Operation for E5@N/E5@N-H/E5@N-HT

Operation for E5@N/E5@N-H/E5@N-HT


Operation
Setting Levels Diagram

CSM_E5_N_E5_N-H_operation_TG_E_3_3

This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some parameters are not displayed depending on the protect level setting and the conditions of use. Control stops when you move from the operation level to the initial setting level.

Basic Type E5CN/E5CN-U/E5AN/E5EN/E5GN


Start in manual mode. Power ON

Start in automatic mode.

Press the O Key or the PF Key for at least 1 s. *4

Operation Level

Adjustment Level Press the O Key less than 1 s.


PF Key

a-m
Manual mode
Press the O Key for at least 3 s while a-m is displayed. (a-m will flash after 1st second.)

*3

PF Key

Monitor/Setting Item Level

*5

Press the O+ M Keys for at least 3 s. (Display will flash after 1st second.)

Press the O+ M Keys for at least 1 s.


c

25
100

*5 *4
c

Manual Control Level

Press the PF Key for at least 1 s.

Press the O Key for at least 1 s.

25
100

Press the O Key for at least 3 s. (Display will flash after 1st second.)

Protect Level
Note: The time taken to move to the protect level can be adjusted by changing the Move to protect level time setting.

*1

Control stops.

Initial Setting Level

Press the O Key for less than 1 s.

Communications Setting Level

Press the O Key for at least 1 s.

Input password while amoV is displayed. (Set value 169)

Advanced Function Setting Level Control in progress Input password. Control stopped Calibration Level Not displayed for some models
*2

Level change *1. You can return to the operation level by executing a software reset. *2. It is not possible to move to other levels from the calibration level by operating the keys on the front panel. It can be done only by first turning OFF the power. *3. From the manual control level, key operations can be used to move to the operation level only. *4. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN/E5EN). *5. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN/E5EN).

Error Displays (Troubleshooting)


When an error occurs, the No.1 display shows the error code. Take necessary measure according to the error code, referring the table below.
No.1 display Meaning Input error * A/D converter error Memory error Action Check the setting of the input type. Also check the input wiring and check for broken wires or short-circuits in the temperature sensor. Turn the power OFF then back ON again. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise. Turn the power OFF then back ON again. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise. Status at error Control output OFF OFF Alarm output Operates as above the upper limit. OFF

s.err (S. Err) e333 (E333) e111 (E111)

OFF

OFF

Note: If the input value exceeds the display limit (-1999 to 9999), though it is within the control range, will be displayed under -1999 and above 9999. Under these conditions, control output and alarm output will operate normally. For details on the control range, refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156). * Errors are shown only when the display is PV, PV/SV, or PV/MV. Errors are not shown for any other status.

Operation for E5@N/E5@N-H/E5@N-HT


Advanced Type E5CN-H/E5AN-H/E5EN-H
Start in manual mode. Power ON

Start in automatic mode.

Press the O Key or the PF Key for at least 1 s. *4

Operation Level

a-m
Press the O Key for at least 3 s while a-m is displayed. (a-m will flash after 1st second.)

Press the O Key less than 1 s. Press the O Key less than 1 s.

Adjustment Level
Press the O Key less than 1 s.

Manual mode

PID Setting Level

*3

Press the O Key less than 1 s.

Bank Setting Level

Press the O + M Keys for at least 3 s. (Display will flash after 1st second.)

Press the O+ M Keys for at least 1 s.


c

25.0
100.0

Manual Control Level

Press the PF Key for at least 1 s. *4


PF Key

Monitor/Setting Item Level

PF Key *5

Protect Level
Note: The time taken to move to the protect level can be adjusted by changing the Move to protect level time setting.

*5 Press the O Key for at least 3 s. (Display will flash after 1st second.)

Press the O Key for at least 1 s.


*1

25.0
100.0

Control stops.

Initial Setting Level Press the O Key for at least 1 s.

Press the O Key for less than 1 s.

Communications Setting Level

Input password while amov is displayed. (Set value 169) Advanced Function Setting Level Input password.
*2

Control in progress Control stopped

Calibration Level

Not displayed for some models Level change

*1. You can return to the operation level by executing a software reset. *2. It is not possible to move to other levels from the calibration level by operating the keys on the front panel. It can be done only by first turning OFF the power. *3. From the manual control level, key operations can be used to move to the operation level only. *4. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN-H/E5EN-H). *5. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN-H/E5EN-H).

Error Displays (Troubleshooting)


When an error occurs, the No.1 display shows the error code. Take necessary measure according to the error code, referring the table below.
No.1 display Meaning Input error * A/D converter error Memory error Action Check the setting of the input type. Also check the input wiring and check for broken wires or short-circuits in the temperature sensor. Turn the power OFF then back ON again. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise. Turn the power OFF then back ON again. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise. Status at error Control output OFF OFF Alarm output Operates as above the upper limit. OFF

s.err (S. Err) e333 (E333) e111 (E111)

OFF

OFF

Note: If the input value exceeds the display limit (-19999 to 32400), though it is within the control range, will be displayed under -19999 and above 32400. Under these conditions, control output and alarm output will operate normally. For details on the control range, refer to the E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157). * Errors are shown only when the display is PV, PV/SV, or PV/MV. Errors are not shown for any other status.

Operation for E5@N/E5@N-H/E5@N-HT


Programmable Type E5CN-HT/E5AN-HT/E5EN-HT
Start in manual mode. Power ON

Start in automatic mode.

Operation Level

a-m
Press the O Key for at least 3 s while a-m is displayed. (a-m will flash after 1st second.)

Press the O Key less than 1 s. Press the O Key less than 1 s.

Program Setting Level


Press the O Key less than 1 s.

Manual mode

PID Setting Level

Press the O Key less than 1 s.

Adjustment Level

Press the O + M Keys for at least 3 s. (Display will flash after 1st second.)

Press the O+ M Keys for at least 1 s.


c

25.0
100.0

Manual Control Level

Press the PF Key for at least 1 s. Monitor/Setting Item Level

Protect Level
Note: The time taken to move to the protect level can be adjusted by changing the Move to protect level time setting.

Press the O Key for at least 1 s.

