[10%-15% capacity of the main pump, meant to handle leakages]
•1000 M2 – one wet riser
•60m & Above guide line Diameter
of pipe should be 150mm.
•Buildings: 12M2 / Sprinkler
•Basements: 9M2 / Sprinkler (2.6 ~3m
Spacing between sprinklers) 4.1 LPM per 20sqm 3-7% Foam - 93%Water
10.1 LPM per m2
Water Curtain needs : 750m2/compartment to ensure smoke doesn't flow from
one compartment to other Helipad System @ Terrace level Average Pressure requirement of the fire pump would be 7 to 8.8Kg/Cm2
Service floors at every 8~10 Floors
If Height is more than 45m. Then it has to be divided in two zones Low zone & High Zone.
To Design the system, so that pump can be utilized:
1) For both the zone Use 2 separate pumps with the
two separate tanks @ the basement.
2) Use the pumps @ the intermittent floors.
3) Use Gravity systems.
4) Best option would be all the pumping system should
be at the Basement & All the zones should be supplied from the base.(Considering Construction Economic design, Piping & Valves, Maintenance) If Height is more than 45m. Then it has to be divided in two zones Low zone & High Zone. Best option would be to use Multi stage Multi Outlet Pumps. .h = difference of each zone lowest portion to the pump center line.
.s = difference of pressure between the highest sprinkler of the zone & the pump centerline. High Zone