FactoryTalk View SE
PUBLIC INFORMATION
Rev 5058-CO900E Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.
Migration topics
Why migrate?
Comparison of RSView32 with FactoryTalk View SE
Doing the migration
ActiveX controls
VBA
Communications
Direct reference tags
Users and Security
Alarms
Moving to a 64-bit system
RSView32 extensions
Helpful links and FAQ
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 2
Why migrate to FactoryTalk View SE?
Do I have to migrate - is RSView32 going away?
No! RSView32 will be supported as long as 32-bit operating systems are
available
However, there are no plans for RSView32 to support 64-bit operating
systems
If moving to 64-bit systems, you will need to either migrate to FactoryTalk
View SE or employ a solution such as virtualization
Why would I want to move to FactoryTalk View SE?
Continued support for the latest Microsoft operating systems
Take advantage of data sharing and the latest technology including mobility,
virtualization, advanced integration of Rockwell Automation core Integrated
Architecture products and FactoryTalk Alarms and Events
Integration with FactoryTalk Historian SE and ME, FactoryTalk AssetCentre,
FactoryTalk VantagePoint, FactoryTalk ViewPoint, etc.
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 3
Benefits of migrating to
FactoryTalk View SE
Application development tools Primary
Server
Secondary
Server
Redundancy
FactoryTalk Live Data and Direct
Referencing
FactoryTalk Services Platform
Audit trails and e-signature for
regulatory compliance
FactoryTalk ViewPoint
Client-side VBA (client-stored and
executed)
Information product integration with
FactoryTalk VantagePoint,
Historian ME/SE
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 4
RSView32 to FactoryTalk View SE -
Terms
System components to remember when moving to FactoryTalk
View SE
Development environment
RSView32 Works FactoryTalk View Studio
Single station runtime system
RSView32 Runtime FactoryTalk View SE Station
Distributed runtime system
RSView Active Display Server FactoryTalk View SE Server/Client
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 5
About FactoryTalk View Studio
FactoryTalk View Studio is the single development environment for both
FactoryTalk View SE and ME
Is also the tool used to migrate RSView32 applications to FactoryTalk View SE
Four types of applications can be created in FactoryTalk View Studio
Network Distributed (SE) - multi-client, multi-server application with components
running on different machines
Network Station (SE) – single-client application with all components running on one
machine, but with the ability to connect to system components on remote machines
Local Station (SE) – single-client application with all components running on a single
machine
FactoryTalk View Machine Edition (ME) – application that runs on either a
PanelView Plus terminal or on a PC running FactoryTalk View ME Station
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 6
How to migrate an RSView32 application
to FactoryTalk View SE
1. Create a FactoryTalk View SE project
Start FactoryTalk View Studio
Select the type of application you want to create: Site Edition (network
distributed or network station) or Site Edition (local)
Click on the New tab, give the new application a name and create it:
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 7
How to migrate an RSView32 application
to FactoryTalk View SE
2. Add a new Area, and then create a new HMI Server in it
Right-click on the application and
select Add New Server > HMI Server
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 8
How to migrate an RSView32 application
to FactoryTalk View SE
Click OK on this dialog
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 9
How to migrate an RSView32 application
to FactoryTalk View SE
Provide a name for the new HMI Server and select the computer that will
host the HMI server; click Finish to import the RSView32 application
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 10
How to migrate an RSView32 application
to FactoryTalk View SE
Finishing steps
Create a data server to communicate with the controller
Convert or configure alarms – HMI tag alarms can be converted to
FactoryTalk Alarms; controller-based alarms are available for use in
View SE through FactoryTalk Alarms and Events
Configure startup components and create client files
Convert graphics to use direct referencing
Migrate functionality created with RSView32 VBA
Create Users and configure Security
Migrate RSView32 extension functionality
Be aware of best practices in FactoryTalk View SE
Knowledge Base AID 37110 has links to many best practice
documents, as well as patches and application notes
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 11
What is migrated?
