Specimens and Electrodes The specimen shape and the electrode arrangement should be such that the resistivity can be easily calculated. For a solid specimen, the preferable shape is a flat plate with plane and parallel surfaces, usually circular. The specimens are normally in the form of discs of 5 to 10cm diameter and 3 to12mm thickness. If the electrodes are arranged to be in contact with the surfaces of the specimen, the measured resistance will be usually greater due to the surface conductivity effects. The electrode which completely covers the surface of the specimen is called the “unguarded” electrode and is connected to the high voltage terminal. The third electrode which surrounds the other measuring electrode is connected to a suitable terminal of the measuring circuit. The width of this "guard“ electrode must be at least twice the thickness of the specimen, and the unguarded electrode must extend to the outer edge of the guard electrode. The gap between the guarded and guard electrodes should be as small as possible. The effective diameter of the guarded electrode is greater than the actual diameter and is given as follows. Let r1, r2, and r be the radii of the guarded electrode, guard electrode including the gap, and the effective radius of the guarded electrode. Let the gap width = g and the specimen thickness = t. Electrode Materials For accurate measurements, the electrodes should have very good contact with the surface of the insulator specimen. Hence, it is necessary to use some type of thin metallic foil (usually of lead or aluminum of about 10 to 50micro meters thickness), usually pressed on to the surface by a roller and made to stick by using a conducting adhesive like petroleum jelly or silicone grease. The electrodes are made simultaneously by cutting out a narrow strip by means of a compass provided with a narrow cutting edge. Some times conducting silver paint is also used for electrode deposition. Measuring Cells The three terminal electrode system and the measuring cell used are shown in Fig. The measuring cell is usually a shallow metal box provided with insulating terminals. The box it self is connected to the guard electrode and is grounded if the guard terminal is grounded. The connecting lead for the guarded electrode is taken through a shielded wire. In case the unguarded electrode is grounded, the entire box is to be placed on insulated supports and is to be placed in a grounded shield to eliminate induced voltages, and the lead from the guard electrode is doubly shielded. In the simple two terminal system, the measuring cell itself is the grounded support for the specimen and a small solid wire is connected to the high voltage terminal of The measuring circuit, as can be seen from below Fig this is a simple and compact arrangement for quick measurements and requires less skill. The arrangement used for the should still allow easy study of liquids is shown in disassembling and cleaning. Fig. This consists of an outer cylindrical case and an inner cylinder with a cylindrical guard electrode. The opposing surfaces of the measuring electrodes should be carefully finished to give a polished surface, and a uniform spacing of about 0.2 5mm is maintained. The insulation should be able to maintain the alignment of the electrode even at the highest temperatures used and Another simple arrangement of accurately maintained. the three electrode system for The arrangement requires less the study of liquids is shown in liquid (usually only about 1 to Fig. 2ml). This consists of a metallic cylindrical container with concentric hollow cylindrical electrodes as guard and guarded electrodes. The inner surface of the container electrode(unguarded) and the outer surfaces of the guard and unguarded electrodes should be carefully finished and a clearance of about 0.25 to 0.5mm should be Partial Discharge Measurement Introduction Earlier the testing of insulators and other equipment was based on the insulation resistance measurements, dissipation factor measurements and breakdown tests. It was observed that the dissipation factor (tan ) was voltage dependent and hence became a criterion for the monitoring of the high voltage insulation. In further investigations it was found that weak points in an insulation like voids, cracks, and other imperfections lead to internal or intermittent (stopping and starting at irregular intervals) discharges in the insulation. Introduction These imperfections being small were not exposed in capacitance measurements but were exposed as power loss components in contributing for an increase in the dissipation factor (loss factor). In modern terminology these are designated as “partial discharges” which in course of time reduce the strength of insulation leading to a total or partial failure or break down of the insulation. Electrical insulation with imperfections or voids leading to partial discharges can be represented by an electrical equivalent circuit shown in Fig. Introduction Partial Discharge Phenomenon The following terminology is often used in partial discharge detection and as such their definitions are of importance: Electrical Discharge The movement of electrical charges through an insulating (dielectric) medium, initiated by electron avalanches. Partial Discharge An electrical discharge that only partially bridges the dielectric or insulating medium between two conductors. Examples are: internal discharges, Surface discharges and corona discharges. Internal discharges are discharges in cavities or voids which lie inside the volume of the dielectric or at the edges of conducting inclusions in a solid or liquid insulating media Partial Discharge Phenomenon Surface discharges are discharges from the conductor into a gas or a liquid medium and form on the surface of the solid insulation not covered by the conductor. Corona is a discharge in a gas or a liquid insulation around the conductors that are away or remote from the solid insulation.