Professional Documents
Culture Documents
Uas Stu
Uas Stu
Designed Temperature = 79 0F 50 77
Wall 0,67 Btu/hr sqft F Tabel 27 Handbook Carrier Flat metal with no insulation
Partition (Wall per room) 0,67 Btu/hr sqft F Tabel 25 Handbook Carrier Flat metal with no insulation
Glass (window) 1 Btu/hr sqft F Tabel 16 Handbook Carrier Ordinary Glass No shading
Ceiling 0,13 Btu/hr sqft F Tabel 27 Handbook Carrier Gypsum slab with 1 inches insulation 2 inches thickness suspended plaster
Floor 0,13 Btu/hr sqft F Tabel 27 Handbook Carrier Gypsum slab with 1 inches insulation 2 inches thickness suspended plaster
Cooling load
Infiltration
Area
(m2) Area (sqft) CFM/area CFM per door
Door 0,81 8,72 2 17,44 table 41
CFM
Room total ∆T (0F) Factor Heat
Room A 17,44 5,6 1,08 105,47712 30,91229
Room B 17,44 5,6 1,08 105,47712 30,91229
Room A Room A
Infiltration 17,44 CFM 56,8 g/lb 0,68 673,60256 Room Total Heat 11947,77
People 5 people 242,5 btu/hr 1212,5
Total room latent 1886,10256
Safety factor 10 % 2074,71282 btu/hr
Room B Room B
Infiltration 17,44 CFM 56,8 g/lb 0,68 673,60256 Room Total Heat 15309,65
People 5 people 242,5 btu/hr 1212,5
Total room latent 1886,10256
Safety factor 10 % 2074,71282btu/hr
Room C Room C
Infiltration 17,44 CFM 56,8 g/lb 0,68 673,60256 Room Total Heat 13732,38
People 5 People 242,5 btu/hr 1212,5
Total room latent 1886,10256
Safety factor 10 % 2074,71282 btu/hr
Outdoor Air
Ventilation
Room A
Room A CFM air out 393,96
Jumlah orang per ruangan 5 ∆T 10,6 gr/lb 56,8
cfm/orang 25 *private office with none smoking (Table 45 Handbook Carrier) *typical comfort application (Tabel 62 Handbook
Bypass factor 0,1 Carrier)
Luas lantai 1075,84 sqft
cfm/sqft floor 0,25 *private office with none smoking (Table 45 Handbook Carrier) Koef. 1,08 Sensible 0,68 Latent
393,96 CFM air out
451,005408 Sensible 1521,631104 Latent
Room B
Room B
Jumlah orang per ruangan 5
CFM air out 393,96
cfm/orang 25 *private office with none smoking (Table 45 Handbook Carrier)
∆T 10,6 gr/lb 56,8
Luas lantai 1075,84 sqft
*typical comfort application (Tabel 62 Handbook
cfm/sqft floor 0,25 *private office with none smoking (Table 45 Handbook Carrier) Bypass factor 0,1 Carrier)
393,96 CFM air out
Room C Koef. 1,08 Sensible 0,68 Latent
Jumlah orang per ruangan 5
451,005408 Sensible 1521,631104 Latent
cfm/orang 25 *private office with none smoking (Table 45 Handbook Carrier) Room C
Luas lantai 1075,84 sqft CFM air out 393,96
cfm/sqft floor 0,25 *private office with none smoking (Table 45 Handbook Carrier) ∆T 10,6 gr/lb 56,8
393,96 CFM air out *typical comfort application (Tabel 62 Handbook
Bypass factor 0,1 Carrier)
Koef. 1,08 Sensible 0,68 Latent
451,005408 Sensible 1521,631104 Latent
Grand Total Heat Calculation
Total
ERSH 36118,68
ERLH 10789,03
Grand Total Heat 46907,71
ESHF 0,769994
Table 65
Room C
0,75 53
0,771007 53,84027
0,8 55
titik 4
h4=h3
p4=p1
h4 263,68 kJ/kg
p4 721,1 kPa
s4 1,33 kj/kg k
T4 13,5 C
h1-h4 151,95 kJ/kg
cooling load 13,6032353 kw
m dot 0,089524418 KG/S
h2-h1 19,37 kJ/kg
daya kompresor 1,734087975 kW
COP 7,844605059
Supply Air Quantity Number of terminal CFM/terminal Perhitungan total Pressure
Room A 862,4267897 CFM 2 431,2133949 Drop
Room B 1156,091264 CFM 2 578,0456319
Room C 1018,314577 CFM 2 509,1572886 duct section item length ft eq ft
to C duct 10 32,8
Total Air Quantity 3036,832631 6 C - A duct 10 32,8
A-B duct 10 32,8
elbow 0 0 7
B-1 duct 5 16,4
1 - 2. duct 5 16,4
Low velocity (comfort air conditioning) Tabel 12
Initial Air Velocity 2000 fpm Carrier p19 Chapter 2
Main duct area 1,518416315 sqft
Total 131,2 7 138,2 ft
duct section cfm cfm capacity %duct area duct area duct size
to C 3037 100 100 1,5184163 10x 24 Friction Loss 0,3 in wg/ 100 ft Kurva
C-A 2019 66 72,5 1,1008518 6 x 34 74,652 Pa/ 100 ft
A-B 1156 38 46 0,6984715 8 x 14 103,16906
B-1 1156 38 46 0,6984715 8 x 14 Major Loss 4 Pa
1 - 2. 578 19 26 0,3947882 6 X 10 Tekanan Blower 114,63229 (Ditambahkan minor loss dengan asumsi major loss
minimum 33 Pa sebesar 90%)
Tabel 13
Chapter 2 Tabel 6
1156 CFM 578 CFM
1 2
B
1156 CFM
2019 CFM