Displays Images
Animations Parameter Files
Text Recipes
Tags Derived Tags
Alarms Events
Expressions Macros
Libraries Global Keys
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 12
Utilities and tools available for migration
Alarm Migration tool
Used to convert HMI alarms to FactoryTalk Alarms
Converts alarm tags to a format usable by the FT Alarms and Events
server
Available in Knowledge Base AID 45583
Tag Import and Export wizard
Built into FactoryTalk View Studio
Used to export HMI tag information to a .CSV file, which can then be:
Imported into a FactoryTalk Alarms and Events server
Edited using Excel, then re-imported into an application
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 13
Utilities and tools available for migration
Legacy Tag Database Conversion utility
Installed with FactoryTalk View v6.1 or 7.0
Also available in Knowledge Base AID 450509
Converts tag database from old (Watcom) format to new (SQL Server
Express) format that supports 64-bit systems
Allows you to import RSView32 project into FactoryTalk View on 64-bit
machine
HMI Tag to Direct Reference Converter Wizard
Converts HMI tag database references in graphic objects to direct
controller references
Available in Knowledge Base AID 31289
Can be used with both View SE and View ME
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 14
Migrating ActiveX controls
Determine whether you use ActiveX controls in your RSView32 project,
and whether you still want to use them in FactoryTalk View SE
Native View SE functionality may replace the ActiveX control
ActiveX controls must be installed and registered on the FactoryTalk View
Studio machine before migration
If this is done, the ActiveX control and its property values should be
retained during migration
If this is not done, the ActiveX control and its configuration will be lost
ActiveX control version is important – version installed on FactoryTalk
View Studio machine must be the same as used in RSView32 project
Back up your RSView32 program to retain the ActiveX property settings
ActiveX controls may not function in FactoryTalk View SE the same way
they did in RSView32 – make sure to evaluate each control individually
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 15
Migrating ActiveX controls
Specific ActiveX controls:
TrendX – will migrate with property settings intact
Native RSView32 trend control will not migrate, must be re-created as TrendX
Knowledge base AID 6948 has a comparison of the native trend control with
TrendX to help
eSignature – is not migrated to FactoryTalk View SE eSignature –
must be manually recreated
Make note of native trend control property settings, configure TrendX
RecipePro – interfaces directly with the RSView32 object model, and
so will not migrate
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 16
VBA execution in RSView32 vs.
FactoryTalk View SE
VBA execution model in
VBA execution model in RSView32
FactoryTalk View SE
HMI Client HMI Client
VBA
HMI Client
HMI Client
VBA
VBA
HMI Tags
HMI Tags
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 17
Migrating VBA
VBA is NOT migrated to FactoryTalk View SE
Some VBA can be re-used - object model references cannot be used as-is
The way VBA is implemented and the object model is very different in RSView32
vs. FactoryTalk View SE
RSView32 VBA:
VBA code in RSView32 runs on the server (server-side) – VBA code triggers
actions that run on the server
Most RSView32 VBA is used to manipulate or access the tag database
VBA is triggered with VBAExec command
FactoryTalk View SE VBA:
FactoryTalk View SE VBA runs on the client (client-side) and has a client-side
object model
VBA code in FactoryTalk View SE runs independently on each client – the
same display on 2 clients can be in different states, depending on user action
FactoryTalk View SE VBA is object-based, triggered by user actions on the
client
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 18
Migrating VBA
If you do want to re-use VBA code, can export code modules from
RSView32 and import into View SE project for copy/paste
Remember to use descriptive object names on displays to make VBA code
more readable (e.g. btnTank1)
To access tags in HMI tag database with VBA:
RSView32 VBA uses the gTagDb object to access tags
FactoryTalk View VBA requires a tag group to be created (and
destroyed) to access tags
Knowledge Base AID 51770 includes sample project with VBA and a lab
manual – good example of migrating VBA code
Many other tips and VBA code examples in the Knowledge Base
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 19
Communications
FactoryTalk View SE can use RSLinx Enterprise as its preferred data
server
RSLinx Enterprise provides optimized communications with all
products in the Logix5000 controller family
If using SLC-500 or PLC 5 controllers, use RSLinx Classic as data server
Configure an OPC Data Server, can talk to RSLinx Classic or third
party OPC Data Servers
Best practice is to separate each server (data or HMI) in its own Area
