Fig. 1. Transmission line circuit for an electrode
The equations (1) can be presented by a equivalent circuit in Fig.1. In this, R, L(x,t), G(x,t) and
C(x,t) are per-unit length resistance, inductance, conductance and capacictance of the electrode,
respectively. These parameters are functions of space and time which can be calculated detailedly in
[1].
The grounding system and lightning current used for simulation
A typical grounding system under towers of telecomunication or wireless systems is presented
in Fig. 2. The three vertical grounding copper electrodes are 7.5mm in radius and 15m long. They
are connected by copper wires which are 5mm in radius. The electrodes resistivity used in
calculation is
and resistivity
()
)
with the rise-time,
( s ) 1 2 3 4 5 6 7 8
Peak value (kV) 6,722 4,543 3,662 3,177 2,929 2,823 2,692 2,539
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
x 10
-5
0
0.2
0.4
0.6
0.8
1
1.2
t(s)
I
s
(
k
A
)
1
2
3
4
5
6
7
8
Fig. 4. Over-voltage at the injected point when the rise-time changes from 1s to 8s
Fig. 5. Peak value of over-voltage at the injected point varies with the rise-time
0 2 4 6 8
x 10
-6
2
2.5
3
3.5
4
4.5
5
5.5
6
6.5
7
ts(s)
U
p
e
a
k
(
k
V
)
From the simulation results in Fig. 4, 5 and Tab. 2, the smaller the rise-time is, the higher the
over-voltage on the grounding systems is. That means the transient response on grounding systems
is affected significantly by the rise-slope of the lightning current. The reason is that the inductance
along electrodes of grounding systems can prevent the impulse current from passing by, and hence
decrease the ability of grounding systems in dissipating this current into the surrounding ground.
Conclusion
Non-uniform transmission line model is applied to simulate the transient phenomenon of
grounding systems in this research. Through the simulation results, the considerable effect of the
rise-slope of the lightning currents to this issue can be clarify. This influcence can be sumarized
briefly as the steeper this parameter is, the less effective the grounding systems are in distributing
the lightning currents into the ground. Hence, grounding systems used for lightning protection have
to be limited in their length or their building area to reduce the effect of inductances along their
component electrodes.
References
[1] Yaqing Liu, Nelson Theethayi, and Rajeev Thottappillil, Member, IEEE An engineering model
for transient analysis of grounding system under lightning strikes: Nonuniform transmission-line
approach, IEEE Trans. Power Del, vol. 20, no. 2, pp. 722 730 , Apr 2005