Design Calculations Sample

The structural calculations report details the design and analysis of a three-storeyed community complex building for Agape Church in Kampala, focusing on critical structural members and parameters. It includes specifications for materials, loads, and compliance with relevant building codes. The report provides detailed calculations for various structural components, including slabs, beams, and footings, ensuring the building's integrity on non-cohesive soils.

Uploaded by

Ekky Cecil
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd

Topics covered

  • Safety factors,
  • Structural integrity,
  • Shear resistance,
  • Design parameters,
  • Load envelope,
  • Material properties,
  • Load distribution,
  • BS5950,
  • Nominal cover,
  • T-beam design
0% found this document useful (0 votes)
72 views35 pages

Design Calculations Sample

The structural calculations report details the design and analysis of a three-storeyed community complex building for Agape Church in Kampala, focusing on critical structural members and parameters. It includes specifications for materials, loads, and compliance with relevant building codes. The report provides detailed calculations for various structural components, including slabs, beams, and footings, ensuring the building's integrity on non-cohesive soils.

Uploaded by

Ekky Cecil
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd

Topics covered

  • Safety factors,
  • Structural integrity,
  • Shear resistance,
  • Design parameters,
  • Load envelope,
  • Material properties,
  • Load distribution,
  • BS5950,
  • Nominal cover,
  • T-beam design

Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No.

13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

Analysis and Design of a Three storeyed building


These calculations are for a three storeyed building to be used as a community complex building.
The building is to be located on a site with non-cohesive soils.
The design calculations have concentrated on structural members which are deemed to be of critical
importance to the structural integrity of the development. The following have been considered:

 Slab panels between grids C-D and 1-5


 Beam 2 (along Grid 3 on 1st floor)
 Beam 7 (along grid G on 2nd floor)
 Column C3 (at grid intersection D2)
 Pad footing F2 (at grid intersection D2)
 Staircase

Design Parameters
General

 The building consists of an auditorium for which analysis and design are to be carried out
 The building is for congregational purposes as it is a place of worship.
 The building contains partitioning walls. External and internal walls are 230mm thick with
12mm plaster on both sides considered
 The main beams of the structure rest centrally on the columns to avoid local eccentricity
 For all structural elements, C25 grade concrete will be used unless otherwise stated
 The floor diaphragms are assumed to be rigid
 Center-line dimensions are followed for analysis and design. It is advisable to consider finite
size joint width in practice
 Preliminary sizes of structural components are assumed by experience and/ calculations
where applicable
 For analysis purposes, the beams are assumed to be rectangular so as to distribute slightly
larger moments in columns in practice, a beam that fulfils the requirement of a flanged
section in design behaves in between the rectangular and flanged section for moment
distribution

1
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

Technical

150mm Maxpan + 50mm topping = 225mm

Allowable bearing pressure (assumed) = 150kN/m2

Type of structure = Two storeyed concrete building

Intended use = Residential building

Relevant building regulations and design codes = BS8110 -1 : 1997

= BS5950 -1 : 1990

= BS6399 -1 : 1984

= CP3: Chap V : 1972

Exposure conditions = Mild (Internal)

= Moderate (External)

Unit weights

Reinforced concrete = 24kN/m3

Max-pans = 0.66kN/m2

Solid concrete blocks = 28.8kN/m2

Characteristic yield strength of reinforcement, fy = 410N/mm2

Characteristic yield strength of shear reinforcement, fyv = 250N/mm2

Grade of concrete, fcu = 25N/mm2

Weight of concrete = 24kN/m2

2
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

DESIGN OF HOLLOW SLAB


The design of the max-pan floor is similar to that of a T-Beam, therefore the same procedure of
design will be followed

Design Data

 Size of max-pan used = 300 x 300 x 150 (Kajjansi max-pans)


 Weight of one max-pan = 9kg
 Concrete topping = 50mm
 Diameter of bars = 12mm
 Weight of concrete = 24kN/m3
 Grade of concrete fcu = 25N/mm3 (mild conditions of exposure)
 Tensile strength of steel fy = 410N/mm3
 Plaster and finishes = 50mm