Will isolate the servers from one another
Optimizes data update time on displays
See Knowledge Base AID 29663 for more information
Separating Servers into separate Areas will require device tag re-
browsing to include Area and RSLinx Enterprise shortcut name in tag
address
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 20
Communications
If you want to import an RSView32 project into FactoryTalk View SE and
want comms to work without re-configuration of device tag addresses:
Put HMI Server and Data Server in the same Area (not a
recommended practice)
Create RSLinx Enterprise controller Shortcut with same name as
RSView32 Node
Device tags will continue to work without address editing
Make tag address editing easier by using the Tag Import and Export
Wizard and editing tag addresses in Microsoft Excel
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 21
Direct Referencing
Direct reference tags in
HMI tag database
FactoryTalk View SE
HMI Client HMI Client
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 22
Direct Referencing
FactoryTalk View SE provides device and memory HMI tags, just like
RSView32
But it also provides direct referencing – allows objects on a display to make
a direct reference to a tag in a controller, without going through the tag
database
Advantages to using direct referencing include:
When tag edits are made in the controller, the edits do not need to be
duplicated in the HMI tag database – objects reference the controller
tags directly and bypass the HMI tag database
Direct referencing provides access to complex tag data types in the
controller, such as arrays and structures
After migrating an RSView32 project to FactoryTalk View SE, use the
Direct Reference Tag Converter utility to convert HMI device tag references
to direct controller references
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 23
Users and Security
RSView32 users are not migrated to FactoryTalk View SE
Users (and user groups) must be manually created and configured
after migrating an RSView32 project to FactoryTalk View SE
FactoryTalk View SE security uses FactoryTalk users
FactoryTalk users and user groups can be either FactoryTalk
Directory-specific users or Windows-linked users, which use Windows
Active Directory user accounts
FactoryTalk users and user groups are shared by all FactoryTalk-
based products, so only need to be created once
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 24
Users and Security
Security in FactoryTalk View SE is based on the FactoryTalk Services
Platform
Authenticates user identities
Authorizes user requests for access to a resource
FactoryTalk View SE uses run time A-P security codes, just as RSView32
did
Displays migrated to FactoryTalk View SE from RSView32 retain their
A-P security code
However, users must be created and re-assigned those security codes
in FactoryTalk View SE
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 25
Alarming
RSView32 supports only tag-based, or HMI alarms
FactoryTalk View SE has support for FactoryTalk Alarms and Events,
which supports two types of alarms:
Tag-based
Device-based
Tag-based alarming with FactoryTalk Alarms and Events offers the
equivalent of HMI tag alarm monitoring, but with an expanded feature set
Tag-based alarming is supported for Logix5000 controllers, PLC-5,
and SLC-500 devices, or for third-party controllers
Device-based alarms use built-in instructions that are programmed and
downloaded to a Logix5000 controller. The controller detects alarm
conditions and publishes alarm and event information to FactoryTalk
Alarms and Events, which can then be displayed by View SE
Device-based alarms are available in RSLogix 5000 v16 or later
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 26
FactoryTalk Alarms and Events
Device-Based Tag-Based
Alarms Alarms
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 27
About Alarming in FactoryTalk View SE
FactoryTalk Alarm and Events server must be added to a View SE project
View SE best practice is to separate all servers into different Areas; create a
separate Area for the Alarm and Events server
The Alarm Migration tool converts View Alarm tags imported with an RSView32
project into a format that can be used by FactoryTalk Alarms and Events
Export Alarm tags from RSView32 project
Convert Alarm tags to FT A&E format with Alarm Migration tool
Import the converted Alarm tags into the FactoryTalk Alarms and Events
server
RSView32 alarm summary control is not migrated to FactoryTalk View SE
Manually convert the RSView32 alarm summary control to an alarm and
event summary control
FactoryTalk Alarms are automatically displayed in the alarm and event
summary control
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 28
Moving to a 64-bit system
RSView32 does NOT support 64-bit operating systems
This is because the RSView32 tag database format does not support
64-bit
Starting with version 6.1 of FactoryTalk View (ME and SE), a new tag
database format based on SQL Server was created to support 64-bit
systems
