Source-changeover systems

for circuit breakers and


switch-disconnectors
40 to 5000 A
Catalogue

2001

Get more with the world's Power & Control specialist


E88157
E79178

Interlocking of two Interpact switch-disconnectors via rotary


handles

Things
E79179

never be
will
Complete source-changeover
assembly with two Interpact
switch-disconnectors the same
E79180

To ensure a continuous supply of electrical power, certain


installations are connected to two sources:
b a normal source N
b a replacement source R used to supply the installation
when the normal source is unavailable.

A source-changeover system switches the load between


Interlocking of two Compact NS circuit breakers on a base
these two sources. It can be automated to manage transfers
plate according to external conditions. A source-changeover system
includes two or three circuit breakers or switch-disconnectors.

With Interpact INS, Compact NS and Masterpact NT and NW,


056426

new installation solutions are available to optimise the size of


the switchboard and simplify installation.

Interlocking of two Masterpact NT and NW circuit breakers


using cables
Source-changeover
systems General contents

Presentation 2

Functions and characteristics 7

Dimensions 33

Electrical diagrams 55

Order forms 91

Schneider Electric 1
Presentation For maximum continuity of
service ...

Manual source-changeover system


87921 RCD

This is the most simple type. It is controlled manually by an operator and


consequently the time required to switch from the normal to the replacement
source can vary.
A manual source-changeover system is made up of two or three mechanically
interlocked manually-operated circuit breakers or switch-disconnectors.

Remote-operated source-changeover system


This is the most commonly employed system for devices with high ratings (above
400 A).No human intervention is required. Transfer from the normal to the
replacement source is controlled electrically.
A remote-controlled source-changeover system is made up of two or three circuit
breakers or switch-disconnectors linked by an electrical interlocking system that
may have different configurations. In addition, a mechanical interlocking system
protects against electrical malfunctions or incorrect manual operations.

Automatic source-changeover systems


An automatic controller may be added to a remote-operated source-changeover
system for automatic source control according to programmable operating modes.
This solution ensures optimum energy management:
Commercial and service sector: b transfer to a replacement source according to external requirements
b operating rooms in hospitals b management of power sources
b safety systems for tall buildings b regulation
b computer rooms (banks, insurance companies, etc.) b emergency source replacement, etc.
b lighting systems in shopping centres…
The automatic controller may be fitted with an option for communication with a
supervisor.
029693

Industry:
b assembly lines
b engine rooms on ships
b critical auxiliaries in thermal power stations…
E79173

Infrastructure:
b port and railway installations
b runway lighting systems
b control systems on military sites…

2 Schneider Electric
Presentation ... in a wide range of applications
E79178

056426

056426
Interlocking of two Interpact switch-disconnectors via rotary
handles
E79179

Interlocking of two Masterpact NT and NW circuit breakers using cables


E79181

E79182
Complete source-changeover assembly with two Interpact
switch-disconnectors
E79180

Interlocking of two Masterpact NT or NW Interlocking of three Masterpact


circuit breakers using connecting rods NW circuit breakers using cables
Interlocking of two Compact NS circuit breakers on a base
plate

Schneider Electric 3
Presentation For maximum continuity of
service ...

Incoming feeders and main LV switchboards

E68384
E79176

or

Currents
from 630 to 6300 A

Power distribution

G
E79177

or

Currents
from 250 to 3200 A

Loads
E52812

or

Currents
from 40 to 400 A

4 Schneider Electric
Presentation ... in a wide range of applications

1 normal source 2 sources with coupler on 2 normal sources


1 replacement source busbars 1 replacement source

E72535
TR1 TR2 TR1 TR2
G
E68385

E72534
UN G

UR

Q1 Q2 Q3 Q1 Q2 Q3

Q1 Q2

Q1 Q2 Q1 Q2 Q3 Q1 Q2 Q3
0 0 0 0 0 0 0 0
1 0 1 0 0 1 0 0
0 1 0 1 0 0 1 0
0 0 1 0 0 1
1 0 1 1 0 1
1 1 0
0 1 1

Generator or permanent source


Q1 Q2 Typical applications
E72536

0 0 b continuous production processes


G 1 0 b operating rooms
0 1 b computer rooms

Q1 Q2

Generator or permanent Generator or permanent


source source
E72537

Q1 Q2
E72536

Typical applications
0 0 b large electrical installations (e.g. airports)
G 1 0 b refrigeration units
0 1 b special electricity tariffs
G
b pumping stations

Q1 Q2

Q1 Q2

LOAD

Schneider Electric 5
6 Schneider Electric
Source- Functions and characteristics

changeover
systems
Presentation 2

Overview of solutions
Manual source-changeover systems 8
Remote-operated source-changeover systems 10
Manual source-changeover systems
Interlocking of two or three toggle-controlled devices 12
Interlocking of two devices with rotary handles 12
Interlocking of devices using keylocks (captive keys) 13
Interlocking of two devices on a base plate 13
Complete source-changeover assembly 13
Remote-operated source-changeover systems
General characteristics 14
Mechanical interlocking 16
Electrical interlocking 18
Standard configurations 19
Associated controllers
Controller selection 20
Controller installation 21
BA controller 22
UA controller 24
Operated sequences
IVE unit 28
BA controller 29
UA controller 29
COM communication option 30
Accessories
Connection and insulation accessories 31

Dimensions 33
Electrical diagrams 55
Order forms 91

Schneider Electric 7
Functions Overview of solutions
and characteristics Manual source-changeover systems
Interpact INS and
Compact NS 40 A to 630 A
Range Interpact Compact
Models INS40 to INS80 INS250 to INS630 NS100 to NS250
INS100 to INS160 INV250 to INV630 NS400 to NS630
Rating (A) 40 to 160 100 to 630 100 to 630
Type of device Switch-disconnectors with Switch-disconnectors N/H/L circuit breakers
extended handles NA switch-disconnectors
Manual source-changeover systems
Interlocking via toggles

2 devices side-by-side 3 devices side-by-side

Interlocking via rotary handles


.1
.2
.4

.1
.2
2
.4

N
ON
I
ON
ON I
ON
I
N I ON
I trippe
d

ON
ON ON I
reset
I tripped
I ø5...8
O
OFF

O OFF

2 devices side-by-side
reset d
trippe

reset
tripped O OFF ø5...8
O
OFF
O OFF
reset
O OFF
O OFF
O OFF

Interlocking via keylocks with captive keys

ON
I

ON
I reset
O
OFF
ø5...8

O
ø5...8
OFF

A number of different devices

Interlocking on a base plate

2 devices side-by-side
push
to
trip

push
to
trip

Complete source-changeover assemblies

2 devices side-by-side

8 Schneider Electric
Functions Overview of solutions
and characteristics Manual source-changeover systems
Compact NS and
Masterpact NT/NW 630 A to 6300
Gammes Compact Masterpact
Models NS630b to NS1600 NT06 to NT16 NW08 to NW63
Rating (A) 630 to 1600 630 to 1600 800 to 6300
Type of device N/H/L circuit breakers H1/L1 circuit breakers N1/H1/H2/H3/L1 circuit breakers
NA switch-disconnectors HA switch-disconnectors NA/HA/HF switch-disconnectors
Manual source-changeover systems
Interlocking via extended rotary handles

2 devices side-by-side tripped


reset
tripped

reset

Interlocking via keylocks with captive keys

I ON
push
O OFF
push

discharged

O OFF

I ON
push
O OFF
push

t II
discharged masterpac

O OFF GERIN
MERLIN

t II
masterpac

GERIN
MERLIN

A number of different devices

Mechanical interlocking using connecting rods

O
FFO
hsup
O
NO h
I FFO
hsup
sup

NO h
I
sup

FFO
O
degr
ahcs
id FF O
O
degr
ahcs
id

O
FFO
hsup

NO h
I
sup

O
FFO
FFO
O hsup

degr
ahcs
I
NO h
id sup

FF O
O
degr

2 devices one above the other


ahcs
id

(1)
Mechanical interlocking using cables

O
FFO
O hsup
FFO
hs u p I
NO h
I NO h
sup
sup

FFO
O
FFO
O
d e gr degr
ahcs ahcs
id id

2 or 3 devices one above the other


FF O
O
hs up

NO h
I
sup

O
FFO
hsup

NO h
I
FFO
O sup

d e gr
ahcs
id

FFO
O
degr
ahcs
id

2 or 3 devices side-by-side (1)

(1) Implemented with NS630b to NS1600 electrically-operated devices only.

Schneider Electric 9
Functions Overview of solutions
and characteristics Remote-operated
source-changeover systems
Compact NS100/1600 100 A to 1600 A
Range Compact
Models NS100 to NS630 NS630b to NS1600

Rating (A) 100 to 630 630 to 1600


Type of device N/H/L circuit breakers N/H/L circuit breakers
NA switch-disconnectors NA switch-disconnectors
Remote-operated source-changeover system
Mechanical interlocking on base plate + electrical interlocking

R R
N 0 . OFF

I . ON
0 . OFF

N
R
N

com

t1 (s)

GERIN UN =
O
MERLIN
NS
N t3 (s)
compact
Hz
UA automatism
50/60 t4 (s)
200/240V UR
R
E UN
DER
DE RECHANG N t2 (s) R

R
ON
EN CAS IL COMMAN 1
REF: UN =
D'APPARELES · 250
AUSSIPOUR NS100
ON OFF
29270 POUR NS400-630
32520 OFF
breaker fault
t5 (s)
for circuit nt order
replacemeN°: · 250 generator
REF fault stop
also for NS100
29270 NS400-630 auto
for
32520
test
stop
manu
R

N N

2 electrically-operated devices side-by-side combined


with an electrical interlocking system

Mechanical interlocking using connecting rods + electrical interlocking

O
FF O
hsup

I
NO h
sup

FFO
O
degr
ahcs
id

FFO
O
hsup

I
NO h
sup

FF O
O
degr
ahcs
id

2 electrically-operated devices one above the other combined


with an electrical interlocking system

Mechanical interlocking using cables + electrical interlocking

FF O
O
hsup

NO h
I
s up

FFO
O
d e gr
ahcs
id

2 electrically-operated devices one above the other combined


with an electrical interlocking system

FF O
O
hs u p

NO h
I
s up

FFO
O
d e gr
ahcs
id

2 electrically-operated devices side-by-side combined


with an electrical interlocking system

Automatic source-changeover systems


Remote-operated source-changeover system combined with an automatic-control system
The automatic controller
operates the devices
depending on external LIN GER
MERNS
IN
N
UN =
O
t1 (s)

compact

parameters.
UR
R
UN
N t2 (s) R
ON 1
UN =
ON OFF

OFF
fault

fault
auto

stop

BA: Simple controller that manu

N
R

manages the changeover BA controller


function.

UA: Controller that also


com

manages engine generator LIN GER


MERNS
compact
IN

UR
N
UN =

t4 (s)
O
t1 (s)

t3 (s)

sets.
R
UN
N ON t2 (s) R
1
UN =
ON OFF

OFF
fault t5 (s)
ator
gener
fault stop
auto

test
stop
manu
R

UA150: UA controller with a N

communication option. UA and UA150 controller

10 Schneider Electric
Functions Overview of solutions
and characteristics Remote-operated
source-changeover systems
Masterpact NT/NW 630 A to 6300 A
Range Masterpact
Models NT06 to NT16 NW08 to NW63

Rating (A) 630 to 1600 800 to 6300


Type of device H1/L1 circuit breakers N1/H1/H2/H3/L1 circuit breakers
HA switch-disconnectors NA/HA/HF switch-disconnectors
Remote-operated source-changeover system
Mechanical interlocking using connecting rods + electrical interlocking

FFO
O
hsup

NO h
I
sup

FFO
O
degr
ahcs
id

FFO
O
hsup

NO h
I
sup

FFO
O

2 electrically-operated devices one above the other combined


degr
ahcs
id

with an electrical interlocking system

Mechanical interlocking using cables + electrical interlocking

O
FFO
hsup

NO h
I
sup

FFO
O
d e gr
ahcs
id

2 or 3 electrically-operated devices one above the other


combined with an electrical interlocking system (1) O
FFO
hsup

NO h
sup
I

FFO
O
d e gr
ahcs
id

2 or 3 electrically-operated devices side-by-side combined


with an electrical interlocking system (1)

Automatic source-changeover systems


Remote-operated source-changeover system combined with an automatic-control system
The automatic controller
operates the devices
depending on external IN
t1 (s)

LIN GER
O
UN =

parameters.
MERNS N
compact

UR
R
UN
N t2 (s) R
ON 1
UN =
ON OFF

OFF
fault

fault
auto

BA: Simple controller that stop


manu

N
R

manages the changeover


BA controller
function.

UA: Controller that also


manages engine generator IN
com

t1 (s)

LIN GER UN =
O

sets.
MERNS N t3 (s)
compact
t4 (s)
UR
R
UN
N ON t2 (s) R
1
UN =
ON OFF

OFF
fault t5 (s)
ator
gener
fault stop
auto

UA150: UA controller with a


test
stop
manu
R

communication option.
UA and UA150 controller

(1) Three devices with Masterpact NW only.

Schneider Electric 11
Functions Manual source-changeover
and characteristics systems
Possible combinations

A manual source-changeover system can All possibilities for manual source-changeover systems
be installed on two or three manually- Type of devices
operated and mechanically interlocked INS40 to INS80 complete assembly
INS100 to INS160 toggle
circuit breakers or switch-disconnectors. INS250 (ratings 100 to 250) keylock
Interlocks prevent connection to both INV100 to INV250 (1) rotary handle
sources at the same time, even INS320 to INS630 on base plate
INV320 to INV630 (1) c
momentarily. c c
NS100 to NS250 c c c cables / 2 side-by-side
NS400 to NS630 c c cables / 3 side-by-side
c c
mixed NS100 to NS630 (2) c c c cables / 2 stacked
c c c
NS630b to NS1600 c c cables / 3 stacked
c c c
NT06 to NT16 c c c connecting rods / 2 stacked
c c c
NW08 to NW63
c
c
(1) visible break function c c
c c c
(2) with rotary handle interlocking c
c c
for NS400/630 c

Interlocking of two or three toggle-controlled devices


E87481

Two devices can be interlocked using this system. Two identical interlocking systems
can be used to interlock three devices installed side by side, in which case one
device is in the ON position and the two others are in the OFF position. Devices must
all have the same configuration, i.e. fixed, plug-in, withdrawable or drawout.
The system is locked using one or two padlocks (shackle diameter 5 to 8 mm).
Two interlocking system models are available for:
b Compact NS100 to 250
b Compact NS400 to 630.

Possible combinations of “Normal” and “Replacement” source circuit breakers


Interlocking of two toggle-controlled devices
ratings “Normal” N “Replacement” R
16 … 100 NS100 NS100
80 … 160 NS160 NS160
125… 250 NS250 NS250
c
150 … 400 NS400 c c NS400
c c c
630 … 630 NS630 c c c c NS630
c c c c c
c c c c
c c c
c c
c
E87482

Interlocking of two devices with rotary handles


The direct or extended rotary handles are padlocked with the devices in the OFF
position. The mechanism prevents simultaneous closing of the devices, but allows
them to be opened.
ON
I

ON
I
ø5...8
Possible combinations of “Normal” and “Replacement” source switch-disconnectors
ratings “Normal” N “Replacement” R
ø5...8
O OFF
Interpact INS (1)
O OFF
40 INS40 INS40
63 INS63 INS63
80 INS80 INS80
100 INS100 c INS100
c c
Interlocking of two Interpact switch-disconnectors with direct 125 INS125 c c c INS125
c c c c
rotary handles 160 INS160 c c c c c INS160
c c c c c c
c c c c c
c c c c
Interpact INS/INV (2) c c c
c c
100 INS250-100/INV100 c INS250-100/INV100
160 INS250-160/INV160 INS250-160/INV160
200 INS250-200/INV200 INS250-200/INV200
250 INS250-250/INV250 INS250-250/INV250
320 INS320/INV320 c INS320/INV320
c c
400 INS400/INV400 c c c INS400/INV400
c c c c
500 INS500/INV500 c c c INS500/INV500
c c
630 INS630/INV630 c INS630/INV630
c
c c
c c c
(1) With extended rotary handles c c c c
c c c
only. c c
c
(2) Possible with INV, but visible-
break function is significantly
impaired.

12 Schneider Electric
Functions Manual source-changeover
and characteristics systems
Possible combinations
E87483

Possible combinations of “Normal” and “Replacement” source circuit breakers


ratings “Normal” N “Replacement” R
Compact NS100/630 (1)
I
ON
16 … 100 NS100 NS100
ON

80 … 160 NS160 NS160


I

ON
I
125 … 250 NS250 NS250
ed
tripp
ON

c
I
t
rese
O
OFF

O OFF 160 … 400 NS400 c c NS400


tripp
ed

c c c
rese
t
O
OFF 630 … 630 NS630 c c c c NS630
O OFF c c c c c
Compact NS630b/1600 c c c c
c c c
250 … 630 NS630b c c NS630b
c
320 … 800 NS800 NS800
Interlocking of two Compact NS circuit breakers with rotary 400 … 1000 NS1000 NS1000
handles. c
480 … 1200 NS1200 c c NS1200
c c c
640 … 1600 NS1600 c c c c NS1600
c c c c c
c c c c
c c c
(1) When mixing NS100/250 and c c
c
NS400/630 circuit breakers, use the
NS400/630 interlocking system.
E87484

Interlocking of a number of devices using keylocks (captive


keys)
Interlocking is based on two identical keylocks with a single key and a keylock
ON
I

adapter (different for each device). This solution enables interlocking between two
ON
I rese
t

O
devices that are physically distant or that have very different characteristics, for
OFF

example between a low and a medium-voltage device, or between Compact NS


O
OFF
circuit breakers and switch-disconnectors.
A system of wall-mounted captive key boxes makes possible a large number of
combinations between many devices.

Combination of “Normal” and “Replacement” devices


All Interpact, Compact and Masterpact circuit breakers and switch-disconnectors from 100 to
Keylock-type interlocking of two circuit breakers with rotary 6300 A with rotary handles or motor mechanisms can be interlocked.
handles or motor mechanisms.