25.0
100.0

Press the O Key for at least 3 s. (Display will flash after 1st second.)

Control stops.

Initial Setting Level Press the O Key for at least 1 s. Advanced Function Setting Level

Press the O Key for less than 1 s.

Communications Setting Level

Input password.

Control in progress Control stopped

Calibration Level

Not displayed for some models Level change

*1. You can return to the operation level by executing a software reset. *2. It is not possible to move to other levels from the calibration level by operating the keys on the front panel. It can be done only by first turning OFF the power. *3. From the manual control level, key operations can be used to move to the operation level only. *4. When the PF Setting parameter is set to A-M. For the E5CN-HT, press the M+U Keys at the same time to implement the PF Key. *5. When the PF Setting parameter is set to PFDP. For the E5CN-HT, press the M+U Keys at the same time to implement the PF Key.

Error Displays (Troubleshooting)


When an error occurs, the No.1 display shows the error code. Take necessary measure according to the error code, referring the table below.
No.1 display Meaning Input error * A/D converter error Memory error Action Check the setting of the input type. Also check the input wiring and check for broken wires or short-circuits in the temperature sensor. Turn the power OFF then back ON again. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise. Turn the power OFF then back ON again. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise. Status at error Control output OFF OFF Alarm output Operates as above the upper limit. OFF

s.err (S. Err) e333 (E333) e111 (E111)

OFF

OFF

Note: If the input value exceeds the display limit (-19999 to 32400), though it is within the control range, will be displayed under -19999 and above 32400. Under these conditions, control output and alarm output will operate normally. For details on the control range, refer to the E5CN-HT/E5AN-HT/E5EN-HT Digital Controllers User's Manual Programmable Type (Cat. No. H169). * Errors are shown only when the display is PV, PV/SV, or PV/MV. Errors are not shown for any other status.

Operation for E5@N/E5@N-H/E5@N-HT


Parameters
Basic Type E5CN/E5CN-U/E5AN/E5EN/E5GN
Some parameters are not displayed depending on the model of the Controller and parameter settings. For details, refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156). Starting in manual mode.
Press the PF Key for at least 1 s. *1 PF Key *2

Power ON
Starting in automatic mode.
PF Key *2 Press the O Key for at least 3 s. Other than the Auto/Manual Switch display

Manual Control Level


Press the O PID Key or the PF 25 Control Key for at least only 1 s. *1 PV/MV
C

Initial Setting Level


Press the O Key for at least 1 s. Press the O Key less than 1 s.

in-t Input Type


5

Adjustment Level

Press the O Key less than 1 s.

Operation Level
Press the O Key less than 1 s.
C

M in-h

Scaling Upper Limit

100

25

Set either of these parameters.

l.adj M at
off

Adjustment Level Display Displayed only once when entering adjustment level.

Process Value Added when Additional PV display is ON.


C

r-s RUN/STOP
run

M in-l Scaling Lower Limit


0

ins Temperature Input Shift


0.0

M 25 Process Value/ Set Point


0

M al-1 Alarm Value 1


0

AT Execute/Cancel

1-point shift M Set either insh Upper Limit of these Temperature 2-point shift M insl Lower Limit Temperature

M dp M d-u
C

Decimal Point

0.0 Input Shift Value parameters.

M a-m Auto/Manual Switch PID control only.


Press the O Key for at least 3 s.
C

M cmwt Communications Writing


off

Added when auto/manual select M addition is ON.

M al1h Alarm Value1 Upper Limit


0

0 For input type of analog


Temperature Unit C, F For input type of temperature SP Upper Limit

0.0 Input Shift Value

m-sp
0

Multi-SP Set Point Setting

M al1l Alarm Value1 Lower Limit


0

M sl-h
1300

Set either of these parameters.

M Current ct1 HeaterMonitor 1 Value


0.0

M p Proportional Band
8.0

M Point sp-m Set RampDuring SP


0

M al-2 Alarm Value 2


0

M sl-l
-200

Limit the set point SP Lower Limit

M hb1 Heater Burnout Detection 1


0.0

M i
233

Integral Time PID settings Derivative Time

M ct1 Heater Current 1 Value Monitor


0.0

M al2h
0

Alarm Value Upper Limit 2

M cntl PID ON/OFF


onof

M oc1 Heater Overcurrent Detection 1


50.0

M d
40

M ct2
0.0

Heater Current 2 Value Monitor

M al2l Alarm Value2 Lower Limit


0

M s-hc
stnd

Standard or Heating/Cooling

Set either of these parameters.

M ct2
0.0

Heater Current 2 Value Monitor

M c-sc Cooling Coefficient


1.00
C

M lcr1 Leakage Current 1 Monitor


0.0

M al-3 Alarm Value 3


0

M st ST (Self-tuning)
on

M hb2
0.0

Heater Burnout Detection 2

Heating/cooling M c-db Dead Band

0.0

M lcr2 Leakage Current 2 Monitor


0.0

M al3h Alarm Value3 Upper Limit


0

M ptrn M
20

For input type of temperature, standard control, or PID

Program Pattern

M oc2
50.0

Heater Overcurrent Detection 2

M of-r
C

50.0 stabilization of P or PD

Manual Reset Value Clear the offset during control.

M prst Program Start


rset

M al3l Alarm Value3 Lower Limit


0

off When assigning PID or


control output to ON/OFF output

M lcr1
0.0 0.0

Leakage Current 1 Monitor

M hys Hysteresis (Heating)


1.0

M sktr Soak Time Remain


0

M o MV Monitor (Heating)
0.0

cp Control Period (Heating) M c-cp


20
Set the ON/OFF output cycle. Control Period (Cooling)

M hs1
50.0

HS Alarm 1

M Hysteresis settings chys Hysteresis (Cooling)


1.0

M c-o MV Monitor (Cooling)


0.0

M lcr2
0.0

Leakage Current 2 Monitor

M soak Soak Time


1
C

M
Press the O and M Keys for at least 3 s. Press the O and M Keys for at least 1 s. Press the O Key less than 1 s.

M orev Direct/Reverse Operation


or-r

M hs2
50.0
C

HS Alarm 2

M wt-b
off

M alt1
2
C

Alarm 1 Type

Wait Band

Protect Level
Note: The time taken to move to the protect level can be adjusted by changing the "Move to protect level time" setting.

