade
1
Centrifugal Fan, belt drive and vibration isolators, Limit switches, Emergency Light, Motor
shall be suitable for and 415 +/- 10% Volts, 50Hz, 3 phase AC supply and Motor shall be
suitable for 415±10% volts, 50 cycles/second, 3 phase AC supply and also suitable for VFD
operation. The unit shall be suitable for outdoor installation.

Make : Kruger / Nicotra


a LIFT WELL PRESSURIZATION
b TE-LWP -01,02,03 & 04 Nos 7
5000 CFM TSP - 75MM WG

e STAIRCASE PRESSURIZATION.
f TE-SP-01 & 02 Nos 3
12000 CFM TSP - 75MM WG

g PUMP ROOM FRESH AIR UNIT ( CEILING SUPSENDED TYPE)


LB-FAU-01 Nos 1
2000 CFM TSP - 75MM WG

Consultants :- Entask Consultancy


Architects: BENTEL ASSOCIATES Page 4 of 16 services Pvt Ltd.
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

Sl No Description Unit Qty Rate Amount


SEWAGE TREATMENT PLANT VENTILATION FAN
Supply, Installation, Testing and Commissioning of cabinet type Double Skin construction
draw thru type , Floor Mounted type Exhaust Units with 50 mm thick , Intake Plenum,
suitable for Outdoor installation of below mentioned capacities( Fan & Filter section only )
as per specification and as indicated in the drawing. Each complete TEFC squirrel cage
induction motor, Each complete with DIDW forward Curved aerofoil blade Centrifugal Fan,
2
belt drive and vibration isolators, Limit switches, Emergency Light, Motor shall be suitable
for and 415 +/- 10% Volts, 50Hz, 3 phase AC supply and Motor shall be suitable for
415±10% volts, 50 cycles/second, 3 phase AC supply and also suitable for VFD operation.
The unit shall be suitable for outdoor installation.

TF - EAU - 01 Nos 1
8000 CFM TSP - 65MM WG

PUMP ROOM VENTILATION FAN


Supply, Installation, Testing and Commissioning of cabinet type Double Skin construction
draw thru type , Suspeneded type Exhaust Units with 50 mm thick , Intake Plenum,
suitable for Outdoor installation of below mentioned capacities( Fan & Filter section only )
as per specification and as indicated in the drawing. Each complete TEFC squirrel cage
induction motor, Each complete with DIDW forward Curved aerofoil blade Centrifugal Fan,
3
belt drive and vibration isolators, Limit switches, Emergency Light, Motor shall be suitable
for and 415 +/- 10% Volts, 50Hz, 3 phase AC supply and Motor shall be suitable for
415±10% volts, 50 cycles/second, 3 phase AC supply and also suitable for VFD operation.
The unit shall be suitable for outdoor installation.

LB - EAU - 01 Nos 1
2000 CFM TSP - 75MM WG

IV TOTAL VALUE FOR CENTRIFUGAL FANS

V PIPING WORKS

PIPING
1.00 Supply, installation, testing & commissioning of MS class ‘C’ pipes for chilled water cut to
required lengths and installed with all welded joints, providing and fixing in position with
the necessary fittings like elbows, tees and reducers, sockets for probe meter: Supports,
Support hangers with vibration isolation arrangement as per specification, drawings /
details.

Make : Jindal /Tata


1.01 350 mm dia Rmt 100
0.01 300 mm dia Rmt
0.02 250 mm dia Rmt 300
0.03 200 mm dia Rmt 100
0.04 150 mm dia Rmt 30
0.05 125 mm dia Rmt 30
0.06 100 mm dia Rmt 25
0.07 80 mm dia Rmt 600
0.08 65 mm dia Rmt 600
0.09 50 mm dia Rmt 780
0.10 40 mm dia Rmt 100
0.11 32 mm dia Rmt 100
0.12 25 mm dia Rmt 450

BUTTERFLY VALVES
2.00 Supply, Installation, testing &commissioning of Butterfly valves with PN 10 rating with
matching flanges. The valves should have feasiblity of changing the inner lining if wornout
and the handles should have lockable facility. (For details refer Technical specfication).