Ultimate load of hollow slab


Reference drawing

Width of max-pan, b = 2(380/2) + 75 = 455mm

Number of max-pans per square meter of floor = 1/(0.455 x 0.3) =7.326,

Consider 8 max-pans

Weight of 8 max-pans = (8x9x10)/1000 = 0.72kN/m2

Volume of 1m2 of 200mm thick slab = 0.20 x 1 = 0.20m3

Volume of 8 max-pans = 8[(0.3x0.3x0.1) + (0.38x0.3x0.05)]

3
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

=0.118m3

Volume of concrete/m2 = 0.20 – 0.118 = 0.082m3

Weight of concrete = 0.082 x 24 = 1.968kN/m2

Weight of finishes = 0.05 x 24 = 1.20kN/m2

Dead load on slab, Gk = weight of max-pan + concrete + finishes

= 0.72 + 1.968 + 1.20

Gk = 3.888kN/m2

Imposed load Qk (BS6399 -1: 1996 Table 1)


Domestic and Residential = 1.5kN/m2
Design load is based on the most critical imposed load
Hence imposed load Qk = 1.5kN/m2

Ultimate design load, n =1.4Gk + 1.6Qk

N = 1.4 x 3.888 + 1.6 x 1.5 N = 7.84kN/m2

Ultimate load per strip of slab, W = 0.455 x 7.84

W = 3.57kN/m

4
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

RC BEAM ANALYSIS & DESIGN BS8110

Load Envelope - Com bination 1


5.768

0.0
mm 4730 4730 5230 2724
A 1 B 2 C 3 D 4 E

10.9

5
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

10

150
225
450
75

15075
225

C20/25
150150150
25
25000
20

410
251

25
25
25

6
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

15075
225

2 fxshear
8
2 fxbars
12 leg

150150150
10
4021
450
186
0
1.000
0.026
0.156
K' > K - No compression reinforcement is required
177
21
162

226
81
1350
PASS - Area of reinforcement provided is greater than area of reinforcement required

804
275
PASS - Area of shear reinforcement provided exceeds minimum required
140
PASS - Longitudinal spacing of shear reinforcement provided is less than maximum

60

25
PASS - Satisfies the minimum spacing criteria

196.3

7
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

239
PASS - Satisfies the maximum spacing criteria

26.0
196.3

1.364

1.000

35.5
25.4
PASS - Actual span to depth ratio is within the allowable limit

8
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

Design of T-Beam (Beam 2 along grid 3 on first


floor)
Reference drawing
225225
450

Depth of beam, D
400 230 400 = 450mm
Width of beam web, bw = 230mm
Length of the beam, L = 5730mm
Bf = bw + 0.7L/5 = 230 + (0.7x5230)/5 = 962
= Use 1030 mm
Assumptions made
Nominal cover to reinforcement = 25mm
Compressive strength of concrete, fcu = 25N/mm2
Diameter of bars = 25mm
Diameter of links = 8mm
Tensile strength of steel, fy = 410N/mm2
Shear strength, fyv = 250N/mm2

Design load on beam


Self-weight of beam = 24 x (0.45-0.225) x 0.23
= 1.242kN/m
Dead load from max-pan slab = 4.488kN/m2
Total dead load, Gk = 1.242 + 4.488 x 4.98
Gk= 23.6kN/m

Imposed load on slab, Qk = 4.0kN/m2


= 4.0 x 4.98 = 19.92kN/m
Qk = 19.92kN/m

Total Ultimate load on slab, W = 1.4Gk + 1.6Qk


W= 64.912kN/m

9
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

RC BEAM ANALYSIS & DESIGN BS8110

mm 4730 5730 5730 5730 4049 4049


A 1 B 2 C 3 D 4 E 5 F 6 G

Load Envelope - Com bination 1


64.912

0.0
mm 4730 5730 5730 5730 4049 4049
A 1 B 2 C 3 D 4 E 5 F 6 G

Bending Moment Envelope


kNm
-189.084 -180.4 -174.0 -189.1
-135.2
-99.2

0.0
16.4
104.923 102.6 89.2 84.9 88.0
104.9
mm 4730 5730 5730 5730 4049 4049
A 1 B 2 C 3 D 4 E 5 F 6 G

Shear Force Envelope


kN
195.369 187.1 183.3 195.4
140.3 155.9
115.4

0.0

-122.5 -106.9
-191.647 -191.6 -184.9 -188.6 -176.6
mm 4730 5730 5730 5730 4049 4049
A 1 B 2 C 3 D 4 E 5 F 6 G