Interlocking of two devices on a base plate


E87485

A base plate is available for mechanical interlocking of two manually-operated


Compact circuit breakers or switch-disconnectors.
Possible combinations of Compact “Normal” and “Replacement” source circuit breakers
ratings “Normal” N “Replacement” R
16 … 100 NS100 NS100
80 … 160 NS160 NS160
125 … 250 NS250 c NS250
150 … 400 NS400 c c NS400
c c c
push
to
trip

630 … 630 NS630 c c c c NS630


c c c c c
push
to
trip
c c c c
c c c
c c
c

Interlocking of two manually-operated Compact NS devices


on a base plate.
Complete source-changeover assembly for two switch-
disconnectors
E72572

These assemblies provide an easy way to implement source changeover functions with:
b a single 3-position rotary handle that controls the two switch-disconnectors
(Normal source ON, OFF, Replacement source ON)
b a smaller size, taking up less room in the switchboard.
A complete source changeover assembly can be ordered with a single catalogue
number..
Possible combinations of “Normal” and “Replacement” source switch-disconnectors
ratings “Normal” N “Replacement” R
100 INS250 -100 INS250 -100
160 INS250 -160 INS250 -160
Complete source-changeover assembly for two Interpact INS 200 INS200 -200 INS250 -200
c
switch-disconnectors. 250 INS250 -250 INS250 -250
c
320 INS320 INS320
c
400 INS400 INS400
c
500 INS500 INS500
c
630 INS630 INS630
c
c
c

Schneider Electric 13
Functions Remote-operated
and characteristics source-changeover
systems
General characteristics
Range Compact
Types of devices NS100 to NS250 NS400 to NS630 NS630b to 1600
Types of circuit breakers N/H/L N/H/L N/H/L
Switch-disconnector version NA NA NA
Mixing possibilities all devices all devices all devices
NS100 to NS250 NS100 to NS630 NS630b to 1600
N/H/L/NA N/H/L/NA N/H/L/NA
fixed or plug-in fixed or plug-in fixed or withdrawable
Electrical characteristics
Rating 15 to 250 A 15 to 630 A 250 to 1600 A
Insulating voltage Ui (V AC) 750 750 750
Positive break indication c c c
Number of poles 3, 4
(N and R devices must have the same number of poles)
Electrical durability (Normal-Replacement-Normal cycle) at 30 000 (NS100) 6 000 (NS400) 5 000 (NS630b to NS1000)
440 V, type N (for other voltages : see the product catalogue) 20 000 (NS160) 4 000 (NS630) 4 000 (NS1250 to NS160)
Operating temperature –25 °C to +70 °C (50 °C for 440 V - 60 Hz)
Control characteristics
Control voltage AC 48 to 415 V - 50/60 Hz
440V - 60 Hz
DC 24-250 V
Maximum consumption AC 500 VA 500 VA 180 VA
DC 500 W 500 W 180 W
Minimum switching time 800 ms 800 ms 800 ms
Interlocking
Mechanical on base plate (vertical or horizontal) c c
by rods (stack-mounted devices) c
by cable (side-by-side or stack-mounted devices) c
Electrical by diagram (without IVE) c c c
with IVE unit c c c
auxiliary contacts used by circuit breaker 1 OF + 1 SDE 1 OF + 1 SDE 1 OF + 1 CE (+ SDE)
Protection and measurement
Overload protection long time c c c
Short-circuit protection short time c c c
instantaneous c c c
Earth-fault protection c c
Zone selective interlocking (ZSI) c c
Earth-leakage protection by Vigi module c c
by control unit c
by add-on Vigirex relay c c c
Current measurements c
Voltage, frequency, power measurements, etc.
Indication and control auxiliaries
Available auxiliary indication contacts OF + SD (+ SDV) 2 OF + SD (+ SDV) 2OF + S
Voltage releases MX shunt c c c
MN undervoltage c c c
Voltage presence indicator c c
Voltage transformer c c
Ammeter module c c
Insulation monitoring module c c
Source-changeover controller
With permanent replacement source c BA controller
With standby generator set c UA controller
Remote communication via bus
Device status indications c c c
Device remote control
Transmission of settings c
Indication and identification of protection status and alarms c
Transmission of measurements c
Installation and connection
Fixed front connected c c c
Fixed rear connected c (long rear connections) c (long rear connections) c (vertical or horizontal)
Withdrawable, plug-in or drawout c (plug-in on base) c (plug-in on base) c (withdrawable on chassis)
Installation and connection accessories
Downstream coupling accessory c c
Bare-cable connectors c c c
Terminal extensions c c
Terminal shields and inter-phase barriers c c
Locking by padlock c c c
by keylock c c c
Front panel escutcheons c c c

14 Schneider Electric
Functions Remote-operated
and characteristics source-changeover
systems
General characteristics
Range Masterpact
Types of devices NT06 to 16 NW08 to 63
Types of circuit breakers N1 / H1 / H2 / H3 / L1 N1 / H1 / H2 / H3 / L1
Switch-disconnector version NA / HA / HF NA / HA / HF
Mixing possibilities all mixing possibilities all mixing possibilities
(fixed, drawout or fixed (fixed, drawout or fixed)
+ drawout) + drawout)
N1/H1/H2/H3/L1/NA/HA/HF N1/H1/H2/H3/L1/NA/HA/HF
Electrical characteristics
Rating 600 to 1600 A 800 to 6300 A
Insulating voltage Ui (V AC) 1000 1000
Positive break indication c c
Number of poles 3, 4
(N and R devices must have the same number of poles)
Electrical durability (Normal-Replacement-Normal cycle) at 6 000 (NT06 to NT12) 10 000 (VW08 to NW16), 8 000 (NW20)
440 V, type N (for other voltages : see the product catalogue) 3 000 (NT16) 5 000 (NW25 to NW40), 1 500 (NW40b to NW63)
Operating temperature –25 °C to +70 °C (50 °C for 440 V - 60 Hz)
Control characteristics
Control voltage AC 48 to 415 V - 50/60 Hz
440V - 60 Hz
DC 24-250 V
Maximum consumption AC 180 VA 180 VA
DC 180 W 180 W
Minimum switching time 800 ms 800 ms
Interlocking
Mechanical on base plate (vertical or horizontal)
by rods (stack-mounted devices) c c
by cable (side-by-side or stack-mounted devices) c c
Electrical by diagram (without IVE) c c
with IVE unit only with UA or BA only with UA or BA
auxiliary contacts used by circuit breaker 1 OF + 1CE + 1 PF 1 OF + 1CE + 1 PF
Protection and measurement
Overload protection long time c c
Short-circuit protection short time c c
instantaneous c c
Earth-fault protection c c
Zone selective interlocking (ZSI) c c
Earth-leakage protection by Vigi module
by control unit c c
by add-on Vigirex relay c c
Current measurements c c
Voltage, frequency, power measurements, etc. c c
Indication and control auxiliaries
Available auxiliary indication contacts 2 OF + SD 2 OF + SD
Voltage releases MX shunt c c
MN undervoltage c c
Voltage presence indicator c c
Voltage transformer c c
Ammeter module c c
Insulation monitoring module c c
Source-changeover controller
With permanent replacement source c BA controller
With standby generator set c UA controller
Remote communication via bus
Device status indications c c
Device remote control
Transmission of settings c c
Indication and identification of protection status and alarms c c
Transmission of measurements c c
Installation and connection accesso
Fixed front connected c c
Fixed rear connected c (vertical or horizontal) c (vertical or horizontal))
Withdrawable, plug-in or drawout c (drawout) c (drawout))
Installation and connection accessories
Downstream coupling accessory
Bare-cable connectors
Terminal extensions
Terminal shields and inter-phase barriers
Locking by padlock c c
by keylock c c
Front panel escutcheons c c

Schneider Electric 15
Functions Remote-operated
and characteristics source-changeover systems
Mechanical interlocking

Electrical interlocking of two or three Interlocking of two Compact NS100 to 630 devices using a
devices is used to create a remote- base plate
operated source-changeover system. A A base plate designed for two Compact circuit breakers can be installed
basic mechanical interlocking system horizontally or vertically on a mounting rail. Interlocking is carried out on the base
plate by a mechanism located behind the breakers. Access to the circuit breaker
enhances the reliability of system
controls and trip units is conserved. Circuit breakers must be fixed or plug-in
operation. versions, with or without earth-leakage protection or measurement modules.
The base plate and the circuit breakers are supplied separately.
b Base plate for Compact NS100 to 250 devices
This base plate is intended for two Compact NS100 to 250 devices.
E79180

b Base plate for Compact NS400 to 630 devices


This base plate is intended for two Compact NS400 to 630 devices. It may also be
used, without any modifications, to interlock a fixed Compact NS100 to 250 with a
Compact NS400 or 630 device.
An adapter kit is required for plug-in versions of the Compact NS100 to 250
devices.
Compact NS100 to 250 devices, in both fixed and plug-in versions, may be
equipped with spreaders.

Possible combinations of “Normal” and “Replacement” Compact source circuit breakers


ratings “Normal” N “Replacement” R
12.5 … 100 NS100 NS100
12.5 … 160 NS160 NS160
12.5 … 250 NS250 NS250
c
160 … 400 NS400 c c NS400
c c c
250 … 630 NS630 c c c c NS630
c c c c c
c c c c
Interlocking of two electrically-operated Compact NS circuit c c c
c c
breakers using a base plate. c
E87491

Interlocking of two Compact NS630b to 1600 or two


Masterpact NT and NW devices using connecting rods
The two devices must be mounted one above the other.
Installation
This function requires:
b an adaptation fixture on the right side of each circuit breaker or switch-
disconnector
b a set of connecting rods with no-slip adjustments.
The adaptation fixtures, connecting rods and circuit breakers or switch-
disconnectors are supplied separately, ready for assembly by the customer.
The maximum vertical distance between the fixing planes is 900 mm.

Possible combinations of “Normal” and “Replacement” source circuit breakers

“Normal” N “Replacement” R
NS630b to NS1600 NS630b to NS1600
NT06 to NT16 NT06 to NT16
NW08 to NW40 NW08 to NW40
c
NW40b to NW63 NW40b to NW63
c
c c
c c c
c c
c

It is not possible to combine Compact NS630b to 1600 and Masterpact NT (or Masterpact NW)
Interlocking of two Masterpact NT and NW circuit breakers
devices.
using connecting rods.
It is possible to combine Masterpact NT and Masterpact NW devices.
The devices must be either both fixed or both withdrawable/drawout to maintain the alignment
between the mechanisms.

16 Schneider Electric
Functions Remote-operated
and characteristics source-changeover systems
Mechanical interlocking
056426

Interlocking of two Compact NS630b to 1600 or two


Masterpact NT/NW or up to three Masterpact NW devices
using cables
For cable interlocking, the circuit breakers may be mounted one above the other or
side-by-side.
The interlocked devices may be fixed or drawout, three-pole or four-pole, and have
different ratings and sizes.
Interlocking between two devices (Compact NS630b to 1600 or Masterpact
NT and NW)
This function requires:
b an adaptation fixture on the right side of each device
b a set of cables with no-slip adjustments.
The maximum distance between the fixing planes (vertical or horizontal) is 2000 mm.
Interlocking between three devices (Masterpact NW only)
This function requires:
Interlocking of two Masterpact circuit breakers using cables.
b a specific adaptation fixture for each type of interlocking, installed on the right
side of each device
b two or three sets of cables with no-slip adjustments.
The maximum distance between the fixing planes (vertical or horizontal) is 1000 mm.
Installation
The adaptation fixtures, sets of cables and circuit breakers or switch-disconnectors
are supplied separately, ready for assembly by the customer.

Possible combinations of “Normal” and “Replacement” source circuit breakers


“Normal” N “Replacement”
NS630b to NS1600 NS630b to NS1600
NT06 to NT16 NT06 to NT16
NW08 to NW40 NW08 to NW40
c
NW40b to NW63 c NW40b to NW63
c c
c c c
c c
c

It is not possible to combine Compact NS630b to 1600 and Masterpact NT (or


Masterpact NW) devices.
All combinations of two Masterpact NT and Masterpact NW devices are possible,
whatever the rating or size of the devices.

Possible combinations of three devices


“Normal” N “Replacement”
NS630b to NS1600 NS630b to NS1600
NT06 to NT16 NT06 to NT16
NW08 to NW40 NW08 to NW40
NW40b to NW63 NW40b to NW63
c
c c
c

Only Masterpact NW may be used for three-device combinations.

types of mechanical interlocking and combinations


See page 13.

Schneider Electric 17
Functions Remote-operated
and characteristics source-changeover systems
Electrical interlocking

Electrical interlocking is used with the Electrical interlocking is carried out by an electrical control device.
mechanical interlocking system. It For Compact NS up to 630 A, electrical interlocking is implemented by the IVE unit
electrically interlocks the two circuit integrating control circuits and an external terminal block. The integrated control
circuits implement the time delays required for correct source transfer.
breakers and implements the time delays
For Compact NS630b to 1600 and Masterpact, this function can be implemented in
required for proper operation of the system. one of two ways:
An automatic controller may be added to b using the IVE unit
take into account information from the b by an electrician based on the diagrams presented in the “Electrical diagrams”
distribution system. part of this catalogue.

Characteristics of the IVE unit


b external connection terminal block:
v inputs: circuit breaker control signals
v outputs: status of the SDE contacts on the “Normal” and “Replacement” source
circuit breakers
b 2 connectors for the two “Normal” and “Replacement” source circuit breakers:
v inputs:
- status of the OF contacts on each circuit breaker (ON or OFF)
- status of the SDE contacts on the “Normal” and “Replacement” source circuit
breakers
v outputs: power supply for operating mechanisms
b control voltage:
v 24 to 250 V DC
v 48 to 415 V 50/60 Hz - 440 V 60 Hz.
The IVE unit control voltage must be same as that of the circuit breaker operating
mechanisms.
E88002

IVE unit.

Necessary equipment
For Compact NS100 to 630, each circuit breaker must be equipped with:
b a motor mechanism
b an OF contact
b an SDE contact.
The components are supplied ready for assembly and the circuit breakers
prewired. The prewiring must not be modified.
For Compact NS630b to 1600, each circuit breaker must be equipped with:
b a motor mechanism
b an available OF contact
b a CE connected-position contact (carriage switch) on withdrawable circuit
breakers
b an SDE contact.
For Masterpact NT and NW, each circuit breaker must be equipped with:
b a remote-operation system made up of:
v MCH gear motor
v MX or MN opening release
v XF closing release
v PF “ready to close” contact
b an available OF contact
b one to three CE connected-position contacts (carriage switches) on drawout
circuit breakers (depending on the installation).

18 Schneider Electric
Functions Remote-operated
and characteristics source-changeover systems
Standard configurations

Compact NS, Masterpact NT and NW


types of mechanical interlocking possible combinations typical electrical diagrams diagram no.
2 devices
QN QR Compact NS100 to 630:
E72573

0 0 b electrical interlocking without emergency


QN QR power off (EPO) auxiliaries: 51201177
1 0 v with EPO by MN 51201178
0 1 v with EPO by MX 51201179
Compact NS630b to 1600:
b electrical interlocking with lockout after fault:
v permanent replacement source (without IVE) 51201180
v with EPO by MN (without IVE) 51201181
v with EPO by MX (without IVE) 51201182
v permanent replacement source (with IVE) 51201183
v with EPO by MN (with IVE) 51201184
v with EPO by MX (with IVE) 51201185
b automatic control without lockout after fault:
v permanent replacement source (without IVE) 51201186
v engine generator set (without IVE) 51201187
Masterpact NT and NW:
b electrical interlocking with lockout after fault:
v permanent replacement source (without IVE) 51201139
v with EPO by MN (without IVE) 51201140
v with EPO by MX (without IVE) 51201141
v permanent replacement source (with IVE) 51201142
v with EPO by MN (with IVE) 51201143
v with EPO by MX (with IVE) 51201144
b automatic control without lockout after fault:
v permanent replacement source (without IVE) 51156226
v engine generator set (without IVE) 51156227
b automatic control with lockout after fault:
v permanent replacement source (with IVE) 51156904
v engine generator set (with IVE) 51156905
b BA/UA controller (with IVE) 51156903

Masterpact NW only
types of mechanical interlocking possible combinations standard configurations diagram no
3 devices: 2 “Normal” sources and 1 “Replacement” source
QN1 QN2 QR b electrical interlocking:
E72574

0 0 0 v without lockout after fault 51156906


QN1 QN2 QR
1 1 0 v with lockout after fault 51156907
0 0 1

3 devices: 2 “Normal” sources and 1 “Replacement” source with source selection


QN1 QN2 QR b automatic control with engine generator set:
E72575

0 0 0 v without lockout after fault (with MN) 51156908


QN1 QN2 QR 1 0 0 v with lockout after fault (with MN) 51156909
0 0 1
1 1 0
0 1 0

3 devices: 3 sources, only one device


QS1 QS2 QS3 b electrical interlocking:
E72576

0 0 0 v without lockout after fault 51156910


QS1 QS2 QS3
1 0 0 v with lockout after fault 51156911
0 1 0
0 0 1

3 devices: 2 sources + 1 coupling


E72577

QS1 QC QS2 b electrical interlocking:


0 0 0 v without lockout after fault 51156912
QS1 QC QS2
1 0 1 v with lockout after fault 51156913
1 1 0 b automatic control with lockout after fault 51156914
0 1 1
1 0 0 (*)
0 0 1 (*)
(*) possible by forcing operation
“Lockout after fault” option. This option makes it necessary to manually reset the device following fault tripping.

Schneider Electric 19
Functions Associated controllers
and characteristics Controller selection

By combining a remote-operated source- Controller BA UA


changeover system with an integrated BA compatible circuit breakers All Compact NS
or UA automatic controller, it is possible to and Masterpact circuit breakers

automatically control source transfer 4-position switch


Automatic operation c c
according to user-selected sequences. Forced operation on “Normal” source c c
These controllers can be used on source- Forced operation on “Replacement” source c c
changeover systems comprising 2 circuit Stop (both “Normal” and “Replacement” sources off) c c
breakers. Automatic operation
Monitoring of the “Normal” c c
For source-changeover systems source and automatic transfer
comprising 3 circuit breakers, the automatic Generator set startup control c
control diagram must be prepared by the Delayed shutdown (adjustable) of generator set c
Load shedding and reconnection of non-priority circuits c
installer as a complement to to diagrams Transfer to the “Replacement” source c
provided in the “electrical diagrams” section if one of the phases of the “Normal” phase is absent
of this catalogue. Test
By opening the P25M circuit breaker c c
053058R

supplying the controller


By pressing the test button on the front of the controller c
Indications
Circuit breaker status indication on the front c c
of the controller: on, off, fault trip
Automatic mode indicating contact c c
Other functions
Selection of type of “Normal” source c
(single-phase or three-phase) (1)
Voluntary transfer to “Replacement” source c c
(e.g. energy management commands)
During peak-tariff periods (energy management commands), c
forced operation on “Normal” source
if “Replacement” source not operational
Additional contact (not part of controller). c c
Transfer to “Replacement”
source only if contact is closed.
(e.g. used to test the frequency of UR).
Setting of maximum startup time c
for the replacement source
BA controller Options
communication option c
Power supply
053058

control voltages (2) 220 to 240 V 50/60 Hz c c


380 to 415 V 50/60 Hz c c
440 V 60 Hz c c
Operating thresholds
undervoltage 0.35 Un i voltage i 0.7 Un c c
phase failure 0.5 Un i voltage i 0.7 Un c
voltage presence voltage u 0.85 Un c c
Characteristics of output contacts (3)
rated thermal current (A) 8
minimum load 10 mA at 12 V
AC DC
utilisation category (IEC 947-5-1) AC12 AC13 AC14 AC15 DC12 DC13
operational current (A) 24 V 8 7 5 6 8 2
48 V 8 7 5 5 2 -
110 V 8 6 4 4 0.6 -
220/240 V 8 6 4 3 - -
250 V - - - - 0.4 -
380/415 V 5 - - - - -
UA controller 440 V 4 - - - - -
660/690 V - - - - - -
(1) For example, 220 V single-phase or 220 V three-phase.
(2) The controller is powered by the ACP auxiliaries control plate. The same voltage must be
used for the ACP plate, the IVE unit and the circuit-breaker operating mechanisms. If this
voltage is the same as the source voltage, then the “Normal” and “Replacement” sources can
be used directly for the power supply. If not, a BC type or equivalent isolation transformer must
be used.
(3) Output contacts (dry, volt-free contacts):
b position of the Auto/Stop switch
b load shedding and reconnection order
b generator set start order.

20 Schneider Electric
Functions Associated controllers
and characteristics Controller installation

ACP auxiliaries control plate


The auxiliaries control plate provides in a single unit:
053060

c protection for the BA or UA controller with two highly limiting P25M circuit
breakers (infinite breaking capacity) for power drawn from the AC source
c control of circuit-breaker ON and OFF functions via two relay contactors
c connection of the circuit breakers to the BA or UA controller via a built-in terminal
block.
Control voltages
c 220 to 240 V 50/60 Hz
c 380 to 415 V 50/60 Hz
c 440 V 60 Hz.
The same voltage must be used for the ACP plate, the controller and the circuit-
breaker operating mechanisms.
Installation
Connection between the ACP auxiliaries control plate and the IVE electrical-
interlocking unit may use:
c wiring done by the installer
c prefabricated wiring (optional).

Installation of the BA and UA controllers


The BA and UA controllers may be installed in one of two manners:
c directly mounted on the ACP auxiliaries control plate
c mounted on the front panel of the switchboard.
The length of the connection between the ACP plate and the controller must not
exceed two metres. Wiring is done by the installer.
ACP auxiliaries control plate.
E72578

Mounting on the ACP plate.


E72579

Mounting on the front panel of the switchboard.

Schneider Electric 21
Functions Associated controllers
and characteristics BA controller

The BA controller is used to create simple Operating modes


source-changeover systems that switch A four-position switch may be used to select:
from one source to another depending on c automatic operation
c forced operation on the “Normal” source
the presence of voltage UN on the “Normal” c forced operation on the “Replacement” source
source. c stop (both “Normal” and “Replacement” sources off).
It is generally used to manage two
permanent sources and can control Setting the time delays
Compact NS and Masterpact NT/NW Time delays are set on the front of the controller.
t1. delay between detection that the “Normal” source has failed and the
circuit breakers and switch-disconnectors. transmission of the order to open the “Normal” source circuit breaker (adjustable
from 0.1 to 30 seconds).
t2. delay between detection that the “Normal” source has returned and the
053059R

transmission of the order to open the “Replacement” source circuit breaker


(adjustable from 0.1 to 240 seconds).

Circuit breaker commands and status indications


The status of the circuit breakers is indicated on the front of the controller.
c ON, OFF, fault.
A built-in terminal block may be used to connect the following input/output signals:
c inputs:
v voluntary order to transfer to source R (e.g. for special tariffs, etc.)
v additional control contact (not part of the controller). Transfer to the
“Replacement” source takes place only if the contact is closed (e.g. used to test the
frequency of UR, etc.)
c outputs:
indication of operation in automatic or stop mode via changeover contacts.

Test
It is possible to test the operation of the BA controller by turning OFF (opening) the
P25M circuit breaker for the “Normal” source and thus simulating a failure of
voltage UN.
E30184

MERLIN GERIN
compact / masterpact

BA automatism
220/240 V 50/60 Hz
2 4 t1
1 8 s
N UN R UR N UN = 0 0.5 15
0.1 30

ON/I ON/I
0.5s 0.5s
OFF/O OFF/O

t2 15 30
s 8 60
fault fault 4 120
UN = I R
0.1 240
reset
stop auto
manu

N R

Front of the BA controller.