Communications Setting Level


Note: Displayed only for models with communications. Changes are effective after cycling power or after a software reset.

M sp-0
0

SP 0

M mv-s
0.0

M alh1
0.2

Alarm 1 Hysteresis

MV at Stop

M sp-1
0

SP 1 SP used by multi-SP SP 2

M mv-e
0.0
C

pmov
MV at PV Error

Move to Protect Level: Displayed only when a password 0 is set. Restricts moving to protect level.

psel Protocol Setting: Switches between


cwf CompoWay/F (SYSWAY)

M sp-2
0

M sprt SP Ramp Set Value


off
MV Upper Limit

Operation/Adjustment Protect: oapt Restricts displaying and modifying menus in operation, 0 adjustment, and manual control levels.

M u-no Communications Unit No.


1

and Modbus.

M sp-3 SP 3
0

M ol-h
105.0

M Initial Setting/ icpt Communications Protect: movement This protect level restricts
1 to the initial setting, communications

M Communications bps Baud Rate


9.6

M ol-l
-5.0

MV Lower Limit

M levels. wtpt Setting Change Protect: by Protects changes to setups M pfpt PF Key Protect operation Restricts PF key
off (E5AN/E5EN only)

setting, and advanced function setting

M len Communications Data Length


7

CompoWay/F (SYSWAY) only

off operating the front panel keys.

orl MV Change Rate Limit


0.0

M sbit Communications Stop Bits


2

*1. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN/E5EN). *2. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN/E5EN).

M
sqrp
0.0
Extraction of Square Root Low-cut Point

M Mask Enable: pmsk Parameteronly when a Displayed


on parameter mask is set.

M prty Communications Parity


even

M to Move prlp Password setting to Protect Level: Password


0

M sdwt
20

Send Data Wait Time

Operation for E5@N/E5@N-H/E5@N-HT

Monitor/Setting Item Level


C

(E5AN/E5EN only)
Monitor/Setting Item Display 2
PF

25
0

Monitor/Setting Item Display 1

PF

Monitor/Setting Item Display 3

PF

Monitor/Setting Item Display 4

PF

Monitor/Setting Item Display 5

Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level).

Press the O Key for at least 1 s.

Advanced Function Setting Level

alt2
2
C

Alarm 2 Type

init Parameter Initialization


off

a1lt Alarm 1 Latch


off

hsu
on

HS Alarm Use

pf
a-m

PF Setting (E5AN/E5EN only)

M alh2 Alarm 2 Hysteresis


0.2

M mspu Multi-SP Uses


off

M a2lt Alarm 2 Latch


off

M hsl HS Alarm Latch


off

M pfd1 Monitor/Setting Item 1


1

M alt3 Alarm 3 Type


2
C

M spru

SP Ramp Time Unit

M a3lt Alarm 3 Latch


off

M hsh HS Alarm Hysteresis


0.1

M (E5AN/E5EN only) pfd2 Monitor/Setting Item 2


0

M alh3
0.2

Alarm 3 Hysteresis

M rest Standby Sequence Reset


a

M prlt Move to Protect Level Time


3

M lba LBA Detection Time


0
C

M pfd3 Monitor/Setting Item 3


0

tr-t Transfer Output Type


off
Linear output Transfer Output Upper Limit

M tr-h
100.0

M sb1n
n-o

Auxiliary Output 1 Open in Alarm

M sero Input Error Output


off

M lbal LBA Level


8.0

M pfd4 Monitor/Setting Item 4


0

M tr-l Transfer Output Lower Limit


0.0

M sb2n
n-o

Auxiliary Output 2 Open in Alarm

M cjc Cold Junction Compensation


on Method

M lbab LBA Band


3.0

M pfd5
0

Monitor/Setting Item 5

M o1-t Linear Current Output


4-20
Linear output

M sb3n
n-o

Auxiliary Output 3 Open in Alarm

M rlrv MB Command Logic Switching


off

M out1 Control Output 1 Assignment


o

M spdp
4

"PV/SP" Display Screen Selection

M ev-m Number of1Multi-SP Uses Two SPs:


1 Four SPs: 2

M hbu
on

HB ON/OFF

M colr PV Change Color


red
C

M out2
none

Control Output 2 Assignment

M odsl MV Display Selection


o

M ev-1
none

M hbl Heater Burnout Latch


off

M pv-b PV Stable Band


5.0

M sub1
alm1

Auxiliary Output 1 Assignment

M pvdp PV Decimal Point Display


on

Event Input Assignment 1

M ev-2
stop

M hbh Heater Burnout Hysteresis


0.1
C

M a1on Alarm 1 ON Delay


0

M sub2
alm2

Auxiliary Output 2 Assignment

M PV Status Display pvst Function


off

Event Input Assignment 2

M sqr Extraction of Square Root Enable


off

M st-b ST Stable Range


15.0

M a2on Alarm 2 ON Delay


0

M sub3
alm3

Auxiliary Output 3 Assignment (E5AN/E5EN only)

M svst SV Status Display Function


off

M amov Move to Advanced Function Setting Level:


0 Displayed when initial

M alfa
0.65

M a3on Alarm 3 ON Delay


0

M csel Character Select


on

M d.ref Display Refresh Period


0.25

M protect is set to 0.

setting/communications

M at-g AT Calculated Gain


0.8
C

M a1of Alarm 1 OFF Delay


0

M t-u Soak Time Unit


m

M ra1m Control Output 1 ON/OFF Count


0 Monitor

Move by setting password (169).