10
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

-189-189
105105
195195
169169

230
450
1030
225
225225
450

C20/25
400 230 400
25
25000
20

410
251

25
25
25
225225
450

2 fxbars
16
2 fxshear
8 legs at
2 fxbars
20
400 230 400
11
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

89
0.944

0.476
4.000

0.468
493

670
PASS - Area of shear reinforcement provided exceeds minimum required
307
PASS - Longitudinal spacing of shear reinforcement provided is less than maximum

189
404
1.000
0.201

K > K' - Compression reinforcement is required


314
226
46
330

982
4140
PASS - Area of reinforcement provided is greater than area of reinforcement required
1640

1963
248
PASS - Area of reinforcement provided is greater than area of reinforcement required

162
1.745

12
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

0.811
4.000

0.934
984

1005
PASS - Area of shear reinforcement provided exceeds minimum required
305
PASS - Longitudinal spacing of shear reinforcement provided is less than maximum
169
1.805

0.798
4.000

1.007
1061

1206
PASS - Area of shear reinforcement provided exceeds minimum required
305
PASS - Longitudinal spacing of shear reinforcement provided is less than maximum

25
PASS - Satisfies the minimum spacing criteria

235.5
200
PASS - Satisfies the maximum spacing criteria

13
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

225225
450
2 fxbars
16

3 ffx
2 xshear
8
20 legs at
bars
400 230 400
105
4011
1030
407
0
1.000
0.025
0.156
K' > K - No compression reinforcement is required
387
45
762

942
248
4140
PASS - Area of reinforcement provided is greater than area of reinforcement required

503
421
PASS - Area of shear reinforcement provided exceeds minimum required
305
PASS - Longitudinal spacing of shear reinforcement provided is less than maximum

52

25
PASS - Satisfies the minimum spacing criteria

221.1
213
PASS - Satisfies the maximum spacing criteria

14
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

26.0
221.1

1.133

1.125

33.1
14.1

PASS - Actual span to depth ratio is within the allowable limit

15
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

Design of L-Beam (Beam 7 along grid G on


second floor)
Reference drawing

225 225
450

Depth of beam, D = 450mm


370 230
Width of beam web, bw = 230mm
Length of the beam, L = 5730mm
Bf = bw + 0.7L/5 = 230 + (0.7x5230)/10 = 596.1
= Use 600 mm
Assumptions made
Nominal cover to reinforcement = 25mm
Compressive strength of concrete, fcu = 25N/mm2
Diameter of bars = 16mm
Diameter of links = 8mm
Tensile strength of steel, fy = 410N/mm2
Shear strength, fyv = 250N/mm2

Design load on beam


Self-weight of beam = 0.186 x 24
= 4.48kN/m
Load from upper walls = 22 x 0.23 x 3
= 15.18kN/m
Total dead load, Gk = 4.48 + 15.18
Gk= 19.66kN/m

Total Ultimate load on slab, W = 1.4Gk + 1.6Qk


W= 27.5kN/m

16
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

RC BEAM ANALYSIS & DESIGN BS8110

Load Envelope - Com bination 1


27.538

0.0
mm 5230 4730 4730
A 1 B 2 C 3 D

58.2

17
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

6262
-72-72
5856
-86-83
-74-71

230
450
600
225
225 225
450

370 230
C25/30
30
26000
20

410
251

35
35
35

18
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

225 225
2 fxbars
16
450
2 fxshear
8 legs at 200
3 fxbars
16
370 230
46
0.501

0.510
4.382

0.400
421

503
PASS - Area of shear reinforcement provided exceeds minimum required
299
PASS - Longitudinal spacing of shear reinforcement provided is less than maximum

19
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

225 225
2 fxbars
16
450
2 fxshear
8 legs at 200
3 fxbars
16
370 230
62
4446
600
399
0
1.000
0.021
0.156
K' > K - No compression reinforcement is required
379
44
456

603
248
4140
PASS - Area of reinforcement provided is greater than area of reinforcement required

503
421
PASS - Area of shear reinforcement provided exceeds minimum required
299
PASS - Longitudinal spacing of shear reinforcement provided is less than maximum

48

25
PASS - Satisfies the minimum spacing criteria

206.4
228
PASS - Satisfies the maximum spacing criteria

20
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

26.0
206.4

1.423

1.127

41.7
13.1
PASS - Actual span to depth ratio is within the allowable limit
225 225

