Professional Documents
Culture Documents
CHAPTER XIV
CLEAN RUNNING WATER REQUIRED
the water supply shall be ample with facilities for its own
distribution. An ample supply of water at not less than 180 F
Hose connection with steam and water mixing valves of hot
and cold water hose connections shall be provided at
locations throughout the building and at loading and vehicle
cleaning slabs
ILLEGAL CONNECTIONS
• No unclean water pipe shall be connected to any potable water supply piping.
No potable water piping system connection to any tank, receptor, equipment,
or plumbing fixture shall be installed to allow unclean water to enter the
potable piping system
• No unclean water piping system shall be connected to a potable water piping
system unless provided with an backflow prevention device approved for the
prevention of a potential hazard
BACKFLOW PREVENTION DEVICES
• Air gap – to comply with the minimum air gap to allow
backflow protection
• Atmospheric vacuum breaker – shall be consists of a body,
a checking member, and an atmospheric opening
• Hose connection backflow preventer – shall consist of two
independent check valves with an independent
atmospheric vent between and a means of field testing and
draining
• Double check valve backflow prevention assembly – shall
consist of two independently acting internally loaded check
valve
• Reduced pressure principle backflow prevention assembly
– shall consist of two independently acting internally
loaded check valves, a differential pressure relief valves,
four properly located test cocks, and two isolation valves
• Pressure vacuum breaker backflow prevention assembly –
shall consist of one check valve force loaded closed and an
air inlet vent valve force loaded open to atmosphere,
positioned downstream of the check valve, and located
between and including two tightly closing shutoff valves at
test cocks
PROTECTION FROM LAWN SPRINKLERS
AND IRRIGATION SYSTEMS
Materials for all potable water carrying pipe, tube, and fittings for the
purpose of supplying drinking water shall meet the requirements of
NSF 61. similar materials shall be used in a water supply piping
system, except valves and similar devices.
Exceptions:
1. Use of CPVC is not permitted for medical applications
2. Use of PEX piping is not permitted for medical applications
3. Use of PEXALPEX piping is not permitted for medical applications
4. Use of PEX piping is not adopted for medical and food
applications
The use of CPVC for hot and cold water distribution systems within the
interior of hotel and residential buildings is allowed provided all of the
following conditions are satisfied:
1. Permit conditions – any building permit issued shall be conditioned
for compliance with the mitigation measures set forth in this section
2. Approved materials – only CPVC plumbing material listed as an
approved material and installed
3. Installation and use – any installation and use of CPVC plumbing
material pursuant to this section shall comply with all applicable
requirements.
4. Worker safety – any contractor applying for a building permit that
includes the use of CPVC plumbing materials must:
- aware of the health and safety hazards
- the worker safety training elements of their injury and illness
prevention plan meet the department of industrial relation’s guidelines
5. Finding compliance – the building official shall not give final
permit approval of any CPVC plumbing materials installed
pursuant to section 1404.1.1, unless he/she finds that the
material has been installed in compliance with the
requirements of this code
PEX (cross linked polyethylene) tubing shall be marked with
the appropriate United States or European standard
designations indicating that the tubing has been approved