When moving from RSView32 to FactoryTalk View SE, evaluate whether
you will be moving to a 64-bit system
If not going to 64-bit, simply import RSView32 into FactoryTalk View
SE
Tag database is converted to new format when migrated to
FactoryTalk View SE v6.1 or later, no extra steps are required
Resulting project can be used on 64-bit systems if needed
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 29
Moving to a 64-bit system
If you are moving to 64-bit, you need to convert the tag database in one of two ways
If you have FactoryTalk View Studio v6.1 or 7.0 installed on a 32-bit machine:
Perform migration of RSView32 on the 32-bit machine
Tag database is converted automatically as part of migration
Resulting View SE project can then be run on either 32-bit or 64-bit machines
If you do not have FactoryTalk View Studio v6.1 or 7.0 installed on a 32-bit machine:
On the 32-bit RSView32 machine, use the Legacy Tag Database migration utility to
export the tag database to a neutral format
Copy the RSView32 project and the neutral format tag database files to the 64-bit
View Studio machine
Run the Legacy Tag Database migration utility again, creating the tag database in
the new SQL format
Import the RSView32 project into a FactoryTalk View SE project – the tag database
will be imported
Legacy Tag Database utility is installed with FactoryTalk View Studio
Can also be found in Knowledge Base AID 450509
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 30
RSView32 Extensions
In most cases, RSView32 extensions are not directly supported in
FactoryTalk View SE – but there are replacements
RSView32 Messenger is replaced by Win-911 software from Specter
Instruments
Download from the Specter Instruments website, or the Rockwell Automation
Software Downloads website
RSView32 SPC functionality can be replaced by integration of a
FactoryTalk View SE project with FactoryTalk Historian SE and
FactoryTalk VantagePoint
RSView32 WebServer has been replaced with FactoryTalk ViewPoint
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 31
Helpful links
RSView32 to FactoryTalk View SE Migration Guide –
Lit Library Doc ID: FTALK-QR004A-EN-P
Covers details on what does and does not convert,
importing RSView32 app into FT View SE
Knowledge Base articles
27708 – RSView32 to View SE Conversion
Guidelines
46786 – How to convert an RSView project to
FactoryTalk View SE Distributed
51770 – Sample app showing VBA migration
70818 – FactoryTalk Alarms and Events with
Win-911
57990 – FactoryTalk ViewPoint tips and best
practices
40891 – FactoryTalk View SE Server
Redundancy Guidelines
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 32
Frequently asked questions
Can you import individual screens (.GFX files) from RSView32 to
FactoryTalk View SE?
Yes, individual RSView32 screens will import into a FactoryTalk View
SE project, as long as there are no unknown ActiveX controls.
Other components such as data logs, parameter files, and macros can
also be added to a FactoryTalk View SE project.
With display-based licensing, do small pop-up windows count as a display
toward the license?
Yes, pop-up displays count toward the number of displays.
Do I need to upgrade to the latest version of RSView32 before I migrate to
FactoryTalk View SE?
No. Versions of RSView32 prior to v7.60 can be imported into an FT
View SE project.
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 33
Frequently asked questions
Can RSView32 and FactoryTalk View SE run on the same machine?
Yes. They can be installed on the same machine, but cannot run at
the same time.
Will offline tag browsing work with an SLC controller?
No. For offline tag browsing, an offline tag file is a ControlLogix project
file (.ACD) that contains tag data.
Can FactoryTalk View SE be used with NO security?
Yes. By default, security is not enabled, and the application is
available to all users.
What is the difference between parameter files in RSView32 vs.
FactoryTalk View SE?
They work the same way in both RSView32 and FactoryTalk View
SE.
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 34
Where do I get more technical
information?
Rockwell Automation Knowledge Base
AID 27708: RSView32 to FactoryTalk View SE Conversion Guidelines
AID 46786: How to convert an RSView project to FactoryTalk View SE Distributed
AID 37110: FactoryTalk View (RSViewSE) Tips and Best Practices TOC
AID 30399: Best Practices: Recommendations for VBA
AID 51770: Sample VBA: Exercise in migrating a View32 application with VBA to View
SE
AID 32549: View SE Distributed System Design Considerations
AID 29663: Best Practices: Guidelines for Structuring Areas
AID 45583: Tool: Converting ViewSE HMI Alarms to FactoryTalk A&E Tag-based
Alarms
Rockwell Automation Literature Library
RSView32 to FactoryTalk View SE Project Migration (PDF)
Technical Support
http://www.rockwellautomation.com/support/
North America: 1-440-646-3434
Worldwide: select location
Your local Rockwell sales office
PUBLIC INFORMATION Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. 35
Thank you!