3 fxbars
16
450

2 fxshear
8 legs at 200
3 fxbars
16
370 230
72
399
1.000
0.066

K' > K - No compression reinforcement is required


367
70
549

603
248
4140
PASS - Area of reinforcement provided is greater than area of reinforcement required

74
0.803

0.584
4.382

0.400
421

21
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

503
PASS - Area of shear reinforcement provided exceeds minimum required
299
PASS - Longitudinal spacing of shear reinforcement provided is less than maximum
56
0.607

0.584
4.382

0.400
421

503
PASS - Area of shear reinforcement provided exceeds minimum required
299
PASS - Longitudinal spacing of shear reinforcement provided is less than maximum

48

25
PASS - Satisfies the minimum spacing criteria

248.9
189
PASS - Satisfies the maximum spacing criteria

22
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

Column Design (C3 at grid intersection D2)


Assumptions made

Column size width, b = 450mm


Depth, h = 450mm
Nominal cover, C = 35mm
Diameter of bars, = 16mm
Diameter of links, = 8mm
Compressive strength of concrete, fcu = 25N/mm2
Tensile strength of steel, fy = 410N/mm2
Shear strength, fyv = 250N/mm2
Height of column from Ground floor = 3.0mm
to beam soffit

Column loading on column C2

Loads from roof level to 2nd floor level = 127.64kN


Loads from 2nd to 1st floor level = 516.15kN
Loads from 1st floor to ground level = 651.47kN
Total Ultimate axial load, N = Summation of column loads
N=1296kN

RC COLUMN DESIGN (BS8110:PART1:1997)


Column definition
Column depth (larger column dim); h = 450 mm
Nominal cover to all reinforcement (longer dim); ch = 35 mm
Depth to tension steel; h' = h - ch – Ldia – Dcol/2 = 399 mm
Column width (smaller column dim); b = 450 mm
Nominal cover to all reinforcement (shorter dim); cb = 35 mm
Depth to tension steel; b' = b - cb - Ldia – Dcol/2 = 399 mm
Characteristic strength of reinforcement; fy = 410 N/mm2
Characteristic strength of concrete; fcu = 25 N/mm2
35

Minor axis (y)


Links - 8 dia links in 1s
399

Reinforcement (each fa
450

2
Characteristic concrete
Major axis (x)
35
450 23
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

Braced Column Design to cl 3.8.4


Check on overall column dimensions
Column OK - h < 4b
Braced column slenderness check
Column clear height; lo = 3000 mm
Slenderness limit; llimit = 60  b = 27000 mm
Column slenderness limit OK
Short column check for braced columns
Column clear height; lo = 3000 mm
Effect. height factor for braced columns - maj axis; x = 0.75
BS8110:Table 3.19
Effective height – major axis; lex = x  lo = 2.250 m;
Slenderness check; lex/h = 5.00
The braced column is short (major axis)
Effect height factor for braced columns - minor axis; y = 0.75
BS8110:Table 3.19
Effective height – minor axis; ley = y  lo = 2.250 m
Slenderness check; ley/b = 5.00
The braced column is short (minor axis)
Short column - axial load and nominal moment only
Ultimate loads
Short column supporting an approximately symmetrical arrangement of beams.
Design ultimate axial load; N = 1296 kN
Design
Total area of column steel required; Asc_req = max ((N - 0.35fcuhb) / (f2msfy ),
2
0.4hb/100) = 810 mm
from BS8110: Pt 1: eqn 29; where; f2ms = 0.67
Area of reinforcement provided; Asc_prov = Ascol = 1206 mm2
Area in "tension" face; Ast = Ascol /2 = 603 mm2
Area of reinforcement provided exceeds area of reinforcement required OK
Check min and max areas of steel
Total area of concrete; Aconc = b  h = 202500 mm2
Area of steel (symmetrical); Ascol = 1206 mm2
Minimum percentage of compression reinforcement; kc = 0.40 %
Minimum steel area; Asc_min = kc  Aconc = 810 mm2
Maximum steel area; As_max = 6 %  Aconc = 12150 mm2
Area of compression steel provided OK
Major axis Shear Resistance of Concrete Columns - (cl 3.8.4.6)
Column width; b = 450 mm
Column depth; h = 450 mm
Effective depth to steel; h' = 399 mm
Area of concrete; Aconc = b  h = 202500 mm2
Design ultimate shear force (major axis); Vx = 150 kN
Characteristic strength of concrete; fcu = 25 N/mm2

