Cool Room
Cool Room
INFORMATION: Application Outside Ambient Temperature, oC: Room Temperature, oC: Temperature Difference, oC:
Calculation chart:
Outside Room Dimensions 10 Length (L) 4.6 m -30 Width (W) 4m 40 Height (H) 2.8 m
0.1
Overall Wall Thickness in meters : 0.2 (for single brick 0.1 m, double brick 0.3m plus insulation, NOTE: double brick wall equivalent to 0.025m of insulation) Estimate Usage: Product load, kg 1000 Miscellaneous Loads: Number of people: Electrical Watts: 10 Other, Watts:
0 1200
0 hrs in coolroom
Incoming temp., oC
Solution: Outside Room Surface Area (A) 2 LxW 18.40 m 2 LxH 12.88 m 2 WxH 11.20 m 2 A =2xtotal 84.96 m
Inside Room Volume (V) V = L' x W ' x H ' 3 V= 36 m Note: for L', W ', H ' use outside dimensions less 2 times overall wall thickness
1) Wall Load a) Outside surface area (A) b) Wall 'U' Factor c) Temp. Difference across wall Refrigeration Load in kW 2) Air Change Load a) Inside Room Volume (V) b) Number Air Changes /24 hours c) Heat removed/ m 3 in cooling from ambient to room temp. Refrigeration Load in kW 3) Product Load I) Cooling load to freezing temperature a) Mass of product, kg b) Temp. Reduction to freezing, K c) Spec. Heat above freezing, Refrigeration Load in kW ii) Freezing Load at freezing temperature a) Mass of product, kg b) LatentHeat of fusion Refrigeration Load in kW iii) Cooling load below freezing temperature a) Mass of product, kg b) Temp. Reduction below freezing, K c) Spec. Heat below freezing, Refrigeration Load in kW 4) Miscellaneous Loads a) Electrical Watt b) People c) Other 5) Sum Of Loads = 1+2+3+4 = Add safety factor (10% of Sum) TOTAL LOAD = 6) Required Refrigerating Power: When compressor runs less than 24 hours/day running hours per day Note: 16 hrs for off cycle defrost 18 hrs for automatic defrost Required Refrigerating Power:
0.032 W/m K
0.375 kW
18
8.985 kW
ot rt TD tw PL it l w h
0.32 1.087488
36 12 74.5 0.38
l1 w1 h1
16 18
0.000 kW 0.000 kW
REFRIGERATION LOAD ESTIMATE FORM 1 --> For Rooms above 0 degree C Date 3-Feb-12 Estimated by Customer: Address: DESIGN INFORMATION: Application Outside Ambient Temperature, oC: Room Temperature, oC: Temperature Difference, oC:
Calculation chart:
0.05
Overall Wall Thickness in meters : 0.05 (for single brick 0.1 m, double brick 0.3m plus insulation, NOTE: double brick wall equivalent to 0.025m of insulation) Estimate Usage: Product load, kg 2000 Miscellaneous Loads: Number of people: Electrical Watts: 20 Other, Watts:
0 500
0 hrs in coolroom
Incoming temp., oC
Solution: Outside Room Surface Area (A) 2 LxW 36.00 m 2 LxH 18.00 m 2 WxH 18.00 m 2 A =2xtotal 144.00 m
Inside Room Volume (V) V = L' x W ' x H ' 3 V= 101 m Note: for L', W ', H ' use outside dimensions less 2 times overall wall thickness
1) Wall Load a) Outside surface area (A) b) Wall 'U' Factor c) Temp. Difference across wall Refrigeration Load in kW 2) Air Change Load a) Inside Room Volume (V) b) Number Air Changes /24 hours c) Heat removed/ m 3 in cooling from ambient to room temp. Refrigeration Load in kW 3) Product Load I) Cooling load to storage temperature a) Mass of product, kg b) Temp. Reduction, K c) Spec. Heat above freezing, Refrigeration Load in kW ii) Heat of Respiration Load a) Mass of product, kg b) Heat of respiration / day Refrigeration Load in kW 4) Miscellaneous Loads a) Electrical Watt b) People c) Other 5) Sum Of Loads = 1+2+3+4 = Add safety factor (10% of Sum) TOTAL LOAD = 6) Required Refrigerating Power: When compressor runs less than 24 hours/day running hours per day Note: 16 hrs for off cycle defrost 18 hrs for automatic defrost Required Refrigerating Power:
0.026 W/m K
1.032 kW
16
9.375 kW
ot rt TD tw PL it l w h
0.52 2.47104
l1 w1 h1
0.5 0 0.5
16 18
0.000 kW 0.000 kW