Make : Audco /Advance /Shakthi


2.01 350 mm dia Nos R.O
2.01 300 mm dia Nos R.O
2.02 250 mm dia Nos 4
2.03 200 mm dia Nos 38

Consultants :- Entask Consultancy


Architects: BENTEL ASSOCIATES Page 5 of 16 services Pvt Ltd.
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

Sl No Description Unit Qty Rate Amount


2.04 150 mm dia Nos R.O
2.05 125 mm dia Nos R.O
2.06 100 mm dia Nos 2
2.07 80 mm dia Nos 90
2.08 65 mm dia Nos 11
2.09 50 mm dia Nos 124
2.10 40 mm dia Nos R.O
2.11 32 mm dia Nos R.O
2.12 25 mm dia Nos R.O

BALL VALVES
3.00 Supply, installation, testing & commissioning of Ball valve with PN 10 rating and matching
flanges (For details refer Technical specfication).
Make : Audco /Advance /Shakthi
3.01 40 mm dia Nos 25
3.02 32 mm dia Nos 25
3.03 25 mm dia Nos 305

BALL VALVES WITH STRAINER


4.00 Supply, installation, testing & commissioning of Ball valve with stainer with PN 10 rating
and matching flanges (For details refer Technical specfication).
Make : Audco /Advance /Shakthi
4.01 40 mm dia Nos R.O
4.02 32 mm dia Nos R.O
4.03 25 mm dia Nos R.O

GATE VALVE
5.00 Supply, installation, testing & commissioning of Gate Valves with matching flanges with
PN 10 rating (For details refer Technical specfication).
Make : Audco /Advance /Shakthi
5.01 50 mm dia Nos R.O
5.02 32 mm dia Nos R.O
5.03 25 mm dia Nos R.O

AUTOMATIC BALANCING VALVE


6.00 Supply, installation, testing & commissioning of Automatic Balancing Valve with matching
flanges with PN 10 rating (For details refer Technical specfication).
Make : TA/ Flowcon / frese /Danfoss
6.01 250 mm dia Nos 2
6.02 200 mm dia Nos 8
6.03 150 mm dia Nos R.O
6.04 125 mm dia Nos R.O
6.05 100 mm dia Nos R.O
6.06 80 mm dia Nos 10
6.07 65 mm dia Nos 1
6.08 50 mm dia Nos 24
6.09 40 mm dia Nos 5
6.10 32 mm dia Nos 5
6.11 25 mm dia Nos 61

Consultants :- Entask Consultancy


Architects: BENTEL ASSOCIATES Page 6 of 16 services Pvt Ltd.
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

Sl No Description Unit Qty Rate Amount


2 - WAY VALVE
7.00 Supply, installation, testing & commissioning of 2-way balancing Valve with matching
flanges with PN 10 rating (For details refer Technical specfication). The valve should be
above provide position feed back status.
Make : TA/ Flowcon / frese /Danfoss
7.01 250 mm dia Nos R.O
7.02 200 mm dia Nos R.O
7.03 150 mm dia Nos R.O
7.04 125 mm dia Nos R.O
7.05 100 mm dia Nos R.O
7.06 80 mm dia Nos 10
7.07 65 mm dia Nos 1
7.08 50 mm dia Nos 24
7.09 40 mm dia Nos 5
7.10 32 mm dia Nos 5
7.11 25 mm dia Nos 61

PUMP SUCTION GUIDE


8.00 Supply, installation, testing & commissioning of Pump suction guide with stainer &
matching flanges with PN 10 rating (For details Technical specfication).
Make : Sant / Emerald
8.01 200 mm dia Nos 11
8.02 150 mm dia Nos R.O

Y - STRAINER
9.00 Supply, installation, testing & commissioning of Y Strainers with matching flanges with PN
10 rating (For details refer Technical specfication) .
Make : Sant / Emerald
9.01 200 mm dia Nos R.O
9.02 150 mm dia Nos R.O
9.03 125 mm dia Nos R.O
9.04 100 mm dia Nos R.O
9.05 80 mm dia Nos 10
9.06 65 mm dia Nos 1
9.07 50 mm dia Nos 24
9.08 40 mm dia Nos 5
9.09 32 mm dia Nos 5
9.10 25 mm dia Nos 61

DUAL PLATE CHECK VALVE


10.00 Supply, installation, testing & commissioning of Dual Plate Check Valve with matching
flanges with PN 10 rating (For details refer Technical specfication).
Make : Audco /Advance /Shakthi
10.01 250 mm dia Nos R.O
10.02 200 mm dia Nos 3
10.03 150 mm dia Nos 8
10.04 125 mm dia Nos R.O
10.05 100 mm dia Nos R.O

