Professional Documents
Culture Documents
Note: The contractor should read the specifications thoroughly and quote the price for
each item. The BOQ should read in conjuction with specification, drawing & equipment
schedule.
NOTE : Quoted price shall be inclusive of Supply, sea freight, insurance, packing and
forwarding charges etc., as applicable
COOLING TOWER
1.00
Supply, Installation, testing and commissioning of CTI approved MULTI CELL INDUCED
DRAFT CROSS FLOW COOLING TOWERS for airconditioning system. Each tower shall be
complete with basin, casing, distribution system, filling, louvers, ladder, fan, Motor and
other complete accessories as described in the technical specifications. Motor shall be
suitable for 415±10% volts, 50 cycles and 3 phase power supply. Tower shall be designed
with high efficiency drift eliminators to meet current environmental standards and
guidelines for microbial control. Each tower cell must be installed with individual cold
water basins and water discharge sumps to facilitate maintenance without causing
disruption to the other cells in operation. Tower for airconditioning system shall be
selected on the basis of following parameters Refer Equipment schedule & Technical
Specification for details
II CENTRIFUGAL PUMPS
2.11 Supply, installation, testing & commissioning of VFD, VFD controller, microprocessor panel
necessary cabling, two sets of sensors, required enclosure, with By Pass control, including lot 1
cabling and cable Termination etc.
1.00 Supply, installation, testing & commissioning of Double skin construction draw thru type
Horizontal Floor mounted / CEILING SUSPENDED AIR HANDLING UNITS with 25 mm thick
Sandwitched PUF insulation as per specification & as indicated in the Equipment Schedule.
Each complete with DIDW FORWARD Curved Centrifugal Fan, Pre filter of 10 micron, 6
row deep water coil of copper tube & aluminium fins construction with blue Hydraufillic
coating for chilled water coil, coil size shall be selected for a maximum face velocity of 500
feet/minute. and squirrel cage induction motor, centrifugal fan belt drive and vibration
isolators, Limit switches,Emergency Light , Guard for inspection door. Motor shall be
suitable for 415±10% volts, 50 cycles/second, 3 phase AC supply and also suitable for VFD
operation. Note: AHU shall be supplied with one set of pre commissioning filters. Refer
Equipment schedule & Technicla Specification for details
PRESSURIZATION FANS
Supply, Installation, Testing and Commissioning of cabinet type Double Skin construction
draw thru type , Floor Mounted type Fresh Air Handling Units with 50 mm thick , Intake
Plenum, suitable for Outdoor installation of below mentioned capacities( Fan & Filter
section only ) as per specification and as indicated in the drawing. Each complete TEFC
squirrel cage induction motor, Each complete with DIDW forward Curved aerofoil blade
1
Centrifugal Fan, belt drive and vibration isolators, Limit switches, Emergency Light, Motor
shall be suitable for and 415 +/- 10% Volts, 50Hz, 3 phase AC supply and Motor shall be
suitable for 415±10% volts, 50 cycles/second, 3 phase AC supply and also suitable for VFD
operation. The unit shall be suitable for outdoor installation.
e STAIRCASE PRESSURIZATION.
f TE-SP-01 & 02 Nos 3
12000 CFM TSP - 75MM WG
TF - EAU - 01 Nos 1
8000 CFM TSP - 65MM WG
LB - EAU - 01 Nos 1
2000 CFM TSP - 75MM WG
V PIPING WORKS
PIPING
1.00 Supply, installation, testing & commissioning of MS class ‘C’ pipes for chilled water cut to
required lengths and installed with all welded joints, providing and fixing in position with
the necessary fittings like elbows, tees and reducers, sockets for probe meter: Supports,
Support hangers with vibration isolation arrangement as per specification, drawings /
details.
BUTTERFLY VALVES
2.00 Supply, Installation, testing &commissioning of Butterfly valves with PN 10 rating with
matching flanges. The valves should have feasiblity of changing the inner lining if wornout
and the handles should have lockable facility. (For details refer Technical specfication).
