Professional Documents
Culture Documents
Repair and Maintenance of Building
Repair and Maintenance of Building
Incorrect design
Faulty construction
Overloading
INTERPRETATION OF
RESULTS :-
Pulse velocity (km/second) Concrete quality (grading)
Above 4.5 excellent
3.5 to 4.5 good
3.0 to 3.5 medium
Below 3.0 doubtful
AIM
To assess the likely compressive
strength of concrete by using rebound
hammer as per IS: 13311 (Part 2) -
1992.
PRINCIPLE :- The rebound of an
elastic mass depends on the hardness
of the surface against which mass
strikes.
APPARATUS :- Rebound hammer
PROCEDURE :-
Before commencement of a test, the rebound hammer should be tested against
the test anvil, to get reliable results, for which the manufacturer of the
rebound hammer indicates the range of readings on the anvil suitable for
different types of rebound hammer.
Apply light pressure on the plunger - it will release it from the locked position
and allow it to extend to the ready position for the test.
Press the plunger against the surface of the concrete, keeping the instrument
perpendicular to the test surface. Apply a gradual increase in pressure until the
hammer impacts. (Do not touch the button while depressing the plunger. Press
the button after impact, in case it is not convenient to note the rebound reading
in that position.)
Take the average of about 10 readings
INTERPRETATION OF RESULTS :-
The rebound reading on the indicator scale has
been calibrated by the manufacturer of the rebound
hammer for horizontal impact, that is, on a
vertical surface, to indicate the compressive
strength. When used in any other position as given
by the manufacturer is to be taken into
Account.
This test is used to assess the corrosion
conditions in a reinforced concrete structure.
The apparatus includes copper-copper sulphate
half-cell, connecting wires and a high impedance
voltmeter
external cathode is provided in the form of copper
rod and copper sulphate solution in the cell. Any
point on reinforcement bar inside the concrete
body functioning as anode when connected
electrically to catholic half-cell generates e.m.f.
This is measured by connecting a mille voltmeter
in the circuit
After surveying the Iqbal Hall of NFC. Following repair and maintenance
required to rehab the building. Pictures are attached for clear perspective.
Efflorescence:-
In different parts of the building especially Washrooms area and
surroundings, need repair of water bound treatment
Horizontal and vertical cracks: -
There is lot of horizontal and vertical
cracks in Hall which is showing that structure
plaster is not much viable.
Penetration of Water due to unbound of
foundation top:-
Rainy and overflow water of tank are
continuous penetrating in the wall due to not
taking of measures to stop. Construction of slab
near foundation up to 3ft may stop this unsafe and
harmful action.
Improper Disposal of 1st & 2nd Floor Sewerage.
Disposal Of sewerage is major problem of
building which is causing the damage to building
aesthetics as well as causing efflorescence in
building walls; the smell is also spreading nearby
areas of the hall. Removal of extensive amounts of
debris, garbage, waste, and unusable construction
materials; sorting and reorganization of equipment
Electric socket:-
Electric socket in rooms as well as in
washroom are totally damaged due to efflorescence
which may cause a serious damaged for livelihood.
Replace these sockets as soon as possible.