24
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

Is a check required? (3.8.4.6)


Axial load; N = 1296.0 kN
Major axis moment; Mx = 0.0 kNm
Eccentricity; e = Mx / N = 0.0 mm
Limit to eccentricity; elimit = 0.6  h = 270.0 mm
Actual shear stress; vx = Vx / (b  h') = 0.8 N/mm2
Allowable stress; vallowable = min ((0.8 N1/2/mm)  (fcu ), 5 N/mm2 ) = 4.000
2
N/mm
No shear check required
Define Containment Links Provided
Link spacing; sv = 175 mm; Link diameter; Ldia = 8 mm; No of links in each group; Ln = 1
Minimum Containment Steel (Cl 3.12.7)
Shear steel
Link spacing; sv = 175 mm
Link diameter; Ldia = 8 mm
Column steel
Diameter; Dcol = 16 mm
Min diameter; Llimit = max( (6 mm), Dcol/4) = 6.0 mm
Link diameter OK
Max spacing; slimit = 12  Dcol = 192.0 mm
Link spacing OK
Check of nominal cover - (BS8110:Pt 1, Table 3.4)
Column depth (larger column dimension); h = 450 mm
Depth to "tension" steel from compression face; h' = 399 mm
Diameter of vertical column reinforcement; Dcol = 16 mm
Diameter of links; Ldia = 8 mm
Cover to tension reinforcement; cten = h - h' - Dcol / 2 = 43.0 mm
Nominal cover to links steel; cnom = cten - Ldia = 35.0 mm
Permissible min nom cover to all reinf (Table 3.4); cmin = 35 mm
Cover OK

25
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

Foundation Design (F2 at grid intersection D2)


Data and assumptions

Safe bearing capacity of the soil, Qs = 200kN/m2


Characteristic strength of concrete, fcu = 25N/mm2
Steel grade, fy = 410N/mm2
Concrete cover, C = 50mm
Shear reinforccement, fyv = 250N/mm2
Column dimensions = 450 x 450mm
Diameter of steel, θ = 16mm
Overall thickness of footing, h = 400mm

Analysis

Serviceability load Ns = 1.0Gk + 1.0Qk + Wb

Allow for weight of footing Wb to be 10% of serviceability load

Assume square footing of side Lm

Dead load Gk from Column C3

Beam 02 grid 2, Beam 10 grid D (2nd floor)

37.11 x 2(5.73/2) + 2.48(2.615+2.723/2) = 222.5kN

Beam 02 grid 2, Beam 05 grid D (1st floor)

17.85 x 2(5.73/2) + 2.48(2.72/2 + 2.615/2) = 108.9kN

Self weight of the column (all floors)

0.45x0.45x24x3x3 = 43.74kN

Total dead axial load, Gk from column C3 = 357.14

Imposed load Qk from Column C3

Beam 02 grid 2 (2nd floor)

16.25 x 2 (5.73/2) = 93.11kN

Beam 02 grid 2 (1st floor)

15.91 x 2(5.73/2) = 91.16kN

Total imposed axial load, Gk from column C3 = 184.27kN

26
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

Service Load, Ns = 1.0Gk + 1.0Qk + Wb

Wb = 0.1(357.14 + 184.27) = 54.14kN

Therefore, Ns = 357.14 + 184.27 + 54.14 = 595.55kN

Plan area of the base, Ap = Ns/Qs =Service load/safe bearing Capacity of section

Ap = 595.55/200

= 2.978m2 Hence L2 = 2.978m2

L = sqrt(2.978) L = 1.73m

Hence provide a 1.8m x 1.8m Square base (Area = 3.24m2)

Self weight of the footing

Assume overall depth of the footing h = 400mm, then self weight of footing = Volume x Density