22 Schneider Electric
Functions Associated controllers
and characteristics BA controller
Operating sequences

Switch set to Auto (automatic operation and special-tariff mode) Switch set to the “N” position (forced
operation on the “Normal” source)

E87487
E87486

BA energised

R ON N ON

R opens

R OFF

end of delay

N closes

N ON

WAITING

Switch set to the “R” position (forced operation on the “Replacement” source) Switch set to the “Stop” position
E87488
E87489

BA energised

STOP

R ON and
N ON UN absent

N opens R opens

N OFF R OFF

WAITING

Key
WAITING The system exits this mode when the
UN : “Normal” source voltage operating mode is modified or when
UR : Replacement” source voltage
N : “Normal” source circuit breaker
an external event occurs (e.g. failure
R : “Replacement” source circuit breaker or return of UN).).

1 The number sends to the indicated step when the


condition is true.

Schneider Electric 23
Functions Associated controllers
and characteristics UA controller

The UA controller is used to create a Operating modes


source-changeover system integrating the A four-position switch may be used to select:
following automatic functions: b automatic operation
b transfer from one source to another b forced operation on the “Normal” source
b forced operation on the “Replacement” source
depending on the presence of voltage UN b stop (both “Normal” and “Replacement” sources off, then manual operation).
on the “Normal” source
b startup of an engine generator set Setting the time delays
b shedding and reconnection of non- Time delays are set on the front of the controller.
priority circuits t1. delay between detection that the “Normal” source has failed and the
transmission of the order to open the “Normal” source circuit breaker (adjustable
b transfer to the “Replacement” source if from 0.1 to 30 seconds).
one of the phases on the “Normal” source t2. delay between detection that the “Normal” source has returned and the
fails. transmission of the order to open the “Replacement” source circuit breaker
The UA controller can control Compact NS (adjustable from 0.1 to 240 seconds).
t3. delay following opening of QN with load shedding and before closing of QR
and Masterpact NT/NW devices. (adjustable from 0.5 to 30 seconds).
t4. delay following opening of QR with load reconnection and before closing of QN
(adjustable from 0.5 to 30 seconds).
053059

t5. delay for confirmation that UN is present before shutting down the engine
generator set (adjustable from 60 to 600 seconds).
t6. delay before startup of the engine generator set (120 or 180 seconds).

Commands and indications


Circuit-breaker status indications on the front of the controller:
ON, OFF, fault.
A built-in terminal block may be used to connect the following input/output signals:
b inputs:
v voluntary order to transfer to source R (e.g. for special tariffs, etc.)
v additional control contact (not part of the controller). Transfer to the
“Replacement” source takes place only if the contact is closed (e.g. used to test the
frequency of UR, etc.)
b outputs:
v control of an engine generator set (ON / OFF)
v shedding of non-priority circuits
v indication of operation in automatic mode via changeover contacts.

Distribution-system settings
Three switches are used to:
b select the type of “Normal” source, whether single-phase or three-phase (e.g.
240 V single-phase or 240 V three-phase)
b select whether to remain (or not) on the “Normal” source if the “Replacement”
source is not operational during operation on special tariffs
E30183

b select the maximum permissible startup time for the engine generator set during
MERLIN GERIN
compact / masterpact operation on special tariffs (120 or 180 seconds).
UA automatism
220/240 V 50/60 Hz
2 4 t1 Test
1 8 s
N UN R UR N UN = 0 15 A pushbutton on the front of the controller may be used to test transfer from the
0.5
0.1 30 “Normal” source to the “Replacement” source, then the return to the “Normal”
t4 5 10 5 10 t3 source. The test lasts approximately three minutes.
ON/I ON/I s 2 15 2 15 s
1 20 1 20
OFF/O OFF/O 0.5 30 0.5 30 COM communications option
t2 15 30 Using the internal bus protocol, this option may be used to remote the following
s 8 60
UN = I R information:
fault fault 4 120
0.1 240 b circuit-breaker status (ON, OFF, fault trip)
reset b presence of the “Normal” and “Replacement” voltages
stop auto
240 300 t5 b presence of an order for forced operation (e.g. special tariffs)
manu 160 360 s
test 120 480 b settings and configuration information
60 600
b status of non-priority circuits (loads shed or not)
N R b position of the switch (stop, auto, forced operation on the “Normal” source, forced
STOP generator operation on the “Replacement” source).

Front of the UA controller.

24 Schneider Electric
Functions Associated controllers
and characteristics UA controller
Operating sequences

Switch set to the “R” position Switch set to the “N” position
(forced operation on the “Replacement” source) (forced operation on the “Normal” source)
E72565

E72566
UA energised UA energised

R N

N ON R ON

R ON N ON
genset startup

genset shutdown

order issued order issued order issued


and UR absent and UR present

R opens
delay t6 (switch C)

R OFF
end of t6 t < t6 and UR present

t4 and load reconnection


genset shutdown

end of t4
UR failure

N closes

N opens
N ON

N OFF
WAITING
t3 and load shedding

Switch set to the “Stop” position


end of t3
E72580

R closes UA energised

R ON
STOP

R ON and R ON and
WAITING N ON UN absent UN present

genset shutdown

order issued

WAITING The system exits this mode when the N opens


operating mode is modified or when
an external event occurs (e.g. failure N OFF R opens
or return of UN).
R OFF

When the UA controller is not energised, the output load reconnection


for generator set startup is activated).
order issued

WAITING

Key
UN : “Normal” source voltage
UR : "Replacement” source voltage
N : “Normal” source circuit breaker
R : “Replacement” source circuit breaker

Schneider Electric 25
Functions Associated controllers
and characteristics UA controller
Operating sequences

Switch set to the “Auto” position (special-tariff mode)

E72581
UA energised
WAITING The system exits this mode when the
operating mode is modified or when
an external event occurs (e.g. failure AUTO MODE
or return of UN).
special tariff order

special-tariff mode 2
When the UA controller is not energised, the output
for generator set startup is activated.
genset startup

order issued

delay t6 (switch C)

t < t6 and UR present end of t6 and UR absent

N opens genset shutdown

N OFF choice
(switch B)
t3 and load shedding
B=0 B=1
end of t3
N opens
R closes
N OFF
R closes load shedding order

load shedding = 1
WAITING

WAITING
special tariff order
UR absent and UR absent and
UN present and B = 1 UN present and B = 0 special tariff order
1
1
R opens WAITING

R OFF special tariff order

N closes 1

N ON and special tariff order

load reconnection order

load reconnection

5
delay t5

end of t5

genset shutdown

Key
UN : “Normal” source voltage
UR : "Replacement” source voltage
N : “Normal” source circuit breaker
R : “Replacement” source circuit breaker
B : Penalties accepted (N ON), i.e. B = 1

1 The number sends to the indicated step when the


condition is true.

26 Schneider Electric
Functions Associated controllers
and characteristics UA controller
Operating sequences

Switch set to the “Auto” position (automatic operation and test mode).
E72582

UA energised

AUTO MODE

UN present UN absent and


TEST UR present

TEST mode (*) 4


LEDs flashing delay t2 1 N opens 3

end of t2 N OFF
genset startup
R opens t3 and load shedding

order issued and order issued and R OFF end of t3


UR absent UR present
delay t6 t4 and load reconnection R closes
(switch C)

end of t4 R ON
t < t6 and UR present

N closes WAITING

end of t6 N opens
N ON

genset shutdown N OFF

t3 and load shedding delay t5

end of t3 end of t5

UR failure and R closes


180 seconds elapsed genset shutdown
UN present
R ON
Main step 5
WAITING UN absent

UR absent or special delay t1


180 seconds TEST tariff
elapsed order
end of t1

genset startup

UR present

5 1 4 2 3 1

WAITING The system exits this mode when the


operating mode is modified or when
an external event occurs (e.g. failure
or return of UN).

When the UA controller is not energised, the output


for generator set startup is activated.

Key
UN : “Normal” source voltage
UR : "Replacement” source voltage
N : “Normal” source circuit breaker
R : “Replacement” source circuit breaker
B : Penalties accepted (N ON), i.e. B = 1
(*) The test lasts 180 seconds.

1 The number sends to the indicated step when the


condition is true.

Schneider Electric 27
Functions Operating sequences
and characteristics

IVE unit
E72583

I
ON
O
I
IN
O
>150 ms
I
OR
O
I
IR
O
>150 ms

I
QN
O
1s 500 ms
I
QR
O
IVE delay 500 ms IVE delay
250 ms 250 ms
Symbols
QN : “Normal” Compact C circuit breaker equipped
for remote operation (motor mechanism)
QR : “Replacement” Compact C circuit breaker
equipped for remote operation (motor mechanism)
ON : Circuit breaker QN opening order
OR : Circuit breaker QR opening order
IN : Circuit breaker QN closing order
IR : Circuit breaker QR closing order
L1 : Faulty “Normal” indication LED
L2 : Faulty “Replacement” indication LED

Key
O OFF (circuit open) Note:
I ON (circuit closed Following all trips (overload, short-circuit, earth-leakage fault, voluntary trip), a manual reset on
: either ON or OFF. the front of the motor mechanism is required.

28 Schneider Electric
Functions Operating sequences
and characteristics

BA controller
E72584

I
UN or KT
O
I
UR
O
I
KR
O

I
ON
O
I
OR
O
T1 500 ms IVE delay T2 500 ms IVE delay
0.1…30 s 250 ms 0.1…240 s 250 ms

Inputs
UN : “Normal” source voltage
UR : “Replacement” source voltage
KT : order for forced-operation on R
KR : additional check before transfer

Outputs
QN : “Normal” source circuit breaker
QR : “Replacement” source circuit breaker

UA controller
E72585

I
UN or KT
O
I
UR
O
I
KR
O
I
KG
O
SH I
O
QN I
O
QR I
O
genset IVE time
T1 startup time T3 IVE time T2 T4 delay T2
0.1...30 s IVE (≤ T6) 0.5...30 s delay 250 ms 10...240 s 0,5...30 s 250 ms 10...240 s

Inputs
UN : “Normal” source voltage
UR : “Replacement” source voltage
KT : order for forced-operation on R
KR : additional check before transfer

Outputs
KG : order to the genset
SH : load-shedding order
QN : “Normal” source circuit breaker
QR : “Replacement” source circuit breaker

Key Important
O OFF (circuit open) If UR is not ON when the transfer order is issued (KT or UN), the sequence is not carried out.
I ON (circuit closed If KR status is not ON when the transfer order is issued (KT or UN), the transfer sequence is
: either ON or OFF. carried out later when KR status becomes I.

Schneider Electric 29
Functions COM communications option
and characteristics

Communications option for Compact NS and Masterpact NT/NW


E87490

The COM communications option is compatible with all the source-changeover


systems for Compact NS100 to 1600 and Masterpact NT/NW circuit breakers and
switch-disconnectors.
It can be used to remote status information. It may not be used to operate the
circuit breakers (only possible locally on the front of the UA150 controller).
Depending on the trip units or control units used, the COM option may also be
used to analyse distribution-system parameters required for the operating and
maintenance assistance.

Circuit breaker communication


switch-disconnector circuit breaker
Compact NS100/1600 status indications
ON / OFF c c
Fault trip c
Connected / disconnected position c c
Masterpact NT/NW status indications
ON / OFF c c
Fault trip c
Connected / disconnected position c c
Operating and maintenance assistance
STR53UE trip unit for Compact NS400/630
Current readings
Phase and neutral rms currents c
Current on the most heavily loaded phase c
Alarm readings
Overload c
Tripping cause (overload, short-circuit, etc.) c
Positions of setting dials c
Micrologic control unit for Compact NS630b/1600 and Masterpact NT/NW
Current readings
Phase and neutral rms currents c
Current on the most heavily loaded phase c
Alarm readings
Overload c
Tripping cause (overload, short-circuit, etc.) c
Positions of setting dials c
Automatic source-changeover controller
Status indications
“Normal” source
ON / OFF c
Circuit breaker ON c
Fault trip (SDE) c
Voltage presence c
“Replacement” source
Circuit breaker ON c
Fault trip (SDE) c
Voltage presence c
Status of R voltage contact c
Controller
Automatic mode c
“Normal” mode c
“Replacement” mode c
Stop mode c
Testing c
“Replacement” engine generator set
Genset failure c
Genset OFF c
Genset ON c
Shedding of non-priority circuits c
Reconnection of non-priority circuits c
Settings
Time delay t1 for validation of UN absence c
Time delay t2 for validation of UN return c
Time delay t3 for wait between opening of N and closing of R c
Time delay t4 for wait between opening of R and closing of N c
Time delay t5 for wait between return of UN and order for genset shutdown c
Time delay t6 for wait before declaring genset failure c
Penalties accepted to avoid special tariff transfer c

30 Schneider Electric
Functions Accessories
and characteristics Connection and insulation
accessories

Downstream coupling accessory


E72586

This accessory simplifies connection to bars and cables with lugs.


It may be used to couple two circuit breakers (Compact NS100 to 630) or switch-
disconnectors (Interpact INS/INV100 to 630) of the same size.
Pitch between outgoing terminals:
b Interpact INS250 and INV100 to 250: 35 mm
b Interpact INS/INV320 to 630: 52.5 mm
b Compact NS100 to 250: 35 mm
b Compact NS400 to 630: 52.5 mm.

Connection and insulation accessories


The coupling accessory can be fitted with the same connection and insulation
accessories as the circuit breakers and switch-disconnectors.

Possible uses Downstream coupling


Possible Outgoing pitch (mm)
Manual source-changeover systems
INS250 (100 to 250 A) with rotary handle c 35
NS100/250 with rotary handle c 35
NS100/250 on base plate with toggle control c 35
INS400/630 (320 to 630 A) with rotary handle c 52.5
NS400/630 with rotary handle c 52.5
NS400/630 on base plate with toggle control c 52.5
Complete source-changeover assembly
INS250 (100 to 250 A) c 35
INS400/630 (320 to 630 A) c 52.5
Remote-operated source-changeover systems
NS100/250 c 35
NS400/630 c 52.5

Schneider Electric 31
32 Schneider Electric
Source- Dimensions

changeover
systems
Presentation 2
Functions and characteristics 7

Source-changeover systems
Interlocking depending on the type of device 34
Manual source-changeover systems
Interlocking of direct rotary handles 35
Interlocking of extended rotary handles 36
Interlocking of toggles 38
Complete source-changeover assembly 39
Downstream coupling accessory 40
Remote-operated source-changeover systems
Interlocking on a base plate 42
Interlocking using connecting rods 46
Interlocking using cables 48
IVE electrical-interlocking unit
BA and UA automatic controllers 53

Electrical diagrams 55
Order forms 91

Schneider Electric 33
Dimensions Source-changeover systems
Interlocking depending on the type
of device

Interpact INS40 to INS630


Type of "Replacement" source device
INS40 to INS100 to INS250 INV100 to INS320 to INV320 to
Type of "Normal" INS80 INS160 100/250 A INV250 INS630 INV630
Type of interlocking source device fixed fixed fixed fixed fixed fixed
complete assembly fixed c c
keylocks fixed c c c c c
rotary handle direct fixed c c c c c
extended fixed c c c c c c

Compact NS100 to NS630


Type of "Replacement" source device
Type of "Normal" NS100 to NS250 NS400 to NS630 mixed NS100 to NS630
Type of interlocking source device fixed withdr./plug-in fixed withdr./plug-in fixed withdr./plug-in
toggle fixed c c
withdrawable/plug-in c c
keylocks fixed c c c c c c
withdrawable/plug-in c c c c c c
rotary handle direct fixed c c
withdrawable/plug-in c c
extended fixed c c
withdrawable/plug-in c c
base plate fixed c c c
withdrawable/plug-in c c c

Compact NS630b to NS1600 and Masterpact NT / NW


Type of "Replacement" source device
Type of "Normal" NS630b to NS1600 NT06 to NT16 NW08 to NW63
Type of interlocking source device fixed withdrawable fixed drawout fixed drawout
toggle fixed
withdrawable/drawout
keylocks fixed c c c c c c
withdrawable/drawout c c c c c c
rotary handle direct fixed
withdrawable/drawout
extended fixed c
withdrawable/drawout
devices installed vertically 2 devices fixed c c c
using connecting rods withdrawable/drawout c c c
3 devices fixed
withdrawable/drawout
devices installed vertically 2 devices fixed c c c c c
using cables withdrawable/drawout c c c c c
3 devices fixed c c
withdrawable/drawout c c
devices installed horizontally 2 devices fixed c c c c c
using cables withdrawable/drawout c c c c c
3 devices fixed c c
withdrawable/drawout c c
Note: It is possible to combine Masterpact NT and NW devices in a source-changeover system.

34 Schneider Electric
Dimensions Manual source-changeover
systems
Interlocking of direct rotary handles

Compact NS100 to 630


Dimensions Front-panel cut-out
E21660

E21661
E68345
F

D
X X M
C

B
A L

G K
F
Z
H H

J J

X X

Y Y

Dimensions (mm)
Type A B C D F G H J K L M N
NS100/160/250N/H/L 325 90 87.5 175 156 133 9.25 9 295 75.5 150 75
NS400/630N/H/L 416 115 100 200 210 157 5 24.6 386 100 175 74.5

Interpact INS/INV250 100 to 250A / Interpact INS/INV320/400/500/630


Dimensions Front-panel cut-out
E68346

E68347

E68348

N
X X D
M X
C

B
A
G L
Z K
F
H H

Y Y

Dimensions (mm)
Type A B C D F G H K L M N
INS/INV250 100A/160A/250A 325 90 87.5 175 156 106 17.5 295 75.5 150 75
INS/INV320/400/500/630 416 115 100 200 210 130 22.5 386 100 175 74.5

Schneider Electric 35
Dimensions Manual source-changeover
systems
Interlocking of extended rotary
handles
Compact NS100 to 630
Dimensions Front-panel cut-out
E68349

E68345

E68350
F

Ø50

J
Q
D
Q
X X X
C
Ø4,2

B P P
A
F
G H H

J J

X X

Y Y

Dimensions (mm)
Type A B C D F G min G max H J P Q
NS100/160/250N/H/L 325 90 87.5 175 156 185 600 9.25 9 25.5 25.5
NS400/630N/H/L 416 115 100 200 210 204 600 5 24.6 30.8 30.8

Interpact INS40/63/80/100/125/160 / Interpact INS/INV250 100 to 250A / Interpact INS/INV320/400/500/630


Dimensions Front-panel cut-out
E68351

E68352

E68353

Ø50

X Q
X D
Q X

C
Ø4,2

B P P
G
Z A F
H H

Y Y

Dimensions (mm)
Type A B C D F G min G max H P Q
INS40/63/80 325 90 87.5 175 156 155 396 0 25.5 25.5
INS100/125/160 325 90 87.5 175 156 200 441 0 25.5 25.5
INS/INV250 100A/160A/250A 325 90 87.5 175 156 185 600 17.5 25.5 25.5
INS320/400/500/630 416 115 100 200 210 204 600 22.5 30.8 30.8

36 Schneider Electric
Dimensions Manual source-changeover
systems
Interlocking of extended rotary
handles
Compact NS630b to 1600
Dimensions
E72587

E72588
Y Y

X
X C

B
Z
G A

Front-panel cut-out
E72589

Ø51

J
Q
Q
X
Ø5

P P
F

H H
Y Y

Dimensions (mm)
Type A B C D F G min G max H J P Q
NS630b/800/1000/1200/1600 411 63.5 98 175 280 218 605 25 24 25.5 25.5

Schneider Electric 37
Dimensions Manual source-changeover
systems
Interlocking of toggles

Compact NS100 to 630


Dimensions 3 poles 4 poles
E21683

E21683

E21684
X X X

Y Y Y
L16 L L16 L
P5 L17 L18
Z

Front-panel cut-out 3 poles on left 4 poles on left

E21687
E21686

C3 C3
X X

C2 C2

Y Y Y Y
R2 R19 R2 R18 R19 R2

Dimensions (mm)
Type C2 C3 L L16 L17 L18 R2 R18 R19 P5
NS100/160/250N/H/L 54 108 52,5 140 245 280 54 89 140 83
NS400/630N/H/L 92,5 184 70 185 325 370 71,5 116,5 185 107

38 Schneider Electric
Dimensions Manual source-changeover
systems
Complete source-changeover
assembly
Assembly for INS250 100 to 250 A / Assembly for INS320/400/500/630
Dimensions
E68354

E68355
Y Y

X
E
X

A
F B
Z C

Front-panel cut-out
E68356/

I
J
X

Y Y
G K
H

Dimensions (mm)
Type A B C D E F G H I J K
INS250 60.4 130.4 296 68 136 131 61.8 279.3 42 84 156
INS320/630 82.5 175 395 102.5 205 155 87 383.7 64 128 210

Schneider Electric 39
Dimensions Manual source-changeover
systems
Downstream coupling accessory

Compact NS100 to NS630


Dimensions

E68358
Y Y
E68357

X X

L36 L37
L35

Dimensions Connection
E55456

E55458
Y Y
L28
L29 Y Y
L30 K4
L31 K1 K1 K1 K3 K1 K1 K1
X X

K8
G2 G29 G52

K9
G30
G3

ØT

G28 K16
K2 K2 K2

L32
L39
L33
L34
L40

Dimensions (mm)
Type G2 G3 G28 G29 G30 G52 K1 K2 K3 K4 K8 K9 K16 L28 L29
NS100/160/250 118 181.5 260.5 96 140 156 35 35 51 156 70 170 8 320 99,5
NS400/630 165.9 265.7 377 143.5 188.5 227.5 45 52.5 75 210 113.5 250.7 3.75 420 127.5