MOTORISED ON/OFF VALVE


11.00 Supply, installation, testing & commissioning of Motorised on/off valve with PN 10 rating
(For details refer Technical specfication).
Make : Audco /Advance /Shakthi
11.01 300 mm dia Nos R.O
11.02 200 mm dia Nos 8
11.03 150 mm dia Nos R.O
11.04 125 mm dia Nos R.O
11.05 100 mm dia Nos R.O
11.06 80 mm dia Nos R.O
11.07 65 mm dia Nos R.O
11.08 50 mm dia Nos R.O
11.09 40 mm dia Nos R.O
11.10 32 mm dia Nos R.O
11.11 25 mm dia Nos R.O

Consultants :- Entask Consultancy


Architects: BENTEL ASSOCIATES Page 7 of 16 services Pvt Ltd.
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

Sl No Description Unit Qty Rate Amount

DIAL TYPE THERMOMETER


12.00 Supply, installation, testing & commissioning of Dial type thermometer (For details refer
Nos 212
Technical specfication).
Make : H GURU / Warry

PRESSURE GAUGE
13.00 Supply, installation, testing & commissioning of Pressure gauge (For details refer Technical
Nos 250
specfication).
Make : H GURU / Warry

FLEXIBLE CONNECTIONS
14.00 Supply, installation, testing & commissioning of Flexible connections of suitable pressure
rating to be installed at CHILLERS, AHU's & Pumpsets inlets & outlets and at pipes crossing
building expansion joints with suitable Flanges (For details refer Technical specfication).

Make : UP Twiga / Arma Flex


14.01 200 mm dia Nos 38
14.02 150 mm dia Nos R.O
14.03 125 mm dia Nos R.O
14.04 100 mm dia Nos R.O
14.05 80 mm dia Nos 20
14.06 65 mm dia Nos 2
14.07 50 mm dia Nos 56
14.08 40 mm dia Nos 10
14.09 32 mm dia Nos 10
14.10 25 mm dia Nos 122

Consultants :- Entask Consultancy


Architects: BENTEL ASSOCIATES Page 8 of 16 services Pvt Ltd.
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

Sl No Description Unit Qty Rate Amount


EXPANSION TANK
15.00 Supply, installation, testing & commissioning of Closed loop expansion tank as per
standards & requirements.The tank shall be made of mild steel and has a synthetic rubber
membrane. Nitrogen gas or compressed air is filled in space between the membrane and
the wall of the tank. The tank should be supplied complete with pumps(1W+1S), isolating
valve, check valve, drain valve & pressure gauge. Before connecting the tank to water Nos 1
system, the gas pressure should be checked through the charging valve and adjusted
according to the requirements. The quoted price shall be inclusive of structural support for
the tank. Capacity of tank is 300 lts.

Make : Anergy / ITT Industries / Grundfos

DRAIN VALVE
16 Drain Valve 25 mm dia Nos. 50
Make : RB / Belimo

AIR SEPARATOR
17 AIR SEPERATOR300 Dia as per the schematic diagram Nos. 1
Make : Anergy / ITT Industries

CHEMICAL DOSING POT


18 Supply, installation, testing & commissioning of Chemical dosing pot along with valves to
Nos 1
be installed at Chillers water inlet line, as per Specifications.
Make : Ion Exchange / PMI Process

AUTO AIR VENT


19 Supply, installation testing & commissioning of Auto Air vents Nos 20
Make : Anergy

TEST POINT
20 Test points For taking pressure & temperature measurements in Chiller's. Nos. 12
Make : H GURU / Warry

21 DRAIN PIPING

Supply,installation, testing & commissioning of followig sizes insulated GI drain pipes Class
'B' from Ahu drain pans to nearest floor drain dnd from CHW pump glands to the nearest
drain complete with interconnection,flanges,elbows,tees,nuts,U-trap etc.the insulation
should be similar to chilled water piping insulation

21.01 80mm dia Rmt R.O


21.02 65mm dia Rmt R.O
21.03 50mm dia Rmt 100
21.04 40mm dia Rmt 100
21.05 25mm dia Rmt 50

V TOTAL VALUE FOR PIPING SYSTEM

Consultants :- Entask Consultancy


Architects: BENTEL ASSOCIATES Page 9 of 16 services Pvt Ltd.
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

Sl No Description Unit Qty Rate Amount


VI AIR DISTRIBUTION SYSTEM

1.00 Supply, Fabrication, installation and testing of sheet metal ducts (FACTORY FABRICATED
DUCTS) in accordance with the approved shop drawings complete with all accessories like
vanes, flanges, suspension rods , anchor bolts, GI bolts & nuts, canvas connections , duct
dampers & splitter dampers etc.,and as required by the specifications. All size duct should
be with ductmate joints. No C & Ss clip joints should be used