= 3.24x0.4x24 = 31.1kN < assumed (54.14) …………. O.K

For ultimate limit state,

Ultimate load, Nu = 1.4x357.14 + 1.6x184.27 = 794.83 kN

Ultimate pressure,

Qu = Nu/L2 = 794.83/1.82 = 245.32 kN/m2

27
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

Effective depth d = h-cover- θ – θ/2 = 400-50-16-8 =326mm

Checking shear stress at the column face

v = Nu/dxColumn perimeter = Nu/dx4C = 794.83x1000/4x326x450 = 1.35N/mm2

v = 1.35 N/mm2 < 5N/mm2 < 0.8√ fcu (4 N/mm2) ……………………….. O.K

Ultimate moment check at the column face

Myy = 0.5 x Qu x L x x2

Myy = 0.5 x 245.32 x 1.8 x 6752

100.6kNm

Moment reinforcement

At the column face which is the critical section

M 100.6 x 10
6
K= 2 = 2 = 0.021
bd f cu 1800 x 326 25
Since K < K’ = 0.156, then no compression reinforcement is required

The lever arm

{ (
Z= d 0.5+√ 0.25−
K
0.9 )} { (
= d 0.5+√ 0.25−
0.021
0.9 )} = 0.976d

0.976d > 0.95d, take Z = 0.95d, = 0.95 x 326 =309.7mm

M 100.6 x 10
6
As =
0.95 Z f y
= = 833.97mm2
0.95 x 410 x 309.7
Provide T16 @ 200mm centers (As prov = 1005mm2)

Check minimum percentage of steel

As min = 0.13bh/100 =0.13x1000x400/100 = 520mm2/m

Since As prov > As min, …………… O.K

Distribution bars

The size of the distribution bars is the same as the main bars

No of bars = (1800/200) + 1 = 10

Lc < (3bc + 9d)/4 Lc = 1800/2 = 900

900 < (3x450 + 9x326)/4

900 < 1071

The reinforcement should be distributed uniformly across the full width of the foundation

28
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

Check for Vertical shear

Vertical shear is checked at distance d from the column face

Shear force V = Ultimate pressure x Area considered

= 200 x 0.326 x 1.8 = 117.36

Shear stress, v = V/Ld = 117360/1800x326 = 0.199N/mm2

Shear resistance

( )( )
1 1
100 A sprov 3 400 1
vc= 0.79 b d d
4
1.25
w

100 A sprov 100 x 1005


= = 0.308 < 3.0, OK
bw d 1000 x 326

( 400d ) = ( 400
326 )
= 1.23 > 1.0 ….ok

1 1
1
vc= 0.79( 0.308 )3 ( 1.23 ) 4 = 0.448N/mm2
1.25

Since vc = 0.448N/mm2 > 0.446 N/mm2, no shear reinforcement is required

29
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

30
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

Staircase Design (East end dog-leg staircase)


Reference drawing

11 x 250 = 2500

31
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

Design Data and Analysis

Height from ground to ceiling, h= 3000mm


Riser, R= 150mm
Treads, T= 250mm
Nosing = 20mm
Thickness of slab t= 225mm
Total Height H= 4225
Height of each flight =3225/2 =1612.5
Number of risers =2112.5/150
n= 11
Rise =2112.5/14 = 146.6mm
Number of treads =11-1 = 10 per flight
Space occupied by treads = 10x250 = 2500mm
Width of landing = 1400mm
From 550 < (2R+T) < 700, 2R+T= 2x146.6+250= 543
Since 550<552<700, OK
Effective span, L= clear distance + distance from end of flight to beam centre + ½(landing breadth)
= 2500 + 240 + ½(1400)
= 3440
Imposed load Qk= 4kN/m2 (BS 6399-1: 1996 table 1)
Finishes and plaster = 25mm (at top and underside of the stair and landing)
Reinforcement grade, fy= 250N/mm
Concrete grade, fcu= 25N/mm2
Concrete cover = 25mm (mild conditions of exposure)
Main bars diameter = 12mm
Weight of concrete =24kN/m3
Thickness of waist =200mm
Loading and moment

Landing
Overall thickness of staircase = thickness of landing slab + thickness of finishes
= 200 + 25 + 25 = 250mm
Dead load, Gk= 0.25 x (1.4/2)x1.22x24 =5.12kN
Imposed load, Qk= 4 x (1.4-0.15) x (1.22/2) =3.05kN
Design load W= 1.4Gk + 1.6Qk
=1.4 x 5.12 + 1.6 x 3.05 =12.05kN