Dimensions (mm)
Type L30 L31 L32 L33 L34 L35 L36 L37 L39 L40 ØT
NS100/160/250 300 89.5 1 123 139.5 74.5 19.5 87.5 9.5 140 6
NS400/630 400 117.5 11.2 187.5 - 96.5 26 115 22.5 210 8

40 Schneider Electric
Dimensions Manual source-changeover
systems
Downstream coupling accessory

Interpact INS250 100 to 250 A / Interpact INS320/400/500/630


Dimensions
Y Y
E55454

E55455
X
X

L36 L37
L35

Dimensions Connection
E55456

E55458
Y Y
L28
L29 Y Y
L30 K4
L31 K1 K1 K1 K3 K1 K1 K1
X X

G2 G29 G52 K8

G30 K9
G3

ØT

G28 K16
K2 K2 K2

L32
L39
L33
L34
L40

Dimensions (mm)
Type G2 G3 G28 G29 G30 G52 K1 K2 K3 K4 K8 K9 K16 L28 L29
INS250-100/160/200/250 106 169.5 248 84 128 144 35 35 51 156 57.5 158 8 320 99.5
INS320/400/500/630 142.4 242.2 352 120 165 204 45 52.5 75 210 88.5 227.2 3.75 420 127.5

Dimensions (mm)
Type L30 L31 L32 L33 L34 L35 L36 L37 L39 L40 ØT
INS250-100/160/200/250 300 89.5 1 123 139.5 74.5 21.5 87.5 9.5 140 6
INS320/400/500/630 400 117.5 11.2 187.5 - 96.5 24 115 22.5 210 8

Schneider Electric 41
Dimensions Remote-operated
source-changeover systems
Interlocking on a base plate

Compact NS100 to 250


Dimensions, 3 or 4 poles Fixed device
∅T9
E68359

E68360
∅T10

H43 H22 H20


X H45 X
H23 H21
H42

H44

P54

H46
Y Y

L31 K25 Z P33


L32 P50 P32
(*) Short terminal shields are mandatory. P52

Withdrawable device
( )
E68361
Z *

P7
P8
Fixing distances P9
Vertical mounting Horizontal mounting
X
E68362

E68363

G51
K35 X

K25 K36 G50

Y
Y Y
K25
K35
K36

U
G50
G51

Dimensions (mm)
Type G50 G51 H20 H21 H22 H23 H42 H43 H44 H45 H46 K25 K35 K36
NS100/160/250N/H/L 137.5 285 62.5 97 45.5 73 60 120 145 300 30.5 157.5 210,5 300
NS400/630N/H/L 180 360 100 152 83 123 60 120 189 378 68.5 210 271.5 400

Dimensions (mm)
Type L31 L32 P7 P8 P9 P32 P33 P50 P52 P54 ØT9 ØT10 U
NS100/160/250N/H/L 110.5 354 27 45 75 178 143 23 85 21 9 6 ≤ 32
NS400/630N/H/L 150.5 466 27 45 100 250 215 23 99 21 9 6 ≤ 32

42 Schneider Electric
Dimensions Remote-operated
source-changeover systems
Interlocking on a base plate

Compact NS400 to 630


Dimensions, 3 or 4 poles ∅T9 Fixed device
E68364

E68365
∅T10 ∅T10

H45
H43 H43 H22 H20
X X

H42 O I I O I I H42 H44 H23 H21

P54

Y Y
H46 Z

L31 K25 P33


L32 P50 P32
(*) Short terminal shields are mandatory. P52

Withdrawable device
E68366

( )
*

P7
P8
P9

Fixing distances
Vertical mounting Horizontal mounting
E68367

X
E68368

Y G51

X
K35

G50
K25 K36

Y Y
Y K25
K35
K36

U
G50
G51
Note :
See the dimensions on page 42

Schneider Electric 43
Dimensions Remote-operated
source-changeover systems
Interlocking on a base plate

“Normal” and “Replacement” source devices: NS100 to NS250


Dimensions Front-panel cut-out
E68369

E68370
97 97
48,5 48,5

X X 76
29

Y Y
NS100 NS100
to 156 to
Z NS250 NS250

145

“Normal” and “Replacement” source devices: NS400 to NS630


Dimensions Front-panel cut-out
E68371

E68372

129 129
64,5 64,5

X X 126

41,5

NS400 Y Y NS400
to 210 to
NS630 NS630

217

Note for Compact NS:


For dimensions with the accessories (IP40 escutcheons and
Vigi escutcheon protection collars), see page ???

44 Schneider Electric
Dimensions Remote-operated
source-changeover systems
Interlocking on a base plate

NS400 to NS630 as the “Normal” device, NS100 to NS250 as the “Replacement” device
Dimensions Front-panel cut-out

E68374
E68373

129
64,5

X 126 X

41,5

Y Y
NS400 NS100
to 210 to
NS630 NS250
217
Z

Schneider Electric 45
Dimensions Remote-operated
source-changeover systems
Interlocking using connecting rods

Two Compact NS630b to NS1600 devices one above the other


Fixed devices Withdrawable devices
Y
E68375

E47724
Y

X X
163,5 123
173 173 12

110
F
25 135 30 5 100 161 30
100 F
900
900 maxi
maxi

184 X 184 X
114 114

182
25,5 160
123,5
F

Two Masterpact NT devices one above the other


Fixed devices Drawout devices
E47723

E47724

X X
123 123
173 173 12

110

5 135 30 5 100 161 30


100 F
900
900 F maxi
maxi

184 X 184 X
114 114

10 153 182
110

46 Schneider Electric
Dimensions Remote-operated
source-changeover systems
Interlocking using connecting rods

Two Masterpact NW devices one above the other


Fixed devices Drawout devices
Y
E46035

E46036
Y

X X
161 203
211 253 43,6
93
F
F
7 100 216,5 30
30 217,5 30
F 100

900 maxi 900 maxi

240 240

X X
117 117

8 242
136,5 242

Two Masterpact NT and NW devices one above the other


Fixed devices Drawout devices
E68376

E68377

X X
161 203
211 253 43,6
93
F
F
7 100 216,5 30
30 217,5 30
F 100

900 maxi 900 maxi

Y
Y

184
184 X X
114 114

10 153
110 12 182
F 110
F

Schneider Electric 47
Dimensions Remote-operated
source-changeover systems
Interlocking using cables

Two Compact NS630b to NS1600 devices side-by-side


Fixed devices Withdrawable devices
E638376

E47728
Y Y
Y Y

X X

R100 mini
R100 mini
2000 maxi
2000 maxi

Two Masterpact NT devices side-by-side


Fixed devices Drawout devices

Y Y
E47727

E47728

Y Y

X X

R100 mini
R100 mini 2000 maxi
2000 maxi

Two Masterpact NT and NW devices side-by-side


Fixed devices Drawout devices
E68379

E68380

Y
Y
Y
Y

X X
X X

R100 mini
R100 mini 2000 maxi
2000 maxi

48 Schneider Electric
Dimensions Remote-operated
source-changeover systems
Interlocking using cables

Two Masterpact NW devices side-by-side


Fixed devices Drawout devices

E46039
E47729

Y Y

Y Y

X X

R100 mini R100 mini


2000 maxi 2000 maxi

Three Masterpact NW devices side-by-side


Fixed devices
E47730

Y Y Y

R100 mini
1000 maxi 1000 maxi

Drawout devices

Y Y Y
E47731

R100 mini

1000 maxi 1000 maxi

Schneider Electric 49
Dimensions Remote-operated
source-changeover systems
Interlocking using cables

Two Compact NS630b to NS1600 devices one above the other


Fixed devices Withdrawable devices
Y

E47726
E68381

X X
163,5 123

12
135 30 110 161 30
F
R100 mini R100 mini
2000
maxi 2000
maxi

Y
Y

184 X 184 X
114 114

R100 mini R100 mini


25,5 160 182
123,5
F

Two Masterpact NT devices one above the other


Fixed devices Drawout devices
E47726

Y
E47725

X X
123 123

12

135 30 110 161 30


F
R100 mini R100 mini
2000
maxi 2000
maxi

184 X 184 X
114 114

R100 mini R100 mini


12 160 182
110

50 Schneider Electric
Dimensions Remote-operated
source-changeover systems
Interlocking using cables

Two Masterpact NW devices one above the other


Fixed devices Drawout devices

E46038
E46037

Y
Y

X X
161 203
43,6
93
F
F
216,5 30
217,5 30
R100 mini 2000 maxi R100 mini
2000 maxi

240 240

X X
117 117

R100 mini R100 mini


242 245
F

Two Masterpact NT and NW devices one above the other


Fixed devices Drawout devices
E68382

E46038

Y
Y

X X
161 203
43,6
93
F
F
216,5 30
217,5 30
R100 mini R100 mini
2000 maxi 2000 maxi

Y
Y

240

184 X X
114 117

R100 mini R100 mini


12 160 245
110

Schneider Electric 51
Dimensions Remote-operated
source-changeover systems
Interlocking using cables

Three Masterpact NW devices one above the other


Fixed devices Drawout devices

E46040
E47745

Y
Y

X X
161 203

F
F
216,5 30
217,5 30
R100 mini
1000 maxi R100 mini
1000 maxi

Y
Y

240 240

X X
117 117

43,6
R100
136,5 mini 93 R100
242 mini
F F 256,5
R100 mini
1000 maxi
1000 maxi

X X

R100 mini R100 mini

52 Schneider Electric
Dimensions Remote-operated
source-changeover systems
IVE electrical-interlocking unit
BA and UA automatic controllers
IVE electrical-interlocking unit
E47732

E47733
11 1 2 1 3 1 4 1 5 1 6

10
9
8
7

137
6
5

150
4
3
2
1

120 160
N

6 65
48 150 mini
83

ACP auxiliaries control plate and BA/UA controller Door cut-out for BA/UA controllers
95
E47734

E47735

E47736

E47737
255
200 140

22

138 140
150 90
172
187

Schneider Electric 53
54 Schneider Electric
Source- Electrical diagrams

changeover
systems
Presentation 2
Functions and characteristics 7
Dimensions 33

Remote-operated source-changeover systems


Compact NS100 to 1600 or Masterpact NT and NW 56
Compact NS100 to 630 57
Compact NS630b to 1600 60
Masterpact NT and NW 68
Source-changeover systems with automatic controllers
Compact NS100 to 1600 87
Masterpact NT and NW 90

Order forms 91

Schneider Electric 55
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS100/1600 or
Masterpact NT/NW devices
Electrical interlocking by the IVE unit
Recommended electrical control system

E43832
L1 L2

11 12 13 14 15 16

84 84
N
SDE"N" SDE"R"
(2) (2) IVE
81 81
R

1 2 3 4 5 6 7 8 9 10
ON OR FN FR

order for transfer to


"replacement" source (1)

order for transfer to


"normal" source (1)

CN 1 + CN 1 +

CN 2 – CN 2 –
(1) : the “normal” and “replacement” source transfer orders must be interlocked electrically
(2) : operating diagram: the SDE “fault-trip” signals are transmitted to the IVE unit. The SDE
auxiliary contacts are mounted in the circuit breakers.

Legends
ON "Normal” source opening order
OR "Replacement” source opening order
FN "Normal” source closing order
FR “Replacement” source closing order
L1 “Normal” source “fault-trip” signal
L2 “Replacement” source “fault-trip” signal Note:
N “Normal” source auxiliary wiring connector Diagram shown with circuits de-energised, circuit breakers
R “Replacement” source auxiliary wiring connector open and relays in normal position.

56 Schneider Electric
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS100/630 devices
Diagram no. 51201177
Source-changeover system without automatic-control system
Without auxiliaries for emergency off Local reset
E28449

E29491
NORMAL
11 12 13 14 15 16

N
IVE
R

1 2 3 4 5 6 7 8 9 10

22 24 82 84 B2 A2 A4 B4

QN
OF2
MT Voluntary remote reset
trip unit

E29492
SDE

11 12 13 14 15 16

N
IVE
21 81 A1 L1
R

1 2 3 4 5 6 7 8 9 10

RN RR

REPLACEMENT

22 24 82 84 B2 A2 A4 B4

Automatic reset
QR
OF2
(1)
MT N
trip unit
SDE IVE
(1)
R

1 2 3 4 5 6 7 8 9 10

21 81 A1 L1

(1) : Prefabricated wiring: cannot be modified

Legends States permitted by mechanical interlocking system


QN Normal” source Compact NS equipped with motor mechanism Normal Replacement
QR “Replacement” source Compact NS equipped with motor mechanism 0 0
SDE “fault-trip” indication contact 1 0
IVE electrical interlocking and terminal block unit 0 1
MT motor mechanism
Note:
OF2 breaker ON/OFF indication contact
Diagram shown with circuits de-energised, circuit breakers
RN reset order for breaker QN
open and relays in normal position.
RR reset order for breaker QR

Schneider Electric 57
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS100/630 devices
Diagram no. 51201178
Source-changeover system without automatic-control system
With emergency off by MN release and automatic reset
E43988

NORMAL
CN1 . CN1 +

(2) CN2 . CN2

D1
F1

D1 22 24 82 84 B2 A2 A4 B4

QN
OF2
MT

trip unit
SDE

MN

BP

D4 21 81 A1 L1

KA3
KA3
D4

REPLACEMENT

D1

D1 22 24 82 84 B2 A2 A4 B4

Automatic reset
QR
OF2
(1)
MT N
trip unit
SDE IVE
(1)
MN R

1 2 3 4 5 6 7 8 9 10

D4 21 81 A1 L1 KA3 KA3

D4

(1) : Prefabricated wiring supplied


(2) : Independent auxiliary source

Legends States permitted by mechanical interlocking system


QN Normal” source Compact NS equipped with motor mechanism Normal Replacement
QR "Replacement” source Compact NS equipped with motor mechanism 0 0
MN undervoltage release 1 0
OF2 breaker ON/OFF indication contact 0 1
SDE “fault-trip” indication contact
Note:
MT motor mechanism
After a fault trip, the breaker must be reset manually by
IVE electrical interlocking and terminal block unit
pressing its reset button.
BP emergency off button with latching
Diagram shown with circuits de-energised, circuit breakers
KA3 auxiliary relay
open and relays in normal position.
F1 auxiliary power supply circuit breaker

58 Schneider Electric
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS100/630 devices
Diagram no. 51201179
Source-changeover system without automatic-control system
With emergency off by MX release / automatic reset
E43987

NORMAL
CN3 . CN3 +
(2) CN4 . CN4

C1
F1

C1 22 24 82 84 B2 A2 A4 B4
opening
order

QN
OF2 KA1
MT KA1

trip unit
SDE

MX

CN5 . CN5 +
C2 21 81 A1 L1 (2) CN6 . CN6

C2 F2

opening
order

REPLACEMENT
KA2
KA2

C1

C1 22 24 82 84 B2 A2 A4 B4

Automatic reset
QR
OF2
(1)
MT N
trip unit
SDE IVE
(1)
MX R

1 2 3 4 5 6 7 8 9 10

KA1
C2 21 81 A1 L1
(3) KA2

C2

(1) : Prefabricated wiring supplied


(2) : This source can be:
■ the source present in the case of voltage monitoring
■ an independent source
In this case, the MX release must be protected.
(3) : The reset orders must be delayed by 0.3 seconds.

Legends
States permitted by mechanical interlocking system
QN “Normal” source Compact NS equipped with motor mechanism
Normal Replacement
QR “Replacement” source Compact NS equipped with motor mechanism
SDE “fault-trip” indication contact 0 0
OF2 breaker ON/OFF indication contact 1 0
MX shunt release 0 1
MT motor mechanism
Note:
IVE electrical interlocking and terminal block unit
After a fault trip, the breaker must be reset manually by
KA1 time-delayed auxiliary relays
pressing its reset button.
KA2 time-delayed auxiliary relays
Diagram shown with circuits de-energised, circuit breakers
F1 auxiliary power supply circuit breaker
open and relays in normal position.
F2 auxiliary power supply circuit breaker

Schneider Electric 59
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201180
Electrical interlocking with lockout after a fault
E59540

N R Auxiliary CN1 . CN1 +


Transfer to
power supply CN2 . CN2
replacement source
ON FR
F1

Transfer to normal OR FN

source

(1)

312
314
(1)
B4

A4

A2

82
84

12
14

312
314
B4

A4

A2

82
84
12
14
CE1

CE1
OF1
QN
SDE1
OF1
QR MCH
SDE1
MCH
MX XF

MX XF
A1

81

11

311

A1

81

11

311
(1)

(1)

(1) Not to be wired on fixed version

Legends
QN “Normal” source Compact NS630b to 1600 States permitted by mechanical interlocking system
QR “Replacement” source Compact NS NS630b to 1600 Normal Remplacement
MCH spring-charging motor
0 0
MX standard opening release
XF standard closing release 1 0
OF... breaker ON/OFF indication contact 0 1
SDE1 “fault-trip” indication contact
Note:
CE1 “connected-position” indication contact (carriage switch)
Diagram shown with circuit breakers in connected position,
F1 auxiliary power supply circuit breaker
open, charged, and ready to close.
ON “Normal” source opening order
Auxiliary power supply = supply voltage of auxiliary relays
OR “Replacement” source opening order
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
FN “Normal” source closing order (0.25 second delay)
MN...)
FR “Replacement” source closing order (0.25 second delay)

60 Schneider Electric
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201181
Electrical interlocking with lockout after a fault and emergency off by shunt release
Auxiliary CN1 . CN1 +
E59541

N R Transfer to power supply CN2 . CN2


remplacement source
ON FR
F1

OR FN
Transfer to
normal source

KA3 KA3

(1)
C12

312
314
(1)
B4

A4

A2

82
84

12
14

C12

312
314
B4

A4

A2

82
84
12
14
CE1

CE1 BP
OF1
QN
SDE1
OF1
QR MCH
SDE1
MCH
MX XF MX2

MX XF MX2
C11
A1

81

11

311

C11
A1

81

11

311
(1)

(1)

KA3

(1) Not to be wired on fixed version

Legends
QN “Normal” source Compact NS630b to 1600
QR “Replacement” source Compact NS NS630b to 1600
MCH spring-charging motor
MX standard opening release States permitted by mechanical interlocking system
XF standard closing release Normal Replacement
OF... breaker ON/OFF indication contact 0 0
SDE1 “fault-trip” indication contact
1 0
CE1 “connected-position” indication contact (carriage switch)
F1 auxiliary power supply circuit breaker 0 1
MX2 shunt release Note:
BP emergency off button with latching Diagram shown with circuit breakers in connected position,
KA3 auxiliary relay open, charged, and ready to close.
ON “Normal” source opening order Auxiliary power supply = supply voltage of auxiliary relays
OR “Replacement” source opening order (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
FN “Normal” source closing order (0.25 second delay) MN...)
FR “Replacement” source closing order (0.25 second delay)

Schneider Electric 61
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201182
Electrical interlocking with lockout after a fault and emergency off by undervoltage
E59537

Auxiliary CN1 . CN1 +


N R Transfer to
power supply CN2 . CN2
replacement source
ON FR
F1

OR FN
Transfer to
normal source

KA3 KA3

(1)

(1)
312
314
C2

D2
B2

A2

82
84

12
14

312
314
D2
B4

A4

A2

82
84
12
14
CE1

CE1 BP

QN OF1

SDE1
OF1
QR MCH
SDE1
MCH

MX XF MN

MX XF MN
D1
A1

81

11

311

D1
A1

81

11

311
(1)

(1)

KA3

(1) Not to be wired on fixed version

Legends
QN “Normal” source Compact NS630b to 1600
QR “Replacement” source Compact NS NS630b to 1600
MCH spring-charging motor
MX standard opening release
XF standard closing release
OF... breaker ON/OFF indication contact
SDE1 “fault-trip” indication contact
CE1 “connected-position” indication contact (carriage switch)
F1 auxiliary power supply circuit breaker
MN undervoltage release
BP emergency off button with latching
KA3 auxiliary relay
ON “Normal” source opening order
OR “Replacement” source opening order States permitted by mechanical interlocking system
FN “Normal” source closing order (0.25 second delay) Normal Replacement
FR "Replacement” source closing order (0.25 second delay)
0 0
1 0
Wiring colour codes
0 1
RD red
GN green Note:
BK black Diagram shown with circuit breakers in connected position,
VT violet open, charged, and ready to close.
YE yellow Auxiliary power supply = supply voltage of auxiliary relays
GY grey (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
WH white MN...)
BN brown

62 Schneider Electric
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201183
Electrical interlocking by IVE with lockout after a fault
E59538

CN1 . CN1 +
N R Auxiliary
power source CN2 . CN2

F1

(2)
N
BN

BK
WH

GN
RD
VT

IVE
(2)
R

BN

BK
WH

GN
RD
VT
(1)
312
314

1 2 3 4 5 6 7 8 9 10
B4

A4

A2

12
14

ON OR FN FR
(1)
Transfer to
remplacement source

312
314
B4

A4

A2

82
84
12
14
CE1

CE1
Transfer to normal
OF1 source
QN
MCH
SDE

QR OF1
MX XF MCH
SDE

MX XF
81
A1

11

311

(1)
GY

81
A1

11

311
YE

(1)
GY

YE

(1) Not to be wired on fixed version


(2) Prefabricated wiring supplied

Legends
QN “Normal” source Compact NS630b to 1600
QR “Replacement” source Compact NS NS630b to 1600
MCH spring-charging motor
MX standard opening release
XF standard closing release
OF... breaker ON/OFF indication contact
SDE1 “fault-trip” indication contact
CE1 “connected-position” indication contact (carriage switch)
F1 auxiliary power supply circuit breaker
IVE electrical interlocking and terminal block unit
ON “Normal” source opening order
OR “Replacement” source opening order
FN “Normal” source closing order (0.25 second delay) States permitted by mechanical interlocking system
FR “Replacement” source closing order (0.25 second delay) Normal Replacement
0 0
Wiring colour codes 1 0
RD red 0 1
GN green
BK black Note:
VT violet Diagram shown with circuit breakers in connected position,
YE yellow open, charged, and ready to close.
GY grey Auxiliary power supply = supply voltage of auxiliary relays
WH white (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
BN brown MN...)