Make : Sail / Jindal / TATA


1.01 24 gauge galvanised sheet steel Sqm 2600
1.02 22 gauge galvanised sheet steel Sqm 400
1.03 20 gauge galvanised sheet steel Sqm 150
1.04 18 gauge galvanised sheet steel Sqm R.O

2.00 Supply, installation, testing and balancing of GSS Volume Control Dampers with operating
handle for Supply air duct branches in accordance with the approved shop drawings and Sqm 16
specifications.
Make : Air Master / KC Industries / Caryaire

3.00 Supply installation testing and commissioning of Fire damper complete with standard
accessories and 600 mm sleeve as per specifications. (Only Damper price of total Cross- Sqm 9
sectional Area)
Make : Air Master / Caryaire / RaviStar with UL Listing

4.00 Supply installation testing and commissioning of Fire/Smoke damper suitable for
motorized actuators, sensors, controls & all accessories as per specification - Torque 5 NM Nos

Make : Belimo / Siemens

EXHUAST VALES FOR TOILETS


5.00 Supply, installation,testing & balancing of Exhaust Valves for Toilet Exhaust as per
specifications & approved shop drawings for the following sizes.
Make : Air Master / Caryaire
5.01 150 Dia Nos R.O
5.02 200 Dia Nos R.O
5.03 100 Dia Nos R.O

6.00 Supply, installation, testing and balancing of powder coated Extruded Aluminium supply air
Diffusers with removable core , Aluminium opposed blade volume control dampers in
accordance with the approved shop drawings and specifications to fit in the tile size of 600
x 600. The neck size shall be of following sizes

Make : Air Master / Caryaire


6.01 450 x 450 Nos R.O
6.02 375 x 375 Nos 10
6.03 300 x 300 Nos 10
6.04 225 x 225 Nos R.O

Consultants :- Entask Consultancy


Architects: BENTEL ASSOCIATES Page 10 of 16 services Pvt Ltd.
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

Sl No Description Unit Qty Rate Amount


7.00 Supply, installation, testing and balancing of powder coated Extruded Aluminium Return
air diffusers with removable core, in accordance with the approved shop drawings and
specifications to fit in the tile size of 600 x 600. The neck size shall be of following sizes

Make : Air Master / Caryaire


7.01 450 x 450 Nos R.O
7.02 375 x 375 Nos 20

8.00 Supply, installation, testing & commissioning of spill boxes made of 22G G.I with round
neck necessary threaded rods for supporting & anchor fasten the of following sizes.

Make : RolaStar / Zeco


8.01 600 x 600 X 350 Nos R.O
8.02 150 x 150 X 250 Nos 370
8.03 400 x 400 X 350 Nos R.O

9.00 Supply, installation, testing & commissioning of Spigot & Butterfly Dampers of the
following sizes
Make : Air Master / KC Industries / Caryaire
9.01 300 mm dia Nos R.O
9.02 250 mm dia Nos R.O
9.03 100 mm dia Nos 370

10.00 Supply, Fabrication, installation and testing of the insulated flexible ducting , complete
with connecting rings, duct supports etc as per standards and specification

Make : Asiana pack / caryaire / interlock


10.01 250 dia Rm R.O
10.02 200 dia Rm R.O
10.03 150 dia Rm 550

11.00 Supply & installation , testing and balancing of Al. Powder coated Continuous grills with
necessary flanges for supply & return air of the following sizes.
Make: Airmaster / Caryaire / Rolastar / Dynacraft
11.01 100 mm wide continous grille Sqm RO
11.02 150 mm wide continous grille Sqm 10
11.03 200 mm wide continous grille Sqm RO
11.04 350 mm wide (STP Ventilation) grille Sqm RO
11.05 200 mm wide (PUMP ROOM Ventilation) Sqm RO
11.06 500 mm wide continous grille Sqm RO
11.07 300 mm wide continous grille Sqm RO
11.08 Aluminium. collar damper Sqm RO

FA LOUVER
12.00 Supply, & installation of powder coated Al. Louver for fresh air , filter, etc as per the sizes
Sqm 6
indicated in the drawing.
Make : Air Master / Caryaire

13.00 Supply, installation and laying of INSULATION FOR FRESH AIR DUCTS with 50MM thick EPS
Sqm RO
and Sand Cement plaster

VI TOTAL VALUE FOR AIR DISTRIBUTION SYSTEM

Consultants :- Entask Consultancy


Architects: BENTEL ASSOCIATES Page 11 of 16 services Pvt Ltd.
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

Sl No Description Unit Qty Rate Amount


VII INSULATION

NITRILE RUBBER INSULATION - Chilled Water Pipes


1.00 Supply, installation and testing of TF Quality Class 'O' Nitrile rubber of preformed pipe
section ( Thicknes as below ) for all pipes with factory laminated aluminum foil facing,,
'fittings, valves, unions, etc as per specifications. The exposed pipes on terrace shall be
with FRP lining and quoted with uv protective paints .