M at-h AT Hysteresis
0.8

M a2of Alarm 2 OFF Delay


0

M alsp Alarm SP Selection


sp-m

M ra2m M ra1

0 Monitor

Control Output 2 ON/OFF Count

M lcma Limit Cycle MV Amplitude


20.0

M a3of Alarm 3 OFF Delay


0

M manl Manual MV Limit Enable


off

0 Alarm Set Value

Control Output 1 ON/OFF Count

M inf Input Digital Filter


0.0

M istp Input Shift Type


ins1

M pvrp PV Rate of Change Calculation Period


4

M ra2 Control Output 2 ON/OFF Count


0 Alarm Set Value

M pvad Additional PV Display


off

M mvse MV at Stop and Error Addition


off

M csca

Automatic Cooling Coefficient Adjustment

M rac ON/OFF Counter Reset


0

off

M o-dp
off

MV Display

M amad Auto/Manual Select Addition


off

M ocu Heater Overcurrent Use


on

M cmov Move to Calibration Level


0

M ret Automatic Display Return Time


off

M rt RT
off

M ocl Heater Overcurrent Latch


off

M och
0.1

Heater Overcurrent Hysteresis

Operation for E5@N/E5@N-H/E5@N-HT


Advanced Type E5CN-H/E5AN-H/E5EN-H
Some parameters are not displayed depending on the model of the Controller and parameter settings. For details, refer to the E5CN-H/E5AN-H/ E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157).

Power ON
Manual Control Level

Protect Level

Operation Level

Adjustment Level

Bank Setting Level

PID Setting Level

Monitor/Setting Item Level

Initial Setting Level

Communications Setting Level

Advanced Function Setting Level

Press the O Key less than 1 s.

PID Setting Level


Press the O Key less than 1 s.

Bank Setting Level


Press the O Key less than 1 s.

d.pid PID1 1 d.pid

Display PID Selection

Display d.bnk Bank0 Bank Selection 0

2 PID2

d.bnk Bank1
1

d.pid
3 PID3

d.bnk d.bnk

2 2 Bank2

d.pid
8

PID8

d.bnk Bank7
7

M
c

1.p
8.0
c

M 8.p
8.0 PID 8 Proportional Band
c

M 0.lsp
0.0
c

M
c

233.0

M 8.i PID 8 Integral Time


233.0

M 0.pid
1
c

0.0

7.lsp
0.0

Bank 7 SP
c

M
0.a2l
0.0

7.a-2

M 1.d
40.0

M 7.pid
1 Bank 7 PID Set No.
c

Bank 7 0.0 Alarm Value 2 Bank 7 Alarm Value 0.0 Upper Limit 2

M 1.olh
105.0

M 8.d
40.0

M
7.a 2h

PID 8 Derivative Time

M 0.spr
off
c

M 0.a-3
0.0
c

-5.0

M
c

M 8.oll
-5.0

0.0 PID 8 MV Lower Limit

M 0.a1h
0.0
c

0.0

Bank 7 0.0 Alarm Value 1 Bank 7 Alarm Value 0.0 Upper Limit 1

M
0.a3l
0.0
c

M 7.a-3 Bank 7 M 7.a3h M 7.a3l

1.aut
1320.0
c

M 1.csc
1.00

M 8.aut M 8.csc
1.00

M
c

M 7.a1h M

0.0 Alarm Value 3 Bank 7 Alarm Value 0.0 Upper Limit 3

PID 8 Automatic Selection 1320.0 Range Upper Limit

0.a 1l
0.0

M 0.sok
1

PID 8 Cooling Coefficient

M
c

7.a 1l M

M 1.lba
0

0.a-2
0.0
c

M
0.wtb
off

Bank 7 Alarm Value 0.0 Lower Limit 1

Bank 7 Alarm Value 0.0 Lower Limit 3

M 8.lba
0

PID 8 LBA Detection Time

M
c

M 7.sok
1

Bank 7 Soak Time

M 7.wtb
off

Bank 7 Wait Band

Set either of these parameters

M 1.oll

105.0

Set either of these parameters

M 8.olh

PID 8 MV Upper Limit

M
c

M 7.spr M 7.a-1

Bank 7 SP off Ramp Set Value

M
c

0.a-1

M 0.a3h

7.a2l

Bank 7 Alarm Value 0.0 Lower Limit 2

Set either of these parameters

M 1.i

0.a 2h

Operation for E5@N/E5@N-H/E5@N-HT

Power ON
Starting in manual mode.

Manual Control Level


Press the PF Key for at least 1 s.
PID Press the O 25.0 Control Key or the PF 100.0 only Key for at least 1 s. *1 PV/MV
c

*1

Starting in automatic mode.

Press the O Key less than 1 s.

Press the O and M Keys for at least 3 s.

Adjustment Level

Operation Level

l.adj M at
off

AT Execute/Cancel

M i
233.0

25.0

Integral Time PID settings Derivative Time

Process Value/ 0.0 Set Point

al-1
0.0

Alarm Value 1

M cmwt M irda
off
Communications off Writing

M d
40.0

M a-m
Press the O Key for at least 3 s.
Auto/Manual Switch PID control only. Added when auto/manual select addition is ON. Bank No.
c

M al1h
Alarm Value

0.0 Upper Limit 1

Infrared Communications Use

M c-sc Cooling Coefficient


1.00

M bank
0

M al1l Alarm Value M

0.0 Lower Limit 1


Set either of these parameters.

M spmd
lsp
SP Mode

M c-db
0.0

Heating/cooling
c

M rsp
0.0
Remote SP Monitor
c

al-2
0.0

Dead Band

Alarm Value 2

M ct1 M hb1 M oc1 M ct2 M hb2


0.0

M
Heater Current 1

M
Manual Reset Value Clear the offset during control.

M
c

of-r

sp-m

Set Point During

al2h M al2l M al-3


0.0

Alarm Value

Set either of these parameters.

Adjustment Level Display Displayed only once when entering adjustment level.

c c

25.0 M

p
8.0

Proportional Band

Process Value Added when Additional PV display is ON.

r-s RUN/STOP
run

0.0 Value Monitor

50.0 stabilization of P or PD

0.0 SP Ramp

0.0 Upper Limit 2

Heater Burnout

M hys
1.0

M ct1
Heater Current 1 Value
c

Press the O and M Keys for at least 1 s.

Alarm Value Set either of these parameters.