Schneider Electric 63
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201184
Electrical interlocking by IVE with lockout after a fault and emergency off by shunt release
E59542

CN1 . CN1 +
N R Auxiliary
power supply CN2 . CN2

KA3
F1

(2)
N
BN

BK
WH

GN
RD
VT

IVE
(2)
R

BN

BK
WH

GN
RD
VT
(1)
C12

1 2 3 4 5 6 7 8 9 10
312
314
B4

A4

A2

12
14

ON OR FN FR
(1)
Transfer to
replacement source

C12

312
314
B4

A4

A2

82
84
12
14
CE1

CE1
Transfer to normal
OF1 source
QN
MCH
SDE
OF1
QR
MX XF MX2 MCH
SDE KA3

MX XF MX2
C11

81
A1

11

311

BP

(1)
C11

81
A1

11

311
GY

YE

(1)
KA3
GY

YE

(1) Not to be wired on fixed version


(2) Prefabricated wiring supplied

Légende
QN “Normal” source Compact NS630b to 1600
QR “Replacement” source Compact NS NS630b to 1600
MCH spring-charging motor
MX standard opening release
XF standard closing release
OF... breaker ON/OFF indication contact
SDE1 “fault-trip” indication contact
CE1 “connected-position” indication contact (carriage switch)
F1 auxiliary power supply circuit breaker
IVE electrical interlocking and terminal block unit
MX2 shunt release
BP emergency off button with latching
KA3 auxiliary relay
ON “Normal” source opening order
OR “Replacement” source opening order
States permitted by mechanical interlocking system
FN “Normal” source closing order (0.25 second delay)
FR “Replacement” source closing order (0.25 second delay) Normal Replacement
0 0
Wiring colour codes 1 0
0 1
RD red
GN green Note:
BK black Diagram shown with circuit breakers in connected position,
VT violet open, charged, and ready to close.
YE yellow Auxiliary power supply = supply voltage of auxiliary relays
GY grey (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
WH white MN...)
BN brown

64 Schneider Electric
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201185
Electrical interlocking by IVE with lockout after a fault and emergency off by undervoltage release
E59543

CN1 . CN1 +
N R Auxiliary
power supply CN2 . CN2

KA3
F1

(2)
N
BN

BK
WH

GN
RD
VT

IVE
(2)
R

BN

BK
WH

GN
RD
VT
(1)

1 2 3 4 5 6 7 8 9 10
312
314
D2
B4

A4

A2

12
14

ON OR FN FR
(1)
Transfer to
replacement source

312
314
D2
B4

A4

A2

82
84
12
14
CE1

CE1
Transfer to normal
OF1 source
QN
MCH
SDE
OF1
QR
MX XF MN MCH
SDE KA3

MX XF MN
81
A1

D1

11

311

BP

(1)
A1

D1

81

11

311
GY

YE

(1)
KA3
GY

YE

(1) Not to be wired on fixed version


(2) Prefabricated wiring supplied

Legends
QN “Normal” source Compact NS630b to 1600
QR “Replacement” source Compact NS NS630b to 1600
MCH spring-charging motor
MX standard opening release
XF standard closing release
OF... breaker ON/OFF indication contact
SDE1 “fault-trip” indication contact
CE1 “connected-position” indication contact (carriage switch)
F1 auxiliary power supply circuit breaker
IVE electrical interlocking and terminal block unit
MN undervoltage release
BP emergency off button with latching
KA3 auxiliary relay
ON “Normal” source opening order
OR “Replacement” source opening order
FN “Normal” source closing order (0.25 second delay)
States permitted by mechanical interlocking system
FR “Replacement” source closing order (0.25 second delay)
Normal Replacement
0 0
Wiring colour codes
1 0
RD red
0 1
GN green
BK black Note:
VT violet Diagram shown with circuit breakers in connected position,
YE yellow open, charged, and ready to close.
GY grey Auxiliary power supply = supply voltage of auxiliary relays
WH white (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
BN brown MN...)

Schneider Electric 65
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201186
Automatic-control system without IVE for permanent replacement source without lockout after a fault
E59544

N R Auxiliary CN1 . CN1 +


power supply CN2 . CN2

F1

KA2
S1
F3
OFF Auto N R

KM2
KM1
KA1 KM2 KM1 KA1 KA2

F2
(1)
312
314
B4

A4

A2

82
84
12
14

(1)

312
314
B4

A4

A2

82
84

12
14
CE1

KA1

CE1
OF1
QN
MCH SDE

OF1
QR
MX XF SDE
MCH

MX XF
A1

81

11

311

(1)
A1

81

11

311

(1) KM1 KM2

(1) Not to be wired on fixed version

Legends
QN Normal” source Compact NS630b to 1600
QR “Replacement” source Compact NS NS630b to 1600
MCH spring-charging motor
MX standard opening release
XF standard closing release States permitted by mechanical interlocking system
OF... breaker ON/OFF indication contact Normal Replacement
SDE1 “fault-trip” indication contact 0 0
CE1 “connected-position” indication contact (carriage switch)
1 0
F1 auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity) 0 1
S1 control switches Note:
KA1 auxiliary relays - UN presence detection Diagram shown with circuit breakers in connected position,
KA2 auxiliary relays - UR presence detection open, charged, and ready to close.
KM1 contactors with 0.25 second delay (for transfer to “Replacement” source) Auxiliary power supply = supply voltage of auxiliary relays
KM2 contactors with 0.25 second delay (for transfer to “Normal” source) (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...)

66 Schneider Electric
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201187
Automatic-control system for replacement source generator set without lockout after a fault
E59539

N1 REPLACEMENT SOURCE

genset
G automatic-control genset startup order CN1 . CN1 +
system Auxiliary
power supply CN2 . CN2

genset genset
monitoring fault F1
KA3

genset genset
voltage voltage
monitoring fault

S1

OFF Auto N R
KM2 KM1
KM2 KM1 KA1 KA2
KA2

F3 (1)

312
314
C2
B4

A2

82
84
12
14

KA1 KA3

F2 (1)
CE1

312
314
B4

A4

A2

82
84
12
14
OF1 CE1
QN
MCH
SDE1
OF1
QR
MX XF MCH
SDE1
KA1

MX XF
A1

81

11

311

(1)
A1

81

11

311
KM1 KM2

(1)

(1) Not to be wired on fixed version

Legends
QN “Normal” source Compact NS630b to 1600
QR “Replacement” source Compact NS NS630b to 1600
MCH spring-charging motor
MX standard opening release
XF standard closing release
OF... breaker ON/OFF indication contact
SDE1 “fault-trip” indication contact
CE1 “connected-position” indication contact (carriage switch)
F1 auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity)
S1 control switches
KA1 auxiliary relays - UN presence detection
KA2 auxiliary relays - UR presence detection
KA3 auxiliary relays - generator set startup if UN absent
KM1 contactors with 0.25 second delay (for transfer to “Replacement” source) States permitted by mechanical interlocking system
KM2 contactors with 0.25 second delay (for transfer to “Normal” source) Normal Replacement
0 0
Wiring colour codes 1 0
RD red 0 1
GN green
BK black Note:
VT violet Diagram shown with circuit breakers in connected position,
YE yellow open, charged, and ready to close.
GY grey Auxiliary power supply = supply voltage of auxiliary relays
WH white (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
BN brown MN...)

Schneider Electric 67
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NT or NW devices
Diagram no. 51201139
Electrical interlocking with lockout after a fault
E59449

Auxiliary CN1 . CN1 +


power supply CN2 . CN2
N R Transfer to
replacement source
F1
ON FR

Transfer to OR FN

normal source

(1)
252
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
(1)

252
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
CE1

CE1

OF1 OF2 OF3 OF4


QN
SDE1

QR OF1 OF2 OF3 OF4


PF
SDE1

MCH
PF

CH
MX XF MCH

CH
MX XF
B1

C1

A1

251

81

11

21

31

41

311

(1)
B1

C1

A1

251

81

11

21

31

41

311
(1)

(1) Not to be wired on fixed version

Legends
QN Normal” source Masterpact NT or NW
QR “Replacement” source Masterpact NT or NW
MCH spring-charging motor States permitted by mechanical interlocking system
MX standard opening voltage release Normal Replacement
XF standard closing voltage release
0 0
OF... breaker ON/OFF indication contact
SDE1 “fault-trip” indication contact 1 0
PF “ready-to-close” contact 0 1
CE1 “connected-position” indication contact (carriage switch) Note:
CH “springs charged” indication contact Diagram shown with circuit breakers in connected position,
F1 auxiliary power supply circuit breaker open, charged, and ready to close.
ON “Normal” source opening order Auxiliary power supply = supply voltage of auxiliary relays
OR “Replacement” source opening order (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
FN “Normal” source closing order (0.25 second delay) MN...)
FR “Replacement” source closing order (0.25 second delay)

68 Schneider Electric
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NT or NW devices
Diagram no. 51201140
Electrical interlocking with lockout after a fault and emergency off by shunt release
E59450

CN1 . CN1 +
Auxiliary
power supply CN2 . CN2
N R Transfer to
replacement source
F1
ON FR

Transfer to OR
KA3
normal source KA3

(1)

C12
252
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
(1)

C12
252
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
CE1

CE1 BP

OF1 OF2 OF3 OF4


QN
SDE1
OF1 OF2 OF3 OF4
QR
PF
SDE1

MCH
PF

CH
MX XF MX2 MCH

CH
MX XF MX2
B1

C1

A1

251

C11

81

11

21

31

41

311

(1)

C11
B1

C1

A1

251

81

11

21

31

41

311
(1)

KA3

(1) Not to be wired on fixed version

Legends
QN “Normal” source Masterpact NT or NW
QR “Replacement” source Masterpact NT or NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 “fault-trip” indication contact
PF “ready-to-close” contact
CE1 “connected-position” indication contact (carriage switch)
CH “springs charged” indication contact States permitted by mechanical interlocking system
F1 auxiliary power supply circuit breaker Normal Replacement
MX2 shunt release 0 0
BP emergency off button with latching 1 0
KA3 time delay for genset startup order to avoid starting the genset for transient UN disturbances 0 1
S1 control switches
ON “Normal” source opening order Note:
OR “Replacement” source opening order Diagram shown with circuit breakers in connected position,
FN “Normal” source closing order (0.25 second delay) open, charged, and ready to close.
FR “Replacement” source closing order (0.25 second delay) Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...)

Schneider Electric 69
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NT or NW devices
Diagram no. 51201141
Electrical interlocking with lockout after a fault and emergency off by undervoltage release
E59451

CN1 . CN1 +
Auxiliary
power supply CN2 . CN2
N R Transfer to
replacement source F1
ON FR

OR
Transfer to KA3 KA3
normal source

(1)
254
252

312
314
C2

D2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
(1)

254
252

312
314
C2

D2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
CE1

CE1
BP
OF1 OF2 OF3 OF4
QN
SDE1
OF1 OF2 OF3 OF4
QR
PF
SDE1

MCH
PF

CH
MX XF MN MCH

CH
MX XF MN
B1

C1

A1

251

D1

81

11

21

31

41

311

(1)
B1

C1

A1

251

D1

81

11

21

31

41

311
(1)

KA3

(1) Not to be wired on fixed version

Legends
QN “Normal” source Masterpact NT or NW
QR “Replacement” source Masterpact NT or NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
MN undervoltage release
OF... breaker ON/OFF indication contact States permitted by mechanical interlocking system
SDE1 “fault-trip” indication contact Normal Replacement
PF “ready-to-close” contact 0 0
CE1 “connected-position” indication contact (carriage switch) 1 0
CH “springs charged” indication contact
0 1
F1 auxiliary power supply circuit breaker
BP emergency off button with latching Note:
S1 control switches Diagram shown with circuit breakers in connected position,
KA3 auxiliary relay open, charged, and ready to close.
ON “Normal” source opening order Auxiliary power supply = supply voltage of auxiliary relays
OR “Replacement” source opening order (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
FN “Normal” source closing order (0.25 second delay) MN...)
FR “Replacement” source closing order (0.25 second delay)

70 Schneider Electric
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NT or NW devices
Diagram no. 51201142
Electrical interlocking by IVE with lockout after a fault
E59452

CN1 . CN1 +
Auxiliary
power supply CN2 . CN2
N R

F1

(3)
N
VT
WH

GN
RD
BK

IVE
(3)
R

VT
WH

GN
RD
BK
(2)
252
254

312
314
1 2 3 4 5 6 7 8 9 10
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44

ON OR FN FR
(2)
Transfer to
replacement source

252
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
CE1

CE1
Transfer to
OF1 OF2 OF3 OF4 normal source
QN
SDE1

QR OF1 OF2 OF3 OF4


PF
SDE1

MCH
PF

CH
MX XF MCH

CH
MX XF
B1

C1

A1

251

81

11

21

31

41

311

(1) (2)
B1

C1

A1

251

81

11

21

31

41

311

(1) (2)
GY

GY
BN

BN
YE

YE

(1) Not to be wired for the “without lockout after a fault” solution
(2) Not to be wired on fixed version
(3) Prefabricated wiring supplied

Legends
QN "Normal” source Masterpact NT or NW
QR “Replacement” source Masterpact NT or NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 “fault-trip” indication contact
PF “ready-to-close” contact
CE1 “connected-position” indication contact (carriage switch)
CH “springs charged” indication contact
IVE electrical interlocking and terminal block unit
F1 auxiliary power supply circuit breaker
ON “Normal” source opening order
OR “Replacement” source opening order States permitted by mechanical interlocking system
FN “Normal” source closing order (0.25 second delay) Normal Replacement
FR “Replacement” source closing order (0.25 second delay)
0 0
1 0
Wiring colour codes
0 1
RD red
GN green Note:
BK black Diagram shown with circuit breakers in connected position,
VT violet open, charged, and ready to close.
YE yellow Auxiliary power supply = supply voltage of auxiliary relays
GY grey (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
WH white MN...)
BN brown

Schneider Electric 71
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NT or NW devices
Diagram no. 51201143
Electrical interlocking by IVE with lockout after a fault and emergency off by shunt release
E59453

CN1 . CN1 +
Auxiliary
N R power supply CN2 . CN2

F1

KA3

(3)
N
WH

GN
RD
BK
VT

IVE
(3)
R

WH

GN
RD
BK
VT
(2)
C12
252
254

312
314

1 2 3 4 5 6 7 8 9 10
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44

ON OR FN FR
(2) Transfer to
replacement source

C12
252
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
CE1

CE1
Transfer to
OF1 OF2 OF3 OF4 normal source
QN
SDE1
OF1 OF2 OF3 OF4
QR
PF
SDE1 KA3

MCH
PF

CH
MX XF MX2 MCH

BP
CH
MX XF MX2
B1

C1

A1

251

C11

81

11

21

31

41

311

(1) (2)
C11
B1

C1

A1

251

81

11

21

31

41

311

(1) (2)
GY

GY
BN

BN
YE

YE

KA3

(1) Not to be wired for the “without lockout after a fault” solution
(2) Not to be wired on fixed version
(3) Prefabricated wiring supplied

Legends
QN “Normal” source Masterpact NT or NW
QR “Replacement” source Masterpact NT or NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 “fault-trip” indication contact
PF “ready-to-close” contact
CE1 “connected-position” indication contact (carriage switch)
CH “springs charged” indication contact
IVE electrical interlocking and terminal block unit
F1 auxiliary power supply circuit breaker
BP emergency off button with latching
KA3 auxiliary relay
ON “Normal” source opening order
OR “Replacement” source opening order States permitted by mechanical interlocking system
FN “Normal” source closing order (0.25 second delay) Normal Replacement
FR “Replacement” source closing order (0.25 second delay) 0 0
1 0
Wiring colour codes
0 1
RD red
GN green Note:
BK black Diagram shown with circuit breakers in connected position,
VT violet open, charged, and ready to close.
YE yellow Auxiliary power supply = supply voltage of auxiliary relays
GY grey (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
WH white MN...)
BN brown

72 Schneider Electric
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NT or NW devices
Diagram no. 51201144
Electrical interlocking by IVE with lockout after a fault and emergency off by undervoltage release
E59454

CN1 . CN1 +
Auxiliary
N R power supply CN2 . CN2

F1

KA3

(3)
N
WH

GN
RD
BK
VT

IVE
(3)
R

WH

GN
RD
BK
VT
(2)
254
252

312
314

1 2 3 4 5 6 7 8 9 10
C2

D2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44

ON OR FN FR
(2) Transfer to
replacement source

254
252

312
314
C2

D2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
CE1

CE1
Transfer to
OF1 OF2 OF3 OF4 normal source
QN
SDE1
OF1 OF2 OF3 OF4
QR
PF
SDE1 KA3

MCH
PF

CH
MX XF MN MCH

BP
CH
MX XF MN
B1

C1

A1

251

D1

81

11

21

31

41

311

(1) (2)
D1
B1

C1

A1

251

81

11

21

31

41

311

(1) (2)
GY

GY
BN

BN
YE

YE

KA3

(1) Not to be wired for the “without lockout after a fault” solution
(2) Not to be wired on fixed version
(3) Prefabricated wiring supplied

Legends
QN “Normal” source Masterpact NT or NW
QR “Replacement” source Masterpact NT or NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
MN undervoltage release
OF... breaker ON/OFF indication contact
SDE1 “fault-trip” indication contact
PF “ready-to-close” contact
CE1 “connected-position” indication contact (carriage switch)
CH “springs charged” indication contact
IVE electrical interlocking and terminal block unit
F1 auxiliary power supply circuit breaker
BP emergency off button with latching
S1 control switches
KA3 auxiliary relay
ON “Normal” source opening order
OR “Replacement” source opening order States permitted by mechanical interlocking system
FN “Normal” source closing order (0.25 second delay) Normal Replacement
FR “Replacement” source closing order (0.25 second delay) 0 0
1 0
Wiring colour codes 0 1
RD red
GN green Note:
BK black Diagram shown with circuit breakers in connected position,
VT violet open, charged, and ready to close.
YE yellow Auxiliary power supply = supply voltage of auxiliary relays
GY grey (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
WH white MN...)
BN brown

Schneider Electric 73
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NT or NW devices
Diagram no. 51156226
Automatic-control system without IVE for permanent replacement source without lockout after a fault
E59447

N R

CN1 . CN1 +
Auxiliary
power supply CN2 . CN2

F1

S1
KA2

OFF Auto N R
F3
KM2 KM1
KM2 KM1 KA1 KA2

KA1
(1)
F2
252
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44

(1)

252
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
CE1

CE1

OF1 OF2 OF3 OF4


QN
SDE1
OF1 OF2 OF3 OF4
QR
PF
SDE1

MCH KA1
PF

CH
MX XF MCH

CH
MX XF
B1

C1

A1

251

81

11

21

31

41

311

(1)
B1

C1

A1

251

81

11

21

31

41

311

(1)
KM1 KM2

(1) Not to be wired on fixed version

Legends
QN “Normal” source Masterpact NT or NW
QR “Replacement” source Masterpact NT or NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact States permitted by mechanical interlocking system
SDE1 “fault-trip” indication contact Normal Replacement
PF “ready-to-close” contact 0 0
CE1 “connected-position” indication contact (carriage switch)
1 0
CH “springs charged” indication contact
0 1
F1 auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity) Note:
S1 control switches Diagram shown with circuit breakers in connected position,
KA1 auxiliary relays - UN presence detection open, charged, and ready to close.
KA2 auxiliary relays - UR presence detection Auxiliary power supply = supply voltage of auxiliary relays
KA3 auxiliary relays - generator set startup if UN absent (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
KM1 contactors with 0.25 second delay (for transfer to “Replacement” source) MN...)
KM2 contactors with 0.25 second delay (for transfer to “Normal” source)