The insulation should meet the green building norms.


Make : Lloyds / Beardsell
1.01 350 mm dia Rmt 100
1.02 300 mm dia Rmt 300
1.03 250 mm dia Rmt 100
1.04 200 mm dia Rmt 30
1.05 150 mm dia Rmt 30
1.06 125 mm dia Rmt 25
1.07 100 mm dia Rmt 600
1.08 80 mm dia Rmt 600
1.09 65 mm dia Rmt 780
1.10 50 mm dia Rmt 100
1.11 40 mm dia Rmt 100
1.12 32 mm dia Rmt 450
1.13 25 mm dia

ACCOUSTIC INSULATION
2.00 Supply, installation and testing of TF Quality Acoustic lining for supply and return air ducts
with 25 mm thick rigid fibre glass of 48Kg/Cum density covered with factory laminated RP
Tissue and finished with with 26G Perforated Aluminium sheet as per the specifications Sqm 300
and as detailed in the drawings. (For details refer Technical specfication).

Make : UP Twiga / Owens corning / Kimmco

AHU/MECHANICAL PLANT ROOM


3.00 Supply and installation of acoustic lining on walls the AHU/mechanical plant room with
50 mm thick TF quality fibre glass and 48 Kg/Cum density with GI frame grid and covered
Sqm 2800
with 22G perforated GI sheet as per the approved shop drawings & specifications. (For
details Technical specfication).
Make : KC Industries / Eqvt

NITRILE RUBBER - Ducts


4.00 Supply & Installation of 13 mm thick TF quality Class 'O' Elastometric nitrile rubber for
duct insulation. The quoted price inclusive of adhesives fixtures etc., Sqm R.O

Make : ArmaFlex / K - Flex

UNDER DECK INSULATION


5.00 Supply and installation of Duct Thermal insulation on ducts with 19mm thick Class-O,
Elestomeric Nitrile rubber insulation. The quoted price shall include 2" wide self adhesive Sqm. 4250
black cotton tape, adhesive etc.,
Make : Beardsell / coolite / Indian packaging services / Styrene

VII TOTAL VALUE FOR INSULATION

Consultants :- Entask Consultancy


Architects: BENTEL ASSOCIATES Page 12 of 16 services Pvt Ltd.
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

Sl No Description Unit Qty Rate Amount

VIII ELECTRICAL WORKS RELATED TO HVAC

1 POWER WIRING
Supply, installation, testing & laying of 1.1 KV grade XLPE insulated, Cu conductor
armoured and PVC sheathed cables.
Make : KEI / POLYLAB / HAVELLS / SBEE
1.01 4C x 16 sqmm - YRY Rmt 100
1.02 4C x 10 sqmm - YRY Rmt 150
1.03 4C x 6 sqmm - YRY Rmt 75
1.04 3C x 6 sqmm - YRY Rmt 150
1.05 3C x 4 sqmm - YRY Rmt 150

2 CONTROL WIRING
Make : KEI / POLYLAB / HAVELLS / SBEE
2.01 2C x 1.5 Sq.mm YRY (Cu) cable Rmt RO
2.02 3C x 1.5 Sq.mm YRY (Cu) cable Rmt 500
2.03 4C x 1.5 Sq.mm YRY (Cu) cable Rmt RO

Control cabling of 3C x 1.0 Sqmm between each pump to remote push button to be
3 Rmt 9
suitably laid in 1' PVC conduit.

4 Supply, installation & Laying of G.I. Cable Tray of following width

4.1 150 mm wide Rmt 250


4.2 250 mm wide Rmt 500

5 EARTHING
Earthing conductor

5.01 25 * 3 GI Flat Rmt 1000


5.02 8 SWG GI wire Rmt 500

Supply, installation, testing of Electrical starter panel for Air Handling Units with necessary
DOL / Start Delta starters, Indicating lamps,ammeter,Voltmeter,necessary controls,
6
cabling, etc as per specification. The price should include end termination (copper).The
starter shall be able to connect to BMS

6.01 1.1 KW Nos 63


6.02 1.5 KW Nos RO
6.03 2.2 KW Nos RO
6.04 3.3 KW Nos 25
6.05 5.5 KW Nos 16
6.06 7.5 KW Nos RO
6.07 9.3 KW Nos RO
6.08 11 KW Nos RO
6.09 15 KW Nos RO
6.10 18.5 KW Nos RO
6.11 20 KW Nos RO

Supply, installation, testing of Electrical starter panel for Pumps with necessary DOL /
7 Start Delta starters, Indicating lamps,necessary controls, cabling, etc as per specification.
The price should include end termination (copper).