Hysteresis (Heating) Hysteresis settings

0.0 Detection 1

0.0 Monitor

0.0 Lower Limit 2

Heater Overcurrent 50.0 Detection 1

M chys

M ct2
c

1.0 Hysteresis (Cooling)

Heater Current 2 Value 0.0 Monitor

Alarm Value 3

0.0 Value Monitor

Heater Current 2

M soak
1

M
Soak Time

lcr1

Leakage Current 1

M al3h Alarm Value

0.0 Monitor

0.0 Upper Limit 3

Heater Burnout Detection 2

M wt-b
off

M
Wait Band

lcr2

Leakage Current 2

M al3l Alarm Value M o


0.0

0.0 Monitor

0.0 Lower Limit 3

M oc2
50.0

M
Heater Overcurrent Detection 2

M
MV at Stop

mv-s
0.0

prst Program Start


rset

MV Monitor (Heating)

M lcr1
Leakage Current 1 0.0 Monitor

M mv-e
0.0
MV at PV Error

M sktr Soak Time Remain


0

M c-o
0.0
MV Monitor (Cooling)

M hs1
50.0

M sprt
HS Alarm 1

M
SP Ramp Set Value

M v-m
0.0
Valve Opening Monitor

off

M lcr2
0.0

Leakage Current 2 Monitor

M ol-h
105.0

M
MV Upper Limit

M hs2
50.0

M ol-l
HS Alarm 2

-5.0

MV Lower Limit

M
c

ins
0.00

M orl
Temperature Input Shift 1-point shift Set either of these parameters.

PF Key *2
MV Change Rate Limit

0.0

Monitor/Setting Item Level


25.0 Monitor/Setting Item Display 1
0.0
PF

(E5AN-H/E5EN-H only)

M
c

M
db
2.0
Position Proportional Dead Band Monitor/Setting Item Display 2
PF

insh

Upper Limit Temperature 0.00 Input Shift Value 2-point shift M Lower Limit Temperature Input Shift Value

Monitor/Setting Item Display 3


PF

M oc-h
0.8
Open/Close Hysteresis

insl
0.00

M sqrp M

Monitor/Setting Item Display 4

PF

Monitor/Setting Item Display 5

Extraction of Square Root 0.0 Low-cut Point

Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level).

PF Key *2

*1. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN-H/E5EN-H). *2. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN-H/E5EN-H).

Operation for E5@N/E5@N-H/E5@N-HT

Press the O Key for at least 1 s. Press the O Key for at least 3 s. Other than the Auto/Manual Switch display

Initial Setting Level


Press the O Key less than 1 s.

Press the O Key less than 1 s.

Protect Level
The time taken to move to the protect level can be adjusted by changing the "Move to protect level time" setting. Level: pmov Move to Protectwhen a password Displayed only

Communications Setting Level


Displayed only for models with communications. Changes are effective after cycling power or after a software reset.

in-t
5

Input Type

alt2
2

Alarm 2 Type

M
in-h
100
Scaling Upper Limit
c

0 is set. Restricts moving to protect

level.

Protocol Setting: psel Switches between cwf CompoWay/F (SYSWAY) and Modbus.

M alh2
0.2

Alarm 2 Hysteresis

oapt Restricts displaying and M


0

Operation/Adjustment Protect:

M
1

M in-l
0

Scaling Lower Limit

M
alt3
2
Alarm 3 Type

modifying menus in 0 operation, adjustment, and manual control levels.


Initial Setting/ Communications Protect: This protect level restricts movement to the initial setting, communications setting, and advanced function setting levels.

u-no M bps M len


7

Communications Unit No.

M
dp
Decimal Point
c

icpt M wtpt M

0 For input type of analog

Communications Baud Rate 9.6 CompoWay/F (SYSWAY) only Communications Data Length
c

M
d-u
c
Temperature Unit C, F For input type of temperature SP Upper Limit

M alh3
0.2

Alarm 3 Hysteresis

M
tr-t Transfer Output Type
off
Linear output

Setting Change Protect: Protects changes to setups off by operating the front panel keys. PF Key Protect Restricts PF key operation

M
sl-h
1300.0

pfpt M

M sbit
2
Communications Stop Bits
c

M
tr-h
100.0
Transfer Output Upper Limit

off (E5AN-H/E5EN-H only)

Mask Enable: pmsk Parameteronly when a Displayed on parameter mask is set.

M prty Communications Parity


even

Limit the set point M sl-l SP Lower Limit

M
tr-l
0.0
Transfer Output Lower Limit

-200.0

M prlp
Password to Move to Protect Level: 0 Password setting

M sdwt
20
Send Data Wait Time

M cntl PID ON/OFF


pid

M o1-t
4-20

Linear Current Output Linear output

M s-hc
stnd

Standard or Heating/Cooling

M
ev-b
1
Bank Numbers Used

M st
on

ST (Self-tuning)
For input type of temperature, standard control, or PID Program Pattern

M
ev-1
none
Event Input Assignment 1

M ptrn
off

M
ev-2 Event Input 2 Assignment
stop

M
pbnk
7
Valid Program Bank When assigning PID or control output to ON/OFF output Control Period (Heating) Set the ON/OFF output cycle. Control Period (Cooling)

M
ev-3
none
Event Input Assignment 3

M
cp
20

M
ev-4
none
Event Input Assignment 4

M
c-cp
20

M
clfl
flot
Closed/Floating

M orev Direct/Reverse Operation


or-r

M
calb
off
Motor Calibration

M
alt1
2
Alarm 1 Type

M
c

M mot
30

Travel Time

alh1

Alarm 1

0.2 Hysteresis

M sqr
off

Extraction of Square Root Enable

M Move to Advanced Function amov Setting Level: initial Displayed when


0 setting/ communications
protect is set to 0.

Move by setting password (169).