74 Schneider Electric
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NT or NW devices
Diagram no. 51156227
Automatic-control system for replacement source generator set without lockout after a fault
E59448

N1
REPLACEMENT SOURCE

genset CN1 . CN1 +


G automatic-control genset startup order Auxiliary
system
power supply CN2 . CN2

genset genset
monitoring fault F1
KA3

genset genset
voltage voltage
monitoring fault

S1

OFF Auto N R
KM2 KM1
KM2 KM1 KA1 KA2
KA2
(1)
F3
252
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
(1)
KA1 KA3

252
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
F2
CE1

CE1

OF1 OF2 OF3 OF4


QN
SDE1

QR OF1 OF2 OF3 OF4


PF
SDE1

MCH KA1
PF

CH
MX XF MCH

CH
MX XF
B1

C1

A1

251

81

11

21

31

41

311

(1)
B1

C1

A1

251

81

11

21

31

41

311
(1)
KM1 KM2

(1) Not to be wired on fixed version

Legends
QN “Normal” source Masterpact NT or NW
QR “Replacement” source Masterpact NT or NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact States permitted by mechanical interlocking system
SDE1 “fault-trip” indication contact Normal Replacement
PF “ready-to-close” contact 0 0
CE1 “connected-position” indication contact (carriage switch)
1 0
CH “springs charged” indication contact
F1 auxiliary power supply circuit breaker 0 1
F2/F3 circuit breaker (high breaking capacity) Note:
S1 control switches Diagram shown with circuit breakers in connected position,
KA1 auxiliary relays - UN presence detection open, charged, and ready to close.
KA2 auxiliary relays - UR presence detection Auxiliary power supply = supply voltage of auxiliary relays
KA3 auxiliary relays - generator set startup if UN absent (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
KM1 contactors with 0.25 second delay (for transfer to “Replacement” source) MN...)
KM2 contactors with 0.25 second delay (for transfer to “Normal” source)

Schneider Electric 75
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NT or NW devices
Diagram no. 51156904
Automatic-control system for permanent replacement source with lockout after a fault (with MN)
E47411

CN1 . CN1 +
N R Auxiliary
power supply CN2 . CN2

F1

KA1

S1

OFF R Auto N

KA1 KA1

KA3 KA2

11 12 13 14 15 16

(3)
N
WH

VT

BK
GN
RD

IVE
(3)
R
WH

VT

BK

GN
RD
(2)
254
252

312
314
D2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44

1 2 3 4 5 6 7 8 9 10
(2)
254
252

312
314
D2
B3

B2

A2

82
84

12
14
22
24
32
34
42
44
CE1

KA2 KA3 KA2 KA3

CE1

OF1 OF2 OF3 OF4


QN
SDE1
OF1 OF2 OF3 OF4
QR
PF
SDE1

MCH
PF

CH
MN XF MCH

CH
MN XF
B1

D1

A1

251

81

11

21

31

41

311

(1) (2)
B1

D1

A1

251

81

11

21

31

41

311
GY

BN

YE

(1) (2)
GY

BN

YE

(1) Not to be wired for the “without lockout after a fault” solution
(2) Not to be wired on fixed version
(3) Prefabricated wiring supplied

Legends
QN “Normal” source Masterpact NT or NW
QR “Replacement” source Masterpact NT or NW
MCH spring-charging motor
XF standard closing voltage release
MN undervoltage release
OF... breaker ON/OFF indication contact
SDE1 “fault-trip” indication contact
PF “ready-to-close” contact
CE1 “connected-position” indication contact (carriage switch)
CH “springs charged” indication contact
IVE electrical interlocking and terminal block unit
F1 auxiliary power supply circuit breaker
F2 circuit breaker (high breaking capacity)
S1 control switches
KA1 auxiliary relays States permitted by mechanical interlocking system
KA2 auxiliary relays Normal Replacement
KA3 auxiliary relays
0 0
1 0
Wiring colour codes
0 1
RD red
GN green Note:
BK black Diagram shown with circuit breakers in connected position,
VT violet open, charged, and ready to close.
YE yellow Auxiliary power supply = supply voltage of auxiliary relays
GY grey (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
WH white MN...)
BN brown

76 Schneider Electric
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NT or NW devices
Diagram no. 51156905
Automatic-control system for replacement source generator set with lockout after a fault (with MN)
E47412

N
CN1 . CN1 +
Auxiliary
KA1 power supply CN2 . CN2

REPLACEMENT SOURCE
F1

genset
G automatic-control genset startup order
system
S1

genset genset OFF R Auto N


monitoring fault KA2

genset genset KA1 KA1


voltage voltage
monitoring fault

KA3 KA2

11 12 13 14 15 16

(3)
N
WH

GN
RD
BK
VT

IVE
(3)
R
WH

GN
RD
BK
VT

(2)
254
252

312
314
D2
B3

B2

A2

82
84

12
14
22
24
32
34
42
44

1 2 3 4 5 6 7 8 9 10
(2)
254
252

312
314
D2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
CE1
KA2 KA3 KA2 KA3

CE1

OF1 OF2 OF3 OF4


QN
SDE1
OF1 OF2 OF3 OF4
QR
PF
SDE1

MCH
PF

CH
MN XF MCH

CH
MN XF
B1

D1

A1

251

81

11

21

31

41

311

(1) (2)
B1

D1

A1

251

81

11

21

31

41

311
GY

BN

YE

(1) (2)
GY

BN

YE

(1) Not to be wired for the “without lockout after a fault” solution
(2) Not to be wired on fixed version
(3) Prefabricated wiring supplied

Legends
QN “Normal” source Masterpact NT or NW
QR “Replacement” source Masterpact NT or NW
MCH spring-charging motor
XF standard closing voltage release
MN undervoltage release
OF... breaker ON/OFF indication contact
SDE1 “fault-trip” indication contact
PF “ready-to-close” contact
CE1 “connected-position” indication contact (carriage switch)
CH “springs charged” indication contact
F1 auxiliary power supply circuit breaker
F2 circuit breaker (high breaking capacity)
S1 control switches
KA1 auxiliary relay
KA2 time delay for genset startup order to avoid starting the genset for transient UN disturbances
KA3 auxiliary relay States permitted by mechanical interlocking system
Normal Replacement
Wiring colour codes 0 0
RD red 1 0
GN green 0 1
BK black
VT violet Note:
YE yellow Diagram shown with circuit breakers in connected position,
GY grey open, charged, and ready to close.
WH white Auxiliary power supply = supply voltage of auxiliary relays
BN brown (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...)

Schneider Electric 77
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156906
2 Normal sources and 1 Replacement source: electrical interlocking without lockout after a fault
E47413

N1 N2 R CN1 . CN1 +
Auxiliary
power supply CN2 . CN2

F1

t1

t2
252
254

312
314
322

324
C2
B3
B2

A2

12
14
22
24
32
34
42
44

252
254

312
314
322
324
C2
B3
B2

A2

12
14
22
24
32
34
42
44
CE1 CE2

252
254

312
314
322
324
C2
B3
B2

A2

12
14
22
24
32
34
42
44
CE1 CE2

OF1 OF2 OF3 OF4


QN1
CE1 CE2

OF1 OF2 OF3 OF4


QN2
PF

MCH OF1 OF2 OF3 OF4


QR
PF

CH
MX XF MCH
PF

CH
MX XF
MCH
C1

A1

251

21
B1

321
11

31

41

CH
311

MX XF
C1

A1

251

21
B1

321
11

31

41

311

C1

A1

251

21
B1

321
11

31

41

311

Legends States permitted by mechanical interlocking system


QN... “Normal” source Masterpact NW Normal 1 Normal 2 Replacement
QR “Replacement” source Masterpact NW 0 0 0
MCH spring-charging motor 1 1 0
MX standard opening voltage release
0 0 1
XF standard closing voltage release
OF... breaker ON/OFF indication contact 1 0 0
PF “ready-to-close” contact 0 1 0
CE “connected-position” indication contact (carriage switch)
CH “springs charged” indication contact Note:
F1 auxiliary power supply circuit breaker Diagram shown with circuit breakers in connected position,
t1 order for transfer from “R” to “N1 + N2” open, charged, and ready to close.
(QN1 and QN2 closing time delay = 0.25 sec. minimum) Auxiliary power supply = supply voltage of auxiliary relays
t2 order for transfer from “N1 + N2”to “R” (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
(QR closing time delay = 0.25 sec. minimum) MN...)

78 Schneider Electric
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156907
2 Normal sources and 1 Replacement source: electrical interlocking with lockout after a fault
E47414

N1 N2 R CN1 . CN1 +
Auxiliary
power supply CN2 . CN2

F1

t1

t2
KA1

KA1
KA1
KA2
252
254

312
314
C2
B3
B2

A2

82
84

12
14
22
24
32
34
42
44

KA2
KA2

252
254

312
314
C2
B3
B2

A2

82
84

12
14
22
24
32
34
42
44
CE1

252
254

312
314
C2
B3
B2

A2

82
84

12
14
22
24
32
34
42
44
CE1

OF1 OF2 OF3 OF4


QN1
CE1
SDE1
OF1 OF2 OF3 OF4
QN2
PF
SDE1

QR MCH OF1 OF2 OF3 OF4


PF
SDE1
CH
MX XF MCH
PF

CH
MX XF MCH
251

11
C1

81

21
B1

A1

311
31

41

CH
MX XF
251
C1

81

21
B1

A1

311
31

41
11

251
C1

81

21
B1

A1

311
31

41
11

Legends
QN... “Normal” source Masterpact NW
QR “Replacement” source Masterpact NW
MCH spring-charging motor States permitted by mechanical interlocking system
MX standard opening voltage release Normal 1 Normal 2 Replacement
XF standard closing voltage release 0 0 0
OF... breaker ON/OFF indication contact 1 1 0
SDE1 “fault-trip” indication contact 0 0 1
PF “ready-to-close” contact
1 0 0
CE1 “connected-position” indication contact (carriage switch)
CH “springs charged” indication contact 0 1 0
F1 auxiliary power supply circuit breaker
S1 control switches Note:
S2 source selection switches Diagram shown with circuit breakers in connected position,
t1 order for transfer from “R” to “N1 + N2” open, charged, and ready to close.
(QN1 and QN2 closing time delay = 0.25 sec. minimum) Auxiliary power supply = supply voltage of auxiliary relays
t2 order for transfer from “N1 + N2”to “R” (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
(QR closing time delay = 0.25 sec. minimumm) MN...)

Schneider Electric 79
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156908
2 Normal sources and 1 Replacement source: automatic-control system for generator set without
lockout after a fault (with MN)
E47415

N1 N2
CN1 . CN1 +
REPLACEMENT SOURCE Auxiliary
power supply CN2 . CN2

genset
G automatic-control genset startup order
system
F1

genset genset
monitoring fault S1

OFF R Auto N
genset genset
voltage voltage
monitoring fault

F2
S2

F2
KA2
KA2 KA4 KA2 KA2 KA2 N1 N2
F2
KA1 KA1 KA4 KA4 N1+N2
KA3 KA3

F2 KA1

KA5 KA6

KA6

KA5
254
252

312
314
322
324
D2
B3
B2

A2

12
14
22
24
32
34
42
44

254
252

312
314
322
324
D2
B3
B2

A2

12
14
22
24
32
34
42
44

CE1 CE2

254
252

312
314
322
324
D2
B3
B2

A2

12
14
22
24
32
34
42
44
CE1 CE2

OF1 OF2 OF3 OF4


QN1
CE1 CE2

OF1 OF2 OF3 OF4


QN2
PF

QR MCH OF1 OF2 OF3 OF4


PF

CH MN XF MCH
PF
CH MN XF MCH
321
D1

311
21
B1

A1

251

31

41
11

CH MN XF
251

321
D1

311
21
B1

A1

31

41
11

D1

311
21
B1

A1

321
251

31

41
11

Legends
QN... “Normal” source Masterpact NW
QR “Replacement” source Masterpact NW
MCH spring-charging motor
XF standard closing voltage release
MN undervoltage release States permitted by mechanical interlocking system
OF... breaker ON/OFF indication contact Normal 1 Normal 2 Replacement
PF “ready-to-close” contact 0 0 0
CE... “connected-position” indication contact (carriage switch) 1 1 0
CH “springs charged” indication contact 0 0 1
F1 auxiliary power supply circuit breaker 1 0 0
F2/F3 circuit breaker (high breaking capacity)
0 1 0
S1 control switches
S2 source selection switches
KA1 auxiliary relay Note:
KA2 auxiliary relays with 10 to 180 sec. time delay Diagram shown with circuit breakers in connected position,
KA3 auxiliary relays with 0.1 to 30 sec. time delay open, charge.
KA4 auxiliary relay Auxiliary power supply = supply voltage of auxiliary relays
KA5 auxiliary relays with 0.25 sec. time delay (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
KA6 auxiliary relays with 0.25 sec. time delay MN...)

80 Schneider Electric
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156909
2 Normal sources and 1 Replacement source: automatic-control system for generator set with lockout
after a fault (with MN))
E47416

N1 N2
CN1 . CN1 +
REPLACEMENT SOURCE Auxiliary
power supply CN2 . CN2
genset
G automatic-control genset startup order
system
F1

genset genset
monitoring fault S1

genset genset OFF R Auto N


voltage voltage
monitoring fault

F2
S2

F2
KA2 KA2
KA2 N1 N2
KA4 KA2 KA2
F2
KA1 KA1 N1+N2
KA3 KA4 KA4 KA3

KA1
F2

KA5 KA7
KA6

KA6

KA8

KA7 KA8
KA7 KA8 KA5
254
252

312
314
322
324
332
334
D2
B3
B2

A2

82
84
12
14
22
24
32
34
42
44

254
252

312
314
322
324
332
334
D2
B3
B2

A2

82
84
12
14
22
24
32
34
42
44

CE1 CE2 CE3

254
252

312
314
322
324
332
334
D2
B3
B2

A2

82
84
12
14
22
24
32
34
42
44
CE1 CE2 CE3

OF1 OF2 OF3 OF4


QN1
CE1 CE2 CE3
SDE1
OF1 OF2 OF3 OF4
QN2
PF
SDE1
QR MCH OF1 OF2 OF3 OF4
PF
SDE1
CH MN XF MCH
PF

CH MN XF MCH
B1

D1

A1

251

81

11

21

31

41

311

321

331

CH MN XF
B1

D1

A1

251

81

11

21

31

41

311

321

331

B1

D1

A1

251

81

11

21

31

41

311

321

331

Legends
QN... “Normal” source Masterpact NW
QR “Replacement” source Masterpact NW
MCH spring-charging motor
XF standard closing voltage release
MN undervoltage release
OF... breaker ON/OFF indication contact
SDE1 “fault-trip” indication contact
PF “ready-to-close” contact States permitted by mechanical interlocking system
CE... “connected-position” indication contact (carriage switch) Normal 1 Normal 2 Replacement
CH “springs charged” indication contact 0 0 0
F1 auxiliary power supply circuit breaker 1 1 0
F2/F3 circuit breaker (high breaking capacity) 0 0 1
S1 control switches 1 0 0
S2 source selection switches 0 1 0
KA1 auxiliary relay
KA2 auxiliary relays with 10 to 180 sec. time delay
KA3 auxiliary relays with 0.1 to 30 sec. time delay Note:
KA4 auxiliary relay Diagram shown with circuit breakers in connected position,
KA5 auxiliary relays with 0.25 sec. time delay open, charge.
KA6 auxiliary relays with 0.25 sec. time delay Auxiliary power supply = supply voltage of auxiliary relays
KA7 auxiliary relay (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
KA8 auxiliary relay MN...)

Schneider Electric 81
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156910
3 sources with only 1 device closed: electrical interlocking without lockout after a fault
E47076

SOURCE 1
SOURCE 2
SOURCE 3 Auxiliary CN1 . CN1 +
power supply CN2 . CN2

F1

t1

t2

t3
252
254

312
314
322
324
C2
B3
B2

A2

12
14
22
24
32
34
42
44

252
254

312
314
322
324
C2
B3
B2

A2

12
14
22
24
32
34
42
44
CE1 CE2

252
254

312
314
322
324
C2
B3
B2

A2

12
14
22
24
32
34
42
44
CE1 CE2

OF1 OF2 OF3 OF4


QS1
CE1 CE2

QS2 OF1 OF2 OF3 OF4


PF

QS3 MCH OF1 OF2 OF3 OF4


PF

CH
MX XF MCH
PF

CH
MX XF MCH
251

321
C1

21
B1

A1

311
31

41
11

CH
MX XF
251

321
C1
B1

A1

21

311
31

41
11

251

321
C1
B1

A1

311
31

41
11

21

Legends
QS... “Source” Masterpact NW
MCH spring-charging motor
States permitted by mechanical interlocking system
MX standard opening voltage release
Source 1 Source 2 Source 3
XF standard closing voltage release
OF... breaker ON/OFF indication contact 0 0 0
PF “ready-to-close” contact 1 0 0
CE... “connected-position” indication contact (carriage switch) 0 1 0
CH “springs charged” indication contact 0 0 1
F1 auxiliary power supply circuit breaker
t1 order for transfer to “Source 1” Note:
(QS1 closing time delay = 0.25 sec. minimum) Diagram shown with circuit breakers in connected position,
t2 order for transfer to “Source 2” open, charge.
(QS2 closing time delay = 0.25 sec. minimum) Auxiliary power supply = supply voltage of auxiliary relays
t3 order for transfer to “Source 3” (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
(QS3 closing time delay = 0.25 sec. minimum) MN...)

82 Schneider Electric
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156911
3 sources with only 1 device closed: electrical interlocking with lockout after a fault
E47077

SOURCE 1
SOURCE 2
SOURCE 3 Auxiliary CN1 . CN1 +
power supply CN2 . CN2

F1

t1

t2

t3

KA1

KA2

KA1 KA1
252
254

312
314
322
324
C2
B3
B2

A2

82
84

12
14
22
24
32
34
42
44

KA3
KA2 KA2

252
254

312
314
322
324
C2
B3
B2

A2

82
84

12
14
22
24
32
34
42
44
CE1 CE2
KA3 KA3

252
254

312
314
322
324
C2
B3
B2

A2

82
84

12
14
22
24
32
34
42
44
CE1 CE2

OF1 OF2 OF3 OF4


QS1
CE1 CE2
SDE1

QS2 OF1 OF2 OF3 OF4


PF
SDE1

QS3 MCH OF1 OF2 OF3 OF4


PF
SDE1
CH MX XF MCH
PF

CH MX XF MCH
251

321
C1

81

21
B1

A1

311
31

41
11

CH MX XF
251

321
C1

81

21
B1

A1

311
31

41
11

251
C1

321
81

21
B1

A1

311
31

41
11

Legends
QS... “Source” Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 “fault-trip” indication contact States permitted by mechanical interlocking system
PF “ready-to-close” contact Source 1 Source 2 Source 3
CE... “connected-position” indication contact (carriage switch)
0 0 0
CH “springs charged” indication contact
F1 auxiliary power supply circuit breaker 1 0 0
t1 order for transfer to “Source 1” 0 1 0
(QS1 closing time delay = 0.25 sec. minimum) 0 0 1
t2 order for transfer to “Source 2”
(QS2 closing time delay = 0.25 sec. minimum) Note:
t3 order for transfer to “Source 3” Diagram shown with circuit breakers in connected position,
(QS3 closing time delay = 0.25 sec. minimum) open, charged, and ready to close.
KA1 auxiliary relays Auxiliary power supply = supply voltage of auxiliary relays
KA2 auxiliary relays (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
KA3 auxiliary relays MN...)

Schneider Electric 83
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156912
2 sources and 1 coupling: electrical interlocking without lockout after a fault
E47078

SOURCE 1 SOURCE 2
Auxiliary CN1 . CN1 +
power supply CN2 . CN2

F1
COUPLING

t1

t2

t3

t4
252
254

312
314
322
324
C2
B3
B2

A2

12
14
22
24
32
34
42
44

252
254

312
314
322
324
C2
B3
B2

A2

12
14
22
24
32
34
42
44
CE1 CE2

252
254

312
314
322
324
C2
B3
B2

A2

12
14
22
24
32
34
42
44
CE1 CE2

OF1 OF2 OF3 OF4


QS1
CE1 CE2

OF1 OF2 OF3 OF4


QC
PF

QS2 MCH OF1 OF2 OF3 OF4


PF

CH MX XF MCH
PF

CH MX XF MCH
251
C1

321
21
B1

A1

311
31

41
11

CH MX XF
251
C1

321
21
B1

A1

311
31

41
11

251
C1

321
21
B1

A1

311
31

41
11

Legends
QS... “Source” Masterpact NW
QC “Coupling” Masterpact NW States permitted by mechanical interlocking system
MCH spring-charging motor Source 1 Source 2 Coupling
MX standard opening voltage release 0 0 0
XF standard closing voltage release 1 1 0
OF... breaker ON/OFF indication contact 1 0 1
PF “ready-to-close” contact 0 1 1
CE... “connected-position” indication contact (carriage switch) 1 0 0
CH “springs charged” indication contact
0 1 0
F1 auxiliary power supply circuit breaker
t1 coupling order for “Source 1 failure” 0 0 1
(QC closing time delay = 0.25 sec. minimum)
t2 coupling order for “Source 2 failure” Note:
(QC closing time delay = 0.25 sec. minimum) Diagram shown with circuit breakers in connected position,
t3 coupling order for “Source 1 restored” open, charge.
(QS1 closing time delay = 0.25 sec. minimum) Auxiliary power supply = supply voltage of auxiliary relays
t4 coupling order for “Source 2 restored “ (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
(QS2 closing time delay = 0.25 sec. minimum) MN...)