7.01 5.5 KW ( 4 No's) - Primary Chilled Water Pumps Set 1


7.02 9.3 KW ( 3 No's) - Condenser Water pumps Set 1
7.03 9.3 KW ( 4 No's) - Secondary Chilled Water Pumps Set 1

Supply, installation, testing & commissioning of Converter box from Aluminium power
8 cable to copper power cable for chillers . The price should include end termination Nos 4
(copper).

Consultants :- Entask Consultancy


Architects: BENTEL ASSOCIATES Page 13 of 16 services Pvt Ltd.
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

Sl No Description Unit Qty Rate Amount


Supply, laying, testing & commissioning of copper power cable from converer box to
9 chillers . (Refer Electrical SLD for cable Details) The price should include end termination Set 4
(copper).

10 Supply, installation, testing & commissioning of Remote lockable push button starter for Nos 21
Ventilation fans, HRW and pumps The price should include end termination (copper).
11 End terminations Nos 20

VIII TOTAL VALUE FOR ELECTRICAL WORKS RELATED TO HVAC

IX BASEMENT VENTILATION WORKS


Supply, Installation, Testing, Commissioning & Handing over of the following for Basement
of Natural fresh air for upper basement and independent Forced exhaust air for both the
basements.
The complete system along with the procurement & installation shall be sourced from
main manufacturer with a written system guarantee & final handing over & acceptance
clearance test

FRESH AIR FAN FOR UPPER BASEMENT


Supply, installation testing & commissioning of high tempearture rated direct driven Smoke
Spill Axial fan with VFD, for demand controlled ventialtion for 8 ACH opearation (For lower
basement) - Fresh air. Each fan shall be complete with mounting legs, Ceiling Suspension
1
Rod, Anchor Fastners & Spring Isolators, inlet screen, flexible connection at outlet, inlet
silencer and rated 180°C for 2 hours Class-H Motor suitable for 415+10% volts, 50 cycles , 3
phase AC supply.
Make : Flaktwoods / System Air / Green Heck / Humidin
a 25000 CFM, Static Pressure :25mmWC, Motor: 9.3 KW Nos 4

FRESH AIR FAN FOR LOWER BASEMENT


Supply, installation testing & commissioning of high tempearture rated direct driven Smoke
Spill Axial fan with VFD, for demand controlled ventialtion for 8 ACH opearation (For lower
basement) - Fresh air. Each fan shall be complete with mounting legs, Ceiling Suspension
2
Rod, Anchor Fastners & Spring Isolators, inlet screen, flexible connection at outlet, inlet
silencer and rated 180°C for 2 hours Class-H Motor suitable for 415+10% volts, 50 cycles , 3
phase AC supply.
Make : Flaktwoods / System Air / Green Heck / Humidin
a 25000 CFM, Static Pressure :25mm , Motor: 5.6 KW Nos 5

EXHAUST AIR FAN WITH VFD FOR UPPER BASEMENT

Supply, installation testing & commissioning of high tempearture rated direct driven Smoke
Spill Axial fan with VFD, for demand controlled ventialtion for 8 ACH/16 ACH opearation
3 (For Upper basement) - Exhaust Air. Each fan shall be complete with mounting legs, outlet
screen, flexible connection at inlet or outlet and rated 180°C for 2 hours Class-H Motor
suitable for 415+10% volts, 50 cycles , 3 phase AC supply.

Make : Flaktwoods / System Air / Green Heck / Humidin


a 30000 CFM, Static Pressure :25mmWC, Motor: 11.0 KW Nos 4

EXHAUST AIR FAN WITH CONSTANT SPEED FOR UPPER BASEMENT

Supply, installation testing & commissioning of high tempearture rated Axial fan with
constant speed star delta starters,non return damper,Each fan shall be complete with
4
mounting legs, outlet screen, flexible connection at inlet or outlet and rated 180°C for 2
hours Class-H Motor suitable for 415+10% volts, 50 cycles , 3 phase AC supply.