32
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

Stair flight

1612.5

2500 + 240 = 2740

slope length S= sqrt*(2.742 + 1.61252)


=3.18 m
Θ = Arc tan(1.6125/2.74) =30.5o < 38o OK

t = 250 + 20 = 270

Projection h = 270sinΘ =270 x sin30.5 = 137.04


Average thickness of stair slab = thickness of waist + finishes + projection h/2
=200+25+25+137.04/2 =318.5mm
The dead load is calculated using the slope while the imposed load acts on the plan length
Ultimate Dead Load, 1.4Gk = 1.4 x 3.44 x 1.0 x 0.3185 x 24
= 36.81kN
Ultimate Imposed Load, 1.6 Qk = 1.6 x 2.74 x 1.22 x 4
= 21.39kN
Total load on flight = 36.81 + 21.39
= 58.2kN
Total load on span, F = load on landing + load on flight
= 12.05 + 58.2
F= 70.25kN
Span moments = support moments
Fl 70.25 x 3.44
M= = = 24.17kNm
10 10

33
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

MOMENT REINFORCEMENT

Effective depth d= 200 – 6 – 25 = 169mm

Effective width B= 1000mm

M 24.17 x 10
6
K= 2 = 2 = 0.0338
bd f cu 1000 x 169 x 25
K = 0.0488 < K’ =0.156, no compression steel required

[ √
Z = d 0.5+ 0.25−
K
0.9 ] [ √
=d 0.5+ 0.25−
0.0488
0.9 ] = 0.942d

Z= 0.942 x 169 =159.28mm

Area of steel

M 24.17 x 10
6
As = =
0.95 f y Z 0.95 x 250 x 159.28
= 638.93mm2

Provide T12 bars@150mm C/C, As= 754mm2

Check for minimum area of steel

100 As 0.24 b w h
bw h
= 0.24 As =
As
0.24 x 200 x 1000
As = = 480mm2/m width
100
Provide T12 bars@225mm C/C (As = 503mm2) as distribution bars

CHECK FOR SHEAR RESISTANCE

F 70.25
Maximum shear force at supports, V= = = 35.125kN
2 2
3
V
Applied shear stress v= = 31.125 x 10 = 0.184
bd 1000 x 169
0.8 √ f cu = 0.8 √ 25 =4.0N/mm2

Since v = 0.184 < 0.8 √ f cu =4.0N/mm2, then the slab dimensions are OK

Design shear stress

( ) 1.25
1

( )
1
100 A sprov 3 400
1
vc= 0.79 bw d d
4

100 A sprov 100 x 754


= = 0.446 < 3.0, OK
bw d 1000 x 169

34
Structural calculations report of Agape Church Commity Complex building on plot No. 1214/15 Block No. 13 at
Najjanankumbi Namuli Zone in Rubaga division, Kampala for Mr STEPHEN SSEKABIRA & NABUKEERA
CHRISTINE MUKULU KYAYOGERA, P.O. Box 24657 K’la, Uganda

( 400d ) ( 400 )
= 169 = 2.36 > 1.0, OK

1 1
1
vc= 0.79( 0.669 ) 3 ( 2.367 ) 4 = 0.685N/mm2
1.25

Since vc = 0.685N/mm2 > 0.634 N/mm2, no shear reinforcement is required

DEFLECTION CHECK

The slab is checked for deflection across the shorter span

Actual span/effective depth ratio = 3440/169 = 20.35

Basic span/effective depth ratio = 20 (Simply supported sections)

Modification factor for steel

(477−fs)
≤2.0
Modification factor MF =0.55 +
( M
120 0.9+ 2
bd )
2 f y x A s−req 2 x 250 x 638.93
fs= = = 141.2N/mm2
3 x A s− prov 3 x 754
6
M 24.17 x 10
2 = 2 =0.846
bd 1000 x 169
(477−141.2)
MF = 0.55 + =1.95 < 2.0
120 ( 0.9+0.846 )
Allowable span/effective depth = (Basic span/effective depth)*MF

=20x1.95

=39.0

Actual span/effective depth =24.79 < 39.0, the deflections are allowable

Percentage of stair flight

2740
= x 100 = 79.7% > 60%........ OK
3440
Check for cracking

Spacing provided < 3d or 750mm whichever is less

3d = 3x169 =507mm

Since maximum spacing provided is 225mm, no cracking will occur.