84 Schneider Electric
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156913
2 sources and 1 coupling: electrical interlocking with lockout after a fault
E47079

SOURCE 1 SOURCE 2
Auxiliary CN1 . CN1 +
power supply CN2 . CN2

F1
COUPLING

t1

t2

t3

t4
KA1

KA2
KA1 KA1
252
254

312
314
322
324
C2
B3
B2

A2

82
84
12
14
22
24
32
34
42
44

KA3

KA2 KA2

252
254

312
314
322
324
C2
B3
B2

A2

82
84
12
14
22
24
32
34
42
44
CE1 CE2
KA3 KA3

252
254

312
314
322
324
C2
B3
B2

A2

82
84
12
14
22
24
32
34
42
44
CE1 CE2

OF1 OF2 OF3 OF4


QS1
CE1 CE2
SDE1

QC OF1 OF2 OF3 OF4


PF
SDE1

QS2 MCH OF1 OF2 OF3 OF4


PF
SDE1
CH
MX XF MCH
PF

CH MX XF MCH
251

321
C1

81

21
B1

A1

311
31

41
11

CH MX XF
251

321
C1

81

21
B1

A1

311
31

41
11

251

321
C1

81

21
B1

A1

311
31

41
11

Legends
QS... “Source” Masterpact NW
QC “Coupling” Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
States permitted by mechanical interlocking system
OF... breaker ON/OFF indication contact
SDE1 “fault-trip” indication contact Source 1 Source 2 Coupling
PF “ready-to-close” contact 0 0 0
CE... “connected-position” indication contact (carriage switch) 1 1 0
CH “springs charged” indication contact 1 0 1
F1 auxiliary power supply circuit breaker 0 1 1
t1 coupling order for “Source 1 failure” 1 0 0
(QC closing time delay = 0.25 sec. minimum) 0 1 0
t2 coupling order for “Source 2 failure” 0 0 1
(QC closing time delay = 0.25 sec. minimum)
t3 coupling order for “Source 1 restored”
(QS1 closing time delay = 0.25 sec. minimum) Note:
t4 coupling order for “Source 2 restored “ Diagram shown with circuit breakers in connected position,
(QS2 closing time delay = 0.25 sec. minimum) open, charged, and ready to close.
KA1 auxiliary relays Auxiliary power supply = supply voltage of auxiliary relays
KA2 auxiliary relays (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
KA3 auxiliary relays MN...)

Schneider Electric 85
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156914
2 sources and 1 coupling: automatic-control system with lockout after a fault
E47080

SOURCE 1 SOURCE 2

S1

KA1 KA1 KA1 KA1

forced
KA1

OFF
auto
KA2 KA1

F3 KA2

KA3

KA3 S2
KA4
KA4

S1 + S2
S1 + C

S2 + C
F2

KA5 KA6
KA7
KA5
KA5

KA6
KA6
COUPLING

KA7 KA7

F2
252
254

312
314
322
324
C2
B3
B2

A2

82
84
12
14
22
24
32
34
42
44

F2
252
254

312
314
322
324
C2
B3
B2

A2

82
84
12
14
22
24
32
34
42
44
CE1 CE2

252
254

312
314
322
324
C2
B3
B2

A2

82
84
12
14
22
24
32
34
42
44
CE1 CE2

OF1 OF2 OF3 OF4


QS1 CE1 CE2
SDE1
OF1 OF2 OF3 OF4
QC
PF
SDE1

QS2 MCH OF1 OF2 OF3 OF4


PF
SDE1
CH MX XF MCH
PF

CH MX XF MCH
B1

C1

A1

251

81

11

21

31

41

311

321

CH MX XF
B1

C1

A1

251

81

11

21

31

41

311

321

B1

C1

A1

251

81

11

21

31

41

311

321

Legends
QS... “Source” Masterpact NW
QC “Coupling” Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
States permitted by mechanical interlocking system
OF... breaker ON/OFF indication contact
Source 1 Source 2 Coupling
SDE1 “fault trip” indication contact
PF “ready-to-close” contact 0 0 0
CE... “connected-position” indication contact (carriage switch) 1 1 0
CH “springs charged” indication contact 1 0 1
F1 auxiliary power supply circuit breaker 0 1 1
F2/F3 circuit breaker (high breaking capacity) 1 0 0
S1 control switches 0 1 0
S2 source selection switches 0 0 1
KA1 auxiliary relays with 10 to 180 sec. time delay
KA2 auxiliary relays with 0.1 to 30 sec. time delay Note:
KA3 auxiliary relays with 10 to 180 sec. time delay Diagram shown with circuit breakers in connected position,
KA4 auxiliary relays with 0.1 to 30 sec. time delay open, charge.
KA5 auxiliary relays with 0.25 sec. time delay Auxiliary power supply = supply voltage of auxiliary relays
KA6 auxiliary relays with 0.25 sec. time delay (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
KA7 auxiliary relays with 0.25 sec. time delay MN...)

86 Schneider Electric
Electrical diagrams Source-changeover systems
with automatic controllers
2 Compact NS100/1600 or
Masterpact NT/NW devices
Source-changeover system with BA controller
E47738

Coupling
N R

E43968
selector
N
R
auto stop
23 22

1 3 5 1 3 5
14 13 16 15 11 12 10 9 5 7 6 8

Q1 Q2

2 4 6 2 4 6

Transfer conditions
ACP

E43969
2 N O L 17 18 20 21 R E 25

24 N O L 9 10 R E 25

N R if contact closed

voluntary transfer order


(e.g. for energy management)

24 N O L R E 25

stop Terminals 20 and 21:


N
additional control contact
23 22

R auto
(not part of controller).
17 18 20

BA
21

11 12 13 14 15 16 10 9 8 7 6 5

11 12 13 14 15 16

N
IVE
R

1 2 3 4 5 6 7 8 9 10

remove jumpers
for NS630b/1600 and
Masterpact NT/NW

Tests on “Normal” and “Replacement”


source voltages
The single-phase check for UN and UR is
implemented across terminals 1 and 5 of
circuit breakers Q1 and Q2.

Legends
Q1 : circuit breaker supplying and protecting the automatic-control circuits for the “Normal” source
Q2: circuit breaker supplying and protecting the automatic-control circuits for the
“Replacement” source Note:
ACP: auxiliaries control plate Diagram shown with circuits de-energised, circuit breakers
BA: automatic controller open and relays in normal position.
IVE: electrical interlocking and terminal block unit

Schneider Electric 87
Electrical diagrams Source-changeover systems
with automatic controllers
2 Compact NS100/1600 or
Masterpact NT/NW devices
Source-changeover system with UA controller
Load shedding and genset management

E43965
N R
E43918modif

sélecteur délestage démarrage groupe


selector load shedding generator
N order start-up order
R
auto stop
23 22 27 26 28 30 29 31

1 3 5 1 3 5 14 13 16 15 11 12 10 9 5 7 6 8

Q1 Q2

2 4 6 2 4 6

ACP
Transfer conditions

E43964
24 N O L 9 10 R E 25 24 N O L 17 18 20 21 R E 25
A
B
C
01

N/ voltage
see "Normal" source A=0 1 phase control N R
si contact fermé
voltage UN test table A=1 3 phases control if contact closed
EJP / voluntary
ordre de
B=0 N=off fault permutation
B=1 N=on generator volontaire (ex: EJP)
voluntary transfer
24 N O L R E 25 C=0 t6=20s t max
C=1 t6=180s start generator
stop
N
23 22

R auto
Terminals 20 and 21:
additional control contact
(not part of controller).
UA
17 18 20

Tests on “Normal” and “Replacement”


21

11 12 13 14 15 16 10 9 8 7 6 5 source voltages
“Normal” source voltage UN test
E43989

ref. UA 29472 29472 29473


ref. UA150 29474 29474 29475
supply
voltage N/ . / /
220/240VAC 220/240VAC 380/415VAC
switch
50/60Hz 50/60Hz 50/60Hz
position
440V - 60Hz

N
11 12 13 14 15 16
A=0
N 1L1 3L2 5L3 1L1 3L2 5L3 1L1 3L2 5L3
IVE Q1 Q1 Q1
R

1 2 3 4 5 6 7 8 9 10
A=1 1L1 3L2 5L3 1L1 3L2 5L3
remove jumpers
for NS630b/1600 and Q1 Q1
Masterpact NT/NW
“Replacement” source voltage UR test
The single-phase check for UR is
implemented across terminals 1 and 5 of
circuit breaker Q2.

Legends
Q1 : circuit breaker supplying and protecting the automatic-control circuits for the “Normal” source
Q2: circuit breaker supplying and protecting the automatic-control circuits for the
“Replacement” source Note:
ACP: auxiliaries control plate Diagram shown with circuits de-energised, circuit breakers
UA: automatic controller open and relays in normal position.
IVE: electrical interlocking and terminal block unit

88 Schneider Electric
Electrical diagrams Source-changeover systems
with automatic controllers
2 Compact NS100/1600 or
Masterpact NT/NW devices
Controller settings Using communication functions
E43966

E43967
boucle COM
COM loop

24 N O L 17 18 20 21 R E 25 2
4 6
8
24 N O L 17 18 20 21 R E 25 4 6
1 2 8
A 10 1
B 14 12 A 10
5
C + B 14 12
0v 24v 3 7
C 5
01 1 9 + 0v 24v 3 7

24v 0v + 15
13
11 01 1 9

N / voltage 24v 0v + 15
13
11

N/ voltage
A=0 1 phase control si contact fermé BBus
A=1 3 phase control N R
if contact closed A=0 1 phase control si contact fermé BBus
N R
A=1 3 phase control if contact closed
EJP / voluntary transfer ordre de EJP / voluntary transfer ordre de
B=0 N=off fault permutation
B=1 N=on generator volontaire (ex: EJP) B=0 N=off fault permutation
voluntary transfer B=1 N=on generator volontaire (ex: EJP)
C=0 t6=20s t max voluntary transfert
C=1 t6=180s start generator C=0 t6=20s t max
C=1 t6=180s start generator

Tests on “Normal” source voltage The address of the UA controller is set


using the two BBus dials.
A=0 single-phase test,
A=1 three-phase test.
Voluntary transfert (e.g. for energy management)
c action in the event of genset failure
B = 0 circuit breaker N opens,
B = 1 circuit breaker N remains closed.
c maximum permissible genset startup time (T6)
C = 0 T = 120 s,
C = 1 T = 180 s.
After this time has elapsed, the genset is considered
to have failed.

Schneider Electric 89
Electrical diagram Source-changeover systems
with automatic controllers
2 Masterpact NT or NW devices
Diagram no. 51156903
Electrical interlocking with lockout after a fault
E47410

source management
N° 1IA038

(3)
N R N
BA/UA controller
WH

VT

BK
GN
RD
for 2 devices
(3) N° 1IA036
R

RD
WH

VT

BK
GN
(2)
252
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
(2)

252
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
CE1

CE1

QN OF1 OF2 OF3 OF4

SDE1
QR OF1 OF2 OF3 OF4
PF
SDE1

MCH
PF

CH
MX XF MCH

CH
MX XF
B1

C1

A1

251

81

11

21

31

41

311

(1) (2)
B1

C1

A1

251

81

11

21

31

41

311
GY

BN

YE

(1) (2)
GY

BN

YE

(1) Not to be wired for the “without lockout after a fault” solution
(2) Not to be wired on fixed version
(3) Prefabricated wiring supplied

Legends
QN Normal” source Masterpact NT or NW
QR “Replacement” source Masterpact NT or NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 “fault-trip” indication contact
PF “ready-to-close” contact
CE1 “connected-position” indication contact (carriage switch)
CH “springs charged” indication contact
IVE electrical interlocking and terminal block unit
States permitted by mechanical interlocking system
Wiring colour codes Normal Replacement
RD red 0 0
GN green 1 0
BK black
0 1
VT violet
YE yellow Note:
GY grey Diagram shown with circuit breakers in connected position,
WH white open, charged, and ready to close.
BN brown

90 Schneider Electric
Source- Orders forms

changeover
systems
Presentation 2
Functions and characteristics 7
Dimensions 33
Electrical diagrams 55

Source-changeover systems for 2 devices 92


Interpact INS40 to INS630 - Switch-disconnectors 92
Compact NS100 to NS630 - Circuit breakers and
switch-disconnectors 94
Compact NS630b to NS1600 - Circuit breakers and
switch-disconnectors 96
Masterpact NT or NW - Circuit breakers and
switch-disconnectors 98
Source-changeover systems for 3 devices 100
Masterpact NW - Circuit breakers and switch-disconnectors 100

Schneider Electric 91
Order forms Source-changeover systems
for 2 devices
Interpact INS40 to INS630
Switch-disconnectors
To indicate your choices, check the applicable square boxes and enter the
appropriate information in the rectangles .

Mechanical interlocking of two INS40 to INS630 devices


Devices with front rotary handles, mounted side by side
Two devices with direct rotary handles
INS250 INS320/400/500/630
Two devices with extended rotary handles
IN40/63/80 INS100/125/160
INS250 INS320/400/500/630
Downstream coupling INS250 INS320/400/500/630
accessory
Long terminal shields INS250 INS320/400/500/630

Complete source-changeover assembly


INS250-100 A INS250-160 A
INS250-200 A INS250-250 A
INS320 INS400
INS500 INS630

92 Schneider Electric
Order forms Source-changeover systems
for 2 devices
Interpact INS40 to INS630
Switch-disconnectors (cont.)
To indicate your choices, check the applicable square Indication and measurements
boxes and enter the appropriate information in the 4P ammeter module For INS250 Rating 100 A
rectangles . 150 A
(one sheet per device, make copies if necessary) 250 A

Device identification: Adaptation kit required for direct handles

Q 1 - NORMAL SOURCE For INS320/630 Rating 400 A

Q 2 - REPLACEMENT SOURCE 600 A

Switch-disconnector 4P current-transformer For INS250 Rating 100 A


module 150 A
Interpact type INS40/63/80
INS100/125/160 250 A
INS250 For INS320/630 Rating 400 A
INS320/400/500/630
600 A
Rating A
Auxiliary contact For INS40/160 1OF/CAF/CAO Standard
Number of poles 3 or 4
Low level
Connections
For INS250/630 1 OF/CAM Standard
Front connection Standard
Low level
Rear connection 2 short 2 long
Rotary handles
INS40/80 Distribution 3x16v rigid/10v flexible
Extended front handles INS40 to INS160 Black Red on yellow front
connectors
INS250 Black Red on yellow front
INS100/160 Snap-on y 95v
connectors INS320 to INS630 Black Red on yellow front
Distribution 4x25v rigid/16v flexible
For complete changeover assembly INS250
INS250 Snap-on 1.5v to 95v (< 160 A)
connectors INS320/630
Snap-on 10v to 185v (< 250 A)
Voltage tap connector for 185v connector
Locking of rotary handles
Padlocking 1 to 3 padlocks (in OFF position)
Clips for connectors Set of 10
Keylocking Keylock adapter (keylock not included)
Distribution 6x1.5v
to 35v
rigid
with interphase barriers Keylocks Ronis 1351B.500 Profalux KS5 B24 D4Z
INS320/630 1 cable 35v to 300v Installation accessories
connectors 2 cables 35v to 240v Front-panel escutcheon For switc-disconnectors
Voltage tap connector for 185v connector
For ammeter module, IP40
Distribution "Distribloc" 125 A 160 A
blocks Multi-stage 125 A 160 A
"Polybloc" 160 A 250 A
Rt-angle extension Set of 3 or 4 250 A 630 A
Straight extension INS250
Edgewise ext. INS630
Spreader INS250 (45 mm)
Front alignment base
INS320/630 52.5 mm 70 mm
One-piece INS250 INS630
CU cable lugs INS100/160 For 95v cable
supplied with INS250 For 120v cable
2 or 3 inter- For 150v cable
phase barriers For 185v cable
INS320/630 For 240v cable
For 300v cable
AL cable lugs INS250 For 150v cable
supplied with For 185v cable
2 or 3 inter- INS320/630 For 240v cable
phase barriers For 300v cable
Terminal shrouds INS40/63/80 INS100/125/160
Terminal shields INS40/63/80 INS100/125/160
INS250 Short Long
INS320/630 Short Long
Long for 52.5mm spreaders
Interphase INS100/160 Set of 6
barriers INS250 Set of 6
INS320/630 Set of 6

Schneider Electric 93
Order forms Source-changeover systems
for 2 devices
Compact NS100 to NS630 / Circuit-
breakers and switch-disconnectors
To indicate your choices, check the applicable square boxes and enter the
appropriate information in the rectangles .

Diagram for two Compact NS devices


Without automatic control, without emergency off auxiliaries (no. 51201177)
Without automatic control, with emergency off by MN (no. 51201178)
Without automatic control, with emergency off by MX (no. 51201179)
Mechanical interlocking of two NS100 to NS630 devices
(fixed, plug-in or withdrawable)
Manually operated devices, mounted side by side:
Two devices with toggles
Two devices with rotary handles
Mechanical and electrical interlocking of two NS100 to NS630 devices
(fixed or plug-in)
Electrically operated devices, mounted side by side:
Select 1 base plate + IVE, the 4 auxiliary contacts and the options / accessories
Base plate + IVE Identical voltages: 48 to 415 V CA 50/60 Hz
24 to 250 V CC 440/480 V AC 60 Hz
"Normal" NS100/250 "Replacement" NS100/250
"Normal" NS400/630 "Replacement" NS400/630
"Normal" NS400/630 "Replacement" NS100/250
Adapter kit for NS400/630 with NS100/250 (plug-in)
Auxiliary contacts 2 OF + 2 SDE (mandatory) Quantity 4
Options Long rear connections Plug-in base
Downstream coupling accessory 3P NS100/250
4P NS400/630
Prefabricated wiring Between device and IVE Quantity
Automatic-control option
Power supply 220/240 V - 50/60 Hz : ACP + BA controller
ACP + UA controller
ACP + UA150 controller
Power supply 380/415 V - 50/60 Hz and 440 V - 60 Hz : ACP + BA controller
ACP + UA controller
ACP + UA150 controller

94 Schneider Electric
Order forms Source-changeover systems
for 2 devices
Compact NS100 to NS630 / Circuit-
breakers and switch-disconnectors (cont.)
To indicate your choices, check the applicable square Communication
boxes and enter the appropriate information in the Communicating OF, SD, SDE or SDV auxiliary contacts
rectangles . Connected/disconnected position indication contacts
(one sheet per device, make copies if necessary)
Motor mechanism + communicating OF, SD, SDE contacts 220-240 V 50/60 Hz
Device identification:
Indication and measurements
Q 1 - NORMAL SOURCE
Q 2 - REPLACEMENT SOURCE Ammeter module standard 3P 4P
Circuit breaker or switch-disconnector I max 3P
Compact type NS100/160/250 Current-transformer module 3P 4P
NS400/630 Insulation-monitoring module 3P 4P
Rating A Voltage-presence indicator
Circuit breaker N, H, L Auxiliary contact OF, SD, SDE or SDV Standard Low level
Switch-disconnector NA
SDE adapter (TM or MA trip units)
Number of poles 2, 3 or 4
Remote operation
Number of poles tripped 2d, 3d, 3dN/2 or 4d
Electrical operation Motor mechanism AC DC V
Fixed device Front connections Long rear conn.
Short rear conn. Mixed rear conn. Voltage releases Instantaneous MX AC DC V
Plug-in/withdr. Plug-in Withdrawable MN AC DC V
Earth-leakage protection ME, MH, MB, MHM Delayed MN AC DC V
Voltage V Rotary handles
4p MB option on 3p NS Direct Black Red on yellow front
Thermal-magnetic or electronic trip unit MCC conversion access. CNOMO conversion access.
Thermal-mag. TMD rating (16 … 250 A)
Extended Black Red on yellow front
TMG rating (16 … 63 A)
Telescopic handle for withdrawable device
MA rating (2.5 … 220 A)
Indication auxiliary 1 early-break switch 2 early-break switches
Electronic STR22 SE GE ME
STR23 SE SV Wiring accessory for early-make switches
STR53 (basic) UE F SV F Locking
STR53UE FT FI FTI Toggle (1 to 3 padlocks) Removable Fixed
ZSI wiring Rotary handle Keylock adapter (keylock not included)
Option T (rating 150…630 A) A Keylocks Ronis 1351B.500 Profalux KS5 B24 D4Z
STR43ME F FI
Motor mechanism Keylock adapter + Keylocks Ronis (special) NS100/250
Option STDAM 110/240 V AC/DC
Keylock adapter (keylock not included) NS400/630
24/48 V AC/24/72 V DC
Keylocks Ronis 1351B.500 Profalux KS5 B24 D4Z
COM wiring
Spare battery for STR43 and STR53 Installation accessories
Connections Front-panel escutcheon Toggle
Rear-connection kit Short Mixed Rotary handle, motor mechanism, escutcheon collar; IP40
Plug-in kit Compact Vigicompact Vigi module or ammeter IP40 Vigi module
Withdrawable kit Compact Vigicompact Toggle cover
Long terminal-shield kit for plug-in or withdr. NS400/630 Sealing accessories
Interphase-barrier kit for plug-in or withdr. NS400/630 DIN rail adapter NS100/250
NS100/250 connectors Snap-on 1.5v to 95v (< 160 A)
Plug-in / withdrawable configuration accessories
Snap-on 10v to 185v (< 250 A)
Auxiliary connections 1 automatic connector fixed part with 9 wires (for base)
Distribution 6 x 1.5v to 35v
NS400/630 connectors 1 cable 35v to 300v 1 auto. conn. moving part with 9 wires (for circuit breaker)
2 cables 35v to 240v 1 support for 3 automatic connector moving parts
Right-angle terminal extensions 9-wire manual auxiliary connector (fixed + moving)
Straight extensions NS100/250 Plug-in base accessories Long insulated terminals Set of 3 Set of 4
Edgewise extensions NS400/630 2 IP4 shutters for base
Spreader NS100/250 (one piece) (45 mm) Chassis accessories Escutcheon collar Toggle Vigi
NS400/630 (52.5 mm) (70 mm)
Locking kit (keylock not included)
CU cable lugs NS100/250 120v 150v 185v
2 carriage switches (conn./disconnected position indication)
NS400/630 240v 300v
Parts of plug-in Plug-in base FC/RC 2P 3P 4P
AL cable lugs NS100/250 150v 185v
withdrawable kits Set of two power connections Standard Vigi
NS400/630 240v 300v
Voltage measurement for lugs NS100/250 y 185v Safety trip for advanced opening
input for connector for lugs NS400/630 For 3P/4P chassis Moving part
Terminal shields NS100/250 Short Long Fixed part
NS400/630 Short Long
Long for 52.5 mm spreaders
Interphase barriers Set of 6
Insulation kit > 600V Without spreaders
NS400/630 With 52.5 mm spreaders
2 insulating NS100/250
screens: NS400/630 52.5 pitch 70 pitch

Schneider Electric 95
Order forms Source-changeover systems
for 2 devices
Compact NS630b to NS1600 / Circuit-
breakers and switch-disconnectors
To indicate your choices, check the applicable square boxes and enter the
appropriate information in the rectangles .