Operation for E5@N/E5@N-H/E5@N-HT

Power ON
Manual Control Level

Protect Level

Operation Level

Adjustment Level

Bank Setting Level

PID Setting Level

Monitor/Setting Item Level

Initial Setting Level

Communications Setting Level

Advanced Function Setting Level

Press the O Key for at least 1 s. Advanced Function Setting Level

init
off

Parameter Initialization

o-dp
off

MV Display

istp
ins1

Input Shift Type

alsp
sp-m

Alarm SP Selection

pfd1
1

Monitor/Setting Item 1

M
spru
m
SP Ramp Time Unit

M
ret Automatic Display Return Time
off

M
mvse
off
MV at Stop and Error Addition

M
rspu
off
Remote SP Enable

M
pfd2
0
Monitor/Setting Item 2

M
rest
a
Standby Sequence Reset

M
a1lt Alarm 1 Latch
off

M
amad
on
Auto/Manual Select Addition
c

M
rsph
1300.0
Remote SP Upper Limit

M
pfd3
0
Monitor/Setting Item 3

M
sb1n
Auxiliary Output 1

M
a2lt
off
Alarm 2 Latch

M
rt
off
RT
c

M
rspl
-200.0
Remote SP Lower Limit

M
pfd4
0
Monitor/Setting Item 4

n-o Open in Alarm

M
sb2n
Auxiliary Output 2

M
a3lt
off
Alarm 3 Latch

M
hsu
on
HS Alarm Use

M
sptr
off
SP Tracking

M
pfd5
0
Monitor/Setting Item 5

n-o Open in Alarm

M
sb3n
n-o
Auxiliary Output 3 Open in Alarm

M
prlt Move to Protect Level
3
Time

M
hsl HS Alarm Latch
off

M
rseo
off
Remote SP Input Error Output

M
spdp
"PV/SP" Display

4 Screen Selection

M
hbu
on
HB ON/OFF

M
sero
off
Input Error Output

M
hsh
0.1
HS Alarm Hysteresis

M
pidi
pv
PID Set Automatic Selection Data

M
odsl MV Display Selection
o

M
hbl Heater Burnout Latch
off

M
cjc
Cold Junction

M
lba
0
LBA Detection Time

M
pidh
0.50
PID Set Automatic Selection Hysteresis

M
pvdp
on
PV Decimal Point Display

on Compensation Method

M
hbh
0.1
Heater Burnout Hysteresis

M
rlrv
off
MB Command Logic Switching
c

M
lbal
8.0
LBA Level
c

M
p-db
0.0
PV Dead Band

M
pvst
off
PV Status Display Function

M
c

M
ST Stable Range

M
PV Change Color
c

M
LBA Band

M
Manual MV Limit Enable

st-b
15.0

colr
red

lbab
3.0

manl
off

svst
off

SV Status Display Function

M
alfa
0.65
c

M
pv-b
5.0
PV Stable Band

M
out1
o
Control Output 1 Assignment

M
pmvd
Direct Setting of

M
d.ref
0.25
Display Refresh Period

off Position Proportional MV

M
at-g
1.0
AT Calculated Gain

M
a1on
0
Alarm 1 ON Delay

M
out2
none
Control Output 2 Assignment

M
pvrp
PV Rate of Change

M
ra1m
0 Monitor
Control Output 1 ON/OFF Count

17 Calculation Period

M
c

M
AT Hysteresis

M
Alarm 2 ON Delay

M
Auxiliary Output 1 Assignment

M
Automatic Cooling

at-h
0.8

a2on
0

sub1
alm1

csca

off Coefficient Adjustment

ra2m

M
lcma
20.0
Limit Cycle MV Amplitude

M
a3on
0
Alarm 3 ON Delay

M
sub2
alm2
Auxiliary Output 2 Assignment

M
ocu
on
Heater Overcurrent Use

0 Monitor

Control Output 2 ON/OFF Count

M
ra1
0 Alarm Set Value
Control Output 1 ON/OFF Count

M
inf
0.0
Input Digital Filter

M
a1of Alarm 1 OFF Delay
0 0

M
sub3
alm3
Auxiliary Output 3 Assignment (E5AN/E5EN-H only)

M
ocl
Heater Overcurrent

M
ra2
Control Output 2 ON/OFF Count

off Latch

M
pvad
off
Additional PV Display

M
a2of Alarm 2 OFF Delay
0

M
csel
on
Character Select

M
och
0.1
Heater Overcurrent Hysteresis

0 Alarm Set Value

M
rac ON/OFF Counter Reset
0

M
a3of
0
Alarm 3 OFF Delay

M
t-u
m
Soak Time Unit

M
pf
a-m
PF Setting

M
cmov
0
Move to Calibration Level

Operation for E5@N/E5@N-H/E5@N-HT


Programmable Type E5CN-HT/E5AN-HT/E5EN-HT
Some parameters are not displayed depending on the model of the Controller and parameter settings. For details, refer to the E5CN-HT/E5AN-HT/ E5EN-HT Digital Controllers User's Manual Programmable Type (Cat. No. H169).

Power ON
Manual Control Level

Protect Level

Operation Level

Program Setting Level

Adjustment Level

PID Setting Level

Monitor/Setting Item Level

Initial Setting Level

Communications Setting Level

Advanced Function Setting Level

Adjustment Level
Press the O Key less than 1 s. Press the O Key less than 1 s.
Adjustment Level Display Displayed only once when entering adjustment level.

PID Setting Level


Press the O Key less than 1 s.

l.adj M at
off

mv-e
0.0

MV at PV Error

hs2
50 0 .

HS Alarm 2

M ol-h
MV Upper Limit
105 0 .

AT Execute/ Cancel

d.pid PID1 1 d.pid

Display PID Selection

2 PID2

M cmwt
off

M ins
0.00

Temperature Input Shift

Communications Writing

d.pid
3 PID3

M irda Infrared Communications d.pid


8 off Use
c

M insh

1-point shift Set either Upper Limit of these Temperature 0.00 Input Shift Value parameters M 2-point shift
0.00

M ol-l MV Lower Limit


-5.0

M orl MV Change Rate Limit


0.0

PID8

M
c

M spmd
psp

inslLower Limit Temperature


Input Shift Value

SP Mode
c

1.p
8.0
c

M 8.p
8.0

PID 8 Proportional Band

M fsp
0.0

M p Proportional Band
8.0

M db Position Proportional
2.0 Dead Band

Fixed SP

M 1.i
233.0

M 1.d
40.0

M 8.i PID 8 Integral Time


233.0

M ct1
0.0

M i
233 0 .