BALL VALVES
3.00 Supply, installation, testing & commissioning of Ball valve with PN 10 rating and matching
flanges (For details refer Technical specfication).
Make : Audco /Advance /Shakthi
3.01 40 mm dia Nos 25
3.02 32 mm dia Nos 25
3.03 25 mm dia Nos 305
GATE VALVE
5.00 Supply, installation, testing & commissioning of Gate Valves with matching flanges with
PN 10 rating (For details refer Technical specfication).
Make : Audco /Advance /Shakthi
5.01 50 mm dia Nos R.O
5.02 32 mm dia Nos R.O
5.03 25 mm dia Nos R.O
Y - STRAINER
9.00 Supply, installation, testing & commissioning of Y Strainers with matching flanges with PN
10 rating (For details refer Technical specfication) .
Make : Sant / Emerald
9.01 200 mm dia Nos R.O
9.02 150 mm dia Nos R.O
9.03 125 mm dia Nos R.O
9.04 100 mm dia Nos R.O
9.05 80 mm dia Nos 10
9.06 65 mm dia Nos 1
9.07 50 mm dia Nos 24
9.08 40 mm dia Nos 5
9.09 32 mm dia Nos 5
9.10 25 mm dia Nos 61
PRESSURE GAUGE
13.00 Supply, installation, testing & commissioning of Pressure gauge (For details refer Technical
Nos 250
specfication).
Make : H GURU / Warry
FLEXIBLE CONNECTIONS
14.00 Supply, installation, testing & commissioning of Flexible connections of suitable pressure
rating to be installed at CHILLERS, AHU's & Pumpsets inlets & outlets and at pipes crossing
building expansion joints with suitable Flanges (For details refer Technical specfication).
DRAIN VALVE
16 Drain Valve 25 mm dia Nos. 50
Make : RB / Belimo
AIR SEPARATOR
17 AIR SEPERATOR300 Dia as per the schematic diagram Nos. 1
Make : Anergy / ITT Industries
TEST POINT
20 Test points For taking pressure & temperature measurements in Chiller's. Nos. 12
Make : H GURU / Warry
21 DRAIN PIPING
Supply,installation, testing & commissioning of followig sizes insulated GI drain pipes Class
'B' from Ahu drain pans to nearest floor drain dnd from CHW pump glands to the nearest
drain complete with interconnection,flanges,elbows,tees,nuts,U-trap etc.the insulation
should be similar to chilled water piping insulation
1.00 Supply, Fabrication, installation and testing of sheet metal ducts (FACTORY FABRICATED
DUCTS) in accordance with the approved shop drawings complete with all accessories like
vanes, flanges, suspension rods , anchor bolts, GI bolts & nuts, canvas connections , duct
dampers & splitter dampers etc.,and as required by the specifications. All size duct should
be with ductmate joints. No C & Ss clip joints should be used
2.00 Supply, installation, testing and balancing of GSS Volume Control Dampers with operating
handle for Supply air duct branches in accordance with the approved shop drawings and Sqm 16
specifications.
Make : Air Master / KC Industries / Caryaire
3.00 Supply installation testing and commissioning of Fire damper complete with standard
accessories and 600 mm sleeve as per specifications. (Only Damper price of total Cross- Sqm 9
sectional Area)
Make : Air Master / Caryaire / RaviStar with UL Listing
4.00 Supply installation testing and commissioning of Fire/Smoke damper suitable for
motorized actuators, sensors, controls & all accessories as per specification - Torque 5 NM Nos
6.00 Supply, installation, testing and balancing of powder coated Extruded Aluminium supply air
Diffusers with removable core , Aluminium opposed blade volume control dampers in
accordance with the approved shop drawings and specifications to fit in the tile size of 600
x 600. The neck size shall be of following sizes
8.00 Supply, installation, testing & commissioning of spill boxes made of 22G G.I with round
neck necessary threaded rods for supporting & anchor fasten the of following sizes.
