DAIKIN AIRCONDITIONING PHILIPPINES, INCORPORATED

18th floor Exxa Tower Bridgetowne, C5 Road, Brgy. Ugong Norte Quezon City
Telephone No.: (632) 53186800

TESTING AND COMMISSIONING REPORT (SA)

DATE: May 22, 2024


CUSTOMER / PROJECT NAME: Starbucks Pioneer
ADDRESS: G/F Pioneer Center, Pioneer Street, Pasig City
CONTACT PERSON / TEL NO.: Charm Timbayan / 09178427326

OUTDOOR UNIT
MODEL NO.: SERIAL NO. CAPACITY NAME AND LOCATION
ACCU
COMP. RR140AGXTL9 K010644
PIPE SIZE (in) S: 3/4 D: 3/8 AMBIENT TEMPERATURE (⁰C) 39°C
PIPING LENGTH (m) 18 meters WIRE SIZE FROM C.B. TO ACCU (mm²) Royal cord #10
HEIGHT DIFFERENCE TRANSMISSION WIRE SIZE (mm²) Royal cord #12
INSULATION THICKNESS (in) Liquid ; 3/8 x 3/4 Gas ; 3/4 x 1" BREAKER CAPACITY (A) 40 ampere
DISCHARGE PRESSURE (psi) (kg/cm²) 128 psi SUCTION AIR TEMPERATURE (⁰C) 40°C
SUCTION PRESSURE (psi) (kg/cm²) 235 psi DISCHARGE AIR TEMPERATURE (⁰C) 44°C
AMPERE: 19 ampere SUCTION PIPE TEMPERATURE (⁰C)
VOLTAGE: 240 volts / 230 volts DISCHARGE PIPE TEMPERATURE (⁰C)
BEFORE OPERATION: OUTDOOR INSTALLATION CONDITION GOOD NO GOOD

DURING OPERATION: RUN TESTING DURATION (min)


ADDITIONAL REFRIGERANT CHARGE (kg) SUPERHEAT

INDOOR UNIT
INDOOR
BREAKER RETURN
THERMOSTAT ROOM TEMP. SUPPLY AIR INSTALLATION
MODEL NO.: SERIAL NO.: LOCATION CAPACITY AIR TEMP.
(A)
SETTING (⁰C) (⁰C) (⁰C)
TEMP. (⁰C) CONDITION
G NG
1 FDMRN140AXVL9 K001252 Office Area 22°C 20°C 21°C 11°C

TO GET SUPERHEAT (SH) *A *B


A Get the temperature of refrigerant at suction of compressor using thermometer.
B Get the saturation temperature corresponding to the pressure at suction line.
NOTE See the back of this page for tables of saturation temperature

SUPERHEAT = TEMPERATURE AT SUCTION LINE


*A - SATURATION TEMPERATURE
*B

SH = 5.1°C - =

REMARKS AND RECOMMENDATIONS:

INSTALLATION SUPPORT CLIENT'S REPRESENTATIVE / INSTALLER

NAME / SIGNATURE NAME / SIGNATURE

Control No. G-06-02.03_version 01_April 2023