M oc-h
0.8

Open/Close Hysteresis

Integral Time PID settings Derivative Time

Heater Current 1 Value Monitor

M 1.olh
105.0

M 8.d PID 8 Derivative Time


40.0

M hb1
0.0

M d
40.0

M Extraction of sqrp Square Root


0.0 Low-cut Point

M stb
0.00

Heater Burnout Detection 1

M 8.ol h
105.0

PID 8 MV Upper Limit

M oc1 Heater Overcurrent


50.0 Detection 1

M c-sc Cooling Coefficient


1.00

Standby Time

M 1.oll
-5.0

M
c

M 8.ol l
-5.0

PID 8 MV Lower Limit

M Current ct2 HeaterMonitor 2 Value


0.0

M Heating/cooling c-db Dead Band


0.0

M psps Program SP Shift Value


0.0

M ps0
-200.0

M of-r
Manual Reset Value Clear the offset during 50.0 stabilization of P or PD control. Hysteresis (Heating) Hysteresis settings Hysteresis (Cooling)

RSP 0 before Correction

1.aut
1320.0
c

M 8.aut
PID 8 Automatic Selection 1320.0 Range Upper Limit

M hb2 M oc2

M 1.csc
1.00

Heater Burnout 0.0 Detection 2

M hys

M ps1
-200.0

RSP 1 before Correction

M 8.c sc PID 8 Cooling Coefficient 1.00 M 8.lba PID 8 LBA Detection


0 Time

1.0

M ps10
-200.0

M 1.lba
0

Heater Overcurrent 50.0 Detection 2

M lcr1 Leakage Current 1


0.0

M chys
1.0

RSP 10 before Correction

M bc0
0

Monitor

M hs1
50 0 .

M wt-b
off

RSP Broken-line Correction Value 0

Wait Band

HS Alarm 1

M mv-r
0.0

bc1
MV at Reset
0

RSP Broken-line Correction Value 1

M lcr2 Leakage Current 2 Monitor


0.0

M bc10
0

RSP Broken-line Correction Value 10

10

Operation for E5@N/E5@N-H/E5@N-HT

Power ON
Starting in manual mode.

Manual Control Level


Press the PF Key for at least 1 s.*1
c

25 .0 Control
100.0 only

PID

PV/MV

Press the O Key or the PF Key for at least 1 s. *1

Starting in automatic mode.

Press the O Key less than 1 s.

Press the O and M Keys for at least 3 s.

Program Setting Level

Operation Level
Operation Level

d.prg d.prg 0 d.prg 1


2

Display Program Selection

d.prg
7

Press the O Key for at least 3 s.


c

25.0

PV

ct 2

Heater Current 2

s-n o

Number of Segments 8 Used, 1 to 32 Display Segment Selection, END or 0 to

0.0 Value Monitor


Leakage Current 1

M 25.0 PV/SP
0.0

M lcr 1
(See note.)

Number of Segments 1 d.seg d.seg end d.seg 0 d.se g 1

0.0 Value Monitor


Leakage Current 2

M a-m Auto/Manual
Switch

M lcr 2 M r-r

M prg
0
Program Number

0.0 Value Monitor


Run/Reset Press the O and M Keys for at least 1 s.

pid
1 M
c

PID Set No.

styp
Alarm Value 1
c

Segment n Format

M seg Segment No. Monitor


0

rst

al-1
0.0 M

ramp M

M
Segment n SP

0.0

M o MV Monitor (Heating)

sp

Hold

Hold

Ral1h

0.0 M

Alarm Upper Limit 1

0.0 M 0.0 M
Segment n Ramp Rate

off
Advance

M c- o MV Monitor (Cooling) M V-m M


0.0
Valve Opening

Rpr

M adv
off

M stb m
Remaining Standby

0.0 Monitor

Ra l1 l
c

0.0 M 0.0 M 0.0 M

Alarm Lower Limit 1

time
0.00 M

Segment n Time

0.0 Time Monitor 0

al-2

Alarm Value 2

M prg t Elapsed Program Time Monitor


0.00
Program Link Destination

Ral2h Ral2l
0.0 M 0.0 M

Alarm Upper Limit 2

lin k
end M

M rptm
c

Program Execution

0 Repetition Monitor

Alarm Lower Limit 2

ts1 s on1

Time Signal 1

0 Set Segment M
Time Signal 1 ON Time

M rsp Remote SP Monitor


0.0

al-3

Alarm Value 3

ct1

Heater Current 1

0.00 M

0.0 Value Monitor

M
Time Signal 1

Ral3h
M
c

0.0

Alarm Upper Limit 3

of1

0.00 OFF Time M


Time Signal 2 Set Segment

al3l
M

0.0

Alarm Lower Limit 3

ts2s
0 M

Rrp t

Program Repetitions

on2
0.0 0 M

Time Signal 2 ON Time

of2

0.00

Time Signal 2 OFF Time

PF Key *2

Monitor/Setting Item Level


25 .0
0.0
Monitor/Setting Item Display 1

(E5AN/EN-HT only)

PF

Monitor/Setting PF Item Display 2

Monitor/Setting Item Display 3

PF

Monitor/Setting Item Display 4

PF

Monitor/Setting Item Display 5

Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level).

PF Key *2

*1. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN/EN-HT). *2. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN/EN-HT).

11

Operation for E5@N/E5@N-H/E5@N-HT

Press the O Key for at least 1 s. Press the O Key for at least 3 s. Other than the Auto/Manual Switch display

Initial Setting Level


Press the O Key less than 1 s.

Press the O Key less than 1 s.

Protect Level
The time taken to move to the protect level can be adjusted by changing the "Move to protect level time" setting. Level: pmov Move to Protectwhen a password Displayed only is set. Restricts moving to protect

Communications Setting Level


Displayed only for models with communications. Changes are effective after cycling power or after a software reset.

in-t
5 M

Input Type

tr-h
100.0 M

Transfer Output Upper Limit

0 M

level.

