Circuit diagrams Wye-delta

Wye-delta, open transition STOP-START

Re

du c st ed v ar te olta rs ge

3
3

The wye-delta open transition starter starts the motor by closing the S and 1M contactors which energize the windings in wye. The inrush current in wye is reduced to 33% of what it would be if the motor was started with an across the line starter. The starting time in wye is adjustable with a timer. After the elapsed time, the S contactor opens which closes the 2M contactor; there is a short period (about 50ms) when the motor is not energized; and then the motor runs full voltage in delta. A wye-delta starter requires a wye-delta wound motor with all six leads terminated outside the motor housing.
INCOMING LINES C A B

CIRCUIT PROTECTIVE DEVICE (WHEN SPECIFIED)

CHFU

H1 H2 H3 H4

CHFU

CXFU STOP 21 S T1 OL T1 T2 T3 1M T1 T2 T3 T6 T4 T5 13 14 13 1M 23 24 T2 MECH T3 INTLK T1 T2 T3 S 14 22 START 13 14 XF

CCT 96 A1 01 01 A1 A1 A1

OL 95 A2 A2 A2 A2

L1 1M

L2

L3

L1 2M

L2

L3

L1

L2

L3

TR S 2M 1M

TR 15 16 18

2M 02 02

TO WYE-DELTA MOTOR

Wye-delta, closed transition STOP-START


The wye-delta closed transition starter works the same way as the open transition wye-delta starter except the closed transition version utilizes a set of resistors during the transition from start to run (wye to delta connection). These resistors eliminate the open circuit and prevent transient currents.
INCOMING LINES C A B

CIRCUIT PROTECTIVE DEVICE (WHEN SPECIFIED)

CHFU H1 CXFU XF

H2 H3

CHFU H4 CCT OL 96 ISR 22

95 21

IST L1 L1 1M L2 L3 L1 L2 2M MECH T1 T2 T3 INTLK OL T1 T2 T3 L3 T T1 T2 T3 T6 T4 T5 T3 T2 T1 L2 L1 T1 L3 L1 L2 L3 S T2 T3 STOP 21 22 START 13 14 1M 13 14 44 JUMPER 2M 02 01 TR 15 21 T 18 22 A1 A1 A1


01

L2

A1

ISR T S TR 2M 1M

A2

A2 A2 A2 A2 A2 MECH INTLK

S 43
02

A1 A1

TO WYE-DELTA MOTOR

R3 R2 R1

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb-control.com

3.83
1SXU 000 023 C0201