Make : Flaktwoods / System Air / Green Heck / Humidin


a 30000 CFM, Static Pressure :25mmWC, Motor: 11.0 KW Nos 4

Consultants :- Entask Consultancy


Architects: BENTEL ASSOCIATES Page 14 of 16 services Pvt Ltd.
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

Sl No Description Unit Qty Rate Amount


EXHAUST AIR FAN WITH VFD FOR LOWER BASEMENT

Supply, installation testing & commissioning of high tempearture rated direct driven Smoke
Spill Axial fan with VFD, for demand controlled ventialtion for 10 ACH opearation (For
5 lower basement) - Exhaust Air. Each fan shall be complete with mounting legs, outlet
screen, flexible connection at inlet or outlet and rated 180°C for 2 hours Class-H Motor
suitable for 415+10% volts, 50 cycles , 3 phase AC supply.

Make : Flaktwoods / System Air / Green Heck / Humidin


a 48750 CFM, Static Pressure :25mmWC, Motor: 11.0 KW Nos 2

EXHAUST AIR FAN WITH CONSTANT SPEED FOR LOWER BASEMENT

Supply, installation testing & commissioning of high tempearture rated Axial fan with
constant speed star delta starters,non return damper,Each fan shall be complete with
6
mounting legs, outlet screen, flexible connection at inlet or outlet and rated 180°C for 2
hours Class-H Motor suitable for 415+10% volts, 50 cycles , 3 phase AC supply.

Make : Flaktwoods / System Air / Green Heck / Humidin


a 48750 CFM, Static Pressure :25mmWC, Motor: 11.0 KW Nos 2

JET FAN
3 JET FAN
Installation of jet fans
QTY OF JET FAN SHALL BE FREEZED AFTER CFD ANALYSIS.
Make : Flaktwoods / System Air / Green Heck / Humidin
a Lower Basement Nos 14
b Upper Basement Nos 13

CFD ANALYSIS
Computational Fluid Dynamics analysis report should include submittal of 3 sets of Color
4 Lot 2
printed report document and the location of Jet fans.

CO SENSORS
Supply, Installation, Testing & Commissioning of CO Sensors (Location of the CO Sensor
5 Nos 14
should be as per CFD Analysis)
Make : Grey Stone / Honey Well

PLC PANEL FOR UPPER BASEMENT


Floor mounted free standing compartmentalized fire rated Electrical MCC Panel as per IS
standards 8623 with Protection Class of IP 42 and Fault level of 25kA. The panel made out
of 14 SWG CRCA sheet finished with Siemens Grey painting. The Panel consists of suitable
dual Incomer (One incomer from Common area panel and another incomer from Fire
emergency panel), Feeders and Starters for 24 nos. of Jet fans of 1.1 KW each (0.14KW for
low speed / 1.1KW for High speed) and 4 nos of dual speed Axial fans of 7.5/15 KW with
Danfoss VFD & 5 nos. of Axial fans of 11 KW each with star delta starters, with 5 nos. spare
feeders, MCCB, Metering panel, top cable entry, aluminum bus bar and custom built
microprocessor logic controller with necessary control wiring etc. Each feeder shall have
TPN MCB, two starters and indication lamps, toggle switch for two speed operations and
6 Electrical interlock for two speed functions. It should control of JET fans for demand Sets 1
ventilation with a logic. Vendor should submit SLD and GA drawings for consultants
approval.
LOGIC CONTROL microprocessor logic PANEL to perform the logical operation of Speed
change in fans from Low to high speed based on the CO Level
in the basement. The control is envisaged for JET Vent fans and AXIAL fans. ALL these fans
should also be SWITCHED on in full speed incase of Receipt of FIRE SIGNAL. The Logical
Operation
of Pollution mode and FIRE mode is desired from the control panel\. This shall also include
all the
necessary cabling & control wiring for all the fans.
Make : ABB / Schneider

PLC PANEL FOR LOWER BASEMENT

Consultants :- Entask Consultancy


Architects: BENTEL ASSOCIATES Page 15 of 16 services Pvt Ltd.
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