Diagram for 2 Compact NS devices


Electrical interlocking with lockout after fault:
Permanent replacement source (without IVE) (no. 51201180)
With emergency off by MX (without IVE) (no. 51201181)
With emergency off by MN (without IVE) (no. 51201182)
Permanent replacement source (with IVE) (no. 51201183)
With emergency off by MX (with IVE) (no. 51201184)
With emergency off by MN (with IVE) (no. 51201185)
Automatic control without lockout after fault:
Permanent replacement source (without IVE) (no. 51201186)
Engine generator set (without IVE) (no. 51201187)
Interlocking using connecting rods between two NS630b to NS1600 devices
Manually operated devices installed side-by-side:
For two fixed NS devices with extended rotary handles
Electrically operated devices installed one above the other:
Select a complete set including two adaptation fixtures and the connecting rods
Complete set for: 2 fixed NS devices
2 withdrawable NS devices
Interlocking using cables between two NS630b to NS1600 devices
Electrically operated devices installed one above the other or side-by-side:
Select a complete set including two adaptation fixtures and the cables
Complete set for: 2 fixed NS devices
2 withdrawable NS devices
1 fixed NS device + 1 withdrawable NS device
Electrical interlocking between two NS630b to NS1600 devices
1 IVE unit 48/415 V - 50/60 Hz and 440 V - 60 Hz
1 wiring kit for connection between 2 fixed / withdrawable devices to the IVE unit
Automatic-control option
Power supply 220/240 V - 50/60 Hz: ACP + BA controller
ACP + UA controller
ACP + UA150 controller
Power supply 380/415 V - 50/60 Hz and 440 V - 60 Hz:
ACP + BA controller
ACP + UA controller
ACP + UA150 controller

96 Schneider Electric
Order forms Source-changeover systems
for 2 devices
Compact NS630b to NS1600 / Circuit-
breakers and switch-disconnectors (cont.)
To indicate your choices, check the applicable square Indication contacts
boxes and enter the appropriate information in the SD trip indication (maximum 1)
rectangles . 6 A-240 V AC Low level
(one sheet per device, make copies if necessary) SDE fault-trip indication (maximum 1) (SDE integrated in electrically operated devices)
6 A-240 V AC Low level
Device identification:
OF ON/OFF indication contacts (maximum 3)
Q 1 - NORMAL SOURCE
6 A-240 V AC qty Low level qty
Q 2 - REPLACEMENT SOURCE
Carriage switches (possible combinations: 3 CE, 2 CD, 1 CT)
Circuit breaker or switch-disconnector
CE - "connected" position 6 A-240 V AC qty Low level qty
Compact type NS630b to NS1600
CD - "disconnected" position 6 A-240 V AC qty Low level qty
Rating A
CT - "test" position 6 A-240 V AC qty Low level qty
Circuit breaker N, H, L
Auxiliary terminals for chassis alone Jumpers (set of 10)
Switch-disconnector NA
3-wire terminal (30 parts) 6-wire terminal (10 parts)
Number of poles 3 or 4
Remote operation
Device Fixed
Electrical operation Standard Communicating
Withdr. with chassis
Power supply AC DC V
Withdr. without chassis
(moving part only) Voltage releases MX AC DC V
MN AC DC V
Chassis alone without connections
MN delay unit Adjustable Non-adjustable
Micrologic control unit
Rotary handles for fixed and withdrawable device
Basic protection 2.0 5.0
Direct Black Red on yellow front
A - ammeter
CNOMO conversion access.
2.0 5.0 6.0 7.0
Extended Black Red on yellow front
AD - external power-supply module V
Telescopic handle for withdrawable device
TCE - external sensor (CT) for neutral protection
Indication auxiliary 6 A-240 V AC 2 early-make switches
Rectangular sensor 280 x 115 mm
2 early-break switches
TCW - external sensor for SGR protection
Locking
LR - long-time rating plug Standard 0.4 to 1 Ir
Toggle (1 to 3 padlocks) Removable system Fixed system
Low setting 0.4 to 0.8 Ir
Rotary handle OFF position ON and OFF positions
High setting 0.8 to 1 Ir
using a keylock Ronis 1351B.500 Profalux KS5 B24 D4Z
LT OFF
Keylock kit (without keylock)
Communication
For electrically VBP - ON/OFF pushbutton locking
COM module Jbus/Modbus Manual operation
operated devices (by transparent cover + padlocks)
Electrical operation OFF position locking:
Digipact Manual operation VCPO - by padlocks
Electrical operation VSPO - by keylocks
Modbus Eco COM module Keylock kit (w/o keylock) Profalux Ronis
(for switchboard display units)
1 keylock Profalux Ronis
Connections
2 identical keylocks, 1 key Profalux Ronis
Horizontal rear connections Top Bottom
Chassis locking in "disconnected" position:
Vertical rear connections Top Bottom
VSPD - by keylocks Keylock kit (w/o keylock) Profalux Ronis
Front connections Top Bottom
Kirk Castell
4x240v bare cable connectors + shields NS - FC fixed
1 keylock Profalux Ronis
Long connection shields NS - FC fixed
2 identical keylocks, 1 key Profalux Ronis
Vertical-connection adapters NS - FC fixed, withdr.
2 keylocks, different keys Profalux Ronis
Cable-lug adapters NS - FC fixed, withdr. Optional connected/disconnected/test position locking
Arc chute screen NS - FC fixed VPEC - door interlock On right-hand side of chassis
Interphase barriers NS - fixed, withdrawable On left-hand side of chassis
Spreaders NS - fixed, withdrawable VPOC - racking interlock
VO - safety shutters on chassis NS - withdrawable VDC - mismatch protection
Accessories
CDM - mechanical operation counter
CDP - escutcheon
CP - transparent cover for escutcheon
OP - blanking plate for escutcheon
Mounting brackets for fixed NS for mounting on horizontal plane
Test kits Mini test kit Portable test kit

Schneider Electric 97
Order forms Source-changeover systems
for 2 devices
Masterpact NT or NW / Circuit-
breakers and switch-disconnectors
To indicate your choices, check the applicable square boxes and enter the
appropriate information in the rectangles .

Diagram for 2 Masterpact NT/NW devices


Electrical interlocking with lockout after fault:
Permanent replacement source (without IVE) (no. 51201139)
With emergency off by MX (without IVE) (no. 51201140)
With emergency off by MN (without IVE) (no. 51201141)
Permanent replacement source (with IVE) (no. 51201142)
With emergency off by MX (with IVE) (no. 51201143)
With emergency off by MN (with IVE) (no. 51201144)
Automatic control without lockout after fault:
Permanent replacement source (without IVE) (no. 51156226)
Engine generator set (without IVE) (no. 51156227)
Automatic control with lockout after fault:
Permanent replacement source (with IVE) (no. 51156904)
Engine generator set (with IVE) (no. 51156905)
BA/UA controller (with IVE) (no. 51156903)
Interlocking using connecting rods (NT/NW devices one above the other)
Select a complete set including two adaptation fixtures and the connecting rods
Complete set for: 2 drawout NT devices 2 fixed NT devices
2 drawout NW devices 2 fixed NW devices
1 NW fixed device + 1 drawout NW device
1 fixed NT device + 1 fixed NW devices
1 drawout NT device + 1 drawout NW device
Interlocking using cables (NT/NW devices one above the other or side-by-side)
Select two adaptation fixtures (one for each device) and a set of two cables
Adaptation fixture for: 1 fixed NT device qty
(NT/NW fixed and drawout 1 drawout NT device qty
devices may be mixed)
+ 1 fixed NW device qty
1 drawout NW device qty
1 set of 2 cables (for two devices)
Electrical interlocking 2 appareils NT/NW
1 IVE unit 48/415 V - 50/60 Hz and 440 V - 60 Hz
1 wiring kit for connection between 2 fixed/drawout devices and IVE unit
Automatic-control option
Power supply 220/240 V - 50/60 Hz: ACP + BA controller
ACP + UA controller
ACP + UA150 controller
Power supply 380/415 V - 50/60 Hz and 440 V - 60 Hz:
ACP + BA controller
ACP + UA controller
ACP + UA150 controller

98 Schneider Electric
Order forms Source-changeover systems
for 2 devices
Masterpact NT or NW / Circuit-breakers
and switch-disconnectors (cont.)
To indicate your choices, check the applicable square Indication contacts
boxes and enter the appropriate information in the OF - ON/OFF indication contacts
rectangles . Standard 4 OF 6 A-240 V AC (10 A-240 V AC and low-level for NW)
(one sheet per device, make copies if necessary) Additional 1 block of 4 OF for NW max. 2 qty

Device identification: EF - combined "connected/closed" contacts

Q 1 - NORMAL SOURCE 1 EF 6 A-240 V AC for NW max. 8 qty

Q 2 - REPLACEMENT SOURCE 1 EF low-level for NW max. 8 qty


SDE - "fault-trip" indication contact
Circuit breaker or switch-disconnector
Standard 1 SDE 6 A-240 V AC
Masterpact type NT NW
Additional 1 SDE 6 A-240 V AC 1 SDE Low level
Rating A
Programmable contacts 2 M2C contacts 6 M6C contacts
Sensor rating A
Carriage switches 6 A-240 V AC Low level
Circuit breaker N1, H1, H2, H3, L1
CE - "connected" position max. 3 for NW qty
Switch-disconnector NA, HA, HF
CD - "disconnected" position max. 3 for NW qty
Number of poles 3 or 4
CT - "test" position max. 3 for NW qty
Option: neutral on right side Not currently available
AC - actuator for additional carriage switches qty
Device Fixed
Drawout with chassis
Remote operation
Drawout without chassis Remote ON/OFF MCH - gear motor V
(moving part only) XF - closing voltage release V
Chassis alone without connections MX - opening voltage release V
Micrologic control unit PF - "ready to close" contact Low level
A - ammeter 6 A-240 V AC
2.0 5.0 6.0 7.0 BPFE - electrical closing pushbutton
P - power meter 5.0 6.0 7.0 Res - electrical reset option V
H - harmonic meter 5.0 6.0 7.0 RAR - automatic reset option
AD - external power-supply module V Remote tripping MN - undervoltage release V
TCE - external sensor (CT) for neutral protection R - delay unit (non-adjustable)
Rectangular sensor NT (280 x 115 mm) Rr - adjustable delay unit
for earth-leakage protection NW (470 x 160 mm)
2eme MX - shunt release V
TCW - external sensor for SGR protection Locking
LR - long-time rating plug Standard 0.4 to 1 Ir VBP - ON/OFF pushbutton locking (by transparent cover + padlocks)
Low setting 0.4 to 0.8 Ir OFF position locking:
High setting 0.8 to 1 Ir VCPO - by padlocks
LT OFF VSPO - by keylocks Keylock kit (w/o keylock) Profalux Ronis
PTE - external voltage measurement input 1 keylock Profalux Ronis
(required for reverse supply)
2 identical keylocks, 1 key Profalux Ronis
BAT - battery module
2 keylocks, different keys (NW) Profalux Ronis
Communication
Chassis locking in "disconnected" position:
COM module Jbus/Modbus
VSPD - by keylocks Keylock kit (w/o keylock) Profalux Ronis
Digipact
1 keylock Profalux Ronis
Eco COM module Modbus
2 identical keylocks, 1 key Profalux Ronis
(for switchboard display units)
2 keylocks, different keys Profalux Ronis
Connections
Optional connected/disconnected/test position lock
Horizontal Top Bottom
VPEC - door interlock On right-hand side of chassis
Vertical Top Bottom
On left-hand side of chassis
Front Top Bottom
VPOC - racking interlock
Vertical-connection adapters NT - FC fixed, draw.
IPA - cable-type door interlock
Cable-lug adapters NT - FC fixed, draw.
IBPO - racking interlock between crank and OFF pushbutton for NW
Arc chute screen NT - FC fixed
DAE - automatic spring discharge before breaker removal for NW
Interphase barriers NT, NW fixed, draw.
VDC - mismatch protection
Spreaders NT fixed, drawout
Accessories
Disconnectable front connection adapter NW fixed
CDM - mechanical operation counter
Lugs for 240v or 300v cables NT fixed, draw.
CB - auxiliary terminal shield for chassis
VO - safety shutters on chassis NT, NW
CDP - escutcheon
VIVC - shutter position indication NW
and locking CP - transparent cover for escutcheon
OP - blanking plate for escutcheon
Brackets for mounting NW fixed on backplates
Test kits Mini test kit Portable test kit

Schneider Electric 99
Order forms Source-changeover systems
for 3 devices
Masterpact NW / Circuit-breakers
and switch-disconnectors
To indicate your choices, check the applicable square boxes and enter the
appropriate information in the rectangles .

Diagram for 3 Masterpact NW devices


2 "Normal" sources + 1 "Replacement" source:
Electrical interlocking without lockout after fault (no. 51156906)
Electrical interlocking with lockout after fault (no. 51156907)
2 "Normal" sources + 1 "Replacement" source with source selection:
Automatic control w/ engine generator set w/o lockout after fault (no. 51156908)
Automatic control w/ engine generator set w/ lockout after fault (no. 51156909)
3 sources, only 1 device ON:
Electrical interlocking without lockout after fault (no. 51156910)
Electrical interlocking with lockout after fault (no. 51156911)
2 "Normal" sources "+ 1 coupling:
Electrical interlocking without lockout after fault (no. 51156912)
Electrical interlocking with lockout after fault (no. 51156913)
Automatic control with lockout after fault: (no. 51156914)
Interlocking using cables (NW devices one above the other or side-by-side)
Select a complete set including three adaptation fixtures and the cables
1 complete set for: 3 sources / 1 device ON, fixed or drawout
2 sources + 1 coupling, fixed or drawout
2 sources + 1 replacement source, fixed or drawout

100 Schneider Electric


Order forms Source-changeover systems
for 3 devices
Masterpact NW / Circuit-breakers
and switch-disconnectors (cont.)
To indicate your choices, check the applicable square Indication contacts
boxes and enter the appropriate information in the OF - ON/OFF indication contacts
rectangles . Standard 4 OF 6 A-240 V AC (10 A-240 V AC and low-level)
(one sheet per device, make copies if necessary) Additional 1 block of 4 OF max. 2 qty
EF - combined "connected/closed" contacts
Device identification:
1 EF 6 A-240 V AC max. 8 qty
Q1 NORMAL SOURCE
1 EF Low level max. 8 qty
Q2 REPLACEMENT SOURCE
SDE - "fault-trip" indication contact
Q3 COUPLING
Standard 1 SDE 6 A-240 V AC
Circuit breaker or switch-disconnector
Additional 1 SDE 6 A-240 V AC 1 SDE Low level
Masterpact type NW
Programmable contacts 2 M2C contacts 6 M6C contacts
Rating A
Carriage switches 6 A-240 V AC Low level
Sensor rating A
CE - "connected" position max. 3 qty
Circuit breaker N1, H1, H2, H3, L1
CD - "disconnected" position max. 3 qty
Switch-disconnector NA, HA, HF
CT - "test" position max. 3 qty
Number of poles 3 or 4
AC - actuator for additional carriage switches qty
Option: neutral on right side Not currently available
Remote operation
Device Fixed
Remote ON/OFF MCH - gear motor V
Drawout with chassis
XF - closing voltage release V
Drawout without chassis
(moving part only) MX - opening voltage release V
Chassis alone without connections PF - "ready to close" contact Low level
Micrologic control unit 6 A-240 V AC
A - ammeter BPFE - electrical closing pushbutton
2.0 5.0 6.0 7.0 Res - electrical reset option V
P - power meter 5.0 6.0 7.0 RAR - automatic reset option
H - harmonic meter 5.0 6.0 7.0 Remote tripping MN - undervoltage release V
AD - external power-supply module V R - delay unit (non-adjustable)
TCE - external sensor (CT) for neutral protection Rr - adjustable delay unit
Rectangular sensor 470 x 160 mm 2eme MX - shunt release V
for earth-leakage protection
Locking
TCW - external sensor for SGR protection VBP - ON/OFF pushbutton locking (by transparent cover + padlocks)
LR - long-time rating plug Standard 0.4 to 1 Ir OFF position locking:
Low setting 0.4 to 0.8 Ir VCPO - by padlocks
High setting 0.8 to 1 Ir VSPO - by keylocks Keylock kit (w/o keylock) Profalux Ronis
LT OFF 1 keylock Profalux Ronis
PTE - external voltage measurement input 2 identical keylocks, 1 key Profalux Ronis
(required for reverse supply)
2 keylocks, different keys (NW) Profalux Ronis
BAT - battery module
Chassis locking in "disconnected" position:
Communication
VSPD - by keylocks Keylock kit (w/o keylock) Profalux Ronis
COM module Jbus/Modbus
1 keylock Profalux Ronis
Digipact
2 identical keylocks, 1 key Profalux Ronis
Eco COM module Modbus
2 keylocks, different keys Profalux Ronis
(for switchboard display units)
Optional connected/disconnected/test position lock
Connections
VPEC - door interlock On right-hand side of chassis
Horizontal Top Bottom
On left-hand side of chassis
Vertical Top Bottom
VPOC - racking interlock
Front Top Bottom
IPA - cable-type door interlock
Interphase barriers Fixed, drawout
IBPO - racking interlock between crank and OFF pushbutton for NW
Disconnectable front connection adapter Fixed
DAE - automatic spring discharge before breaker removal for NW
VO - safety shutters on chassis
VDC - mismatch protection
VIVC - shutter position indication and locking
Accessories
CDM - mechanical operation counter
CB - auxiliary terminal shield for chassis
CDP - escutcheon
CP - transparent cover for escutcheon
OP - blanking plate for escutcheon
Brackets for mounting NW fixed on backplates
Test kits Mini test kit Portable test kit

Schneider Electric 101


Notes

102 Schneider Electric


Notes

Schneider Electric 103


Notes

104 Schneider Electric


ABTED201149EN © 2001 Schneider Electric - All rights reserved

Schneider Electric Industries SA As standards, specifications and designs change from time to time, please ask for confirmation
of the information given iin this publication
5, rue Nadar
92506 Rueil-Malmaison Cedex France This document has been printed on ecological paper
Tel: +33 (0)1 41 29 82 00
Fax: +33 (0)1 47 51 80 20 Design: Schneider Electric - AMEG
Photos: Schneider Electric
[Link] Printed::

BTP312EN 07/2001

You might also like