9.00 Supply, installation, testing & commissioning of Spigot & Butterfly Dampers of the
following sizes
Make : Air Master / KC Industries / Caryaire
9.01 300 mm dia Nos R.O
9.02 250 mm dia Nos R.O
9.03 100 mm dia Nos 370
10.00 Supply, Fabrication, installation and testing of the insulated flexible ducting , complete
with connecting rings, duct supports etc as per standards and specification
11.00 Supply & installation , testing and balancing of Al. Powder coated Continuous grills with
necessary flanges for supply & return air of the following sizes.
Make: Airmaster / Caryaire / Rolastar / Dynacraft
11.01 100 mm wide continous grille Sqm RO
11.02 150 mm wide continous grille Sqm 10
11.03 200 mm wide continous grille Sqm RO
11.04 350 mm wide (STP Ventilation) grille Sqm RO
11.05 200 mm wide (PUMP ROOM Ventilation) Sqm RO
11.06 500 mm wide continous grille Sqm RO
11.07 300 mm wide continous grille Sqm RO
11.08 Aluminium. collar damper Sqm RO
FA LOUVER
12.00 Supply, & installation of powder coated Al. Louver for fresh air , filter, etc as per the sizes
Sqm 6
indicated in the drawing.
Make : Air Master / Caryaire
13.00 Supply, installation and laying of INSULATION FOR FRESH AIR DUCTS with 50MM thick EPS
Sqm RO
and Sand Cement plaster
ACCOUSTIC INSULATION
2.00 Supply, installation and testing of TF Quality Acoustic lining for supply and return air ducts
with 25 mm thick rigid fibre glass of 48Kg/Cum density covered with factory laminated RP
Tissue and finished with with 26G Perforated Aluminium sheet as per the specifications Sqm 300
and as detailed in the drawings. (For details refer Technical specfication).
1 POWER WIRING
Supply, installation, testing & laying of 1.1 KV grade XLPE insulated, Cu conductor
armoured and PVC sheathed cables.
Make : KEI / POLYLAB / HAVELLS / SBEE
1.01 4C x 16 sqmm - YRY Rmt 100
1.02 4C x 10 sqmm - YRY Rmt 150
1.03 4C x 6 sqmm - YRY Rmt 75
1.04 3C x 6 sqmm - YRY Rmt 150
1.05 3C x 4 sqmm - YRY Rmt 150
2 CONTROL WIRING
Make : KEI / POLYLAB / HAVELLS / SBEE
2.01 2C x 1.5 Sq.mm YRY (Cu) cable Rmt RO
2.02 3C x 1.5 Sq.mm YRY (Cu) cable Rmt 500
2.03 4C x 1.5 Sq.mm YRY (Cu) cable Rmt RO
Control cabling of 3C x 1.0 Sqmm between each pump to remote push button to be
3 Rmt 9
suitably laid in 1' PVC conduit.
5 EARTHING
Earthing conductor
Supply, installation, testing of Electrical starter panel for Air Handling Units with necessary
DOL / Start Delta starters, Indicating lamps,ammeter,Voltmeter,necessary controls,
6
cabling, etc as per specification. The price should include end termination (copper).The
starter shall be able to connect to BMS
Supply, installation, testing of Electrical starter panel for Pumps with necessary DOL /
7 Start Delta starters, Indicating lamps,necessary controls, cabling, etc as per specification.
The price should include end termination (copper).
Supply, installation, testing & commissioning of Converter box from Aluminium power
8 cable to copper power cable for chillers . The price should include end termination Nos 4
(copper).
10 Supply, installation, testing & commissioning of Remote lockable push button starter for Nos 21
Ventilation fans, HRW and pumps The price should include end termination (copper).
11 End terminations Nos 20
Supply, installation testing & commissioning of high tempearture rated direct driven Smoke
Spill Axial fan with VFD, for demand controlled ventialtion for 8 ACH/16 ACH opearation
3 (For Upper basement) - Exhaust Air. Each fan shall be complete with mounting legs, outlet
screen, flexible connection at inlet or outlet and rated 180°C for 2 hours Class-H Motor
suitable for 415+10% volts, 50 cycles , 3 phase AC supply.