Protocol Setting: psel Switches between cwf CompoWay/F and Modbus.

in-h
100 M

Scaling Upper Limit

tr-l
0.0 M

Transfer Output Lower Limit

M
1

u-no

Communications Unit No.

in-l
0 M 0

Scaling Lower Limit

oapt Protect
0 M 0

Operation/Adjustment

o1-t
4-20 M

Linear Current Output

M bps
9.6

Communications Baud Rate CompoWay/F only

dp
M

Decimal Point

icpt
M

Initial Setting/ Communications Protect

M len
7

ev-1
none M

Event Input Assignment 1

Communications Data Length

M
Setting Change Protect

d-u
c
Communications Stop Bits
c

Temperature Unit

ev-2
none M

Event Input Assignment 2

wtpt
off M off M

sbit
2

M prty Communications Parity


even

sl-h
1300.0 M

SP Upper Limit

ev-3
none M

Event Input Assignment 3

pfptPF Key Protect pmsk


on M 0 M
Parameter Mask Enable

M sdwt
20

Send Data Wait Time

sl-l
-200.0 M

SP Lower Limit

ev-4 Event Input 4 Assignment


none M

cntl PID ON/OFF


pid M

clfl Closed/Floating
flot M

prlp Protect Level: Password setting

Password to Move to

s-hc
stnd M

Standard or Heating/Cooling

calb
off M

Motor Calibration

cp
20 M

Control Period (Heating)

mot
Control Period (Cooling)

Travel Time

30 M

c-cp
M

sqr
off M

Extraction of Square Root Enable

20

orev Direct/Reverse Operation


or-r M

Tt-u
h-m M

Program Time Unit

alt1
2 M
c

Alarm 1 Type

Time/Rate of t-pr Step Programming Rise

time M
Alarm 1 Hysteresis

alh1
0.2 M

pru
m M

Time Unit of Ramp Rate

alt2
2 M
c

Alarm 2 Type

rtsm Reset Operation


stop M

alh2
0.2 M

Alarm 2 Hysteresis

p-on
cont M

Operation after Power ON

alt3
2 M
c

Alarm 3 Type

eset
rst M

Operation at End of Operation

alh3
0.2 M

Alarm 3 Hysteresis

pvst PV Start
sp M

tr-t
off M

Transfer Output Type

amov
0 M

Move to Advanced Function Setting Level

12

Operation for E5@N/E5@N-H/E5@N-HT

Power ON
Manual Control Level

Protect Level

Operation Level

Program Setting Level

Adjustment Level

PID Setting Level

Monitor/Setting Item Level

Initial Setting Level

Communications Setting Level

Advanced Function Setting Level

Press the O Key for at least 1 s. Advanced Function Setting Level

init
off M

Parameter Initialization

cjc
on M

Cold Junction Compensation Method PV Change Color

sub1
alm1 M

Auxiliary Output 1 Assignment

pfd1
1 M

Monitor/Setting Item 1

rest
a M

Standby Sequence Reset

colr
red M
c

sub2
alm 2 M

Auxiliary Output 2 Assignment

pfd2
0 M

Monitor/Setting Item 2

sb1n
n-o M

Auxiliary Output 1 Open in Alarm

pv-b
5.0 M

PV Stable Band

sub3
M

alm 3 (E5AN/E5EN-HT only)

Auxiliary Output 3 Assignment

pfd3
0 M

Monitor/Setting Item 3

sb2n
n-o M n-o M

Auxiliary Output 2 Open in Alarm

a1on
0 M

Alarm 1 ON Delay

csel
on M

Character Select

pfd4
0 M

Monitor/Setting Item 4

sb3n hbu
on M

Auxiliary Output 3 Open in Alarm

a2on Alarm 2 ON Delay


0 M

alsp
sp- m M

Alarm SP Selection

pfd5
0 M

Monitor/Setting Item 5

HB ON/OFF

a3on
0 M

Alarm 3 ON Delay

rspu
off M

Remote SP Enable

spdp
3 M

"PV/SP" Display Screen Selection

hbl
off M

Heater Burnout Latch

a1of
0 M

Alarm 1 OFF Delay

rsph
1300 .0 M

Remote SP Upper Limit

odsl
o M

MV Display Selection

hbh
0.1 M

Heater Burnout Hysteresis

a2of
0 M

Alarm 2 OFF Delay

rspl
- .0 200 M

Remote SP Lower Limit

pvdp
on M

PV Decimal Point Display

alfa
0.65 M

a3of
0 M

Alarm 3 OFF Delay

sptr
off M

SP Tracking

pvst
off M

PV Status Display Function

at-g
1.0 M
c

AT Calculated Gain

istp
ins1 M

Input Shift Type

rseo
off M

Remote SP Input Error Output

svst
off M

SV Status Display Function

at-h
0.8 M

AT Hysteresis

mvre MV at Reset and Error Addition


off M

pidi
pv M

PID Set Automatic Selection Data

d.ref
0.25 M

Display Refresh Period

lcma
20.0 M

Limit Cycle MV Amplitude

amad
on M

Auto/Manual Select Addition

pidh
0.50 M

PID Set Automatic Selection Hysteresis

ra1m
0 M

Control Output 1 ON/OFF Count Monitor Control Output 2 ON/OFF Count Monitor Control Output 1 ON/OFF Count Alarm Set Value Control Output 2 ON/OFF Count Alarm Set Value ON/OFF Counter Reset

inf
0.0 M

Input Digital Filter

rt
off M

RT

p-db
0.0 M

PV Dead Band

ra2m
0 M

pvad
off M

Additional PV Display

hsu
on M

HS Alarm Use

manl
off M

Manual MV Limit Enable

ra1
0 M

o-dp
off M

MV Display

hsl HS Alarm Latch


off M

pmvd
off M

Direct Setting of Position Proportional MV

ra2
0 M

ret
off M

Automatic Display Return Time

hsh
0.1 M

HS Alarm Hysteresis

pvrp
M

PV Rate of Change

17 Calculation Period
Automatic Cooling Coefficient Adjustment

rac
0 M

a1lt Alarm 1 Latch


off M

lba
0 M
c

LBA Detection Time

csca
off M

pend
0.0 M

Program End ON Time

a2lt
off M

Alarm 2 Latch

lbal LBA Level


8.0 M
LBA Band

ocu
M

Heater Overcurrent

s-u
h-m M

Standby Time Unit

on Use
Heater Overcurrent Latch

a3lt
off M

Alarm 3 Latch

lbab
3.0 M

ocl
off M

psad
off M

Program SP Shift Value Addition

prlt
3 M

Move to Protect Level Time

out1
o M

Control Output 1 Assignment

och
M

Heater Overcurrent

0.1 Hysteresis
PF Setting

rcad
off M

RSP Broken-line Correction Display Addition

sero
off M

Input Error Output

out2
none M

Control Output 2 Assignment

pf
r-r M

cmov
0 M

Move to Calibration Level