You are on page 1of 5

Standard Motors for

Semi-Hermetic Screw Compressors (50 Hz)

HS. Models

400 V +/-10%

/ - 3 - 50 Hz

CS. Models

400 V +/-10%

/ - 3 - 50 Hz (PW)

VSK Models
respectively

230 V - 3 - 50 Hz

BITZER // S_HS_ELEC_GB // Page 1

(PW)

or 400 V - 3 - 50 Hz

Principle of the Part Winding Motor


for BITZER Screw Compressors
1

W2

U1

W2

U1

7
8

U2
2

V1

V2

W1

U2

K1
L1

L2

L3

K2

BITZER // S_HS_ELEC_GB // Page 2

V1

W1

V2

K1
L1

P.W. Start

L2

L3

D.O.L. Start
Connection

Electrical Connection
Semi-Hermetic Screw Compressors
Criteria for the selection of contactors,
wire sizes, fuses and motor overload relays (1)
/

Based on max. absorbed power / max. amps


(see Software & Literature)
never select for nominal power!!

Contactors for operational category AC 3

Schematic Wiring Diagrams


see Applications Manuals

BITZER // S_HS_ELEC_GB // Page 3

(SH-100-3, page 43 ff)


(SH-110-2, page 47 ff)

Electrical Connection
Semi-Hermetic Screw Compressors
Criteria for the selection of contactors, wire sizes, fuses and motor
overload relays (2)
Electronic motor protection module belongs to the standard extent of
delivery
/ HS.53 / CS. / HS.85
SE-E1
/ VSK
INT69VSY-II
/ HS.64 / 74
SE-E1 (previously: INT389R)
Options
/ HS.64 / 74 / 85
SE-C1 and SE-C2 (option)
for frequency inverter drive (less tripping caused by harmonics)
"dirty" power supply high degree of harmonics
The use of SE-E1 with all Semi-hermetics requires:
/ External motor overload relay
/ Timer against short cycling

BITZER // S_HS_ELEC_GB // Page 4

Electrical Connection
for Open Drive Screw Compressors
Criteria for the selection of contactors,
wire sizes, fuses and motor overload relays
/

Based on motor nominal power / max. amps

Contactors for operational category AC 3

Motor overload relays according to requirements of motor supplier

Schematic Wiring Diagrams


see Applications Manuals

BITZER // S_HS_ELEC_GB // Page 5

(SH-500-2, page 45 ff)


(SH-510-1, page 52 ff)

You might also like