Supply, installation testing & commissioning of high tempearture rated Axial fan with
constant speed star delta starters,non return damper,Each fan shall be complete with
4
mounting legs, outlet screen, flexible connection at inlet or outlet and rated 180°C for 2
hours Class-H Motor suitable for 415+10% volts, 50 cycles , 3 phase AC supply.
Supply, installation testing & commissioning of high tempearture rated direct driven Smoke
Spill Axial fan with VFD, for demand controlled ventialtion for 10 ACH opearation (For
5 lower basement) - Exhaust Air. Each fan shall be complete with mounting legs, outlet
screen, flexible connection at inlet or outlet and rated 180°C for 2 hours Class-H Motor
suitable for 415+10% volts, 50 cycles , 3 phase AC supply.
Supply, installation testing & commissioning of high tempearture rated Axial fan with
constant speed star delta starters,non return damper,Each fan shall be complete with
6
mounting legs, outlet screen, flexible connection at inlet or outlet and rated 180°C for 2
hours Class-H Motor suitable for 415+10% volts, 50 cycles , 3 phase AC supply.
JET FAN
3 JET FAN
Installation of jet fans
QTY OF JET FAN SHALL BE FREEZED AFTER CFD ANALYSIS.
Make : Flaktwoods / System Air / Green Heck / Humidin
a Lower Basement Nos 14
b Upper Basement Nos 13
CFD ANALYSIS
Computational Fluid Dynamics analysis report should include submittal of 3 sets of Color
4 Lot 2
printed report document and the location of Jet fans.
CO SENSORS
Supply, Installation, Testing & Commissioning of CO Sensors (Location of the CO Sensor
5 Nos 14
should be as per CFD Analysis)
Make : Grey Stone / Honey Well
POWER CABLING
Supply and Laying of Following Size fire rated FRLS aluminium/copper cables with
necessary supports. The cables shall be pvc sheathed or armoured cables with including
standard cu lugs with terminating
Make : KEI / POLYLAB / HAVELLS / SBEE
3 C X 1.5 Sq.mm FRLS Armoured Copper Cable 2 runs for high & Low speed (from Car Park
a Rmt 600
Ventilation Panel to Jet Vent Fans)
4 C X 25 Sq.mm FRLS Armoured Aluminium Cable (from Car Park Ventilation Panel to
b Rmt 450
Extract Fans)
2C X 1 Sq.mm FRLS Copper cable unarmoured in 19 mm PVC conduit (from PLC Panel to CO
c Rmt 500
Sensor )
Providing & Install cable terminations for the below cables including double compression
8 type chrome plated brass glands and lugs(crimping type), gland earthing, PVC taping as
required and all accessories complete.
a 3 C X 1.5 Sq.mm FRLS Armoured Copper Cable (from Jetfan to electrical panel) Set 50
4 C X 25 Sq.mm FRLS Armoured Aluminium Cable (from Emergency extract fan to electrical
b Set 20
panel)
2C X 1 Sq.mm FRLS Copper cable unarmoured in 19 mm PVC conduit (from CO Sensor to
c Set 30
PLC Panel)
Supply of Sheet steel Ladder Type cable tray of 450 mm width with necessary supports for
9
extract fans
a 450 mm wide Rmt RO
b 300 mm wide Rmt 350
Supply,Installation of Earthing wire for, Extract Fans, Supply Fans, Electrical Panel (25 x 3
10 Rmt 300
mm width G.I)
11 Supply,Installation of Earthing Wire for Jet Vent fans - 8SWG Rmt 510
Supply, Fabrication suitable to site condition and installation of MS Frame work using ISMC
12 for Extract Fans/ Supply fans etc., with 2 coat of redoxide and 2 coat of black enamal Kgs 300
painting.
GRAND TOTAL
Architects: BENTEL ASSOCIATES Page 1 of 1 Consultants :- Entask Consultancy services Pvt Ltd.