NG125H circuit-breakers C curve IEC 947.2: 36 kA

function

This circuit-breaker is specially designed for functions requiring a high breaking capacity (up to 36 kA): - main incomer in the sub-distribution switchboards; - outgoer, protection of loads directly supplied by a power switchboard.

description

common technical data # rating: 1080 A # reference temperature: 40 C # Uimp: 8 kV # Ui: 690 V # maximum voltage rating: 500 V AC # breaking capacity: as in IEC 947.2
type voltage (V) AC breaking capacity (A)

# electrical durability: 10 000 cycles at In # tropicalisation as in IEC 68.1: treatment 2 (relative humidity: 95 % at 55 C) # weight (g):
type 1P 240 2P 480 3P 720 4P 960

1P 220240 36000 1P 380415 9000 (1) 2, 3, 4P 380415 36000 (1) 1-pole breaking capacity in the IT isolated neutral system (double fault).

# isolation with positive break indication # 3-position toggle: open-tripped-closed # built-in padlocking facility on 3P and 4P # fault display on front face by: 5 fault indicator 5 position of toggle: tripped # test button to check proper operation of the tripping mechanism # fast closing

# compatible with Pragma F24 and Prisma G/GX enclosures and Prisma P cabinets # degree of protection: IP20B (IP40D for the part outside the enclosure) # connection: 5 6 63 A ratings: tunnel terminals for 1.5 to 50 mm2 copper cables 5 80 A rating: tunnel terminals for 16 to 70 mm2 copper cables 5 connection of aluminium cables, copper cables with lug or busbar for 3P and 4P (see connection accessories) 5 upstream voltage taps on each pole, by 6.35 mm Fast-on lugs, for auxiliary circuit supply

C curve

# the magnetic trip units operate at 8 In 20 %

catalogue numbers

type

rating (A)

catalogue number

width in mod. of 9 mm

NG125H C curve
1P 10 16 20 25 32 40 50 63 80 18705 18706 18707 18708 18709 18710 18711 18712 18713 3 3 3 3 3 3 3 3 3

18712

2P

1 3

2 4
18721

10 16 20 25 32 40 50 63 80

18714 18715 18716 18717 18718 18719 18720 18721 18722

6 6 6 6 6 6 6 6 6

90236E.fm/2

Updated: 09/11/99

Schneider Electric

circuit protection circuit-breakers up to 80 A

NG125H circuit-breakers C curve IEC 947.2: 36 kA

catalogue numbers

type

rating (A)

catalogue number

width in mod. of 9 mm

NG125H C curve (continued)


3P

1 3 5

2 4 6
18730

10 16 20 25 32 40 50 63 80

18723 18724 18725 18726 18727 18728 18729 18730 18731

9 9 9 9 9 9 9 9 9

4P

1 3 5 7

2 4 6 8
18739

10 16 20 25 32 40 50 63 80

18732 18733 18734 18735 18736 18737 18738 18739 18740

12 12 12 12 12 12 12 12 12

additional information
Schneider Electric

auxiliaries: page 90250/2 accessories: page 90251/2 Vigi module: page 90243/2 discrimination table: page 92511/2

dimensions: page 90148/2 derating: page 92515/2 tripping curves: page 90180/2