You are on page 1of 7

R Y B

R G A W B
Banks Office Building
PT 2A VSS V At Patna
11 KV HT Panel
11KV, 800A VCB

CT OC+EF ASS A

Tri-Vector Meter
CT

Section 1 Section 2
R G A W B R G A W B

PT 2A VSS V PT 2A VSS V

11KV, 800A VCB 11KV, 800A VCB

OC+ EF OC+ EF
CT
CT

ASS A ASS A
CT CT

To 1000 KVA,
11KV/0.415KV To 1000 KVA,
Transformer 1 11KV/0.415KV
VCB Section Transformer 2
From HT panel Section 1 From HT panel Section 2
11 KV
3x185 sq.mm.
XLPE FRLS
cables from
HT panel

1000 KVA 1000 KVA


11/0.415KV 4x3.5x400 sq.mm. 11/0.415KV
TR 1 FRLS AL cable TR 2

0-500 V 0-500 V
PM 2A VSS V PM 2A VSS V
R Y B R Y B

2500A 2500A
4P MDO ACB 4P MDO ACB
Microprocessor Microprocessor
ASS A OC+EF ASS A
OC+EF

0-1500 A
0-1500 A

To APFC panel 1 To APFC panel 2

To LT panel Section 1 Main LT Panel - Incomer side To LT panel Section 2

Transformer Section
R
Y
B
1
ACB Panel No.1 1000A ACB

R
Y
B
2
To AMF Panel (EP-I)
1000A ACB
From LT

Section 1
breaker for

3
APFC-I
630A SDFU

4
Spare 400A SDFU

5
Spare 200A SDFU
R
Y

Outgoing side
Main LT panel
sq.mm.
ALcable

B
4x3.5x400

ACB Panel No.2 1000A ACB


415 V LT panel

APFC-II 630A SDFU


2500A 4P MDO ACB Bus Coupler

To AMF Panel (EP-II) 400A SDFU


9

250A SDFU
To AMF Panel (EP-III)
100A SDFU
10

Spare
From LT

200A SDFU
11
Section 2

Spare
breaker for

Main LT Panel
From output of AMF panel of 600 KVA generator set

1000A 4P
MDO ACB
(With EF and OC protection) R Y B
0-500 V

2A VSS V
ASS A
0-1500 A

1 2 3 4 5 6 7

200A SDFU
300A SDFU

200A SDFU

100A SDFU

100A SDFU
300A SDFU
630A SDFU

Lighting & fan

New panel
AC Plant

CVPS

Spare

Spare

Emergency Panel EP-I Spare


From output of AMF panel of 250 KVA generator set

400A SDFU
R Y B
0-500 V

2A VSS V
ASS A
0-400 A

1 2 3 4 5

125A SDFU
125A SDFU
200A SDFU

200A SDFU

63A SDFU
Executive area

Executive area
Computer load
Power load

Spare

Emergency Panel EP-II


From output of AMF panel of 110 KVA generator set

250A SDFU
R Y B
0-500 V

2A VSS V
ASS A
0-300 A

1 2 3 4
200A SDFU

100A SDFU

63A SDFU
63A SDFU
Existing 110 KVA load

Spare

Spare

Spare

Emergency Panel EP-III


From LT panel From proposed generator set

630A SDFU
R Y B
0-500 V

2A VSS V
ASS A
0-400 A

Digital PF meter

A/M Switch
8x63A SDFU
APF Relay

8 Nos. 63A TP contactors

8x25 KVAR capacitors

APFC Panel