Sl No Description Unit Qty Rate Amount


Floor mounted free standing compartmentalized fire rated Electrical MCC Panel as per IS
standards 8623 with Protection Class of IP 42 and Fault level of 25kA. The panel made out
of 14 SWG CRCA sheet finished with Siemens Grey painting. The Panel consists of suitable
dual Incomer (One incomer from Common area panel and another incomer from Fire
emergency panel), Feeders and Starters for 7 nos. of Jet fans of 1.1 KW each (0.14KW for
low speed / 1.1KW for High speed) and 2 nos of Axial fans of 9.5 KW with Danfoss VFD & 1
no. of Axial fans of 7.5 KW with star delta starters, with 5 nos. spare feeders, MCCB,
Metering panel, top cable entry, aluminum bus bar and custom built microprocessor logic
controller with necessary control wiring etc. Each feeder shall have TPN MCB, two starters
and indication lamps, toggle switch for two speed operations and Electrical interlock for
7 two speed functions. It should control of JET fans for demand ventilation with a logic. Sets 1
Vendor should submit SLD and GA drawings for consultants approval.
LOGIC CONTROL microprocessor logic PANEL to perform the logical operation of Speed
change in fans from Low to high speed based on the CO Level
in the basement. The control is envisaged for JET Vent fans and AXIAL fans. ALL these fans
should also be SWITCHED on in full speed incase of Receipt of FIRE SIGNAL. The Logical
Operation
of Pollution mode and FIRE mode is desired from the control panel\. This shall also include
all the
necessary cabling & control wiring for all the fans.
Make : ABB / Schneider

POWER CABLING
Supply and Laying of Following Size fire rated FRLS aluminium/copper cables with
necessary supports. The cables shall be pvc sheathed or armoured cables with including
standard cu lugs with terminating
Make : KEI / POLYLAB / HAVELLS / SBEE
3 C X 1.5 Sq.mm FRLS Armoured Copper Cable 2 runs for high & Low speed (from Car Park
a Rmt 600
Ventilation Panel to Jet Vent Fans)
4 C X 25 Sq.mm FRLS Armoured Aluminium Cable (from Car Park Ventilation Panel to
b Rmt 450
Extract Fans)
2C X 1 Sq.mm FRLS Copper cable unarmoured in 19 mm PVC conduit (from PLC Panel to CO
c Rmt 500
Sensor )

Providing & Install cable terminations for the below cables including double compression
8 type chrome plated brass glands and lugs(crimping type), gland earthing, PVC taping as
required and all accessories complete.
a 3 C X 1.5 Sq.mm FRLS Armoured Copper Cable (from Jetfan to electrical panel) Set 50
4 C X 25 Sq.mm FRLS Armoured Aluminium Cable (from Emergency extract fan to electrical
b Set 20
panel)
2C X 1 Sq.mm FRLS Copper cable unarmoured in 19 mm PVC conduit (from CO Sensor to
c Set 30
PLC Panel)

Supply of Sheet steel Ladder Type cable tray of 450 mm width with necessary supports for
9
extract fans
a 450 mm wide Rmt RO
b 300 mm wide Rmt 350

Supply,Installation of Earthing wire for, Extract Fans, Supply Fans, Electrical Panel (25 x 3
10 Rmt 300
mm width G.I)

11 Supply,Installation of Earthing Wire for Jet Vent fans - 8SWG Rmt 510

Supply, Fabrication suitable to site condition and installation of MS Frame work using ISMC
12 for Extract Fans/ Supply fans etc., with 2 coat of redoxide and 2 coat of black enamal Kgs 300
painting.

IX TOTAL VALUE FOR BASEMENT VENTILATION WORKS

TOTAL AIR CONDITIONING WORKS

Amount Excluding VAT & Service Tax


VAT Amount
Service Tax Amount
Amount Including VAT & Service Tax
Excise Duty Component Included in the Supply Portion

Consultants :- Entask Consultancy


Architects: BENTEL ASSOCIATES Page 16 of 16 services Pvt Ltd.
Project:-OZONE GALLERIA @ RANCHI Summary

PROJECT: OZONE GALLERIA MALL @ RANCHI

SUMMARY SHEET FOR HVAC LOWSIDE WORKS

Sl No Description Total Amount (in Rs)

I TOTAL VALUE FOR COOLING TOWER

II TOTAL VALUE FOR CENTRIFUGAL PUMPS

III TOTAL VALUE FOR AIR HANDLING UNIT & HRW

IV TOTAL VALUE FOR CENTRIFUGAL FANS

V TOTAL VALUE FOR PIPING SYSTEM

VI TOTAL VALUE FOR AIR DISTRIBUTION WORKS

VII TOTAL VALUE FOR INSULATION

VIII TOTAL VALUE FOR ELECTRICAL WORKS RELATED TO HVAC

IX TOTAL VALUE FOR BASEMENT VENTILATION

GRAND TOTAL

Architects: BENTEL ASSOCIATES Page 1 of 1 Consultants :- Entask Consultancy services Pvt Ltd.